Documente Academic
Documente Profesional
Documente Cultură
REPORT ON
Prepared by:
MARCH 2013
TABLE OF CONTENTS
A. MECHANICAL 3
1.0 INTRODUCTION 3
MECHANICAL
1.0 INTRODUCTION
Purpose
The proposed consist of 28 stories high rise building. The floor utilization is
as follows:
1. (B3 B1) floors are car park areas. Pump room and other service rooms.
2. Ground floor is entrance lobbies, for the Service Apartment, Substation room
and refuse room.
Internal
3.1.2 Occupancy
5% on latent load
3.1.4 Ventilation
Total fresh air for each flat shall be based on 2 persons per bedroom space.
Each flat shall be slightly negative to the corridor. The whole building shall
be positive with respect to the outdoors to prevent infiltration.
Air Handling units shall also be interlocked with the fire alarm system so as
to switch off in fire situation within relevant zone.
Fire dampers shall be positioned in all ductwork crossing firewalls, with the
exception of smoke exhaust ducts. They shall be triggered from fusible link
connection cited in the damper.
3.1.8.2 Recirculation FCUs shall be provided with only aluminum panel filter
3.2.0 AHU /FCU Coil Face Area : Air velocity not to exceed
2.5m/s.
3.3.1 Air conditioning for the building has been designed with DX ducted split units
where total units are 350 numbers.
20 numbers of condensing units are kept at gym roof floor serving floors from
LEVEL 28 to LEVEL 30.
3.3.2 Fresh Air Treatment Units shall be installed ( on Roof floors). Treated Fresh
Air shall be ducted via risers and discharged in ceiling void of each
flat/corridor and flat behind the FCUs.
All floor toilets, pantries and kitchens shall be ventilated. Total extracted air
shall be ducted to roof floor and connected to the heat recovery system.
3.3.3 Heat recovery thermal wheel shall be provided within FAHUs on the roof to
recover the possible sensible and latent cooling from the extracted air and
reduce the air conditioning load of fresh air intake.
3.3.9.2 Flats
Each flat shall have separate FCU for living dinning and bed room for one
Bed room apartment.
Each flat shall have separate FCU for living dinning and separate FCU for
Bed room 1 & 2 for 2 bed room apartment.
3.4.1 Ventilation for basement floors car parking shall be via duct system with
ducted in line extract fan.
3.4.2 Fresh air will be provided by ducted in line make-up fresh air fan.
3.4.3 The extract and fresh air fans shall be fans for normal and smoke mode
operations.
3.5 Equipment
All FCUs for apartment areas shall be horizontal ducted concealed with fan,
motor, drain pan and all required piping, wiring, controls.
FAHU shall be double skin construction, floor mounted, double deck type
with supply and extract fans along with thermal wheel and heat shoe pipe.
The FAHUs shall have primary and bag filters at intake air section.
The systems shall provide an appropriate environment for a high quality and be
compatible with the architectural/interior designs. In general, this should include:
Good air quality and outside air quantity for all people-occupied areas
HVAC systems in compliance with the following must be provided for all areas of the
building.
The life expectancy of the plant and equipment used shall be in accordance with
CIBSE, ASHRAE, BS 7543 or other recognized International Standards, with an
expected life in the order of 2530 years, subject to existing economical availability
Minimized space utilization for plant and equipment and distribution, by planning the
most appropriate location for plant, co-ordination with structure (for optimizing
ceiling heights) and providing efficient distribution systems. All systems will be fully
accessible for a safe service environment.
The systems proposed should comply with the following recognized international
Industry standards:
CIBSE
ASHRAE
NFPA (Life Safety Systems)
Note 2 Air change rate shall depend on kitchen equipment heat output and on
extract volume from canopies. A minimum face velocity must be
provided to each canopy, refer to the kitchen section of this document.
Note 7 Toilet extract to be sized on 10AC/Hr, with make-up air via the toilet
lobby, supplied from the nearest supply air system.
Note 8 Ventilation to these areas to be designed to maintain internal air
temperature below 25C/77F for 95% of the year, if possible without a
cooling system. If a cooling system is required, the internal design
temperature shall be 24C/75F.
Note 9 Ventilation rates to be based on 8-12 l/s per guest, final figure to balance
the exhaust rate. All supply air will be direct supplied to room.
Note 10 Extract volume from bathroom shall be greater or equal to the supply air
volume to the room and a minimum of 6AC/Hr.