Sunteți pe pagina 1din 27

gradeup ELECRIAL MACHINES (Formula Notes)

TRANSFORMERS:

Gross cross sectional area = Area occupied by magnetic material + Insulation


material.
Net cross sectional area = Area occupied by only magnetic material excluding area
of insulation material.
Hence for all calculations, net cross sectional area is taken since (flux) majorly
flows in magnetic material.
= BAn

t
Weight of
Specific weight of t/f = f
t
KVA rating of
f

Net Cross Sectional area


Stacking/iron factor :- (k s ) = Gross Cross Sectional area

k s is always less than 1


Gross c.s Area = AG = length breadth
Net c.s Area = An = k s AG
Effective C.S.Area
Utilization factor of transformer core = Total C.S Area
U.F of cruciform core = 0.8 to
0.85
mmF
Flux = Reluctance = = m sin t
d d
According to faradays second law e1 = N1 dt = N1 dt m sin t
Instantaneous value e1 = N1 m sint 2
of emf in primary

Transformer emf equations :-


E1 = 4.44 N1 Bmax An f (1)
E2 = 4.44 N2 Bmax An f (2)

E
Emf per turn in Iry = N1 = 4.44 Bmax An f
1
ry E2
Emf per turn in II = = 4.44 Bmax An f
N2

Emf per turn on both sides of the transformer is same


E1 E2
=
N1 N2
E1 N1 1
= =
E2 N2 k
E2 N2 1
Transformation ratio = K = = Turns ratio = K = N1 N2
E1 N1

gradeup 1
gradeup
For an ideal two-winding transformer with primary voltage V1 applied
across N1 primary turns and secondary voltage V2 appearing across N2 secondary
turns:
V1 / V2 = N1 / N2
The primary current I1 and secondary current I2 are related by:
I1 / I2 = N2 / N1 = V2 / V1
For an ideal step-down auto-transformer with primary voltage V1 applied
across (N1 + N2) primary turns and secondary voltage V2 appearing
across N2 secondary turns:
V1 / V2 = (N1 + N2) / N2
The primary (input) current I1 and secondary (output) current I2 are related by:
I1 / I2 = N2 / (N1 + N2) = V2 / V1.

For a single-phase transformer with rated primary voltage V1, rated primary
current I1, rated secondary voltage V2 and rated secondary current I2, the voltampere
rating S is:
S = V1I1 = V2I2

For a balanced m-phase transformer with rated primary phase voltage V1, rated
primary current I1, rated secondary phase voltage V2 and rated secondary current I2,
the voltampere rating S is:
S = mV1I1 = mV2I2

The primary circuit impedance Z1 referred to the secondary circuit for an ideal
transformer with N1 primary turns and N2 secondary turns is:
Z12 = Z1(N2 / N1)2

During operation of transformer :-

E1 V1
Bm
f f
V1
Bmax = constant = constant
f

Equivalent ckt of t/f under N.L condition :-

N1 N2
I0

Iw I
V1 R0 X0 E1 E2

No load /shunt branch.

gradeup 2
gradeup
No load current = I0 = I + Iw = I0 0
Iw = I0 cos 0
I = I0 sin 0
No load power = v1 I0 cos 0 = v1 Iw = Iron losses.
v1 v1 No load power
R0 = ; X0 = Iw =
Iw1 I V1

Transferring from to :-
R1 R 21
I22 R 2 = I12 R 21
I 2
R 21 = R 2 2
I 1
R2
=
K2
R
R 21 = K22

From to :-
I12 R1 = I22 . R11
I12
R11 = I22
. R1
R11 = R1 . K 2

Total resistance ref to primary = R1 + R 21


R 01 = R1 + R 2 /k 2
Total resistance ref to secondary = R 2 + R11
R 02 = R 2 + k 2 R1
Total Cu loss = I12 R 01
Or
2
I2 R 02

Per unit resistance drops :-


I1 R1
P.U primary resistance drop = E1
I R
P.U secondary resistance drop = 2E 2
2
I1 R01
Total P.U resistance drop ref to I ry = E1
ry I2 R02
Total P.U resistance drop ref to II = E
2
The P.U resistance drops on both sides of the t/f is same
I1 R01 I2 R02
E1
= E2

Losses present in transformer :-


t/f windings
1. Copper losses
major losses
2. Iron losses t/f core
cu parts
3. Stray load losses Iron parts
4. Dielectric losses minor losses
insulating materials.
gradeup 3
gradeup
1. Cu losses in t/f:

Total Cu loss = I12 R1 + I22 R1


= I12 R 01
= I22 R 02
VA rating of t/f
Rated current on I ry =
E1
VA rating of t/f
Similarly current on II ry =
E2
Cu losses I12 or I22. Hence there are called as variable losses.
FL Cu loss in watts
P.U Full load Cu loss =
VA rating of t/f
I12 R01
= E1 I1
If VA rating of t/f is taken as base then P.U Cu loss I12 as remaining terms are constant.

P.U Cu loss at x of FL = x 2 PU FL Cu loss

ry
P. U resistance drop ref to I =
I1 R01 I1

or E1 I1
P. U resistance ref to Iry
I12 R01
= E1 I1

P.U Resistance drop = P.U FL cu loss

% FL Cu loss = % R = % Resistance drop.

Iron (or) Core losses in t/f :-

1. Hysteresis loss :

Steinmetz formula :-

x
Wh = Bmax . f . v Area under one hysteresis loop.

Where
= stienmetz coefficient
Bmax = max. flux density in transformer core.
f = frequency of magnetic reversal = supply freq.
v = volume of core material
x = Hysteresis coeff (or) stienmetz exponent
= 1.6 (Si or CRGo steel)
2. Eddycurrent loss:
Eddy current loss ,(We ) R ce Ie2
As area decreases in laminated core resistance increases as a result conductivity decreases.
2 2 2
We = K. Bma x f .t
thickness of laminations.
Supply freq
Constant
(it is a function of )
gradeup 4
gradeup
During operation of transformer :- V1
Bm
f

V1
Case (i) :-
f
= constant, Bmax = const.
we f 2

we = B f 2

Const.

wi = wh + we When Bmax = const.


2
wi = Af + Bf

V1
Case (ii) :- constant, Bm const.
f
V 2
we f1 . f 2
we V1 2
wi = wh + we
A V11.6
wi =
f0.6
+ BV1 2

P.U iron loss :-


Iron loss in watts
P.U iron loss =
VA rating of t/f

As VA rating is choosen as base then the P.U iron loss are also constant at all load conditions.

To find out constant losses :-


W0 = Losses in t/f under no load condition
= Iron losses + Dielectric loss + no load primary loss (I02 R1)
Constant losses = W0 I02 R1
Where , R1 = LV winding resistance.

To find out variable losses :-


Wsc = Loss in t/f under S.C condition
= F.L Cu loss + stray load losses (Cu and Iron) + Iron losses in both wdgs
Variable losses = WSC Iron losses corresponding to VCC
O.C test :-
V1 rated Wi
S.C test :-
VSC (Wi )S.C
Wi V1 2
Wi V1 rated 2
(Wi )SC
=
VSC
VSC 2
(Wi )S.C = Wi
V 1 rated
VSC 2
Variable losses = WSC (Wi )SC V
1 rated

gradeup 5
gradeup
Under the assumption that small amount of iron losses corresponds to VSC and stray load
losses are neglected the wattmeter reading in S.C test can be approximately taken as F.L
Cu losses in the transformer.
Wse F.L Cu loss
ISC2 . R 01
WSC
R 01 = 2
ISC

Efficiency :-

output power
Efficiency of transformer is given by =
input power
output power
=
output power+losses
E2 I2 cos 2
=E
2 I2 cos 2 + F.L cu losses+Iron losses
E2 I2 cos 2
F.L = E2 I2 cos 2 + I22 R02 + Wi

x (E2 I2 ) cos 2
x of F.L =
x (E2 I2 ) cos 2 + x 2 (I2 2 R 02 ) + Wi

S.C test O.C test

KVA cos
Transformer efficiency =
KVA cos + wi + Cu losses

Voltage drop in t/f at a Specific load p.f = I2 R 02 cos 2 I2 X02 sin 2

I2 R02 cos 2 I2 X02 sin 2


% Voltage regulation = 100
V1

I R02 I X02
=2 cos 2 2 sin 2
V1 V1

P.U resistance P.U reactance
% Regulation = (P. U R) cos 2 + (P. U X) sin 2 100

gradeup 6
gradeup
AUTO TRANSFORMER:

Primary applied voltage, Vab = Secondary voltage V2 referred to primary + primary leakage impedance
drop + secondary leakage impedance drop ref. to primary.
N1 N2 N1 N2
Vab =
N2
V2 + I1 (r1 + jx1 ) + (I2 I1 )(r2 + j x2 ) N2

LV
K of auto transformer = HV
(KVA)induction = (V1 V2 ) I1

I/P KVA = V1 I1

(KVA)induction (V1 V2 ) I1
i/p KVA
= V1 I1
LV
=1
HV
=1K
(KVA) induction = (1 K) i/p KVA

(KVA) conduction = I/p KVA (KVA)ind

(KVA)conduction = K I/p KVA

Wt. of conductor in section AB of auto t/f (N1 N2 ) I1

Wt of conductor in section BC of auto t/f (I2 I1 )N2


Total wt. of conductor in auto t/f is
I1 (N1 N2 ) + (I2 I1 )N2
2 (N1 N2 ) I1
Total wt. of conductor in 2 wdg transformer
I1 N1 + I2 N2
2 I1 N1
wt.of conductor in an auto t/f 2(N1 N2 )I1
=
wt.of conductor in 2 wdg t/f 2N1 I1
N
= 1 N2
1

=1K
Wt. of conductor in auto t/f = (1 K) (wt. of conductor in 2 wdg t/f)
Thus saving of conductor material if auto t/f is used} = K {conductor wt in 2 wdg transformer.
(% FL losses)Auto t/f = (1 K)(% FL losses)2 wdg t/f
(% Z)AT = (1 K) (% Z)2 wdg t/f
1
(KVA)AT = (KVA)2 wdg t/f .
1K

gradeup 7
gradeup
DC MACHINES :

Lap Winding Wave Winding


(1) Coil Span : S S
Ycs = P Ycs = P
(2) Back Pitch Yb = U Ycs Yb = U Ycs
(3) Commutator Pitch Yc = 1 2 (c+1)
Yc = p
for Progressive winding
for Progressive winding
Yc = -1 2 (c+1)
for Retrogressive winding Yc = - p
for Restrogressive winding
(Yc Must be integer)
(4) Front Pitch Yf =Yb +2 Yf =2Yc - Yb
for Progressive winding
Yf =Yb -2
for Retrogressive winding

(5) Parallel Paths A=P A=2


(6) Conductor Current I I
Ic = Aa Ic = 2a
(7) No of brushes No of brushes = A = P No of brushes = 2

S = No of commutator segments
P = No of poles
2C
U = No of coil sides / No of poles = S
C = No of coils on the rotor
A = No of armature parallel paths
Ia = Armature current
phasor sum coil emf chord 2
Distribution factor (K d ) = = =
arthematic sum of coil emf arc
elecrrical angle of coil
Pitch factor ( K p ) = 1800
*100%
P
0electrical = 2 0mechanical
ZI
Armature mmf/Pole (Peak) , ATa = 2AP
a

ZI pole arc
AT (Compensating Winding) = 2AP
a
* pole pitch
B
AT(Inter pole) = ATa + i lgi
0
Where Bi = Flux density in inter pole airgap

lgi = length of inter pole airgap , 0 = 4 107


AT(Inter pole)
No of turns in each interpole , Ninterpole = Ia
Z pole arc
The no of compensating conductor per pole, Ncw /pole = 2 A P (pole pitch )
The Mechanical power that is converted is given by Pconv = Tind m
Where T = Induced torque = Angular speed of the machines rotor
m

gradeup 8
gradeup

The resulting electric power produced Pconv = EA IA


The power balance equation of the DC Machine is Tind m = EA IA
ZNP
The induced emf in the armature is Ea = 60A
PZ
Torque developed in Dc machine , Te = 2A Ia
Where = Flux\pole , Z = No of armature conductors , P = No of poles , N = Speed in rpm ,
A = No of armature parallel paths, Ia = Armature current
The terminal voltage of the DC generator is given by Vt = Ea - Ia R a
The terminal voltage of the DC motor is given by Vt = Ea + Ia R a
nl fl Nnl Nfl
Speed regulation of dc machine is given by ,SR = fl
* 100 % = Nfl
* 100 %
Vnl Vfl
Voltage regulation , VR = Vfl
* 100 %
Shunt Generator:
For a shunt generator with armature induced voltage Ea, armature current Ia and
armature resistance Ra, the terminal voltage V is:
V = Ea - IaRa
The field current I f for a field resistance R f is:
If = V / Rf
The armature induced voltage Ea and torque T with magnetic flux at angular
speed are:
Ea = k f = km
T = k fIa = kmIa
where k f and km are design coefficients of the machine.
Note that for a shunt generator:
- induced voltage is proportional to speed,
- torque is proportional to armature current.
The airgap power Pe for a shunt generator is:
Pe = T = EaIa = km Ia
Series Generator:

For a series generator with armature induced voltage Ea, armature current Ia,
armature resistance Ra and field resistance R f, the terminal voltage V is:
V = Ea - ( IaRa + IaR f )= Ea - Ia(Ra + R f)
The field current is equal to the armature current.
The armature induced voltage Ea and torque T with magnetic flux at angular
speed are:
Ea = k f Ia = km Ia
T = k fIa2 = kmIa2
where k f and km are design coefficients of the machine.
Note that for a series generator:
- induced voltage is proportional to both speed and armature current,
- torque is proportional to the square of armature current,
- armature current is inversely proportional to speed for a constant Ea

gradeup 9
gradeup
The airgap power Pe for a series generator is:
Pe = T = EaIa = km Ia2
Cumulatively compounded DC generator : - ( long shunt)
(a) Ia = If + IL
(b) Vt = Ea - Ia (R a + R s )
V
(c) Isf = Rx = shunt field current
f
(d) The equivalent effective shunt field current for this machine is given by
Nse Armature reaction MMF
Isf =Isf + Ia - ( )
Nf Nf

Where Ns e = No of series field turns


Nf = = No of shunt field turns

Differentially compounded DC generator : - ( long shunt)


(a) Ia = If + IL
(b) Vt = Ea - Ia (R a + R s )
Vx
(c) Isf = = shunt field current
Rf
(d) The equivalent effective shunt field current for this machine is given by
Nse Armature reaction MMF
Isf =Isf - Nf
Ia - ( Nf
)

Where Ns e = No of series field turns , Nf = = No of shunt field turns

Shunt Motor:
For a shunt motor with armature induced voltage Ea, armature current Ia and
armature resistance Ra, the terminal voltage V is:
V = Ea + IaRa
The field current I f for a field resistance R f is:
If = V / Rf
The armature induced voltage Ea and torque T with magnetic flux at angular
speed are:
Ea = k f = km
T = k fIa = kmIa
where k f and km are design coefficients of the machine.
Note that for a shunt motor:
- induced voltage is proportional to speed,
- torque is proportional to armature current.
The airgap power Pe for a shunt motor is:
Pe = T = EaIa = km Ia
V Ra PZ
The speed of the shunt motor , = K - (K)2T Where K =
2A

gradeup 10
gradeup
Series Motor :

For a series motor with armature induced voltage Ea, armature current Ia,
armature resistance Ra and field resistance R f, the terminal voltage V is:

V = Ea + IaRa + IaR f = Ea + Ia(Ra + R f)

The field current is equal to the armature current.


The armature induced voltage Ea and torque T with magnetic flux at angular
speed are:
Ea = k f Ia = km Ia
T = k fIa2 = kmIa2
where k f and km are design coefficients of the machine.

Note that for a series motor:


- induced voltage is proportional to both speed and armature current,
- torque is proportional to the square of armature current,
- armature current is inversely proportional to speed for a constant Ea

The airgap power Pe for a series motor is:


Pe = T = EaIa = km Ia2
Losses:

constant losses (P k) = Pw f + Pi o

Where, Pio = No of load core loss

Pwf = Windage & friction loss


Variable losses (Pv ) = Pc + Ps t + Pb
2
where Pc = Copper losses = Ia R a

Ps t = Stray load loss = I2

Pb = Brush Contact drop = Vb Ia , Where Vb = Brush voltage drop


The total machine losses , PL = Pk +Vb Ia + K v Ia 2

Efficiency

The per-unit efficiency of an electrical machine with input power Pin, output
power Pout and power loss Ploss is:

= Pout / Pin = Pout / (Pout + Ploss) = (Pin - Ploss) / Pin

Rearranging the efficiency equations:

gradeup 11
gradeup
Pin = Pout + Ploss = Pout / = Ploss / (1 - )

Pout = Pin - Ploss = Pin = Ploss / (1 - )

Ploss = Pin - Pout = (1 - )Pin = (1 - )Pout /

Temperature Rise:

The resistance of copper and aluminium windings increases with temperature,


and the relationship is quite linear over the normal range of operating
temperatures. For a linear relationship, if the winding resistance is R1 at
temperature 1 and R2 at temperature 2, then:

R1 / (1 - 0) = R2 / (2 - 0) = (R2 - R1) / (2 - 1)
where 0 is the extrapolated temperature for zero resistance.

The ratio of resistances R2 and R1 is:


R2 / R1 = (2 - 0) / (1 - 0)

The average temperature rise of a winding under load may be estimated from
measured values of the cold winding resistance R1 at temperature 1 (usually
ambient temperature) and the hot winding resistance R2 at temperature 2, using:
= 2 - 1 = (1 - 0) (R2 - R1) / R1

Rearranging for per-unit change in resistance Rpu relative to R1:


Rpu = (R2 - R1) / R1 = (2 - 1) / (1 - 0) = / (1 - 0)

Copper Windings:

The value of 0 for copper is - 234.5 C, so that:


= 2 - 1 = (1 + 234.5) (R2 - R1) / R1

If 1 is 20 C and is 1 degC:
Rpu = (R2 - R1) / R1 = / (1 - 0) = 1 / 254.5 = 0.00393

The temperature coefficient of resistance of copper at 20 C is 0.00393 per


degC.

Aluminium Windings:
The value of 0 for aluminium is - 228 C, so that:
= 2 - 1 = (1 + 228) (R2 - R1) / R1

If 1 is 20 C and is 1 degC:
Rpu = (R2 - R1) / R1 = / (1 - 0) = 1 / 248 = 0.00403
The temperature coefficient of resistance of aluminium at 20 C is 0.00403 per
degC.

gradeup 12
gradeup

Dielectric Dissipation Factor:

If an alternating voltage V of frequency f is applied across an insulation system


comprising capacitance C and equivalent series loss resistance RS, then the
voltage VR across RS and the voltage VC across C due to the resulting
current I are:
VR = IRS
VC = IXC
V = (VR2 + VC2)

The dielectric dissipation factor of the insulation system is the tangent of the
dielectric loss angle between VC and V:
tan = VR / VC = RS / XC = 2fCRS
RS = XCtan = tan / 2fC

The dielectric power loss P is related to the capacitive reactive power QC by:
P = I2RS = I2XCtan = QCtan

The power factor of the insulation system is the cosine of the phase
angle between VR and V:
cos = VR / V
so that and are related by:
+ = 90

tan and cos are related by:


tan = 1 / tan = cos / sin = cos / (1 - cos2)
so that when cos is close to zero, tan cos

gradeup 13
gradeup
SYNCHRONOUS MACHINES:

Principle of operation :-

Whenever a conductor cuts the magnetic flux, an emf is induced in that conductor

Faradays law of electromagnetic induction.

Coil span () :- It is the distance between two sides of the coil. It is expressed in terms of
degrees, pole pitch, no. of slots / pole etc
Pole pitch :- It is the distance between two identical points on two adjacent poles.
Pole pitch is always 180 e = slots / pole.
P
elec = mech
2
Slot pitch or slot angle :- (T)Slot angle is the angle for each slot.
P(180)
For a machine with P poles and s no. of slots, the slot angle = = d
180
= s

p

Pitch factor or coil span factor or chording factor :- (K P)

The emf induced | coil in short pitched winding


KP = The emf induced |coil in full pitched winding

The vector sum of induced emf | coil


=
Arithmetic sumof induced emf | coil

2E cos/2
KP =
2E

Kp = cos /2
cos n
Pitch factor for nth harmonic i.e, K pn = 2

180
chording angle to eliminate nth harmonics ()=
n
n1
coil spam to eliminate nth harmonics ,() = 180
n
Distribution factor | spread factor | belt factor | breadth factor(kd) :-

The emf induced when the winding is distributed


K d = The emf induced when the winding is concentrated

Vector sum of emf induced


Kd =
Arithmetic sum of emf induced

gradeup 14
gradeup

m
sin
2
Kd =
m sin
2
The distribution factor for uniformly distributed winding is
mr
sim
kd4 = mr 2


2 180

mn
sin
For nth harmonic, kdn = 2
n
m sin
2

360
To eliminate nth harmonics ,phase spread (m) =
n
Generally, KVA rating, power output kd and Eph (induce emf) k d . Tph .
60
KVA60 (3 ) Pout60 (3 ) kd60 sin m120 sin 30 120
KVA120 (3 )
= Pout120 (3)
=
kd120
= 2
120
m60
=
sin 60

60
= 1.15
sin
2

60
KVA60 (3) Pout60 (3) kd60 sin 90
KVA90 (2)
= Pout90 (2)
= kd90
= 2
90 = 1.06
sin 60
2

60
KVA60 (3) Pout60 (3) kd60 sin 180
= = = 2
180 = 1.5
KVA180 (1) Pout180 (1 ) kd180 sin 60
2

KVA90 (2 ) Pout90 kd90 sin902 180


KVA180 (1 )
= = = = 1.414
Pout180 kd180 sin1802 90

1
Speed of space harmonics of order (6k 1) is (6k . Ns
1)

120 f
where Ns = synchronous speed = p

2S
The order of slot harmonics is 1
P

where S = no. of slots , P = no. of poles

Slot harmonics can be eliminated by skewing the armature slots and fractional slot winding.

The angle of skew = s = (slot angle)

= 2 harmonic pole pitches


= 1 slot pitch.
2s
Distribution factor for slot harmonics, k d 1
p

gradeup 15
gradeup

m
sin
Is kd1 = 2
i.e., same that of fundamental
m sin
2
2s
Pith factor for slot harmonics, k p 1 = k p1 = cos 2
p

The synchronous speed Ns and synchronous angular speed of a machine with p pole
pairs running on a supply of frequency fs are:

s = 2fs / p
NS N
Slip S =
NS

120 f
Where NS = = synchronous speed
p
The magnitude of voltage induced in a given stator phase is Ea = 2 Nc f = K
Where K = constant

The output power Pm for a load torque Tm is:

Pm = sTm

The rated load torque TM for a rated output power PM is:

TM = PM / s = PM p/ 2fs = 120PM / 2Ns

Synchronous Generator:

For a synchronous generator with stator induced voltage Es, stator current Is and
synchronous impedance Zs, the terminal voltage V is:

V = E - IsZs = Es - Is(Rs + jXs)

where Rs is the stator resistance and Xs is the synchronous reactance

E = (V cos + Ia R a )2 + (V sin Ia Xs )2
+ lag p.f
leading p.f.

gradeup 16
gradeup

Synchronous Motor:

For a synchronous motor with stator induced voltage Es, stator current Is and synchronous
impedance Zs, the terminal voltage V is:

V = Es + IsZs = Es + Is(Rs + jXs)


where Rs is the stator resistance and Xs is the synchronous reactance

Voltage regulation :

|E| |V|
% regulation = |V|
100
E V = Ia Zs
EV
% regulation =
V
Ia Zs
= 100
V
regulation Zs
As Zs increases, voltages regulation increases.

Ia Zs
Condition for zero | min. voltage regulation is, Cos ( + ) = 2V
Condition for max. Voltage regulation is, =
Ifm 1 1
Short circuit ratio (SCR) = Ifa
=
Zs (adjusted)|unit
=
Xs (adjusted)|unit

1 1
SCR
Xa Armature reaction

Voltage regulation Armature reaction


1
SCR
Voltage regulation

Small value of SCR represent poor regulation.

armature mmf
a =
reluctance

But reluctance Air gap

armature mmf
a =
airgap

1
a
Air gap length
1
Armature reaction a
Airgap length

gradeup 17
gradeup

1
SCR Airgap length
Armature reaction

Air gap length SCR

machine size SCR.


Cost SCR
EV
Power = sin
Xs

1
P SCR
Xs

Power SCR
Large value of SCR represent more power output.
Synchronizing power coefficient or stability factor Psy is given as
dp d EV
Psy = = sin
d d Xs
EV
= cos
Xs
Psy is a measure of stability
stability Psy
1
But Psy X SCR
s

Stability SCR
Stability SCR Air gap length

Stability Air gap length

When the stator mmf is aligned with the d axis of field poles then flux d perpole is set up
and the effective reactance offered by the alternator is X d .

maximum Voltage (Vt )line (at min. Ia )


Xd = = = Direct axis reactance
minimum current 3 Ia (min )

When the stator mmf is aligned with the q axis of field poles then flux q per pole is set up
and the effective reactance offered by the alternator is X q.

minimum voltge Vt line (at maximum Ia )


Xq = = = Quadrature axis reactance
maximum voltage 3 Ia (max )

gradeup 18
gradeup

Cylindrical rotor Synchronous machine ,


Ef Vt
The per phase power delivered to the infinite bus is given by P =
Xs
sin
Salient pole synchronous machine ,

The per phase power delivered to the infinite bus is given by

Ef Vt Vt2 1 1
P= Xd
sin + 2
X sin 2
q Xd

Condition for max. power:-


For cylindrical rotor machine :-
dp
At constant Vt and Ef , the condition for max. power is obtained by putting =0
d
dp Ef Vt
= cos =0
d Xs
Cos = 0
= 90
Hence maximum power occurs at = 90
dp
For salient pole synchronous machine :- =0
d
Vt Ef 1 1
cos + Vt 2 cos 2 =0
Xd Xq Xd

2
Ef Xq 1 E Xq
+ 4V
f
Cos = 4V
t Xd Xq 2 X t d Xq

The value of load angle is seed to be less than 90.


max. power occurs at < 90
Synchronizing power = Psy. .
EV
cos . .
=
Xs
Synchronizing power
Synchronizing torque = .

Power flow in Alternator :-


EV V2
Complex power = S = P + jQ = VIa Where Active power flow (P) = cos( ) cos ;
Zs Zs

EV V2
Reactive power flow (Q) = sin( ) sin ;
Z2 Zs
Condition for max. power output :-
EV V2
P= cos( ) cos
Zs Z2
dp
= 0 for max power condition
d
ie = 0
If R a = 0; = = 90 ; then max power is given by
=

EV V2
Pmax = cos
Zs Zs

gradeup 19
gradeup

INDUCTION MACHINES:

The power flow diagram of 3 induction motor is

Power i/p to stator Mechanical power


Rotor i/p power
from mains
= airgap power Pg developed, Pm

Power of
rotor shaft

Stator Stator Rotor Rotor core loss Friction loss Windage


I2R core I2R (negligible for at bearings loss
loss loss loss small slips) and sliprings
of (if any)

ns nr
The slip of induction machine is (S) = ns
Ns Nr
= Ns
Where Ns is synchronous speed in rpm
ns is synchronous speed in rps
Nr = Ns (1 s)
Ns Nr = SNs
P . SNs PNs
Rotor frequency, f2 = 120
=S 120
= Sf1

For an induction machine with rotor resistance Rr and locked rotor leakage reactance Xr, the
rotor impedance Zr at slip s is:Zr = Rr + jsXr
The stator circuit equivalent impedance Zrf for a rotor / stator frequency ratio s is:
Zrf = Rrs / s + jXrs

For an induction motor with synchronous angular speed s running at angular speed m and
slip s, the airgap transfer power Pt, rotor copper loss Pr and gross output power Pm for a
gross output torque Tm are related by:
Pt = sTm = Pr / s = Pm / (1 - s)
Pr = sPt = sPm / (1 - s)
Pm = mTm = (1 - s)Pt
The power ratios are:
Pt : Pr : Pm = 1 : s : (1 - s)
The gross motor efficiency m (neglecting stator and mechanical losses) is:
m = Pm / Pt = 1 - s

Rotor emf, Current Power :-


At stand still, the relative speed between rotating magnetic field and rotor conductors is
synchronous speed Ns ; under this condition let the per phase generated emf in rotor circuit
be E2 .

E2 /ph = 4.44 Nphr 1 f1 K dr K pr


E2 /ph = 4.44 Nphr 1 f1 K wr

gradeup 20
gradeup

K wr = Rotor winding factor

But during running conditions the frequency of the rotor becomes, running with speed Nr

P(Ns Nr ) P SNs
120
= 120
= Sf1
fr = Sf1
Emf under running conditions is
E = 2 fr Kw2 Nphr 1
= SE2

Rotor leakage reactance = 2 (Rotor frequency)


(Rotor leakage Inductance)
Rotor leakage reactance at stand still = 2 f1 2
= x2
Rotor leakage reactance at any slips = 2 f2 2

= sx2

Rotor leakage impedance at stand still

= r22 + x22

At any slip s, rotor

= r22 + (sx2 )2

Per phase rotor current at stand still

E
=
r22 + x22

Per phase rotor current at any slip s is given by


SE2 E2
I2 = =
r22 + (sx2 )2 (r1 /s)2 + x22

The rotor current I2 lags the rotor voltage E2 by rotor power factor angle 2 given by
sx
2 = tan1 2
r 2

gradeup 21
gradeup

Perr phase power input to rotor is

Pg = F2 I2 cos 2
Per phase rotor resistance
cos 2 =
Per phase rotor impedance

r2 /s
=
(r2 /s)2 + (x2 )2

r2 /s
Pg = E2 I2
(r2 /s)2 + (x2 )2
`
E2 r2
= I2
(r2 /s)2 + (x2 )2 s

r2
= I22 s
Pg is the power transferred from stator to rotor across the air gap. There fore Pg is called air
gap power
r
Pg = I22 2 s
2 1S
= I2 r2 + I22 r2
S

Pg = (Rotor ohmic loss) + Internal mechanical power developed in rotor (Pm )


= S Pg + (1 S)Pg

1S
Pm = (1 S) Pg = I22 r2
S

S
Rotor ohmic loss = Pm = SPg
1S

Internal (or gross) torque developed per phase is given by

Internal mechanical power developed inrotor


Te =
Rotor speed in mechanical radian per sec

Pm (1S)Pg Pg
Te = r
= (1S)s
= s

Electromagnetic torque Te can also be expressed as

Pg 1 I22 r2 Rotor ohmic loss


Te = s
= =
s S (s ) slip
Rotor ohmic loss
Te = (s ) slip

gradeup 22
gradeup
Power available at the shaft can be obtained from Pg as follows.
Output or shaft power, Psh = Pm Mechanical losses

Mechanical losses implies frication and windage losses

Psh = Pg Rotor ohmic loss Friction and windage losses


= Net mechanical power output or net power output
sh P Psh
Output or shaft torque Tsh = = (1s) s
Rotor speed

If the stator input is known. Then air gap power Pg is given by


Pg = stator power input stator I 2 R loss stator core loss.

Ratio of Rotor input power, rotor copper losses and gross mechanical output is
1
Ir2 R 2 /s : Ir2 R 2 : Ir2 R 2 1
s
1 : S : (1 S)
Rotor copper losses = S Rotor input
Gross mechanical output =(1 S) Rotor input.
S
Rotor copper losses = (Gross Mechanical output)
1S
Efficiency of the rotor is approximately
Gross mechanical power output
Equal to rotor = Rotor input
(1S) Rotor input
=
Rotor input
=1S
NS N
=1
NS
N
=
Ns
N
rotor Ns

Total torque is
m Ve2 r2
Te = r2 2
Nm
s Re + + (x2 + Xe )2 s
s
m is the number of stator phases.
Torque equation can be written as
m r
Te = I22 s2
s
m
Te = rotor input per phase.
s

gradeup 23
gradeup
Thus the slip SmT at which maximum torque occurs is given by
r2
SmT =
Re2 + X2

Substituting the value of maximum slip in the torque equation, gives maximum torque
m Ve2
Tem =
s
2Re + Re2 + X22

r2
If stator parameters are neglected then applying maximum transfer theorem to r2 /s then
s
=x2

Slip corresponding to maximum torque is


r2
Sm = x2 (Breakdown slip)

Nm = Ns (1 Sm )
Nm = Ns (1 R 2 /x2 )

Nm is the stalling speed at the maximum torque

Starting torque:-
At starting, slip S = 1.00, starting torque is given by
m Ve2 r2
Test = s
(Re + r2 )2 + X2

Motor torque in terms of :


The torque expression of an induction motor can also be expressed in terms of maximum
S
torque Tem and dimension less ratio . In order to get a simple and approximate
Sm,T
expression, stator resistance r1 , or the stator equivalent resistance R e , is neglected.
2Re + Re2 + X2
T r2
Te = r 2
s
em Re + 2 + X2
s

Since r1 or Re is neglected
Te 2X r2
Tem
= r 2
s
2 + X2
s

The slip at which maximum torque occurs is


r
SmT = 2 r2 = SmT X
X
Te 2X SmT X
= X 2

Tem S
mT + X2 s
s
T 2
Te = SmT S
em +
S SmT

2Tem
Te = SmT S
+
S SmT

gradeup 24
gradeup
Losses and efficiency :-
There are three cases in iron losses.
Case (i) : If the ratio of voltage to frequency is constant and flux is also constant then
Iron loss = Hysteresis loss + eddy current loss

Ph = K h + Bm1.6 Pe = K e f 2 Bm2
V V
Given is constant. As Bm
f f
Bm is constant
Ph f and Pe f 2
Case (ii) : If the ratio of voltage to frequency is not constant and flux is also not constant
v
const const
f

Ph = K h f Bm1.6 Pe = K e f 2 Bm
2

Ph v1.6 f 0.6 Pe v 2

Case (iii) : If frequency is constant and voltage is variable then


1.6
Ph = K h f Bm Pe = K h f 2 Bm
2

v 1.6
= Kh f
f

Ph v1.6 Pe v12

Short circuit current with normal voltage applied to stator is


V
I = Ibr Vbr

I = short circuit current with normal voltage


Ibr = short circuit current with voltage Vbr .
Power factor on short circuit is found from
Pbr = 3 Vbr Ibr cos br
Pbr
Cos br =
3 Vbr Ibr

As Pbr is approximately equal to full load copper losses


Pbr
R br = Ibr2

The blocked rotor impedance is


Vbr
Zbr =
Ibr
Blocked rotor reactance = X br = Zbr 2 R br2
Efficiency of Induction machines :-
output power
Generally efficiency = input power
Net mechanical output Net electrical output
Efficiency of Induction motor = Efficiency of Induction generator =
Electrical power input mechanical power input

gradeup 25
gradeup

GD Psc 3 Isc2 r1
= 3 Isc2 r1
GF

Wound rotor
GD I22 r2 r2 I 2
= I12 r1
= I2
GF r1 1

Direct on line (across the line) starting :-


The relation between starting torque and full load torque is
1 r2
Te = I22
s s
r
Te.st I22.st 2
= 1
r2
Te.fl I22.ft
Sfl

I 2
= 2 st Sfl
I2 fl
The above equation valids of rotor resistance remains constant.
Te.st I 2
Te.fl
= Ist Sfl
fl

Ist (Effective rotor to stator turns ratio) I2 st


Where Ifl
= (Effective rotor to stator turns ratio) I2 fl
Per phase short circuit current at stand still (or at starting) is,
V1
Isc =
Zsc

Where Zsc = (r1 + r2 ) + j(x1 + x2 )


Here shunt branch parameters of equivalent circuit are neglected.
Therefore, for direct switching,
V1
Ist = Isc =
Zsc

Test I 2

Tesf
= Isc Sfl .
fl

Stator resistor (or reactor) starting :-


Since per phase voltage is reduced to xv, the per phase starting current Ist is given by
xv
Ist = 1 = xIsc
Z sc
Te.st I 2
As be fore
Te.fl
= Ist Sfl
fl
xI 2
= I sc Sfl
fl

In an induction motor, torque (voltage)2

starting torque with reactor starting xv 2


= v 1 = x2
starting torque with direct switching 1

gradeup 26
gradeup

Auto transformer starting :-


Per phase starting current from the supply mains is Ist = x 2 Isc

Te.st Per phase starting current in motor winding


= Sfl
Te fl Perphase motor full load current

Te.st Ist Isc


Te.fl
= Ifl2
Sfl

Test with an autotransformer xv 2


= v 1 = x2
Test with direct switching 1

Star delta method of starting :


starting torque with star delta starter

starting torque with direct switching in delta
V 2
L 1
3
= [V 2 =
L] 3
star delta starter also reduces the starting torque to one third of that produced by direct switching
in delta.
With star delta starter, a motor behaves as if it were started by an auto transformer starter with x =
1
= 0.58 i.e with 58% tapping.
3
1 2r 1 2
Starting torque with star delta starter Te .st I
ws st .y
12 I 1 I d 2
3 st .d
= 1 r = (Ifl .d )2
Sfl = I sc . d Sfl
Full load torque with startor winding in delta,Tefld (I )2 2 3 fl .
ws fl d Sfl

gradeup 27

S-ar putea să vă placă și