Sunteți pe pagina 1din 8

Medium-Voltage

Equipment
3AG01 / 3AF01 Catalog HG 11.41
2002
Outdoor Vacuum Circuit-Breakers
up to 40.5 kV
Contents

Page

Application

Introduction 3
Typical uses 3
Features 3

Technical Data

3AG01
Dimensions 4
Product range 5

Technical Data

3AF01
Dimensions 5
Product range 5

Secondary Equipment

Operation 6
Accessories 6

Construction

General description 7
Maintenance, tests 7

2 Siemens HG 11.41 2002


3AG01 / 3AF01 Outdoor Vacuum Circuit-Breakers up to 40.5 kV

Application

Introduction Typical uses Features

The Siemens outdoor vacuum Transformer substations and Fully type-tested


circuit-breaker types 3AG01/ switching substations operated Conforms to IEC standards
3AF01 are structure-mounted, by:
easy-to-install outdoor vacuum High electrical and mecha-
Automobile industry nical service life
circuit-breaker for use in 12/36/
40.5 kV systems. They are a Cement industry No fire hazard
porcelain-clad, three-pole Chemical industry Suitable for auto-reclosing
circuit-breakers fitted with reli-
Electrochemical plants duty
able and well-proven vacuum
interrupters from Siemens. Iron and steel works Negligible maintenance
Adequate phase clearances and Lignite open-cast mines High reliability
heights have been provided
to meet the standard safety Mining industry Perfect harmony between
requirements. They are suitable Petrochemical plants vacuum interrupter and
for direct connection to over- operating mechanism
Petroleum industry
head lines.
Pipeline installations
The design of 3AG01/3AF01 in-
corporates a minimum number Power supply utilities
of moving parts and a simple Rolling mills
assembly which ensures a long
electrical and mechanical ser- Distribution network
vice life. It has all the advan- Shipbuilding industry
tages inherent to the use of
Textile, paper and food
vacuum interrupters like low
industries
drive and arc energy, light
weight, shock-proof perfor-
mance and many more.
HG11_41-155afp.eps

HG11_41-156afp.eps

3AG01 3AF01
Maximum ratings Maximum ratings
12 kV /25 kA /1600 A 40.5 kV /31.5 kA /2000 A

Siemens HG 11.41 2002 3


3AG01 / 3AF01 Outdoor Vacuum Circuit-Breakers up to 40.5 kV

Technical Data

Type 3AG0144 3AF0143 3AF0144 3AF0153 3AF0154


Rated voltage, 12 kV, 50 or 60 Hz 36 kV 1), 50 or 60 Hz 36 kV 1), 50 or 60 Hz 36 kV 1), 50 or 60 Hz 36 kV 1), 50 or 60 Hz
frequency
Rated current 1600 A 1600 A 2000 A 1600 A 2000 A
Rated power-frequency 28 kV 70 kV 70 kV 70 kV 70 kV
withstand voltage
Rated lightning impulse 75 kV 170 kV 2) 170 kV 2) 170 kV 2) 170 kV 2)
withstand voltage (peak)
Rated short-circuit 25 kA 25 kA 1) 25 kA 1) 31.5 kA 1) 31.5 kA 1)
breaking current
Rated short-circuit 63 kA 62.5 kA 62.5 kA 80 kA 80 kA
making current (peak)
Rated short-time 25 kA, 3 s 25 kA, 3 s 25 kA, 3 s 31.5 kA, 3 s 31.5 kA, 3 s
withstand current
Rated operating O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
sequence O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Service conditions 25 C to + 55 C 3) 25 C to + 55 C 3) 25 C to + 55 C 3) 25 C to + 55 C 3) 25 C to + 55 C 3)
Degree of protection IP 55 IP 55 IP 55 IP 55 IP 55
Approx. total weight 515 kg 880 kg 880 kg 880 kg 880 kg
Notes: 1) 40.5 kV, 31.5 kA, 4 s on request.
2) Higher withstand voltages on request.
3) 40 C on request.

3AG01
Dimensions Front view Side view
555 555
350 350 185 185 Item Description
M
A Interrupter assembly
A D B Vacuum interrupter
B E C Support insulator
C D Top terminal
E Bottom terminal
F F Operating mechanism housing
L Front G Steel structure
H H Plexiglass for mechanical indications
3350 10

2560 10

K (ON-OFF indicator, spring charged


2960 10

2610 10

K K indicator, operation counter)


J Gland plate for control cable
J 395
1790 10

K Earthing terminal
G
L Facility for padlock
HG11_41-2563-agpen.eps

1390

M Terminal connector (optional)


400

850

Foundation plan Foundation detail Top/bottom terminal


1485 70 aluminium (D,E)
Foundation bolts
180 1265 are optional
90

50

M16 x 400 14 diam. (4x)


HG11_41-2564-agpen.eps
HG11_41-2565-agpen.eps
420

350
850

400

80
40

M16 (8x)

1625 20 40 20

Note: Extended structure for mounting instrument transformers can be provided as an option.

4 Siemens HG 11.41 2002


3AG01 / 3AF01 Outdoor Vacuum Circuit-Breakers up to 40.5 kV

Technical Data

Product range

Circuit-breaker Circuit-breaker with Circuit-breaker with Circuit-breaker with


current transformer voltage transformer current transformer and
voltage transformer

Voltage Voltage
transformer transformer

Circuit- Circuit- Circuit- Circuit-


HG11_41-2570-agpen.eps
HG11_41-2569-agpen.eps

HG11_41-2571-agpen.eps

HG11_41-2572-agpen.eps
breaker breaker breaker breaker

Current Current
transformer transformer

3AF01
Dimensions Front view Side view
725 725 275 275
350 350 Item Description
A Interrupter assembly
A E
B Vacuum interrupter
B F C Support insulator
C D Base frame
E Top terminal
D F Bottom terminal
256

L L G Operating mechanism housing


H Steel structure
3720 +10

J Plexiglass for mechanical indications


(ON-OFF indicator, spring charged
3020 10

G Front indicator, operation counter)


1565 10

M K Gland plate for control cable


J
L L L Earthing terminal
L
K M Facility for padlock
HG11_41-2566-agpen.eps

1585 10

H
600

1730 650
1930
Foundation detail Top/bottom terminal
aluminium (E,F)
Foundation plan Foundation bolts 14 diam. (4x)
are optional
50

M16 x 400
HG11_41-2567-agpen.eps

M16 (8x)
800

600

HG11_41-2568-agpen.eps

90
40
350

350 75 75
1730 20 40 18
50

Note: Extended structure for mounting instrument transformers can be provided as an option.

Siemens HG 11.41 2002 5


3AG01 / 3AF01 Outdoor Vacuum Circuit-Breakers up to 40.5 kV

Secondary Equipment

Operation, accessories

Operating mechanism
The well-proven operating mechanism
of indoor vacuum circuit-breakers
3AG01/3AF01 have been incorporated
in the outdoor vacuum circuit-breaker.
They are equipped with a motor spring
stored-energy operating mechanism.
The motor can be operated either by
AC or DC standard supply voltages.

Features
Integrated mechanical breaker
position indication CLOSED/OPEN,
spring charged indication and
mechanical counter
Unambiguous assignment of actuat-
ing openings and control elements
to corresponding breaker position
indications
All switching operations are from
front including cable termination
Ergonomically favorable height of all
control elements from ground

Instrument transformers
On clients requirement the breakers
can be supplied with an extended
structure for mounting outdoor current
and voltage transformers on the
incoming and outgoing supply sides,
3AF01 vacuum

HG11_41-157afp.eps
respectively.
circuit-breaker
Accessories
The following accessories can
be provided:
Auxiliary switch
(5 NO+5 NC or 11 NO+11 NC)
Closing solenoid
(AC/DC voltages) Operating mechanism
Tripping solenoid chamber of 3AF01
(AC/DC voltages)
HG11_41-159afp.eps
HG11_41-158afp.eps

Emergency manual
spring charging in the
event of loss of
control supply

6 Siemens HG 11.41 2002


3AG01 / 3AF01 Outdoor Vacuum Circuit-Breakers up to 40.5 kV

Construction

General description Maintenance, tests


Suitability Construction Arc quenching principle Maintenance
Siemens outdoor vacuum The vacuum interrupter is When the contacts separate, The Siemens outdoor
circuit-breakers are designed to mounted in a porcelain insula- the current to be interrupted vacuum circuit-breakers are
handle all switching duties that tor to form an interrupter as- initiates a metal-vapour arc practically maintenance-
occur in primary distribution sembly. For a cross-sectional discharge. Current continues free and need minimum
systems including rapid auto- view of a typical interrupter flowing through the metal- attention of operating per-
reclosing. The breakers are assembly of 36 kV, see below. vapour plasma until the next sonnel. Maintenance is
extremely reliable in service, Three such assemblies along current zero. The arc is then confined to merely clean-
require minimum maintenance with the bottom insulators are extinguished and the conduc- ing and lubricating of the
and have a long service life mounted on a baseframe tive metal vapour condenses operating mechanism.
due to the use of vacuum inter- which has a common operating on the metal surfaces within a Change of vacuum inter-
rupters. They can be used in all shaft. This assembly is moun- few microseconds. As a result, rupter is not foreseen
kinds of environments by virtue ted on a steel structure, inten- the dielectric strength between throughout the normal life
of their small size and weight, ded to locate the power termi- the contacts builds up very of a circuit-breaker in a dis-
low vibration operation and nals at a safe distance above rapidly. tribution system. Vacuum
they are unaffected by tempe- the ground. The structure also The contacts are so designed interrupters are designed
rature or fire risks. encloses the operating mecha- that the self generated axial for 30,000 operations at
nism. All the control and actu- field causes the arc to remain rated current. Necessary
ating devices are installed in diffuse even at high currents. mechanical arrangement is
this mechanism housing. The This keeps the stress on the also provided to check the
circuit-breaker can be either contact surfaces uniform and presence of vacuum as a
operated electrically from a any local melting is avoided precommissioning and in
remote control room or locally when interrupting large cur- service check.
by hand. The necessary me- rents.
chanical indicating devices for Tests /Standards
ON/OFF indication, spring The use of special copper
chromium contacts ensures Siemens outdoor vacuum
charged indication and opera- circuit-breakers
tion counter are provided in that the chopping current is
less than 5 A. 3AG01/3AF01 have been
the mechanism housing. Also fully type tested and con-
mounted in the mechanism form to the latest IEC/IS
housing are the special cage standards.
clamp type terminal blocks for
control cables when required. Seismic capacity
The outdoor vacuum
circuit-breakers are design-
ed in accordance with
internationally accepted
requirements. Specific
Ventilation tube confirmations on request.

Top aluminium flange


Notes
If not stated otherwise on
the individual pages of this
catalog, we reserve the
right to include modifica-
Porcelain insulator
tions, especially regarding
dimensions and weights.
Drawings and photographs
are not binding.
All product designations
Vacuum interrupter used are trademarks
or product names of
Siemens AG or of other
suppliers.
HG11_41-2573-agpen.eps

If not stated otherwise, all


dimensions in this catalog
Bottom aluminium flange are given in mm.

Responsible for:
Current link Technical contents:
Siemens Ltd.
Switching rod Kalwa Switchboard Works
PTD/M-PM
Typical cross-sectional view Thane 400602
of a 36 kV /40.5 kV pole India

Siemens HG 11.41 2002 7


For further details, please contact:
Siemens AG Siemens Ltd.
Power Transmission and Distribution Power Transmission and Distribution
Medium Voltage Division Medium Voltage Division
Department PTD M C S Kalwa Business Centre, PTD/EXP (International Sales)
Postfach 32 20 Thane Belapur Road
91050 Erlangen Thane 400 601
Germany India
Tel.: +49 9131 7 33678 Tel.: +91 22 27623635
Fax: +49 9131 7 34654 Fax: +91 22 27623723
www.siemens.com/ptd

www.siemens.com/medium-voltage-devices Printed in India


KGK 12.02 4.0 8 En 6001/D6251