Penerangan Kantor

Bagian Perencanaan
Date: 05-05-2017
Customer: Universitas 17 Agustus Surabaya
Customer code: Fakultas Teknik
Customer Representative: Teknik Elektro

Designer: Muhammad Sholeh

The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed
relationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire
positioning, reflection properties and electrical supply.

PT. SARANA MULTI SENTOSA


Puri Surya Jaya, Cluster Vancouver
Blok B1 No. 20
Gedangan - Sidoarjo 61254

Telephone: +62318012950
Fax: +62318012953
Mobile Phone: +6281331174788
E-Mail: saranadm@saranadwimakmur.com
CalcuLuX Indoor 5.0b
Penerangan Kantor PT. SARANA MULTI SENTOSA
Bagian Perencanaan Date: 05-05-2017

Table of Contents

1. Summary 3

1.1 Room Summary 3


1.2 Project Luminaires 3
1.3 Calculation Results 3

2. Calculation Results 4

2.1 Grid: Graphical Table 4


2.2 Grid: Iso Contour 5

3. Luminaire Details 6

3.1 Project Luminaires 6

CalcuLuX Indoor 5.0b Philips Lighting B.V. Page: 2/6


Penerangan Kantor PT. SARANA MULTI SENTOSA
Bagian Perencanaan Date: 05-05-2017

1. Summary

1.1 Room Summary

Room Dimensions Surface Reflectance


Width 5.00 m Ceiling 0.50
Length 10.00 m Left Wall 0.30
Height 3.00 m Right Wall 0.30
Working Plane Height 0.80 m Front Wall 0.30
Back Wall 0.30
Floor 0.10
Room Position (Front Bottom Left)
X -2.50 m
Y -5.00 m
Total Average Room Surface Luminance (cd/m2):
Ceiling Left Right Front Back Floor
6.4 14.8 14.8 15.1 15.1 10.7

Unified Glare Rating (CIE): Undefined


The overall maintenance factor used for this project is 0.80.

1.2 Project Luminaires

Code Qty Luminaire Type Lamp Type Power (W) Flux (lm)
A 6 TBS300/236 M1 2 * TL-D36W 72.0 2 * 3200
B 2 FBH220/226 AL.REFLECTOR 2 * PL-C/2P26W 66.4 2 * 1800

The total installed power: 0.56 (kWatt)

Number of Luminaires Per Arrangement:


Luminaire Code
Arrangement Power (kWatt)
A B
Room Block 6 0 0.43
Room Block1 0 2 0.13

1.3 Calculation Results

(Il)luminance Calculations:
Calculation Type Unit Ave Min/Ave Min/Max Result
Grid Surface Illuminance lux 394 0.60 0.44 Total

CalcuLuX Indoor 5.0b Philips Lighting B.V. Page: 3/6


Penerangan Kantor PT. SARANA MULTI SENTOSA
Bagian Perencanaan Date: 05-05-2017

2. Calculation Results

2.1 Grid: Graphical Table

Grid : Grid at Z = 0.80 m


Calculation : Surface Illuminance (lux)
Result Type : Total
7
6
5

241 321 376 389 379 379 389 376 321 241
4

236 310 373 387 377 377 387 373 310 236
A A

271 361 433 468 469 469 468 433 361 271
3

300 389 469 514 533 533 514 469 389 300
2

B
303 398 482 530 542 542 530 482 398 303
1

270 359 433 460 461 461 460 433 359 270
Y(m)

A A
0

270 359 433 460 461 461 460 433 359 270
-1

303 398 482 530 542 542 530 482 398 303

B
300 389 469 514 533 533 514 469 389 300
-2

271 361 433 468 469 469 468 433 361 271
-3

236 310 373


A 387 377 377 387 373
A 310 236
-4

241 321 376 389 379 379 389 376 321 241
-5
-6
-7

-6.5 -5.5 -4.5 -3.5 -2.5 -1.5 -0.5 0.5 1.5 2.5 3.5 4.5 5.5 6.5
X(m)

A TBS300/236 M1
B FBH220/226 AL.REFLECTOR

Average Min/Ave Min/Max Project maintenance factor Scale


394 0.60 0.44 0.80 1:75

CalcuLuX Indoor 5.0b Philips Lighting B.V. Page: 4/6


Penerangan Kantor PT. SARANA MULTI SENTOSA
Bagian Perencanaan Date: 05-05-2017

2.2 Grid: Iso Contour

Grid : Grid at Z = 0.80 m


Calculation : Surface Illuminance (lux)
Result Type : Total
7.5
6.5
5.5

300
4.5

250

A A

250
3.5

35

40
0
45

350
0
2.5

500

300
1.5
0.5

250
Y(m)

A A
400

250
-0.5

0
45

500
-1.5

300

B
-2.5

350

0
0

45
40
-3.5

250

A A
35

250
-4.5

300
-5.5
-6.5
-7.5

-6.5 -5.5 -4.5 -3.5 -2.5 -1.5 -0.5 0.5 1.5 2.5 3.5 4.5 5.5 6.5
X(m)

A TBS300/236 M1
B FBH220/226 AL.REFLECTOR

Average Min/Ave Min/Max Project maintenance factor Scale


394 0.60 0.44 0.80 1:75

CalcuLuX Indoor 5.0b Philips Lighting B.V. Page: 5/6


Penerangan Kantor PT. SARANA MULTI SENTOSA
Bagian Perencanaan Date: 05-05-2017

3. Luminaire Details

3.1 Project Luminaires

TBS300/236 M1 2xTL-D36W/840 Luminous Intensity Diagram (candela/1000 lumen)


120o 150o 180 o 150o 120o

90o 90o

60o 60o
Light output ratios
DLOR : 0.73
ULOR : 0.00
TLOR : 0.73 250
Ballast : Electronic
Lamp flux : 3200 lm
Luminaire wattage : 72.0 W
Measurement code : LVW0858300

30o 0o 30o
C = 180o Imax C = 0o
C = 270o C = 90o

FBH220/226 AL.REFLECTOR 2xPL-C/2P26W/840 Luminous Intensity Diagram (candela/1000 lumen)


120o 150o 180 o 150o 120o
Light output ratios
DLOR : 0.57
ULOR : 0.00
TLOR : 0.57
Ballast : Standard 90o 90o
Lamp flux : 1800 lm
Luminaire wattage : 66.4 W
Measurement code : LVT2600314
60o 60o

150

30o 0o 30o
C = 180o Imax C = 0o
C = 270o C = 90o

CalcuLuX Indoor 5.0b Philips Lighting B.V. Page: 6/6