Documente Academic
Documente Profesional
Documente Cultură
FUNCTION - 2
INTRODUCTION:
The learning objectives that are used in the detailed teaching syllabus,
Column 3 Methods for demonstrating competence and Column 4
Criteria for evaluating competence in Table A-III/2 of the STCW Code, set
out the methods and criteria for evaluation.
LEARNING OBJECTIVES:
Upon successful completion of the training under this Function, trainees shall
be expected to have gained the minimum knowledge, understanding and
proficiencies needed to carry out and undertake at the management level the
tasks, duties and responsibilities for electrical, electronic and control
engineering of ships powered by main propulsion machinery of 3,000 kW
propulsion power or more.
SCOPE:
Function 2 of this updating course covers the topics relating to the gaps that
were identified in order for Management Level Marine Engineer Officers who
were certified under the STCW 1978 Convention, as amended in 1995 to
meet the additional knowledge, understanding and proficiencies (KUPs)
UNDER THE 2010 STCW Manila Amendments for Electrical, Electronic and
Control Engineering at the Management Level
FUNCTION 2 - UPDATING
ELECTRICAL, ELECTRONICS AND CONTROL ENGINEERING
MODULE 1
Manage Operation of Electrical and Electronic Control Equipment
Module 1
A bipolar junction
transistor (BJT or bipolar transistor) is a
type of transistor that relies on the contact of
two types of semiconductor for its operation.
BJTs can be used as amplifiers, switches, or
in oscillators. BJTs can be found either as
individual discrete components, or in large
numbers as parts of integrated circuits.
As with the previous curve, the graph shown here should only be
regarded as a 'typical' example as the precise result will vary a bit from
device to device and with the temperature, etc.
BIAS CIRCUIT
Field-effect transistor
Thyristors
SCRs
A silicon-controlled
rectifier (or semiconductor-
controlled rectifier) is a four-
layer solid state current controlling
device. The name "silicon controlled
rectifier" is General Electric's trade name
for a type of thyristor. The SCR was
developed by a team of power
engineers led by Gordon Hall[1] and
commercialized by Frank W. "Bill"
Gutzwiller in 1957.
GTO
DIACs
TRIACs
Resistor values are normally shown using colored bands. Each color
represents a number as shown in the table.
The standard color code cannot show values of less than 10. To show
these small values two special colors are used for the third band: gold,
which means 0.1, and silver, which means 0.01. The first and
second bands represent the digits as normal.
For example
Red, violet, gold bands represents 27 x 0.1 = 2.7
Green, blue, silver bands represent 56 0.01 = 0.56
You may have noticed that resistors are not available with every
possible value, for example 22k and 47k are readily available, but 25k
and 50k are not!
Why is this? Imagine that you decided to make resistors every 10
giving 10, 20, 30, 40, 50 and so on. That seems fine, but what happens
when you reach 1000? It would be pointless to make 1000, 1010, 1020,
1030 and so on because for these values 10 is a very small difference,
too small to be noticeable in most circuits. In fact, it would be difficult
to make resistors sufficiently accurate.
To produce a sensible range of resistor values you need to increase the
size of the 'step' as the value increases. The standard resistor values
are based on this idea and they form a series that follows the same
pattern for every multiple of ten.
The E6 series (6 values for each multiple of ten, for resistors with 20%
tolerance)
10, 15, 22, 33, 47, 68 ... then it continues 100, 150, 220, 330, 470,
Variable Resistors
Variable resistors consist of a resistance track with
connections at both ends and a wiper which moves along
the track as you turn the spindle. The track may be made
from carbon, cermet (ceramic and metal mixture) or a coil
of wire (for low resistances). The track is usually rotary but
straight track versions, usually called sliders, are also
available.
Variable resistors may be used as a rheostat with two connections (the
wiper and just one end of the track) or as a
potentiometer with all three connections in use.
Miniature versions called presets are made for setting
up circuits, which will not require further adjustment.
POTENTIOMETER
Variable resistors used as potentiometers have all three terminals
connected. This arrangement is normally used to vary voltage, for
example to set the switching point of a circuit with a sensor, or control
the volume (loudness) in an amplifier circuit. If the terminals at the
ends of the track are connected across the power supply then the
wiper terminal will provide a voltage that can be varied from zero up to
the maximum of the supply.
PRESETS
These are miniature versions of the standard variable resistor. They are
designed to be mounted directly onto the circuit board and adjusted
only when the circuit is built. For example to set the frequency of an
alarm tone or the sensitivity of a light-sensitive circuit. A small
screwdriver or similar tool is required to adjust presets.
Multi turn presets are used where very precise adjustments must be
made. The screw must be turned many times (10+) to move the slider
from one end of the track to the other, giving very fine control.
Capacitor
Capacitors store electric charge. They are used with resistors in timing
circuits because it takes time for a capacitor to fill with charge. They
are used to smooth varying DC supplies by acting as a reservoir of
charge. They are also used in filter circuits because capacitors easily
pass AC (changing) signals but they block DC (constant) signals.
Capacitor values can be very difficult to find because there are many
types of capacitor with different labeling
systems!
Electrolytic Capacitors
Electrolytic capacitors are polarized and they must be connected the
correct way round, at least one of their leads will be marked + or -.
They are not damaged by heat when soldering. There are two designs
of electrolytic capacitors; axial where the leads are attached to each
end (220F in picture) and radial where both leads are at the same end
(10F in picture). Radial capacitors tend to be a little smaller and they
stand upright on the circuit board.
However, older ones use a colour-code system that has two stripes (for
the two digits) and a spot of colour for the number of zeros to give the
value in F. The standard color code is used, but for the spot, grey is
Examples:
Many small value capacitors have their value printed but without a
multiplier, so you need to use experience to work out what the
multiplier should be.
Example:
Polystyrene Capacitors
This type is rarely used now. Their value (in pF)
is normally printed without units. Polystyrene
capacitors can be damaged by heat when
soldering (it melts the polystyrene!) so you
should use a heat sink (such as a crocodile clip).
Clip the heat sink to the lead between the capacitor and the joint.
Variable Capacitor
Variable capacitors are mostly used in radio tuning
circuits and they are sometimes called 'tuning
capacitors'. They have very small capacitance values,
typically between 100pF and 500pF (100pF = 0.0001F).
The type illustrated usually has trimmers built in (for
making small adjustments - see below) as well as the main variable
capacitor.
Trimmer Capacitor
This type of variable capacitor (a trimmer) is operated
with a small screwdriver or similar tool. It is designed to
be set when the circuit is made and then left without
further adjustment.
Instrument transformers
Thermistor
Lamp replacement
The most economic point in lamp life can be assessed in two ways:
Switches
There are three important features to consider when selecting a switch:
Switch Contacts
Switch contacts are rated with a maximum voltage and current, and
there may be different ratings for 4AC and DC. The AC values are
higher because the current falls to zero many times each second and
an arc is less likely to form across the switch contacts.
For low voltage electronics projects the voltage rating will not matter,
but you may need to check the current rating. The maximum current is
less for inductive loads (coils and motors) because they cause more
sparking at the contacts when switched off.
Type of Switches
ON-OFF - Single Pole, Single Throw = SPST A simple on-off switch. This
type can be used to switch the power supply to a circuit. When used
with mains electricity this type of switch must be in the live wire, but it
is better to use a DPST switch to isolate both live and neutral.
ON OFF - Push-to-
make = SPST
Momentary
A push-to-make switch returns to its normally open (off) position when
you release the button, this is shown by the brackets around ON. This
is the standard doorbell switch.
ON-(OFF) - Push-to-break = SPST Momentary A push-to-break switch
returns to its normally closed (on) position when you
release the button.
ON-ON - Single Pole, Double Throw
= SPDT This switch can be on in both
positions, switching on a separate device in each case.
It is often called a changeover switch. For example, a
SPDT switch can be used to switch on a red lamp in one
position and a green lamp in the other position.
Drum-type controllers
For large motors and for heavy duties a drum type starter is
appropriate, particularly where frequent starting or speed regulation is
required such as for winches, i.e. cranes etc. For still heavier duties or
where automatic operation by pushbutton, float switch, pressure
switch, thermostat, etc. is required contactor type starters will be
necessary.
Transformers
The same
voltage is
Induction regulators
Diodes devices
Some designs use thyristors but it is more common for all the devices
to be silicon diodes. Diodes are available in either polarity so it is
essential when fitting replacements to maintain correct polarity.
Alternatively some diodes are of a double-sided construction in which
case it is essential to fit them the correct way round.
Not all diodes are clearly marked but by using an Avometer or similar
instrument the conducting direction can be determined.
DIODES
Function
Diodes allow electricity to flow in only one direction. The arrow of the
circuit symbol shows the direction in which the current can flow. Diodes
are the electrical version of a valve and early diodes were actually
called valves.
Reverse Voltage
When a reverse voltage is applied a perfect diode does not conduct,
but all real diodes leak a very tiny current of a few A or less. This can
ZRC TRAINING CENTER PHILS. INC. CEBU Page 22
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
be ignored in most circuits because it will be very much smaller than
the current flowing in the forward direction. However, all diodes have a
maximum reverse voltage (usually 50V or more) and if this is exceeded
the diode will fail and pass a large current in the reverse direction, this
is called breakdown.
Testing diodes
You can use a multimeter or a simple tester (battery, resistor and LED)
to check that a diode conducts in one direction but not the other. A
lamp may be used to test a rectifier diode, but do NOT use a lamp to
test a signal diode because the large current passed by the lamp will
destroy the diode!
For general use, where the size of the forward voltage drop is less
important, silicon diodes are better because they are less easily
damaged by heat when soldering, they have a lower resistance when
conducting, and they have very low leakage currents when a reverse
voltage is applied.
Bridge rectifiers
There are several ways of connecting diodes to make a rectifier to
convert AC to DC. The bridge rectifier is one of them and it is available
in special packages containing the four diodes required. Bridge
rectifiers are rated by their maximum current and maximum reverse
voltage. They have four leads or terminals: the two DC outputs are
labelled + and -, the two AC inputs are labeled.
Zener Diodes
Zener diodes are used to maintain a fixed voltage. They are designed
to reakdown in a reliable and non-destructive way so that they can
be used in reverse to maintain a fixed voltage across their terminals.
The diagram shows how they are connected, with a resistor in series to
limit the current.
Example:
a = anode k = cathode
A soldering iron is a tool with a metal tip that gets really hot. Were talking
like 800 degree Fahrenheit, though you can adjust the temperature on a
good iron. Its job is to transfer heat to things like wires, transistor leads, and
pads on PCBs. After the appropriate areas are heated properly, solder is
applied. If you plan on soldering, then youre better off spending $30-$40 on
a 20-30 Watt iron instead of on a cheap $15 one. Youll get a longer-lasting
tool that will work for a much wider variety of applications and youll get
proper heat control to boot. There are also soldering guns available, but you
should only use these when repairing thick cables and never on PCBs, as the
tips have a live voltage running through them that can damage sensitive
electronics.
Solder is a thin tube, usually rolled in spools, made of various metal alloys.
Its job is to hold the individual components together. The individual
components and their quantities can vary, but for computer electronics,
youre usually looking at a 60% tin and 40% lead. Lead-free solder is also
available, though it has higher melting temperatures and less wettability,
meaning you may need a better soldering iron to use it and removing it can
be more tedious. Lead-free solder is better for the environment and has
other benefits, and they function more or less the same way.
The inside of the tube is filled with flux, a substance that gets rid of
oxidation and helps clean the surfaces involved in the fusing process. For
electronic use, you want rosin-core/rosin-flux solder. Acid-flux is used in
plumbing and the acid can damage the sensitive components on PCBs.
Many whove never used a soldering iron are afraid of damaging equipment,
but more important is the danger to yourself! Soldering irons get really hot
(think, and solder itself is molten metal. Be sure to wear safety glasses, keep
loose clothing and hair out of the way, and be careful with your fingers.
Better still, use protective gloves. Solder can contain lead, so be sure to
wash your hands thoroughly after handling it. Its also really important to
work in a well-ventilated area because the fumes from the rosin can cause
damage to your lungs when inhaled. Honestly, its more common sense and
preparation than anything. Just take proper precautions and youll be fine.
In order to conduct heat properly, your soldering iron needs to be free of any
old solder. After being exposed to air, it oxidizes and thus insulates against
heat. We want heat to conduct so that we can apply everything quickly and
efficiently. A dirty tip means that youll have to hold the iron on longer and
risk heat damage to the PCB, and nobody wants that. Keep a wet sponge
handy, and after the soldering iron is fully heated, softly scrape it against the
sponge to remove old solder. The tip should be nice and shiny, or at least
very close to it.
Next, were going to tin the tip. This will protect the tip and allow heat to
conduct better via the presence of new solder. On the hot iron, carefully
apply a small amount of fresh solder and coat the tip. It should still be shiny
if youve done it right. As soon as you tin the tip you should start soldering
your components together. After every few joins, clean and re-tin, and again
before putting your iron away into storage. This will really help increase the
longevity of your tool. A good soldering iron should easily last years this way.
Hold the iron in your dominant hand and a long piece of solder in your other
hand. When soldering two components together, you want to touch the area
where they join with the soldering iron. Hold it there for about a second, then
slide the solder underneath the tip of the iron, sandwiching it to the PCB
(refer to above image, cursor points to solder). Hold it for another second or
two, feeding in how much solder you need. This amount will vary depending
on the project, application, and diameter of the solder, so check your
instructions and study the pictures to get a good idea of the end result.
Now, this is really important. Pull away the solder first, and continue holding
the iron for another second. This allows the solder to continue to melt and
pool, forming a good joint. Then, you can remove the iron. The total process
shouldnt take more than 5 seconds, and usually youre aiming for 3-4.
Wait a few seconds and dont disturb the solder. It cools very quickly, but
moving or blowing on the joint will cause it to deteriorate. A bad solder
connection will look really oxidized, overly dull, and grainy. It also sort of
looks like a ball of solder formed on the area. A good connection should be
smooth and uniform and its sides will be concave. It wont look like a raised
ball, itll look flat.
Desoldering
Snubber circuits
the process of commutating an electric
current.
Electronics Calculators.
Navitron NT888G
Self-steering gear
Smoothing circuits
Stabilization
Integrated circuit
The wire bond PBGA (Plastic Ball Grid Array) is the most common
package type used for the medium i/o count devices. Again, the
package choice is driven by cost (wire bond substrates are cheaper
than flip-chip substrates because of the lower connection density),
relative high density of i/o and better electrical performance than large
leaded packages. The package size is frequently driven by the ball grid
array pitch. Obviously, the package with the balls on 1.27 mm pitch is
much larger than the same number of balls on a 0.5 mm pitch. As a
general rule, the cost of a package substrate and the printed circuit
board scale with area; larger area equals higher cost. But, finer
(smaller) pitch parts increase the cost and complexity of both the
laminate substrate of the package and the cost and complexity of the
printed circuit board. In many cases, the use of 0.5 mm pitch balls will
require a high density interconnect (HDI) printed circuit board, which is
much more expensive than standard printed circuit board technologies.
Having more connections in a small area also increases the layer count
in the printed circuit board. For general use, the most common pitch
seems to be 1 mm.
Flip chip packages are the preferred choice when the best electrical
performance is necessary for high i/o devices. Flip chip packages are
used over a range of power dissipations from less than 1 W to over 100
W.
Measured Thermal Resistance for Three Substrate Types for Flip Chip
360 2525 mm Device Figure 7 shows a pictorial view of a bare die flip
chip package. For low power devices, the standard thermal resistances
for the package are useful as a guide to their performance. Table 3
provides the thermal resistance of a 360 i/o, 25 x 25 mm, exposed-die
flip chip package with three different substrate materials. It is
interesting to contrast the two different ceramic substrates. The high
temperature cofired substrate with approximately 90% alumina has a
conductivity of approximately 16 W/m-K. The metallization is either
tungsten or other glass frit composition with low enough conductivity
that the metallization patterns do not significantly improve thermal
performance of the package. The HiCTE (High Coefficient of Thermal
Expansion) ceramic is a low fired ceramic with a higher glass content
and much lower thermal conductivity, usually about 2 W/m-K, but uses
copper metallization. The copper content must be considered when
determining the conductivity of the substrate. The third common style
of substrate is a plastic laminate, usually consisting of a laminate core
such as BT laminate with large drilled vias and buildup layers of
dielectric and plated copper. The vias in the buildup layers are usually
much smaller diameter and constructed by photolithography or by
laser ablation. At higher powers, most of the heat transfer will be
through a heat sink. Hence, the standard junction to ambient or
junction to board thermal resistances are almost irrelevant. The
relevant thermal metric is jc.
CMRR
The common-mode rejection ratio (CMRR) of a differential
amplifier (or other device) is the rejection by the device of unwanted
input signals common to both input leads, relative to the wanted
difference signal. An ideal differential amplifier would have infinite
CMRR; this is not achievable in practice. A high CMRR is required when
a differential signal must be amplified in the presence of a possibly
large common-mode input. An example is audio transmission
over balanced lines.
Theory
Ideally, a differential amplifier takes the voltages, and on its two
inputs and produces an output voltage ,
where is the differential gain. However, the output of a real
differential amplifier is better described as
The CMRR is defined as the ratio of the powers of the differential gain
over the common-mode gain, measured in positive decibels (thus using
the 20 log rule):
INSTRUMENTATION AMPLIFIER
420 mA
Voltage regulator
F= 1/T
= 1/[(0.693)*R*C]
= 1/[(0.693)*(R1*C1 +R2*C2)
IC applications
If youve come across a circuit diagram for the first time maybe in a
hobby electronics magazine like Everyday Practical Electronics or even
a Haynes car repair manual then you can be forgiven for being a bit
confused. A diagram full of spaghetti-like lines and weird symbols
how on earth do you make sense of it all?
In this special article Ill explain how to interpret even complex circuit
diagrams properly and generally find your way around them with
confidence. Most seasoned electronics hobbyists and technicians can
read them like they were written in plain English, and actually it
doesnt take much practice to understand them, as youll soon
discover.
When our elder sister magazine Practical Electronics was launched
back in 1964, each and every circuit diagram and assembly drawing
was expertly and beautifully drawn entirely by hand, using fantastically
skilled artists and draughtsmen. These days, computer software is
used to draft circuit diagrams on-screen (schematic capture), offering
us the bonus of being able to re-arrange parts with a mouse-click to
obtain the best-looking diagram layout. The design data can then be
fed into a printed circuit board design package and a whole PCB can be
designed and manufactured from that.
Whether hand-drawn or produced on a CAD package, there are some
basic principles that are common to all circuit diagrams. Good circuit
diagram design helps ensure that anyone can pick up a diagram and
Mapping it out
Other times, well definitely not want them to meet each other! For
example a road bridge passing over a road underneath; in electronics
terms, these are times when electrical wires or conductors are
fully insulated from each other and our circuit diagrams need to show
that very clearly. Just imagine the potential problems if we cant figure
it out if something is supposed to be connected to something else!
One major difference between our road map analogy and a circuit
diagram is that a map is geographical: it has to show the location of
roads and towns in correct relation to each other. (One exception is the
world-famous map of the London Underground, a design masterpiece
that shows which tube stations are on which line. But not
geographically.)
At a junction
If lines on a diagram cross each other but you dont see a blob then
the crossing wires are not joined to each other. Sometimes youll see
a hoop to emphasize that wires arent joined together. But thats a bit
old-fashioned these days.
Each component has a unique symbol, and its important that you
learn to recognize what they are. After a little experience youll soon be
reading diagrams with ease. Sometimes the symbol also attempts to
explain how the component works, such as the one-way arrowhead of
a diode (which only conducts one way, but not the other), or a
capacitor, which is physically divided by an internal gap (filled with
a dielectric). Components are labelled with unique serial numbers, e.g.
resistors start with R1, R2 etc, capacitors are labelled C1, C2 in the
circuit diagrams, and so on. Either their values
will also be shown in the drawing or there will be
a separate components list.
In summary:
Joints or junctions where wires or components are electrically
connected to each other are represented by a blob.
Lines that cross each other but do not have a blob,
are not connected to each other.
A battery has two terminals marked + and -. A car battery usually has
+12V and -12V markings. (Its pedantic but technically correct to say
that the use of +12V and -12V is misleading, because it implies that
mathematically theres a potential difference (voltage) of 24V between
the terminals: its markings should really
is +12V and 0V. But ordinary consumers
just know them as the positive and
negative terminals.)
Ground symbols are used to keep circuit diagrams clear and simple:
everything having a ground symbol is connected together, its just that
the wires arent drawn in the circuit diagram itself. Consider them as
invisible common connections through a car body.
Supply rails are the voltage supplies used to power the circuit. They
will be clearly marked with their voltage.
Now you can explain to your car-mechanic friends why all along
theyve been wrong to talk of +12V and -12V of a car battery!
Weve now seen how circuit diagrams describe how components are
joined into a circuit, how blobs indicate junctions in wiring, and weve
explained how power rails and ground symbols show how supply
voltages are distributed around the circuit. Lets move on from our
simple car battery idea and look at electronic circuit diagrams proper.
Apart from simple discrete components joined together by wires (or the
copper tracks of a printed circuit board), youll see integrated circuits
(i.c.s) or chips used at the heart of circuitry. Integrated circuits can
have anything from four pins to the many hundreds seen on central
processing units.
Imagine that you have a hugely complex circuit containing logic or CPUs or
digital displays. It becomes messy if not impossible to have a circuit diagram
showing thousands of wires joining various parts together. A schematic
shorthand we use is to draw a bus a line representing a group of
connections, such as an address bus or memory bus.
The skilful use of lines and buses in circuit diagrams shows the reader how
everything is connected together, leaving no room for doubt. Now that you
know the basics, lets see how some unusual components are represented in
circuit diagrams.
Set the multimeter it for the voltage youre measuring. You can
measure volts DC(direct current),
millivolts DC or volts AC(alternating
current). If your multimeter has an
auto range function, its not necessary
to select the voltage youre measuring.
Turn the power on. The current will run through the circuit, up the red
probe and through the multimeter then out the black probe and into
the circuit.
ZRC TRAINING CENTER PHILS. INC. CEBU Page 52
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
Some multimeters will beep when the reading is less than 1. This
doesnt necessarily indicate a good diode, because a shorted diode will
also cause a bee.
CRO Operation
CRO Controls
The fixture and circuit board are used for the strain gage test resulting
in actual "live" measurements of the UUT's flexing during the test
cycle. During strain gage testing the fixture gets a detailed inspection
and is fine tuned to keep strain at the lowest possible levels.
Closed Loop
A control system, sometimes called feedback, possessing a
monitoring feedback, the deviation signal from this being used to
control the action of a final controlling element in such a manner as to
Process Control
Deals with the behavior of dynamical system over time. The desired
output of a system is called the reference variable. When one or more
output variables of a system need to show a certain behaviour over
time, a controller manipulates the inputs to a system to obtain the
desired effect on the output of the system.
Control
Ability to purposefully direct or suppress.
A. Determine the behavior or supervise the running.
B. Power to direct or determine
A device such as a valve or damper that acts to change the value of the
manipulated variable. Positioned by an actuator.
SOLENOID VALVES
BALL VALVES
Electronic governors
General Requirements
Explain that electrical designed for land use often not suitable for
use in ships
Electromagnetic device
Generator Voltage
AIR
The basic operation of the gas turbine is similar to that of the steam
power plant except that air is used instead of water. Fresh atmospheric
air flows through a compressor that brings it to higher
pressure. Energy is then added by spraying fuel into the air and
igniting it so the combustion generates a high-temperature flow. This
high-temperature high-pressure gas enters a turbine, where it expands
down to the exhaust pressure, producing a shaft work output in the
process. The turbine shaft work is used to drive the compressor and
other devices such as an electric generator that may be coupled to the
shaft. The energy that is not used for shaft work comes out in
the exhaust gases, so these have either a high temperature or a high
velocity. The purpose of the gas turbine determines the design so that
the most desirable energy form is maximized. Gas turbines are used to
power aircraft, trains, ships, electrical generators, or even tanks.[
[1]
Other uses include cooling the barrels of machine guns, cooling
of lubricant oil in pumps; for cooling purposes in heat exchangers; cooling
products from tanks or columns, and recently, cooling of various major
components inside high-end personal computers. The main mechanism for
water cooling is convective heat transfer.
Periodic Inspections
[2] divides standby power systems into two categories, as follows: Legally
Required Standby Systems: Those systems required and so classed as legally
required standby by municipal, state, federal, and other codes or by any
governmental agency having jurisdiction. These systems are intended to
automatically supply power to selected load (other than those classed as
emergency systems) in the event of failure of the normal source. FPN:
Legally required standby systems are typically installed to serve loads, such
as heating and refrigeration systems, communications systems, ventilation
and smoke removal systems, sewage disposal, lighting systems, and
industrial processes that, when stopped during any interruption of the
normal electrical supply, could create hazards or hamper rescue and fire-
fighting operations. Optional Standby Systems: Those systems intended to
supply power to public or private facilities or property where life safety does
not depend on the performance of the system. Optional standby systems are
intended to supply on-site generated power to selected loads either
automatically or manually. FPN: Optional standby systems are typically
installed to provide an alternate source of electric power for such facilities as
industrial and commercial buildings, farms, and residences and to serve
loads such as heating and refrigeration systems, data processing and
communications systems, and industrial processes that, when stopped
during any power outage, could cause discomfort, serious interruption of the
process, damage to the product or process, and the like.
Control Theory
Main engine control system is used for automatic remote control and
protection of main ship's diesels. It permits to change direction and
speed rotation of propeller directly from the bridge by navigators. The
system consists of the equipment installed on the bridge, engine
control room (ECR) locally mounted near the engine.
1. Engine telegraph.
2. Automatic control panel. It has the following items mounted on panel
front:
a) Manual power limiter.
b) Engine speed fine adjustment potentiometer.
c) Illuminated push-button for bridge control demand.
d) "Control transfer inhibited" signal display.
e) "Control on the bridge/ECR" signal display.
f) Direction of engine rotation indicator (LED).
g) Engine RPM indicator.
h) Fuel oil lever actuator position indicator.
3. Shield push-button for emergency stop and emergency maneuvering.
Transfer Functions.
In engineering, a transfer function (also known as the system
function[1] or network function and, when plotted as a graph, transfer
curve) is a mathematical representation, in terms of spatial or
temporal frequency, of the relation between the input and output of
a linear time-invariant system with zero initial conditions and zero-
point equilibrium.[2] With optical imaging devices, for example, it is
the Fourier transform of the point spread function (hence a function
of spatial frequency) i.e. the intensity distribution caused by a point
object in the field of view.
Natural frequency
The frequency at which a system oscillates when not subjected to a
continuous or repeated external force.
Control systems
A control system is a device, or set of devices, that manages,
commands, directs or regulates the behavior of other device(s) or
system(s). Industrial control systems are used in industrial production
for controlling an equipment or a machine.
Lets begin with the measurement of dead time and time constant of a
self-regulating process. Typically, one will place the controller in
manual control mode, wait for the process variable to settle down, and
then make a step change of a few percent in the controller output. At
first the process variable does nothing (dead time) and then it begins
changing (time constant) until finally it settles out at a new level.
To measure the dead time and time constant, draw a horizontal line at
the same level as the original process variable. Well call this the
baseline. Then find the maximum vertical slope of the process variable
response curve. Draw a line tangential to the maximum slope all the
way to cross the baseline. Well call this crossing the intersection.
The process time constant is measured along the time axis as the time
spanned between the intersection (described previously)
Controller Modes
Controllability
When tuning a loop for the shortest possible settling time, one finds
that there is a minimum limit on settling time. If you tune the controller
any tighter, the loop will begin oscillating. The minimum settling time
depends mostly on the amount of dead time in a control loop, and will
be between two and four times the length of the dead time. The ratio
System response
The order of a system is defined as
being the highest power of
derivative in the differential
equation, or being the highest
power of s in the denominator of
the transfer function. A first-order
system only has s to the power one
in the denominator, while a second-
order system has the highest power
of s in the denominator being two.
Tuning
Tuning a Controller
Introduction
First Order Response Processes are also easy to control. The tuning
method described below is based on a first order response.
You will see later in the interactive exercises that this is very difficult to
control!
Let us consider first the simple case of a first-order lag in series with a time
delay. This setup is shown in a diagram below.
Look at the open loop response of the process to a step change in the
manipulated variable.
Evaluate
Finally substitute these values into the table below to obtain the
relevant controller parameters.
Gain = *G
Therefore by substituting all the values in for the above and re-arranging we
get the following values for the controller parameters:
Does not work well for complex responses - leads to inaccurate tuning
model.
In this case the tangent should be drawn at the point where the slope of the
response is steepest. Now we have estimates for the parameters and it may
be necessary to change them in order to get the optimum values. To do this
it is possible to use a model of the process and controller to see the effect of
altering the control parameters. There is the chance to do this in the case
study section.
.. in
which
case
it is
very difficult to
control And it
may not be possible using a PI controller.
Gains for Real Processes and Controllers
the process gain, , will in general have odd dimensions! This also makes it
hard to interpret or compare gain values.
If the value of the gain is large, say 100, then this means that the change
in y is 100 times greater than the corresponding change in u. This could lead
to y going out of bounds or else the change in u being very restrictive.
Alternatively, if the gain is very small, say 0.01, then for a large change
in u there is hardly any response in y.
What is required is a gain of around 1. This enables both input and output to
be used to their full ranges which in turn improves the controllability.
Firstly remember that you have a value of the dimensionless gain for the
controller as evaluated above.
The transmit end, a digital coder converts the incoming analog video signal
to PCM digital data. The coder also contains a time-division multiplexer,
called a high level mux, which creates a digital sub channel that is time-
division multiplexed with the PCM video data. This high level mux/video
coder outputs a digital data stream and a clock signal, used for synchronicity.
These signals then enter the optical transmitter for digital line coding, light
source modulation, and an interface to the optical transmission fiber. This
high level mux receives its input from a second TDM, called the low level
mux, which controls a data bus that can interface with a variety of input
signals such as digitized audio and digital data signals. At the receive end, an
optical receiver converts the signal from optical to electrical and provides
line decoding plus clock recovery. The PCM data and recovered clock are
then sent to a digital video decoder that converts the digital video back to an
It is useful to think of a partition in the system between its signal codecs and
the optical transmitter and receiver. In this example, the system uses an
eight channel optical link. It is important to decide how these digital channels
are utilized. Figure 2 shows all eight inputs and outputs on the transmission
terminals in use, leaving no room for future expansion. More system capacity
could be achieved with additional optical terminals or optical terminals that
offer a higher channel count. Many multichannel video transport systems
require linking one transmit site to several receive sites in a point-to-
multipoint configuration. Figure 3 illustrates an example of this type of
system. In this figure, there are three end-of-the-line receive sites and one
intermediate receive site where a digital drop/add function has been
incorporated. At the intermediate hub, all channels from the headend are
dropped for local use and are retransmitted to the next site. Two channels
are also added to the intermediate hub for transmission to the next hub.
Digital systems can be used to build fiber optic video transport networks
from a set of basic common components that can provide configurations that
range from simple point-to-point links to complex point-to-multipoint systems
Flow characteristics
All control valves have an inherent flow characteristic that defines the
relationship between 'valve opening' and flow rate under constant
pressure conditions. Please note that 'valve opening' in this context
refers to the relative position of the valve plug to its closed position
against the valve seat. It does not refer to the orifice pass area. The
orifice pass area is sometimes called the 'valve throat' and is the
narrowest point between the valve plug and seat through which the
fluid passes at any time. For any valve, however it is characterized, the
relationship between flow rate and orifice pass area is always directly
proportional.
In this Tutorial, the term 'valve lift' is used to define valve opening, whether
the valve is a globe valve (up and down movement of the plug relative to the
seat) or a rotary valve (lateral movement of the plug relative to the seat).
Rotary valves (for example, ball and butterfly) each have a basic
characteristic curve, but altering the details of the ball or butterfly plug may
modify this. The inherent flow characteristics of typical globe valves and
rotary valves are compared in Figure 6.5.2.
Globe valves may be fitted with plugs of differing shapes, each of which has
its own inherent flow/opening characteristic. The three main types available
are usually designated:
Fast opening.
Linear.
Equal percentage.
The fast opening characteristic valve plug will give a large change in
flowrate for a small valve lift from the closed position. For example, a
valve lift of 50% may result in an orifice pass area and flow rate up to
90% of its maximum potential.
The self-acting type of control valve tends to have a plug shape similar to the
fast opening plug in Figure 6.5.1. The plug position responds to changes in
liquid or vapour pressure in the control system. The movement of this type of
valve plug can be extremely small relative to small changes in the controlled
condition, and consequently the valve has an inherently high range ability.
The valve plug is therefore able to reproduce small changes in flow rate, and
should not be regarded as a fast opening control valve.
For example, at 40% valve lift, a 40% orifice size allows 40% of the full flow
to pass.
These valves have a valve plug shaped so that each increment in valve
lift increases the flow rate by a certain percentage of the previous flow.
The relationship between valve lift and orifice size (and therefore flow
rate) is not linear but logarithmic, and is expressed mathematically in
Equation 6.5.1:
Equation 6.5.1
Where:
The maximum flow rate through a control valve with an equal percentage
characteristic is 10 m/h. If the valve has a turndown of 50:1, and is subjected
to a constant differential pressure, by using Equation 6.5.1 what quantity will
ZRC TRAINING CENTER PHILS. INC. CEBU Page 97
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
pass through the valve with lifts of 40%, 50%, and 60% respectively?
Where:
Equation 6.5.1
The increase in volumetric flow rate through this type of control valve
increases by an equal percentage per equal increment of valve
movement:
It can be seen that (with a constant differential pressure) for any 10%
increase in valve lift, there is a 48% increase in flow rate through the control
valve. This will always be the case for an equal percentage valve with range
ability of 50. For interest, if a valve has a range ability of 100, the
incremental increase in flow rate for a 10% change in valve lift is 58%.
Table 6.5.1 shows how the change in flow rate alters across the range of
valve lift for the equal percentage valve in Example 6.5.1 with a range ability
of 50 and with a constant differential pressure.
Table 6.5.1 Change in flow rate and valve lift for an equal
percentage characteristic with constant differential pressure
1. The first step in control valve selection involves collecting all relevant
data and completing the ISA Form S20.50. The piping size must be set
prior to valve sizing, and determining the supply pressure may require
specifying a pump. The novice might have to iterate on the needed
piping, pump pressure and pressure drop through the piping network.
2. Next, the size of the valve is required; select the smallest valve C v that
satisfies the maximum Cv requirement at 90% opening. While
performing these calculations, checks should be made regarding
flashing, cavitation, sonic flow and Reynolds number to ensure that the
proper equation and correction factors are used. As many difficulties
occur due to oversized valves as to undersized valves. Adding lots of
safety factors will result in a valve that is nearly closed during normal
operation and has poor range ability.
4. The valve body can be selected based on the features in Table 5 and
the typical availability in Table 6. Note that the valve size is either
equal to the pipe size or slightly less, for example, a 3-inch pipe with a
2-inch globe valve body. When the valve size is smaller than the
process piping, an inlet reducer and outlet expander are required to
make connections to the process piping.
Actuators
The arm muscle and hand (the actuator) turned the valve - (the
controlled device).
One form of controlling device, the control valve, has now been covered. The
actuator is the next logical area of interest.
The operation of a control valve involves positioning its movable part (the
plug, ball or vane) relative to the stationary seat of the valve. The purpose of
the valve actuator is to accurately locate the valve plug in a position dictated
by the control signal.
The actuator accepts a signal from the control system and, in response,
moves the valve to a fully-open or fully-closed position, or a more open or a
more closed position (depending on whether 'on / off' or 'continuous' control
Pneumatic.
Electric.
Other significant actuators include the hydraulic and the direct acting types.
These are discussed in Block 7, 'Control Hardware: Self-Acting Actuation'.
Pneumatic actuators are commonly used to actuate control valves and are
available in two main forms; piston actuators (Figure 6.6.1) and diaphragm
Piston actuators
Piston actuators are generally used where the stroke of a diaphragm actuator
would be too short or the thrust is too small. The compressed air is applied to
a solid piston contained within a solid cylinder. Piston actuators can be single
acting or double acting, can withstand higher input pressures and can offer
smaller cylinder volumes, which can act at high speed.
Diaphragm actuators
The diaphragm (Figure 6.6.2) is pushed upwards, pulling the spindle up, and
if the spindle is connected to a direct acting valve, the plug is opened. The
actuator is designed so that with a specific change of air pressure, the
spindle will move sufficiently to move the valve through its complete stroke
from fully-closed to fully-open.
As the air pressure decreases, the spring(s) moves the spindle in the
opposite direction. The range of air pressure is equal to the stated actuator
spring rating, for example 0.2 - 1 bar.
The direct acting actuator is designed with the spring below the diaphragm,
having air supplied to the space above the diaphragm. The result, with
increasing air pressure, is spindle movement in the opposite direction to the
reverse acting actuator.
The effect of this movement on the valve opening depends on the design
and type of valve used, and is illustrated in Figure 6.6.3. There is however,
an alternative, which is shown in Figure 6.6.4. A direct acting pneumatic
actuator is coupled to a control valve with a reverse acting plug (sometimes
called a 'hanging plug').
considered. Figure 6.6.5 and Figure 6.6.6 show the net effect of the various
combinations.
Fig. 6.6.5 Net effect of various combinations for two port valves
Fig. 6.6.6 Net effect of the two combinations for three port valves
The air fed into the diaphragm chamber is the control signal from the
pneumatic controller. The most widely used signal air pressure is 0.2 bar to 1
normally closed
When the valve and actuator assembly is calibrated (or 'bench set'), it is
adjusted so that an air pressure of 0.2 bar will just begin to overcome the
resistance of the springs and move the valve plug away from its seat.
As the air pressure is increased, the valve plug moves progressively further
away from its seat, until finally at 1 bar air pressure, the valve is 100% open.
This is shown graphically in Figure 6.6.7.
Therefore, if the actuator is supplied with air at 0.6 bar (halfway between 0.2
and 1 bar), for example, instead of the valve taking up the expected 50%
open position, the actual opening will be greater, because of the extra force
provided by the differential pressure.
Also, this additional force means that the valve is not closed at 0.2 bar. In
order to close the valve in this example, the control signal must be reduced
to approximately 0.1 bar.
A minimum, when the process is calling for maximum heat, and the
control valve is 100% open.
A maximum, when the process is up to temperature and the control
valve is closed.
The steam pressure in the heat exchanger increases as the heat load
increases. This can be seen in Tutorial 6.5, Example 6.5.3 and Table 6.5.7.
If the pressure upstream of the control valve remains constant, then, as the
steam pressure rises in the heat exchanger, the differential pressure across
the valve must decrease.
Figure 6.6.8 shows the situation with the air applied to a direct acting
actuator. In this case, the force on the valve plug created by the differential
pressure works against the air pressure. The effect is that if the actuator is
supplied with air at 0.6 bar, for example, instead of the valve taking up the
expected 50% open position, the percentage opening will be greater because
of the extra force provided by the differential pressure. In this case, the
control signal has to be increased to approximately 1.1. bar to fully close the
valve.
Fig. 6.6.8 Direct acting actuator, air-to-close, direct acting valve -
normally open
It may be possible to recalibrate the valve and actuator to take the forces
created by differential pressure into account, or perhaps using different
springs, air pressure and actuator combinations. This approach can provide
an economic solution on small valves, with low differential pressures and
where precise control is not required. However, the practicalities are that:
Note: For simplicity, the above examples assume a positioner is not used,
and hysteresis is zero.
The formulae used to determine the thrust available to hold a valve on its
seat for various valve and actuator combinations are shown in Figure 6.6.9.
Where:
The thrust available to close the valve has to provide three functions:
3. To provide a sealing load between the valve plug and valve seat to
ensure the required degree of tightness.
Positioners
For many applications, the 0.2 to 1 bar pressure in the diaphragm chamber
may not be enough to cope with friction and high differential pressures. A
This is an additional item (see Figure 6.6.11), which is usually fitted to the
yoke or pillars of the actuator, and it is linked to the spindle of the actuator
by a feedback arm in order to monitor the valve position. It requires its own
higher-pressure air supply, which it uses to position the valve.
A valve positioner relates the input signal and the valve position, and will
provide any output pressure to the actuator to satisfy this relationship,
according to the requirements of the valve, and within the limitations of the
maximum supply pressure.
Example: Taking a PN5400 series actuator fitted to a DN50 valve (see Table
in Figure 6.6.10)
1. With a standard 0.2 to 1.0 bar spring range (PN5420), the maximum
allowable differential pressure is 3.0 bar.
2. With a 1.0 to 2.0 bar spring set (PN5426), the maximum allowable
differential pressure is increased to 13.3 bar.
For example, if the control signal was 0.6 bar (50% valve lift), the positioner
would need to allow approximately 1.5 bar into the actuator diaphragm
chamber. Figure 6.6.12 illustrates this relationship.
Valve Sizing
Control valve sizing involves determining the correct valve to install from the
many valves commercially available. The procedure is based on information
provided by valve manufacturers, who specify the capacity of their valves
using the valve coefficient, Cv. The valve coefficient is defined as the flow of
water that will pass through the valve when fully open with a pressure drop
of 1 psi. In these tables, the units of Cv are gallons of water per minute per
psi1/2. The engineer must calculate the desired Cv for the process fluid and
conditions by applying appropriate correction factors and select the valve
using tables of Cv versus valve stem position and line size provided by the
manufacturers
The required flow and pressure drop information used to size a valve is based
on the process operations and equipment, and ISA Form S20.50 (ISA, 1992)
provides a helpful method for recording the data. The size of the valve
depends on the pressure drop across the valve. A general guideline for
pumped systems is that the valve pressure drop should be 25-33% of the
For liquids in turbulent flow, the defining equation is the equation for flow
through an orifice, which can be rearranged and supplemented with
correction factors.
Where
When the process conditions, including the valve (C v), are known, equation
(9) can be used to calculate the flow. When designing the process, the
desired flow is known but the valve is not; equation (9) can be rearranged to
calculate the valve coefficient required for the specified conditions. The
pressure decreases as the liquid flows through the valve. The possibility
exists for the liquid to partially vaporize due the pressure drop, and this
Flashing occurs when vapor remains downstream of the valve after the
pressure recovery. This situation will not result in damage to the valve and is
an acceptable design. Special flow models are required for valve sizing when
vaporization occurs and can be found is standard references, e.g., Driskell
(1983).
For gases and vapors with subsonic flow, the development of the equation is
similar but must consider the change in density with an expansion factor and
the lack of ideal behavior with the compressibility.
relationship for
gases and vapors
with subsonic flow
through an orifice
Where
Fg = gas flow rate (std. ft3/h)
specific gravity of the process fluid relative to air at standard
Gg =
conditions
N = unit conversion factor (equal to 1380 for English units)
P1 = upstream pressure (psia)
T1 = upstream temperature (R)
dimensionless expansion factor which depends on P1/P2 and
Y = the specific heat ratio; ranges from 0.67 to 1.0 (see Driskell
1983)
z = compressibility factor
When the pressure drop across the valve is large, sonic flow can occur which
will require special calculations for valve sizing (Hutchison, 1976). The
general behavior of flow versus pressure drop is shown in Figure 10. When
choked flow occurs, the downstream pressure does not influence the flow
rate. A rough guideline is that sonic flow does not occur when the pressure
drop is less than 42% of the supply pressure. Sonic flow through valves
occurs often and does not represent difficulties when the proper valve trim
design and materials are used.
ELECTRONIC PID
CONTROLLER
Single-loop controllers
A modern high pressure, high temperature water tube boiler holds a small
quantity of water and produces large quantities of steam. Very careful control
of the drum water level is therefore necessary. The reactions of steam and
water in the drum are complicated and require a control system based on a
number of measured elements.
When a boiler is operating the water level in the gauge glass reads higher
than when the boiler is shut down. This is because of the presence of steam
bubbles in the water, a situation which is accepted in normal practice. If
however there occurs a higher increase in steam demand from the boiler the
pressure in the drum will fall. Some of the water present in the drum at the
higher pressure will now flash off and become steam. These bubbles of
steam will cause the drum level to rise. The reduced mass of water in the
drum will also results in more steam being produced, which will further raise
the water level. This effect is known as swell. A level control system which
is used only level as a measuring element would close the feed control valve,
when it should be opening it.
When the boiler load returns to normal the drum pressure will rise and steam
bubble formation will reduce, causing a fall in water level. Incoming colder
feed water will further reduce steam bubble formation and what is known as
shrinkage of the drum level will occur.
The problems associated with swell and shrinkage are removed by the use of
a second measuring element, steam flow . A third element feed water flow
is added to avoid problems that would occur if the feed water pressure were
to vary.
If not managed correctly, severe failure and disruption to plant operation can
occur. To avoid these, ZI-CHEM offers a comprehensive range of chemical
and application technologies to manage the water quality in these water
circuits.
These include:
With an electrical system connecting all the equipment with power, the
control system controlling all the actions of the system, a monitoring system
is needed to log the actions, performance and status of the components in
these systems.
Safety system
Local control
Control refers to sending command messages to a device to operate
the I&C and power-system devices. Traditional supervisory control and
data acquisition (SCADA) systems rely on operators to supervise the
system and initiate commands from an operator console on the master
computer. Field personnel can also control devices using front-panel
push buttons or a laptop computer.
Failure Mode and Effects Analysis (FMEA) was one of the first
systematic techniques for failure analysis. It was developed
by reliability engineers in the 1950s to study problems that might arise
from malfunctions of military systems. An FMEA is often the first step
of a system reliability study. It involves reviewing as many
components, assemblies, and subsystems as possible to identify failure
modes, and their causes and effects. For each
Component, the failure modes and their resulting effects on the rest of
the system are recorded in a specific FMEA worksheet. There are
numerous variations of such worksheets. An FMEA is mainly a
qualitative analysis.[1]
Functional,
Process FMEA.
power supply
Every power supply must obtain the energy it supplies to its load, as well as
any energy it consumes while performing that task, from an energy source.
Depending on its design, a power supply may obtain energy from:
Solar power.
2/2 Valve; 2 3/2 Valve; 3 4/2 Valve; 4 4/3 Valve; 4 5/2 Valve; 5
Ports, 2 Ports, 2 Ports, 2 Ports, 3 Ports, 2
Positions Positions Positions Positions Positions
Flow) Flows)
Lines Lines
Flow Gauge Lever Lubricator
Connected Crossing
Flame trap
Main engine safety trip which trips the main engine when no corrective
action is taken to the alarm and in certain cases the main engine is
tripped manual .
Manual tripping of main engine is done in chance of the collision or
grounding of the ship when sailing in conjusted water and in navigation
of the ship in restricted visibility. .
So when any main engine trips are activated the Main engine stops
and again it should be started with the help of starting air after
correcting the faults.
UMS systems
Concept of unattended machinery spaces(UMS)
Is a way of operating the automatically controlled machinery of vessel (e.g.
ship) ; UMS Mode means that, instead of ship, provided he is in permanent
control over a signaling device (control)
Nowadays, however, far more UMS ships are in operation. Crews have grown
familiar with the systems and training is more prolific. In the immediate
future more owners will adopt UMS, not only as a means of cutting crew to a
minimum and thus cut operational costs, but also for reasons of safety.
For diesel plant with fixed-pitch propellers the fuel supply and direction of
engine rotation should be affected by a single control lever. The controls
must operate the machinery in a time sequence acceptable for the engines,
and able to shut-off the fuel supply if the desired and actual direction of
rotation of the engine and the cam-shaft position does not match.
In addition to alarm indication for the lubricating oil system, the system must
be able to shut down the engine if lubricating (lube) oil is lost. The circuit and
sensors for this function must be additional to the alarm circuit required.
On the bridge, both audible and visual alarms are to operate and indication
given when the speed of the main engines is to be reduced due to the
following fault condition: high scavenge air temperature, oil mist detected in
crankcase, low piston coolant outlet flow, low piston coolant pressure, also
for low cylinder coolant pressure if on a separate circuit.
Where the lube oil cooling water and oil fuel booster pumps are not driven by
the main engine, the standby pump is to start automatically if the discharge
pressure from the working pump falls below a predetermined value.
Testing regime for UMS
AC, 3 phase power is preferred over DC as it gives more power for the
same size.
Bus Bars which acts as a carrier and allow transfer of load from one
point to another. Circuit breakers which act as a switch and in unsafe
condition can be tripped to avoid breakdown and accidents. Fuses as
safety device for machinery.
For smaller supply fuse and miniature circuit breakers are used.
Emergency Power
Rating of the emergency power supply should be made in such a way that it
provides supply to the essential systems of the ship such as
Types of protection
All these alarms are to be indicated at the control location for machinery as
individual alarms; where the alarm panel with individual alarms is installed
on the engine or in the vicinity; common alarm in the control location for
machinery is required.
Referring to the above starting diagram of an auxiliary engine, the" main air"
from the main air bottle arrives at the air starting valve. There is a tapping
from the main air starting line, "pilot air" going to the starting air distributor.
When the engine rotates, the camshaft also rotates which in turn rotates "the
In the next article, we will take up the study of the various valves mentioned
in the starting air systems namely master air starting valve, cylinder valves
and so forth.
Steam boiler
A boiler or steam generator is a device used to create steam by
applying heat energy to water. Although the definitions are somewhat
flexible, it can be said that older steam generators were commonly
termed boilers and worked at low to medium pressure (1300 psi or 6.895
2,068.427 kPa) but, at pressures above this, it is more usual to speak of
a steam generator.
Following failure will have alarms and display-feed water high salinity , high water
level, boiler pressure high and low, superheated outlet temperature high , fuel
pump low outlet pressure, heavy fuel temperature high and low (or high and low
viscosity), uptake high gas temperature, control system power failure, automization
steam/ air pressure low
Feed water high salinity
This is the single most important item to estimate the performance of an ion
exchange system. It is also one of the first things to check when plant
Higher ratio of silica to This may increase silica leakage and require a
total anions change in regeneration conditions.
See also a detailed description of the water analysis, with the concentration
units to use and a table of the most common ions in water.
Salinity limits
Wet and dirty steam can contaminate or spoil the product where it is
used directly. Wet steam can increase the water film thickness of the
heat transfer surface, lower processing temperatures, perhaps
interfering with proper sterilisation of food products or processing of
pharmaceuticals, and causing wastage. At best, lower process and
production efficiency will increase process time and unit costs.
Overfilling the boiler can lead to waterhammer in the steam system,
risking damage to plant and even injury to personnel.
Spoilt product
Lower production rates
Poor product quality
Increased plant and component maintenance
Damage to the steam system
Risk to personnel
The oil pump in an internal combustion engine circulates engine oil under
pressure to the rotating bearings, the sliding pistons and the camshaft of the
engine. This lubricates the bearings, allows the use of higher-capacity fluid
bearings and also assists in cooling the engine.
All combustion requires the correct measure of oxygen; too much or too little
can cause undesirable effects. However, the error is almost always
intentionally on the high-side (too much oxygen) because the main effect on
the high side is low efficiency. Too little air results in carbon monoxide
formation, sooting and even explosion if accumulated soot and other non-
combusted suddenly get enough oxygen to rapidly burn.
Synchronous motor
The synchronous motor and induction motor are the most widely used types
of AC motor. The difference between the two types is that the synchronous
motor rotates in exact synchronism with the line frequency. In contrast the
induction motor requires "slip", the rotor must rotate slightly slower than the
AC current alternations, to develop torque. Therefore small synchronous
motors are used in timing applications such as in synchronous
clocks, timers in appliances, tape recorders and precision
servomechanisms in which the motor must operate at a precise speed.
Let us assume that the drive is operating on a 480V power system. The 480V
rating is rms or root-mean-squared. The peaks on a 480V system are 679V.
As you can see, the VFD dc bus has a dc voltage with an AC ripple. The
voltage runs between approximately 580V and 680V.
Note that in a real VFD, the switches shown would actually be transistors.
When we close one of the top switches in the inverter, that phase of the
motor is connected to the positive dc bus and the voltage on that phase
becomes positive. When we close one of the bottom switches in the
converter, that phase is connected to the negative dc bus and becomes
negative. Thus, we can make any phase on the motor become positive or
negative at will and can thus generate any frequency that we want. So, we
can make any phase be positive, negative, or zero.
Motor control
Motor control is the process by which humans and animals use their
neuromuscular system to activate and coordinate the muscles and limbs
involved in the performance of a motor skill. Fundamentally, it is
the integration of sensory information, both about the world and the current
state of the body, to determine the appropriate set of muscle forces and joint
activations to generate some desired movement or action. This process
requires cooperative interaction between the central nervous system and
the musculoskeletal system, and is thus a problem of information
processing, coordination, mechanics, physics, and cognition.[1][2] Successful
motor control is crucial to interacting with the world, not only determining
action capabilities, but regulating balance and stability as well.
In the first case, the impulse controlled circuit of Fig. 6.94 is complemented
with a thermal relay (Fig. 6.99). In the other two cases, combinations of two
and three contactors provide the control of the motor. The circuit in Fig.
6.100 is appropriate for the direction change and switching on or off three-
phase motors. The direction of the rotation can be changed only, if the motor
has been turned off previously by the "Off" button. This method is
advantageous, because the arc between the contacts of the contactor can
die out during the relatively long time of the switching process, therefore a
possible fault is eliminated.
Figure 6.101 shows a circuit, with which the star-delta starting of motors can
be accomplished. The main and control circuits are shown separately. Three
contactors are used: the main contactor K, the contactor providing the star
connection Y, and the contactor implementing the delta connection, denoted
by . By pressing the "On" button, the motor starts in star connection,
because contactor K connects the supply voltage across the coils after
contactor Y has been energized. An interlock ensures that this can happen
only if contactor is off. At the same time, the NO auxiliary contact of the
main contactor closes providing self holding for both contactors K and Y.
Furthermore, the time relay TR starts. After the delay time is over, an NC
contact of the time relay opens the holding circuit of contactor Y, and its NO
contact closes and energizes contactor . Again, an interlocking circuit
inhibits the simultaneous operation of contactors Y and .
The operation method of the overload thermal relay implies that the
temperature rise of the bimetallic strips reflects only the average
temperature rise of the motor. Therefore, the hottest parts of the motor can
remain without protection. Bimetallic strips heated indirectly can follow even
the current proportional to the average motor temperature only with a delay.
With indirect heating, the heat is transmitted from the heating wire to the
bimetal through an insulating layer. Even in this thin layer, the heat
conduction is so low that it can cause a delay in the temperature rise of the
bimetal, when an overload occurs. If the load drops rapidly, the hot heating
wire might heat the bimetal further, resulting in false tripping. Although the
motor is not in danger, the protection disconnects it from the supply.
Consequently, thermal relays are not appropriate for the protection of large
motors and/or motors with frequently varying load
Circuit breaker
Fuse
In electronics and electrical engineering, a fuse (from the
French fuser, Italian fuso, "spindle"[1]) is a type of low
resistance resistor that acts as a sacrificial device to
provide overcurrent protection, of either the load or
source circuit. Its essential component is a metal wire or
strip that melts when too much current flows through it,
interrupting the circuit that it connects. Short circuits,
overloading, mismatched loads, or device failure are the
prime reasons for excessive current. Fuses are an
alternative to circuit breakers.
Overload relays
A starter will contain protective devices for the motor. At a minimum this
would include a thermal overload relay. The thermal overload is designed to
open the starting circuit and thus cut the power to the motor in the event of
the motor drawing too much current from the supply for an extended time.
The overload relay has a normally closed contact which opens due to heat
generated by excessive current flowing through the circuit. Thermal
overloads have a small heating device that increases in temperature as the
motor running current increases.
The IGBT combines the simple gate-drive characteristics of the MOSFETs with
the high-current and lowsaturation-voltage capability of bipolar transistors
by combining an isolated gate FET for the control input, and a bipolar
power transistor as a switch, in a single device. The IGBT is used in medium-
to high-power applications such as switched, traction control and induction
heating. Large IGBT modules typically consist of many devices in parallel and
can have very high current handling capabilities in the order of hundreds
of amperes with blocking voltages of 6000 V.
Their high pulse ratings, and low prices on the surplus market, also make
them attractive to the high-voltage hobbyist for controlling large amounts of
power to drive devices such as solid-state Tesla coils and coil guns.
They are still employed in very high power applications, such as locomotives,
where the high power capability of the thyristors and the simplicity of the
design can make them a more attractive proposition than transistor based
controllers.
A derivative of the thyristor drive is the simple AC phase controller. This uses
a single phase controlled triac to provide a variable voltage AC output for
regulating a universal motor. This is the type of motor speed control most
commonly used in domestic appliances, such as food mixers, and small AC
powered tools, such as electric drills.
Three
phase generator
If the first phase has a voltage given by V=V0 sint, then the second is
V=V0 sin(t +1200) and the third V=V0 sin(t + 2400).
The potential differences generated is often fairly low but high currents are
created. These are usually sent to a transformer in a switchyard which
changes the AC currents to very high voltage and low current for long
distance transmission. ( Reason, power =VI, if we are to transmit say 100MW
to a place several hundred kilometers away, we don't want ohmic heating of
the cables. This is caused by high currents in the cables! So - low currents,
meaning high PDs. ) High voltage transmission towers only carry groups of
three cables - the 3 phases. The return cable is the Earth itself.
ZRC TRAINING CENTER PHILS. INC. CEBU Page 161
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
At the other end, the PDs are transformed to low values and eventually the
individual phase cables go to consumers, eg your house! Big energy
consumers eg businesses may require all three phases into their
places. Households usually need only one phase.
A happy quirk of the three phases is that if the return cables are all joined,
the three voltages add TO NOTHING! So at the generator and every
transformer one cable of every phase is joined and stuck in the ground! This
can be seen in Australia at the power poles holding a transformer in the
streets providing power to houses. Down one side is a massive cable sunk
into the ground. Houses get one phase each with a return line, these return
lines are joined into the Earth.
Distribution
The main bus bar has three heavy, thick bars of conductor (usually copper),
running horizontally throughout the length of the main switch board. Each of
the conductors is insulated between each other and wherever it is supported
or clamped to the switchboard. The bus bar lies at the bottom most portion
of the switchboard such that it can be easily supported and insulated. At
times, there may be two divisions of the bus bar which are connected to
each other by either a circuit breaker or a clamping (sliding contact) device.
The main switchboard is the main power distribution center of the ship. Thus
the main bus bars are contained within the switchboard feeding various ship
board auxiliaries. A ship may contain two or more generators connected to
the main bus bar via the circuit breaker.
Various protection for the generators like overload, reverse power, etc. are
connected to circuit breaker such that the faulty generator is electrically
isolated from the main bus bar.
The main switch board gets its supply from the main generators located in
the engine room. The distribution system can be divided into Feeder side and
the Load side. The feeders are the generators and the loads are various ship
board auxiliary machineries. The Load side is further divided into Essential
and Non-Essential services. Essential services are very critical auxiliaries
which are directly affecting the safety of personnel, ship in terms of
navigation and propulsion. They include supply to navigational aids like
radars, communication equipment, navigational lights, and steering gear
motors. These essential services may be supplied directly from the main
switch board or via sectional boards or distribution boards. Non-essential
services are those that do not affect the safety of ship and personnel. For
example, air conditioning compressors and fans are non-essential services as
they dont affect the safety of the ship or personnel
.
The operating voltage is stepped down to 220 volts and this voltage
is given to the 220 Volts auxiliaries panel. From this panel, the supply
goes for various lighting systems and other sockets for accommodation and
galley for domestic use.
Duration: 3 days
Target Group: All Electrical Officers & Marine Engineers.
Course Contents:
Familiarization lay out and safety features of high voltage power plant
on board.
The functional, operational and safety requirements for a marine high
voltage system.
Assignment of suitably qualified personnel to carry out maintenance
and repair of high voltage switch gear of various types.
Producing a switching strategy for isolating components of high
voltage system.
Selecting suitable apparatus for isolation and testing of high voltage
apparatus.
Carrying out a switching and isolation procedure on a marine high
voltage system complete with safety documentation.
Performing test of insulation resistance and polarization index on high
voltage equipment.
Taking remedial action necessary during faults in high voltage system.
Risks & hazards associated with High Voltage.
High voltage alternators safety features.
Earthing and key interlocks for isolation of high voltage equipment
Legislative background and Code of Safe Working Practices and PPE.
High Voltage switch gear, SF 6,Vacuum circuit breakers and contactors,
construction, operation, maintenance and tests.
grounding
The requirement ashore is the safety of human beings. So, inorder to prevent
human-electrical accidents, the neutral is earthed. The priority is neither the
safety of the machinery nor the continuous necessary operation of the
machinery. But the scenario onboard ship is totally different. The priority is
the continuous operation of the machineries which are classed "essential".
The distribution system followed onboard is "insulated neutral" system. The
main priority onboard is the safety of ship which includes navigation & fire
safety..etc. If due to earth fault, the machinery classed as"essential" gets
isolated, say for eg: steering gear, then the safety of ship is at question,
which may lead to collison, grounding, fire & pollution etc..So the priority
onboard ship is to maintain the continuity of the supply to the machinery in
the event of "single earth fault occurring".
RISK ASSESSMENT
The access to high voltage switchboards and equipment must be strictly
controlled by using a risk assessment and a permit to work system. Isolation
procedures must involve a safety key system and earthing down procedures.
Remember the acronym:
Disconnect
Isolate
Earth
To help identify high voltage system work precautions, a risk assessment
must be completed by the Chief Engineer or Chief Electrical officer before
work begins, and this should consider:
How familiar are the personnel with the high voltage system and
equipment?
ZRC TRAINING CENTER PHILS. INC. CEBU Page 178
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
Can the work be done with the equipment dead?
Is it necessary for someone to work on or near live high voltage
equipment?
What precautions have been taken to avoid danger and prevent injury?
Is the person(s) carrying out the work competent or adequately
supervised?
Figure 1
PPE, Personal Protective Equipment, are the tools that ensure the basic
health protection and safety of users. PPE is any device or appliance
designed to be worn by an individual when exposed to one or more health
and safety hazards. PPE includes all clothing and other work accessories
designed to create a barrier against workplace hazards, and using PPE
requires hazard awareness and training on
the part of the user. Employees must be
aware that the equipment does not eliminate
the hazard; if the equipment fails, exposure
will occur. To reduce the possibility of failure,
equipment must be properly fitted and
maintained in a clean and serviceable
condition.
Head Protection
Protective hats for head protection against impact blows must be able to
withstand penetration and absorb the shock of a blow. In some cases, hats
should also protect against electric shock. Recognized standards for hats
have been established by the American National Standards Institute (ANSI).
The wearer should be able to identify the type of helmet by looking inside
the shell for the manufacturer, ANSI designation and class. Protective hats
are made in the following types and classes:
Type 1 - helmets with full brim, not less than 1 and 1/4 inches wide;
Type 2 - brimless helmets with a peak extending forward from the
crown.
Hats and caps under Class A are intended for protection against impact
hazards. They are used in mining, construction, shipbuilding, tunneling,
lumbering, and manufacturing.
Class B utility service hats and caps protect the wearer's head from impact
and penetration by falling or flying objects and from high-voltage shock and
burn. They are used extensively by electrical workers.
For protection of feet and legs from falling or rolling objects, sharp objects,
molten metal, hot surfaces, and wet slippery surfaces, workers should use
appropriate foot guards, safety shoes, or boots and leggings. Leggings
protect the lower leg and feet from molten metal or welding sparks. Safety
snaps permit their rapid removal.
Aluminum alloy, fiberglass, or galvanized steel foot guards can be worn over
usual work shoes, although they may present the possibility of catching on
something and causing workers to trip. Heat-resistant soled shoes protect
Suitable eye protectors must be provided where there is a potential for injury
to the eyes or face from flying particles, molten metal, liquid chemicals,
acids or caustic liquids, chemical gases or vapors, potentially injurious light
radiation, or a combination of these. Every protector shall be distinctly
marked to facilitate identification of the manufacturer and must meet the
following minimum requirements:
Ear Protection
Exposure to high noise levels can cause hearing loss or impairment. It can
create physical and psychological stress. There is no cure for noise-induced
The devices should be selected to fit the specific task. Rubber is considered
one of the best materials for insulating gloves and sleeves and must conform
to ANSI standards (copies available from ANSI, 1430 Broadway, New York, NY
10018). Other glove and clothing materials such as latex, nitrile, butyl
rubber, neoprene, etc. are available. Each material is thoroughly tested and
rated against specific chemical compounds. You need to know what hazard
you are protecting against to choose the correct material.
Helmets
Head protection covers a wide range of products. This ranges from a basic
impact helmet such as used by a pedal cyclist, to a sophisticated helmet with
integrated respiratory and communications equipment.
Body Armour
When a product is called into action that saves limbs, vital organs and other
body parts knowing that the product has been tested to conventional limits
means everything.
Respiratory equipment (RPE) test for protection against smoke, dust to
vapours and oxygen deficiency.
Hearing protection BSI has a notified body status and can test earmuffs,
earplugs, earmuffs with electrical audio input, level dependant earmuffs.
Eye protection
Testing for personal eye protection equipment, welding filters, mesh face
screens, sunglasses & swimming goggles.
Protective Clothing
BSI testing against combined risks, flame retardant and high visibility
warning clothing. Chemical, Biological, Radiological and Nuclear (CBRN)
protection clothes.
Confined space - An enclosed space which has limited egress and access,
and has an atmospheric hazard (e.g., explosive atmosphere or asphyxiating
hazard) and/or other serious safety hazards (e.g., electrical hazard).
High voltage - Circuits with a nominal voltage more than 600 volts.
Isolating switch - A switch intended for isolating an electric circuit from the
source of power. It has no interrupting rating, and is intended to operate only
after the circuit has been opened by some other means.
Low voltage - Circuits with a nominal voltage less than or equal to 600
volts.
Switching devices - Devices designed to close and/or open one or more
electric circuits. Included in this category are circuit breakers, cutouts,
disconnecting (or isolating) switches, disconnecting means, interrupter
switches, and oil (filled) cutouts.
Operating Procedures
Qualified High Voltage Electrical Worker
Energized electrical work on systems shall only be performed by a UC Irvine
Qualified High Voltage Electrical Worker. UC Irvine is responsible for
determining whether an employee is qualified to perform energized electrical
work. This qualification shall be made based on completion of applicable
training and experience.
Observers
During the time that work is being performed on any exposed conductors or
exposed parts of equipment connected to high voltage systems, a Qualified
High Voltage Electrical Worker, or an employee in training, must be in close
proximity at each work location to:
Act primarily as an observer for the purpose of preventing an accident
Render immediate assistance in the event of an accident.
UC Irvine employees must use insulated tools and handling equipment that
are rated for the voltages to be encountered when working near exposed
energized conductors or circuit. Tools and handling equipment should be
replaced if the insulating capability is decreased due to damage. Protective
gloves must be used when employees are working with exposed electrical
parts above fifty (50) volts.
The area in the immediate vicinity of the workspace must be surveyed and
all potential hazards such as ladders, stacked boxes, ceiling tiles, or doors
that may fall or swing into the workspace must be secured to prevent
interference with the work being performed.
A clear escape path must be maintained from the work space to an exit from
the area.
Special Requirements
High Voltage
Work on systems greater than 600 volts must be performed using de-
energized electrical work practices, whenever possible. Energized electrical
work on greater than 600 volt electrical systems must only be performed by
a Qualified Electrical Worker. The following work practices are required, in
addition to the requirements described above, for energized electrical work.
Work Practices
Work on greater than 600 volts must be performed following the same
requirements as described above under Operating Procedures, including the
use of permits, Qualified High Voltage Electrical Workers, tools, PPE, and
safety observers.
Voltage Detection
The operating voltage of equipment and conductors must be determined
before performing any energized electrical work on high voltage systems.
This should be performed using a calibrated and working high voltage probe
designed for high voltage circuits at the level of voltage to be encountered.
Proper planning and preparation will make any type of testing simpler
and safer.
Having to stop work to fetch other tools or testers interrupts focus and
can contribute to an accident.
What tools will you use to verify the energized or de-energized state?
Figure2. For your second test, pick a digital, not solenoid, electrical
tester.
These little tools are good for a first test, but should always be followed up
with a direct-contact meter. At Shermco Industries, we issue each of our
technicians a proximity tester like the one shown in Figure 1 to keep in their
top pocket or somewhere it can be easily seen, if it lights up in the presence
of voltage.
Keep in mind that proximity tester readings can be thrown off if:
Proximity testers also wont detect shielded cable. To better understand why
proximity testers have these limitations, read the Fluke application note on
the subject, Understanding capacitive voltage sensors. The key word is
proximity.
Proximity varies not just by distance, but also by the strength of the voltage
field. And distance has to account for everything between the tester and
ZRC TRAINING CENTER PHILS. INC. CEBU Page 194
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
the electrical source, including the air, insulation, breaker material, twist
locks and so forth. The real issue is that proximity testers may indicate
voltage, or they may not, depending on specific circumstances. For absence
of voltage testing, a different, completely reliable test method is required.
Solenoid testers wear out and the voltage scale becomes scarred up. If
you cant read the voltage indicator and the solenoid is so weak that it
barely vibrates, its not reliable to use.
Solenoid testers arent fused and dont comply with CAT safety rating
requirements. If a transient hits the system while youre connected,
theres nothing to protect you from serious injury.
C) Digital multimeter
Multimeters are the best standard tool for making accurate contact
measurements to determine if a circuit is live. However: Turning the
multimeter dial to the wrong function (amps instead of volts, for example) is
one of the most common mistakes people make when using a multimeter.
Older models that are not auto-ranging could be put into a range that is too
high, making the voltage appear much smaller than it really is. Someone in a
The Fluke Model 117 for example, has a low impedance function for voltage
testing that can be a great safety feature. The Fluke 117 also has a built-in
non-contact voltage test function, for people who want to start with a
proximity test and then move to a contact test, with the same instrument.
OSHA states that test equipment, and their accessories, shall be rated for
the circuits theyll be connected to. The NFPA 70E contains similar
statements.
My crew proceeded to lock and tag the system and, since it was a double-
ended substation, it was fairly easy to isolate the problem transformer. The
terminal chamber cover was removed and, being
completely certain the circuit was de-energized, I was about to untape the
connections in preparation for testing. At the last moment, I decided to follow
Hydraulic system
Hydraulic maintenance
Hydraulic fluids are the life blood of the hydraulic system. The hydraulic fluid
transmits pressure and energy, seals close-clearance parts against leakage,
minimizes wear and friction, removes heat, flushes away dirt and wears
particles, and protects surfaces against rusting. Conventional petroleum
ZRC TRAINING CENTER PHILS. INC. CEBU Page 198
MANAGEMENT LEVEL COURSE ENGINE
FUNCTION - 2
(mineral) oils are normally used in hydraulic systems,
but fire-resistant, synthetic, and biodegradable fluids
are used in other situations.
There are four key objectives that are essential to
gaining optimum service life of hydraulic fluids:
In modern equipment using servo valves, oil degradation can be even more
damaging. High pressure (up to 4000 psi), high temperatures, and small
reservoirs stress the fluid. With minimal residence time and high pressures,
entrained air bubbles can cause extreme localized heating of the hydraulic
fluid. This results in nitrogen fixation that, when combined with oil oxidation,
can form deposits which will plug oil filters and cause servo valves to stick.
Keep the Fluid Clean keeping hydraulic fluids clean begins with good
storage and handling practices. To prevent contamination before use, store
new fluid in a protected area and dispense it in clean, DEDICATED containers.
Clean the fill cap before removing it to add hydraulic fluid. On critical NC
For systems that exhibit high deposit, sludge and/or varnish formation: a
petroleum based cleaner (such as Mobil System Cleaner) may be required.
Follow manufacturers recommendations.
Safety Precautions
Hydraulic systems operate under very high pressures. Shut the system down
and relieve system pressure before opening any part of the system that is
under pressure. Do not allow spray from any high pressure leak to contact
any part of the body, as serious injection injuries may result. Pumps, valves
and motor may become hot; be cautious of incidental contact between bare
skin and hot surfaces. Keep hands and clothing away from moving parts of
the
system.
Symbols for Fitting and Representations
Pneumatic control equipment
Example circuits:
A time delay in a pneumatic circuit provides a delay between the operation
of a valve and the movement of a piston. Time delays are achieved by
connecting aunidirectional-flow control valve and a reservoir in series.
A pneumatic circuit with a time delay is shown in the diagram and explained
below.
Types of Fittings
Connection Type
Compression fittings include all types of fittings which use compressive force
to connect the vessel to the fitting.
Tee with compression fitting nuts on each end. Image Credit: Parker
Hannifin
Mechanical grip fittings are two-ferrule assemblies. The back ferrule grips
the vessel while pressing up against the front ferrule, which spring-loads the
front ferrule and creates a seal between the piping and fitting body. These
Crimp Fittings
End Fittings
Threaded Fittings
The thread size is measured and based on the inside of the vessel. Thread
size standards include NPT (National Pipe Thread) and BSP (British Standard
Pipe), though many other standards exist and usage often
varies by country and industry. Each thread size corresponds to a particular
number of threads per inch (TPI). Plumbingsupply.com provides an excellent
overview on pipe thread sizing. Below is a chart depicting nominal thread
sizes and their corresponding values.
Thread
Designati
OD OD Actual on - Thread per inch
Nominal
Size
(fraction
(inches) (inches) NPT BSP
inch)
2-3/8 2.375 2 8 11
3-1/2 3.5 3 8 11
4 4.0 3-1/2 8 11
4-1/2 4.5 4 8 11
5-5/8 5.563 5 8 11
6-5/8 6.625 6 8 11
Function
Image Credit:
Parker
Hannifin
Image Credit:
Parker
Hannifin
Image Credit:
Automationdir
ect.com
Image Credit:
Taiwan Chelic
Corporation
Specifications
Sizing
Once the type of fitting required has been determined, the most fundamental
aspect of pneumatic fittings can be addressed: proper sizing. Proper sizing is
essential to successful fitting selection, as oversized or undersized parts will
either be completely incompatible or will seal or connect inadequately.
The two systems of measurement are Metric (mm) and English ("). The first
step to proper sizing is selecting the appropriate measurement
system for compatibility with the equipment or assembly being fitted.
Pneumatic fittings often are rated for certain temperature and pressure
ranges based on what they are designed to handle.
Materials
Metals
Aluminum - lightweight and corrosion resistant. By itself, aluminum has low
tensile strength and is used for its corrosion resistance and low density in
low pressure applications. It is alloyed with zinc, copper, silicon, manganese,
and/or other metals to improve its strength and hardness.
Plastics
Fluororesins such as polytetrafluoroethylene (PTFE) and polyvinylidene
fluoride (PVDF) are fluorocarbon-based polymers typically used for
temperature requirements above 500F (250C). They exhibit very good
chemical resistance and dielectric properties.
Composites
Features
Pneumatic fittings may have other features which add functionality needed
for certain applications.
Lined fittings are manufactured with an integral lining. The linings are often
made from engineered polymers for use with process materials or in
applications such as food processing where media cleanliness is important.
When did the problem begin? Was it a sudden failure or a gradual failure?
Where in the machine cycle does the problem occur? Was it at startup or
after the system has been operating for a while?
Asking, "When did the problem begin?' can often lead to troubleshooting
steps looking for worn components or leaks. Sudden malfunctions can point
to breaks and possible mechanical problems, ruptures in lines, or other
catastrophic failures. By determining the when, the problem search can be
narrowed in its scope.
Asking, "Where in the machine cycle does the problem occur?" can reveal a
reoccurring condition.
A maintenance person who stops and asks the three Ws can reduce
downtime by not having to guess at what is wrong. However, if these
questions do not yield a satisfactory diagnosis the maintenance person must
begin the mechanics of troubleshooting by visually inspecting the machine.
Walking around the machine will often uncover problems such as worn or
burst hoses, loose components, and broken components. This is the time to
become familiar with the components contained in the pneumatic system.
Every pneumatic system should have two forms of documentation that will
assist in troubleshooting. One document is a schematic drawing of the
pneumatic circuit (Fig. 3). The schematic is a road map. It not only explains
the operating function of the components but also is a valuable diagnostic
tool.
After becoming familiar with the components and operation of the pneumatic
system, start the machine and operate it to get a first-hand view of the
malfunction. See if the malfunction that has been reported occurs again.
While operating the machine, perform a visual inspection.
If there are manual controls for the machine, do they feel stiff or loose in
their operation?
Before attempting repair on the machine after it has been operated, once
again check to see if power supplied to the machine has been turned off.
Check to see if any stored pressure remains in the system, because this
stored pressure can cause premature actuation of the system's actuators
and cause injury to personnel and damage to the machine.
Isolate subsystems
Any lines that have been disconnected and any ports that have been opened
should be plugged properly to prevent unnecessary air leakage and the
entrance of contaminants.
While operating the machine, a close watch should be kept on the pressures
within the system, so maximum allowable pressures are not exceeded.
Caution and safety are the two keys to this diagnostic step.
Make a list
During the previous step, the immediate problem may be quite obvious.
However, in troubleshooting, the obvious may not be the root cause.
After making a list of possible causes, check those items on the list and
eliminate them without going back over ground previously covered. This list
will also reduce the time required for troubleshooting and can eliminate the
parts exchanging syndrome that often accompanies troubleshooting.
After making a list and narrowing the possible causes, it is now time to make
a decision on which one of the remaining causes is most likely to be the
reason for the malfunction. Reaching this conclusion may, at first, appear
difficult but this step is essentially the starting point for the repair portion of
troubleshooting. Up to now the system has been evaluated, now it is time to
test the conclusion.
In the example, testing the conclusion may be merely the need to add
lubricant to the lubricator or make an adjustment to the drip rate of the
lubricator.
Repair or replace
To simply replace the part with a new or rebuilt component would reduce the
amount of downtime; however, the question of inventory cost now becomes
a factor.
After the malfunction has been corrected, one final step remains the need to
report the findings.