Sunteți pe pagina 1din 14

Applied Energy 134 (2014) 215228

Contents lists available at ScienceDirect

Applied Energy
journal homepage: www.elsevier.com/locate/apenergy

Comprehensive analysis on thermal and daylighting performance


of glazing and shading designs on ofce building envelope
in cooling-dominant climates
Yu Huang, Jian-lei Niu , Tse-ming Chung
Department of Building Service Engineering, Faculty of Construction and Environment, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong Special
Administrative Region

h i g h l i g h t s

 We conducted an evaluation on the performance of energy-efcient envelope designs.


 Both thermal and daylighting performance of glazing and shading were considered.
 In cooling-dominant climate, low-e glazing is the best energy-efcient window design.
 Double-layer glazing performs the worst; overhang performs better than interior blind.
 Orientation and latitude can signicantly affect the performance of window design.

a r t i c l e i n f o a b s t r a c t

Article history: Conducting energy-efcient designs on building window can be a solution to relieving the pressure
Received 15 April 2014 caused by growing building energy consumption. In this paper, a series of simulation studies were carried
Received in revised form 28 July 2014 out to evaluate the performance of several popular energy-efcient window designs in cooling-dominant
Accepted 30 July 2014
climates. Both thermal and daylighting performance were considered during the analysis. Results indi-
Available online 24 August 2014
cate that among all designs studied, low-e glazing achieves a best performance, while double-layer glaz-
ing performs the worst. Energy-efcient designs on the east and west orientations are the most cost-
Keywords:
effective in cooling-dominant climates. As latitude rises, the performance of window designs on the south
Shading design
Low-e glazing
orientation is getting better. It is also discovered that only in area very close to equator performance of
Building envelope north facing window designs is satisfactory. Furthermore, as the reectivity of blind louver decreases,
Energy-efcient design both thermal and daylighting performances drop.
Solar heat gain 2014 Elsevier Ltd. All rights reserved.

1. Introduction As early as 2000, Nielsen et al. presented a work of an easy


method for determining the net energy gain through window area.
Window provides the occupants with a connection to the out- The method took into consideration of orientation, shading and
side environment. The open view through windows is considered glazing material [1]. Menzies and Wherrett conducted several sur-
as a highly desirable feature for ofce building especially in high- vey studies to look into the sustainability and comfort issues of
rise cities. Glazing area is a key factor being noticed in building multi-glazed window. They claimed that during design of window
energy consumption. area, the architects considered more about comfort. When it comes
As the most common fenestration style, window plays a very to sustainability, they did not consider much [2]. Aydin performed
important part in providing thermal comfort and optimum illumi- a numerical analysis on the heat transfer process in double pane
nation levels in building, and also a very popular architectural form. windows using a nite difference technique. He discovered that
Due to its relatively high U-value than wall area, the thermal perfor- for heat transfer through windows, there exist optimum thick-
mance of glazing material is a top concern within professionals. nesses of air layer between glasses [3,4]. Tian et al. developed a
generalized window energy rating system for typical ofce build-
ing application and conducted a simulation study utilizing a typical
Corresponding author. Tel.: +852 2766 7781; fax: +852 2765 7198.
Hong Kong ofce model. They claimed that their approach took
E-mail addresses: 10900570r@polyu.edu.hk (Y. Huang), bejlniu@polyu.edu.hk
both daylighting and thermal performance into consideration.
(J.-l. Niu), betmchng@polyu.edu.hk (T.-m. Chung).

http://dx.doi.org/10.1016/j.apenergy.2014.07.100
0306-2619/ 2014 Elsevier Ltd. All rights reserved.
216 Y. Huang et al. / Applied Energy 134 (2014) 215228

They also claimed that their approach could be applied directly in Chow et al. made a very detailed review on the state-of-art tech-
area with similar climatic and geographic conditions to Hong Kong nologies of window glazing applied in cooling dominate climate.
[5]. Ochoa et al. conducted a simulation study tend to develop a They introduced traditional single-glazed and double-glazed win-
design method for windows which took into consideration both dows. They also paid much attention on newly developed water-
low energy consumption and high visual comfort. They claimed ow window [18]. Bojic and Yik investigated the application of
that since the two aspects cannot be satised at the same time, low-e glazing to high-rise residential buildings in Hong Kong
necessary balance between different factors should be selected through a simulation work. They received a saving of 4% during
very carefully. They also discovered that choosing visual comfort the simulation and claimed that the application of expensive
criteria is more difcult [6]. Tsikaloudaki et al. performed a simu- advanced glazing in residential building may not be economically
lation work in an ISO reference room to study the impact of differ- viable in Hong Kong. They also found that the location of the target
ent parameters on window performance in ofce buildings in room within the building played a very important role [19]. Assem
Mediterranean zone. They discovered that solar transmittance and Al-Mumin utilized EnergyPlus software to simulate the glazing
played a more important role than thermal transmittance. They performance in fully glazed tall ofce building in Kuwait. They dis-
also discovered that if the solar transmittance is low, the fenestra- covered that glazing heat gain is a major part in ofce building heat
tion would not be quite important [7]. gain. In order to meet the government code, low-e glazing is neces-
Gasparella et al. developed a simulation work to study the sary in government building, while in private building, some extra
impacts of glazing type, window size, orientation and internal heat measure should also be applied [20]. Fang et al. conducted a series
gain to energy performance of residential building in four central of experimental and simulation study to test the thermal perfor-
and southern Europe cities. They found that the application of large mance of low-e coating applied on vacuum glazing with a three-
glazing area could enhance winter performance. But in summer, dimensional nite volume model. They claimed that while the
shading system should be applied to avoid heat gain, south facing emittance is small, the application of two coatings on glazing could
window performed best in winter. They also found that thermal only offer a very limited improvement in thermal performance.
transmittance appeared to be the most important factor that Under most circumstances, application of only one coating with
affects the performance of window [8]. Singh and Garg collected vacuum glazing could already provide an excellent thermal perfor-
the parameters of different window glazing in Indian market and mance [21].
conducted an energy rating. They tend to make a reference for Aldawoud modeled the performance of an electrochromic glaz-
designing buildings with different purpose and climate [9]. Bojic ing system in hot dry climate and compared the result with tradi-
et al. also investigated the performance of clear glazing, tinted tional xed shading device. He claimed that though higher cost,
glazing and reective glazing in high-rise residential buildings the electrochromic glazing could signicantly reduce annual and
and claimed that before assessing or retrotting residential build- peak cooling load compared with external shading device [22].
ings, annual cooling load reduction, energy consumption and eco- Lee and Tavil also conducted a simulation work to assess the energy
nomic appraisal should be conducted beforehand [10]. Poirazis and visual performance of electrochromic windows with overhang.
et al. conducted a simulation work on energy performance of They tested performance of various combinations of overhang posi-
glazed ofce buildings in Sweden. They claimed that in order to tion and control strategies. They claimed that a reduction of 10%
keep the energy performance of full glazed single skin ofce build- could be achieved in cold climate, and a reduction of 5% could be
ing acceptable, a well-designed shading system is necessary [11]. achieved in hot climate. They also claimed that performance of
Wong et al. conducted a simulation study on energy and thermal electrochromic glazing on moderate-area window is not that signif-
comfort performance of double-glazed faade in Singapore. They icant compared with large window [23]. Dussault et al. conducted a
claimed that due to the natural ventilation between two glazed simulation work to investigate a double-layer smart window with a
layers, double layer faade could minimize energy consumption controllable absorbing layer added on the interior surface of the
while enhance thermal comfort. They also claimed that during high exterior glass pane in Quebec City, Canada. They claimed that appli-
humidity period, introduction of mechanical fans could solve the cation of the smart window on south and west faades could
condensation problem [12]. Smith et al. investigated a new retrot receive a best performance, while application on north faade is
measure which installed a secondary glazing on existing single- not better than widely-applied low-e glass [24]. Inoue et al. exam-
glazed window. They tested four different secondary glazing ined the performance of an autonomous responsive dimming glass
options and claimed that all four different glazing could signicant through experiments and simulation. The dimming glass consisted
reduce heat gain through window area, and the retrot measure of a transparent heating layer, an electrochromic layer and a poly-
could considered to be a sound alternative for existing single- mer gel layer. They claimed that with appropriate control of the
glazed window [13]. Arici and Karabay calculated the optimum heating layer, the shading effects of the dimming glass is signicant
air layer thickness in four different climate zones in Turkey under [25]. Lu and Law investigated the overall energy performance of a
heating condition. They claimed that the optimum thickness is single-glazed photovoltaic window in a typical Hong Kong ofce
between 12 and 15 mm. They also claimed that with application building through a simulation work. They took into consideration
of a well-designed window, a saving of up to 60% could be achieved not only the heat gain reduction from solar radiation, but also the
[14]. Ismail et al. conducted a simulation study to compare the electricity generation as well as the daylighting performance. They
thermal efciencies of double layer glass window lled with claimed that the application of PV window could reduce around
absorbing gas exposed to solar radiation with both single layer 65% of the total heat gain through window area, and an extra
glass window and double layer glass window naturally ventilated 9001300 kW h annual electricity could be expected. They also
in hot climate. Three different mixtures of absorbing gas were sim- claimed that in the overall energy performance, the impact of ther-
ulated. They claimed that double layer glass window with absorb- mal performance is the greatest, while the impact of daylighting
ing gas and PCM performed better than regular double layer glass performance is not signicant [26]. Chow et al. also conducted a
window naturally ventilated [15,16]. Manz et al. investigated the simulation work on the overall performance of PV ventilated win-
impact of different parameters on the thermal performance of tri- dow, they discovered that compared to conventional single glazing,
ple vacuum glazing through a simulation study. They suggested a natural-ventilated PV window could reduce the space cooling load
that even considering the effect of support pillar radius, separation by about 28%. They also claimed that different orientations would
and thermal conductivity, the performance of triple vacuum glaz- receive a different energy performance, and a best performance
ing is still better than other insulated glazing [17]. could be received with a solar cell transmittance of 0.450.55
Y. Huang et al. / Applied Energy 134 (2014) 215228 217

[27,28]. Chow and Li also constructed a water-ow window to test Recently, with the development of building energy simulation
its performance in practical building-like condition. They also built software, researchers were able to make comparisons and summa-
a mathematical model to simulate the annual energy performance. rize principles from large number of cases. Many literatures focus
They claimed that a reduction of 8% could be achieved while com- on the structure and optical parameters of window glazing, aiming
pared to normal double-glazed window [29]. Chow et al. tried to at exploring their effects on the lighting energy consumption. The
apply ventilation in double glazed window glazing. They also con- ideal window size, direction and types to minimize energy con-
ducted a simulation study to research the impact of different con- sumption of buildings were studied by Inanici and Nur Demirbilek
gurations. Their nding indicated that in warm area like Hong [46]. Through large number of case simulations, the effect of indoor
Kong, a better energy performance could be achieved in summer temperature setting point on the daylighting performance of win-
with the application of ventilated window glazing [30]. Jonsson dows was studied by Kontoleon and Bikas [47]. They claimed that
and Roos tested the visual and energy performance of antireection the glazed opening percentages had a huge effect on thermal per-
coating. They applied the coating on different types of glazing and formance of the buildings. Al-Homound also simulated the day-
simulated their performance. They discovered that in most cases, lighting performance under different climate situation and made
antireection coating performed well, but when applied on low-e interesting analysis with other experimental studies [48]. More-
glazing, the antireection coating did not make any impact [31]. over, Johnson et al. simulated the economically optimum window
Windows also provides daylighting, which helps to reduce area and orientations through software simulation [49]. With the
energy consumption from articial lighting system as well as air- support of detailed data, researchers could also evaluate the per-
conditioning load. However, large window area can also lead to a formance of advanced shading or window materials [50].
large amount of unwanted solar radiation heat gain. Achieving a From the above literature review, it is obvious that in thermal
balance between letting in daylight and blocking out solar heat performance aspect, there have been several studies on energy per-
gain is a major challenge. formance of blind and overhang shading systems. Key variables that
The US government proposed a project named Green Light Pro- affect the performance have also been investigated. But most stud-
gram in 1991, with the purpose to promote the development of ies focus on residential building, research on commercial building is
efcient lighting and to control the lighting electricity. Policies limited. Current studies tend to consider the building envelope as a
such as scal subsidies and time-of-use price were also carried whole, the impact of orientation is often ignored. Majority of reports
out. It was believed that proper daylighting design can largely focus on simulation or experiment on one single local building, the
reduce the building energy consumption, and the vision efciency impacts of geography location are not discussed. Besides, though
could also be improved at the same time [32,33]. there have been many studies on automated blinds, its performance
Li and Tsang carried out detailed studies on key building param- is not stable and its application is not widely acceptable. In most
eters affecting the daylighting designs, and found out that daylight- cases, designers still prefer conventional blind devices. While in
ing performance in ofce buildings as well as school buildings could visual performance aspect, daylighting performance of window
be quite effective, in which situation about 25% of the total electric glazing and shading device has been investigated. The indoor day-
lighting energy consumption could be saved. It was also found that lighting illumination level and distribution under different devices
the scale of the room and the shading option could largely affect the and control strategies has also been studied. The energy saving from
daylighting performance of the buildings. These basic studies laid a articial lighting system under different daylighting devices and
solid foundation for further investigations [34]. control strategies has been discussed. However, daylight is always
Window opening provides the nearby space a satisfying day- coupled with solar radiation. Daylighting application will always
lighting level, but the day lighting level deep inside the room bring in solar radiation heat gain for building inner space, which
may not always be desirable. In order to fulll the minimum would become cooling load for air-conditioning system eventually.
requirement of visual environment, an articial lighting system is These two conict factors make it complicated to achieve an opti-
necessary. Early studies mainly focus on the simulation of energy mum design for transparent surface of building envelope. There
saving from the articial lighting dimming as a function of the day- are few literatures on this issue in existing studies [51].
lighting availability. Bodart and De Herde developed a calculation Lighting and air-conditioning energy consumptions are the top
model to predict the energy consumption of the interaction of day- two components of total building energy consumption. In this
lighting and articial lighting system. They argued that only con- paper, a simulation study was conducted to study the comprehen-
sidering the quantity of daylight, articial lighting energy sive daylighting and thermal performance of energy-efcient win-
consumption could be reduced by 5080% [35]. Li et al. discovered dow designs in cooling-dominant climates. Several popular design
that with the application of high frequency dimming control of patterns, namely double-layer glazing, low-e glazing, interior blind
daylighting equipment, the articial lighting energy consumption and overhang were selected. The main object of the study is to
could be reduced by more than 30% [33]. They also discovered that evaluate the cost-effectiveness of these popular design patterns
utilizing energy-efcient light tting with dimming control and and clearly indicate the impacts of orientation as well as latitudes,
proper daylighting schemes, the energy consumption could be fur- so that detailed guidelines could be achieved for practical building
ther cut. The performances of two basic categories of photoelectric design in cooling-dominant climates.
lighting controls: the onoff control and the dimming control were
also discussed. It was believed that when it came to brightness of
the working plane, the daylight availability is the key parameter 2. Methodology
to estimate the energy saving under onoff and dimming controls,
as the daylight availability decreases, the dimming control acts Two popular building simulation programs, namely EnergyPlus
more efciently, but when it was in a high level, the onoff control and Daysim were used in combination in this research. EnergyPlus
turned out to be better [36]. is a building energy simulation program, which is based on the
As the awareness of daylighting getting popular, various sorts of state-space techniques, to calculate the space load required to
daylighting equipment have been manufactured. The application maintain a set condition in a building installed with a variety of
of advanced daylighting equipment is expected to reduce solar specied HVAC systems. Many previous studies have proved its
heat gain while improving the comfort level. The number of studies accuracy and adaptability [5254]. Daysim is a dynamic RADI-
on these daylighting devices is large. Table 1 gives a summary of ANCE-based daylighting simulation program that calculates the
representative studies on the topic. annual daylight amount received within buildings. Daysim allows
218 Y. Huang et al. / Applied Energy 134 (2014) 215228

Table 1
Summary of literature review result on energy saving potential of advanced daylighting equipment in buildings.

Authors Concern addressed Methodology Conclusion


Galasiu et al. [37] The impact of window blinds on two On-site measurement in two side-by-side ofces. Daylighting can reduce 5060% of lighting energy
photocontrolled lighting system: Lighting energy consumption was recorded from consumption in the building. Window blind would
continuous dimming and automatic 6 AM to 6 PM for a year largely reduce the energy saving due to
on/off daylighting. Of the two photocontrolled lighting
system studied, automatic on/off system achieves
a greater saving
Athienitis and To develop a methodology for An experiment is conducted to achieve the The lighting energy saving from this window
Tzempelikos simulation of ofce equipped with daylight transmittance equations of the window system could be more than 75% in overcast days
[38] motorized reective blind in system as a function of sky condition. A simulation and even 90% for clear days. Meanwhile, proper
between double-layer glazing is then processed to determine the energy saving control of blinds can avoid glare. However,
from the system frequent movement of blinds should be prevented
Chaiwiwatworakul The performance of automated blind An experiment was conducted in a test building. A The application of step-less controlled blind can
et al. [39] cooperation with dimming dimming controller was installed in the lighting result in a lighting energy saving of up to 80%. At
controlled articial lighting system system. Indoor illumination level as well as the same time, the indoor visual environment can
in tropical region lighting energy consumption was measured also be improved
Lee and Selkowitz The lighting energy saving potential A 9-month monitored eld study was carried out Work plane illumination level can be maintained
[40] of two different daylighting control in a 401 m2 unoccupied mockup. Indoor for over 95% of the monitored period. A lighting
system on automated rolling shades illumination level as well as lighting energy energy saving of 510% and 2540% can be
consumption was measured achieved for dimming control and DALI-based
control, respectively
Kim et al. [41] The lighting energy saving ability of A survey is rst conducted to collect the blind use The automated blind can reduce the room
automated blind and the pattern. With the operation data two control temperature by around 23 C while no air-
insufciency of the control algorithm patterns were developed to apply in the conditioning is applied. However, when it comes to
experiment. The temperatures in test rooms with thermal comfort, automated blind performs worse
no air-conditioning were tested than manual blinds
Inoue [42] The impact of automatic response Several window systems with the combination of A reduction of at least 20% can be expected from
dimming glass on the air- thermotropic glass, low-e glass, air gap and phase- air-conditioning energy consumption. The indoor
conditioning load change materials were prepared and measured in a visual environment is also improved
building with no HVAC system. The indoor
temperature was recorded. A series of simulation
works were also conducted
Li et al. [43] The impacts of the solar lm coating A eld measurement in an ofce building was A 30% decline in solar radiation heat gain is
on cooling energy requirements and arranged. The solar radiation heat, indoor observed. The electric lighting energy saving
electric lighting loads illumination level and energy consumption were depends largely on the amount of diffuse radiation.
recorded Also, the performance of solar lm coating
depends largely on the building shape and type of
HVAC system
Ghisia and Tinker The practicality of advanced A methodology is rst developed to calculate the With the application of ber optics daylighting
[44] daylighting equipment with the lighting energy saving from the illumination level. system, lighting energy savings ranging from 17.7%
application of ber optics in Brazil Then a large number of simulations are carried out to 92.0% could be achieved in the seven cities in
and the UK to get the daylighting effect of ber optics Brazil and savings ranging from 10.8% to 44.0%
could be achieved in the UK
Menzies and The sustainability and comfort issues A large scale case study involving four buildings The daylighting effects of window devices studied
Wherrett [2] of several multi-glazing windows was held. The energy use in the buildings was can reduce energy use in buildings while make the
recorded. A survey was conducted to determine environment more comfortable. However, if
the comfort situation comfort issue was considered rst, the energy
saving effect will be weakened
Sullivan et al. [45] To develop a methodology to Large number of DOE-2 based simulation was A generally good agreement between prediction
calculate the HVAC and lighting undertaken to form a data base, summary of result from the method developed and case study
energy saving from application of principles is then conducted from the data base can be achieved
daylighting device

users to calculate the annual electric lighting energy consumption


under certain illumination level set-point. Daysim could be directly
coupled with thermal simulation program such as EnergyPlus
[55,56].
A 20-oor high-rise ofce building model was dened for the
simulation study. The ofce building is a square building with a
northsouth orientation. The oor area is 100 m  100 m. The
height of oor is 3.2 m. The window-wall ratio of each vertical fa-
ade is 0.35. There is no window glazing on roof area. The detailed
inside partition of a typical oor is presented in Fig. 1.
Four cities with different climates were selected. The four cities
from south to north are Singapore, Hong Kong, Miami and Houston.
All the four cities are located in Northern Hemisphere. Their lati-
tudes are 1180 , 22150 , 25470 and 29450 . Since over 75% of the Fig. 1. Partition of a typical oor of the building.
world populations live within 2060 north latitude, the selection
of these four cities is considered representative. Within these four 2.1. Simulation set up for thermal performance
cities, solar elevation angle at the same time decrease from south
to north. All the four cities are located within cooling-dominant The details of building construction, including structure and
climates. materials of wall, roof, ceiling, oor and window were dened
Y. Huang et al. / Applied Energy 134 (2014) 215228 219

strictly according to local standards of building design [5759]. The tion measuring points was 0.8 m, which is a typical height of work-
detailed structure and parameters of wall and roof are shown in ing desk. The maximum allowable Discomfort Glare Index was 22
Table 2. The peak occupant density was 13 m2/person. The peak [60].
lighting power density was 15 W/m2. The peak equipment power Two different occupant behavior models were applied. For the
density was 10 W/m2. The minimum fresh air supply was 8 L/s/ rst occupant behavior model, occupants were considered to have
person. The cooling load caused by inltration plays an important no daylighting awareness. They would simply turn on the light
part in the building cooling load. In the simulation study, a consis- above their seats once they arrive at the ofce, and switch it off
tent 1 m3/m2 h air inltration was applied, so that the simulation while they leave. Under this condition, there was no dimming con-
result could be as realistic as possible. The operation schedules of trol of the articial lighting. The articial lighting system was set to
occupant, lighting and equipment are presented in Fig. 2 (in air- be strictly operated according to the schedules in Fig. 2. The simu-
conditioning schedule, 1 on y-axis stands for ON status for lation based on the rst occupant behavior model is serving as the
air-conditioning system while 0 stands for OFF status). During Base Case. While in the contrast cases, the second occupant behav-
air-conditioning hours, the indoor air temperature was set at 25 C. ior model was applied, while the occupants were supposed to con-
The simulation time step was 10 min. The simulation period was sider daylighting as priority. While they arrive at the ofce, the
1 year. articial lighting system would be switched off by default, and
daylighting is rst considered. Only when the illumination level
2.2. Simulation set up for daylighting performance is lower than 500 lux or glare appears, articial lighting system
will be turned on.
There are two major factors which directly affect the quality of
visual environment: illumination level and illumination distribu- 3. Results and discussions
tion. If the illumination level is too low, articial lighting system
will be necessary to maintain a visual comfortable environment. 3.1. Simulation result of the thermal performance of different energy-
If a signicant ratio of luminance appears within a small area, a efcient window designs
glare appears, occupants will also prefer to articial lighting to
maintain a satisfactory visual environment. During the daylighting 3.1.1. Glazing materials
simulation study, both factors should be considered. Double-layer glazing and low-e glazing can be considered as dif-
During the daylighting simulation, the peak lighting power ferent kinds of glazing materials, thus their performances are dis-
density was 15 W/m2. The indoor illumination level set point was cussed in one section in the study. The double-layer glazing
500 lux. The lighting control system was set to be Manual on/off applied here was two layers of clear glass described in Table 2 with
switch near the door which is a popular lighting control type in a 6 mm air layer in between. The low-e glazing applied here was
commercial buildings. The illumination measuring point matrix double-layer glazing with a low-e coating applied on the inner
was distributed uniformly into each ofce. The height of illumina- surface of the outer glazing layer. The optical features of the

Table 2
Detailed data of building materials.

Material Thickness (m) Conductivity (W/m K) Density (kg/m3) Specic heat (J/kg K)
A. Wall in Hong Kong and Singapore
White mosaic tile 0.005 1.5 2500 840
Cement render 0.01 0.72 1860 840
Concrete panel 0.1 2.16 2400 657
Gypsum plaster 0.01 0.51 1120 960
B. Roof in Hong Kong and Singapore
Concrete tiles 0.025 1.1 2100 657
Asphalt 0.02 1.2 2300 1700
Cement screed 0.05 0.72 1860 840
Expanded polystyrene 0.05 0.035 23 1470
Concrete 0.15 2.16 2400 657
Gypsum plaster 0.01 0.51 1120 960
C. Wall in Houston and Miami
1IN stucco 0.0253 0.6918 1856 837
8IN concrete HW 0.2032 1.311 2240 837
IN gypsum 0.0127 0.16 785 830
D. Roof in Houston and Miami
Roof membrane 0.0095 0.16 1121 1460
IEAD NonRes roof 0.0125 0.049 265 837
Metal decking 0.0015 45 7680 418

Properties Data
E. Optical features of glass layer applied in simulation
Solar transmittance at normal incidence 0.708
Front side solar reectance at normal incidence 0.075
Back side solar reectance at normal incidence 0.075
Visible transmittance at normal incidence 0.753
Front side visible reectance at normal incidence 0.075
Back side visible reectance at normal incidence 0.075
Infrared transmittance at normal incidence 0
Front side infrared emissivity at normal incidence 0.84
Back side infrared emissivity at normal incidence 0.84
220 Y. Huang et al. / Applied Energy 134 (2014) 215228

1. Occupant 2. Equipment

3. Lighting 4. Air-conditioning
Fig. 2. Schedules setting for occupant, lighting, equipment and fresh air supply.

low-e glazing layer are listed in Table 3. Fig. 3 presents the space even better. While low-e glazing presented in Table 3 is applied,
cooling load caused by window heat gain in different cases. It window heat gain was cut by almost 50%. While low-e glazing with
should be noted that in the following discussion heat gain result better optical parameters is applied, better thermal performance
is converted into heat gain per unit area of window surface. can be expected.
The application of double-layer glazing in cooling-dominant
area can reduce window heat gain by around 1520%. Compared
3.1.2. Interior blind
to single-layer glazing, double-layer glass has an extra glass layer
Compared to external shading devices like overhang, one key
which can help block out part of solar radiation. When radiation
advantage of blind is its adjustability. The occupants can adjust
projected on the second glazing surface, part of it travels directly
the tilt angle of louvers according to outdoor weather condition.
through, part of it is reected back to the backside of the rst glaz-
Obviously the performance of blind depends largely on the tilt
ing layer, and the rest of it is absorbed by the glazing material. Part
angle of blind louver. Fig. 4 below presents the denition of tilt
of the absorbed radiation will be radiated into the room by long-
angle used in the simulation. As the tilt angle gets smaller, less
wavelength radiation. The reected part of radiation will again
solar radiation is allowed to get into the building. Window heat
be absorbed and reected by the rst glazing layer, and then
gain is reduced, while daylighting effect is also weakened. Accord-
repeats previous process. Therefore while introducing in the sec-
ing to previous study, occupants do not adjust interior blind very
ond glazing layer what really matters is the blocking effect of
often. They tend to set the blinds in certain positions based on
glass material. With respect to low-e glazing, the performance is
long-term perceptions of sun light and sun heat, and then just
leave them there [61,62]. In this study, the impact of occupant
behavior was investigated. Performances of interior blind with
Table 3
Optical features of low-e glazing layer applied in simulation.
three different tilt angles were simulated. The simulation results
of the thermal performance are presented in Fig. 5.
Properties Data
In Singapore, the interior blind on the east and west facades can
Solar transmittance at normal incidence 0.4 cause about 20% more heat gain reduction of the building than
Front side solar reectance at normal incidence 0.281 those on the south and north orientations. The blind on the south
Back side solar reectance at normal incidence 0.403
Visible transmittance at normal incidence 0.742
faade reduces the least heat gain compared with those on the
Front side visible reectance at normal incidence 0.064 other facades. In Hong Kong, the blind on the south faade contrib-
Back side visible reectance at normal incidence 0.052 utes almost the same as those on the east and west faades. The
Infrared transmittance at normal incidence 0 north facing blind reduces only less than half of the heat gain com-
Front side infrared emissivity at normal incidence 0.84
pared with devices facing the other orientations. With respect to
Back side infrared emissivity at normal incidence 0.05
Houston and Miami, performance of the blind on the north faade
Y. Huang et al. / Applied Energy 134 (2014) 215228 221

A. Singapore B. Hong Kong

C. Miami D. Houston
Fig. 3. Thermal performances of double-layer glazing and low-e glazing.

Louvers reectivity is also an important parameter that affects


the blinds performance. Fig. 6 presents the thermal performance
of interior blinds with different reectivity in Hong Kong. It is clear
that blind with higher louver reectivity performs better. Same
conclusion can be achieved from simulation result in other cities.

3.1.3. Overhang
Overhang may be the most traditional and popular shading
design in the world. The depth of overhang is a key factor that
affects the performance. Fig. 7 presents the thermal performance
of overhangs with depth from 0.6 m to 1 m. The height of window
in this study was 1.2 m.
When the overhang depth is more than half of the windows
height, the impact of overhang depth is not very signicant. The
impact of depth is higher on overhangs facing the east and west.
In practical projects, overhangs facing east and west can be longer.
With respect to the north faade, a short overhang or interior shad-
ing could be considered.

3.2. Simulation result of the daylighting performance of different


energy-efcient window designs

Fig. 4. Denition of blind tilt angle. In the following section, the daylighting performances of differ-
ent glazing and shading designs will be presented and discussed. In
order to investigate the impact of orientation, windows facing dif-
drops to only 1/3 of blind facing the other orientations. Similar ferent orientations are discussed separately. Within all the contrast
conclusions can also be achieved from the simulation result with cases, energy saved from daylighting is divided into four parts. In
different blind tilt angles. all the gures presented in this section, the South bar stands
The inuence of louver tilt angle on the blind is quite signi- for the lighting energy consumption under this condition: in this
cant. In most cases, setting the slat angle at 90 can only reduce ofce building, occupants in all the south facing rooms are acting
the window heat gain by about 1520%, while setting the slat angle according to the second occupant behavior model as described in
at 30 a reduction of around 4050% is achieved. It can be con- the Methodology part, while occupants in all the other rooms are
cluded that as the slat angle decreases, the thermal performance acting according to the rst occupant behavior model. Similar illus-
of the blind will be even better. trations can be applied to other orientations. In this way, the effect
222 Y. Huang et al. / Applied Energy 134 (2014) 215228

A. Singapore B. HongKong

C. Miami D. Houston
Fig. 5. Effect of tilt angle on blind performance.

coefcient stands for a small impact of external environment to


the building indoor environment [63]. In this study, the model
building was a simple square building with a large interior zone.
The shape coefcient can be calculated to be 0.056, which means
the impact of outdoor environment on the building energy con-
sumption is rather small. In this case, the lighting energy saving
from daylighting is also relatively small. From the simulation result
of the case it can be concluded that in buildings with small shape
coefcient, the design of window should consider thermal perfor-
mance as priority. In buildings with larger shape coefcient, day-
lighting performance will be better. However, it does not mean
daylighting is not effective in ofce buildings. Actually, though
Fig. 6. Thermal performances of interior blind with different reectivity in Hong
Kong. the proportion is small, the lighting energy saved from daylighting
is still rather considerable. Besides, the difference among different
cases also follows certain pattern that worth discussion.
of different window designs on the daylighting performance of From the simulation result it is clear that in almost all cases,
windows facing a specic orientation can be achieved separately. daylighting performances on the east and west orientations are
Fig. 8 gives the annual articial lighting electricity reduction better than those on the south and north orientations. In low
from application of daylighting strategy. Case A, Case B, Case C latitude area like Singapore, the difference is much larger. In dou-
and Case D are lighting energy consumption in the Contrast Case. ble-layer glazing cases, the difference between daylighting perfor-
Case A stands for the result with the application of double-layer mance of the east, west orientations and the south, north
glazing. Case B stands for the result with the application of low-e orientations is within 10%. In interior blind cases, the difference
glazing. Case C stands for the result with the application of interior is almost 50% in Singapore and 25% in Hong Kong.
blind (the blind tilt angle is 90). Case D stands for the result with Compared with double-layer glazing and low-e glazing cases,
the application of overhang (the depth of the overhang is 1 m). daylighting performances of interior blind in Singapore and Hong
Before the discussion, it should be noticed that in the Base Case, Kong are signicantly worse. While in Miami and Houston, the
the annual lighting energy consumption is 7.8  106 kW h, while in gap between shading device and energy-efcient glazing is much
all the Contrast Cases, the annual lighting energy saving are around smaller. In cooling-dominant area with relatively low latitude,
1.5  105 kW h. The proportion is small. The reason lies in the application of interior blind will signicantly affect the daylighting
shape coefcient of the model building. The shape coefcient is performance, while in area with high latitude the inuence is not
the ratio of the area of buildings external surface to the buildings that much. The daylighting performance of overhang equipped
volume. The shape coefcient characterizes the impact of external window is almost the same as the daylighting performance of dou-
environment to the buildings indoor environment. A small shape ble-layer glazing and low-e glazing. Daylighting performance of
Y. Huang et al. / Applied Energy 134 (2014) 215228 223

A. Singapore B. Hong Kong

C. Miami
D. Houston
Fig. 7. Thermal performance of overhang with different depth.

1. Case A 2. Case B

3. Case C 4. Case D
Fig. 8. Annual lighting energy consumption in different cases.
224 Y. Huang et al. / Applied Energy 134 (2014) 215228

interior blind is the worst within all window design measures lighting performances on the east and west orientations even drop
studied. to less than 80%. While in Miami, when the overhang depth changes
The daylighting performance of interior blind is also signi- from 0.6 m to 1 m, daylighting performances on the east and west
cantly affected by the louver tilt angle. As shown in Fig. 9, in Singa- orientations drop to over 90%.
pore and Hong Kong, the daylighting performance drops rapidly
with the tilt angle. While the tilt angle decreases to 30, Daylight- 3.3. Comprehensive evaluation considering both thermal and
ing prots on the south and north orientations completely disap- daylighting performances
pear. Daylighting prots on the east and west orientations also
drop to a very low level. In Miami and Houston, though there is Window is an important and indispensable element in modern
a drop on daylighting performance when the tilt angle gets smaller, architecture. Window can supply the occupants with an access to
daylighting effects on all orientations are still retained. the day lighting and pleasant outside view, which is considered
The reectivity of blind louver is also an important factor that to be a valuable feature in high-rise cities. Window is also, how-
affects the performance of blind. Fig. 10 gives the simulation result ever, a major route of the large amount of unwanted solar heat
for the annual lighting energy saving with different blind louver gain. The two conicting considerations bring forward a challenge
reectivity. Due to length limitation, only result of Hong Kong is in the window design area.
presented here. From above data an interesting conclusion can be In cooling dominant area, applying energy efcient window
achieved. With the decreasing of reectivity, the daylighting per- designs on building envelope can largely reduce heat gain through
formance of blind also drops. The performance of blind can easily window area, which is a major component of the building air-con-
be halved when the reectivity drops to 0.3. It is also clear that ditioning system load. Since almost all of the heat gain through
when the reectivity is higher the interior blinds ability to reduce window is radiation heat gain, the thermal resistance of glazing
lighting power is also higher. As displayed in the gure, no matter material cannot affect the windows thermal performance signi-
stays at which tilt angle, the interior blind with higher reectivity cantly. Application of double-layer glazing can reduce the window
always performs better. When the occupants adjust the tilt angle, heat gain by about 1520%. Application of low-e glazing can
they can still expect a considerable daylighting effect if the reec- achieve an even higher reduction. When low-e glazing described
tivity is high. Similar results can be achieved from results of the in Table 3 is applied, the window heat gain reduction can be as
other three cities, of which the results are not presented due to much as 50%. As shown in Fig. 8, the daylighting performance of
length limitation. the low-e glazing stays almost the same as that of the double-layer
Fig. 11 presents the annual lighting energy saving from daylight- glazing. Considering that low-e glazing has a better thermal perfor-
ing with different overhang depth. As the depth increases, daylight- mance than double-layer glazing, low-e glazing is a better choice
ing performance of the overhang becomes worse. The decrease in for energy-efcient design and retrotting than double-layer glaz-
daylighting performance is signicant on the east and west orienta- ing in cooling-dominant climates.
tions. As the latitude rises, the affection of depth on daylighting per- According to the simulation result, the interior blind installation
formance on east and west orientations becomes smaller. In Hong can help reduce window heat gain by around 20% blind while lou-
Kong, when the overhang depth changes from 0.6 m to 1 m, day- vers tilt angle is 90, and the thermal performance of the blind

1. Singapore 2. Hong Kong

3. Miami 4. Houston
Fig. 9. Annual lighting energy saving from daylighting with different blind tilt angle.
Y. Huang et al. / Applied Energy 134 (2014) 215228 225

B. East orientation
A. South orientation

C. North orientation
Fig. 10. Annual lighting energy saving from daylighting with different blind louver reectivity in Hong Kong.

1. Singapore 2. Hong Kong

3. Miami 4. Houston

Fig. 11. Annual lighting energy saving from daylighting with different overhang depth.
226 Y. Huang et al. / Applied Energy 134 (2014) 215228

Table 4
Thermal performance of three different window designs on different orientations.

Orientation Low-e glazing Blind Overhang


M (kW h) d (%) c (%) M (kW h) d (%) c (%) M (kW h) d (%) c (%)
A. Singapore
South 484,586 11.6 10.1 162,845 3.9 3.4 400,516 9.6 8.3
East 615,952 14.7 12.7 218,155 5.2 4.5 549,131 13.1 11.3
North 485,540 11.8 10.0 165,252 4 3.4 405,652 9.7 8.4
West 571,504 13.6 11.6 196,918 4.7 4 491,024 11.8 10.1
Total saving 2,157,582 51.7 44.4 743,170 17.8 15.3 1,846,324 44.2 38
B. Hong Kong
South 248,462 12.3 10.1 92,694 4.6 3.8 234,806 11.7 9.7
East 290,100 14.3 12.1 103,482 5.1 4.3 256,976 12.8 10.6
North 189,964 9.4 8.0 54,556 2.7 2.3 108,708 5.4 4.5
West 311,273 15.5 13.0 110,516 5.5 4.6 281,881 14 11.6
Total saving 1,039,795 51.5 42.9 361,248 17.9 14.9 882,373 43.8 36.5
C. Miami
South 416,319 13.2 12.1 179,526 5.7 5.2 444,455 14.2 12.9
East 443,908 14.1 12.9 175,699 5.6 5.1 426,027 13.6 12.4
North 247,777 7.6 7.2 72,122 2.2 2.1 115,456 3.7 3.3
West 481,484 15.3 13.9 179,792 5.7 5.2 431,147 13.7 12.6
Total saving 1,589,487 50.5 46.3 607,140 19.3 17.7 1,417,088 45.2 41.3
D. Houston
South 349,151 13.4 11.9 146,437 5.6 5 375,747 14.4 12.8
East 360,146 13.8 12.4 130,492 5 4.5 316,064 12.1 10.8
North 207,162 8.0 6.9 56,978 2.2 1.9 97,426 3.7 3.3
West 414,414 15.8 14.1 147,206 5.6 5 366,970 14 12.5
Total saving 1,330,872 50.9 45.4 481,113 18.4 16.4 1,156,208 44.3 39.5

decreases as the reectivity decreases. As presented in Fig. 10, day- exibility of blind makes it able to deal with shading and daylight-
lighting performance of the interior blind also decreases with the ing under different weather condition, while double-layer glazing
louvers reectivity. The impact of occupants behavior on the may easily suffer from glare or overheating. From this perspective,
blinds performance also gets smaller as the reectivity rises. Thus double-layer glazing may be the last choice for window design in
it is clear that the louvers reectivity is the key factor that affects cooling-dominant climates.
the blinds comprehensive performance. The higher the reectivity Orientation is an important factor that affects the performance
is, the better the blind performs. of energy-efcient window designs. In order to better quantify the
As shown in Fig. 7, a reduction of around 40% in window heat cost-effectiveness of energy-efcient window designs, heat gain
gain can be expected with the application of overhang. As the reduction of three different designs (low-e glazing described in
depth gets larger, the thermal performance gets better. However, Table 3, interior blind with a reectivity of 0.8 and a louver tilt
the daylighting performance drops as the depth increases. While angle of 90, overhang with a depth of 1 m) on ofce building
the overhangs depth changes from 0.6 m to 1 m, its thermal per- faade facing different orientations in four cities and their propor-
formance is improved by about 20%, while its daylighting perfor- tions in the total envelope surface heat gain are compared in
mance drops around 810% in most cases. Depth is the key factor Table 4 below. Two variables, namely d and c are dened to make
that affects the comprehensive performance of overhang. There the discussion easier:
exist an ideal depth so that the overhang could block out large
M
amount of solar radiation while still retain an acceptable amount d  100% 1
W
of daylight.
It is clear from the simulation that the thermal performance of M
overhang is better than interior blind while louvers tilt angle is c  100% 2
G
90. Although reducing the tilt angle of blind would improve the
thermal performance of the blind, gaps still exist in most cases. W (kW h) represents the annual heat gain through window area. G
As shown in Fig. 8, the daylighting performance of overhang is also (kW h) stands for the annual heat gain through building faade. M
better than that of interior blind. As the tilt angle decreases, the (kW h) is the annual heat gain reduction from different window
blinds daylighting performance gets weaker. Thus in the respect designs.
of comprehensive performance, overhang is a better shading It is clear that the thermal and daylighting performances of all
choice than interior blind in cooling-dominant climates. the three window designs are better on the east and west orienta-
As discussed above, in low-e glazing case, the window heat gain tions. On the north orientation, both thermal and daylighting per-
reduction can be as much as 50%, while a reduction of around formances are the worst.
3540% in window heat gain can be expected with the application Geography location could also affect the performance of differ-
of overhang. Also as shown in Fig. 8, the daylighting performance ent window designs. Although there exist difference in both ther-
of overhang equipped window is almost the same as the daylight- mal and daylighting performance on different orientations, as the
ing performance of double-layer glazing and low-e glazing. Overall latitude rises, the difference becomes smaller. The impact of depth
speaking, the comprehensive performance of the low-e glazing is on overhang also decreases as the latitude rises.
better than that of the overhang. In cooling-dominant climates,
low-e glazing is the best energy-efcient window design consider- 4. Conclusion
ing both thermal and daylighting performances.
While the tilt angle of louver is set at 90, the performances of In this paper, the thermal and daylighting performance of sev-
blind and double-layer glazing are at the same level. But the eral popular energy-efcient design measures on ofce building
Y. Huang et al. / Applied Energy 134 (2014) 215228 227

window was simulated and discussed. The factors that may affect [12] Wong Nyuk Hien, Wang Liping, Chandra Aida Noplie, Pandey Anupama Rana,
Wei Xiaolin. Effects of double glazed faade on energy consumption, thermal
the performance of different measures were investigated. A com-
comfort and condensation for a typical ofce building in Singapore. Energy
prehensive evaluation is also presented to assess the overall energy Build 2005;37:56372.
performance of different window designs. [13] Smith Nick, Isaacs Nigel, Burgess John, Cox-Smith Ian. Thermal performance of
Window is a major source of solar heat gain for commercial secondary glazing as a retrot alternative for single-glazed windows. Energy
Build 2012;54:4751.
buildings. At the same time window is also an important architec- [14] Arici Muslum, Karabay Hasan. Determination of optimum thickness of double-
ture element which supplies the occupants with daylight and out- glazed windows for the climatic regions of Turkey. Energy Build
door viewing. Large window area can ensure a considerable saving 2010;42:17738.
[15] Ismail Kamal AR, Salinas Carlos T, Henriquez Jorge R. A comparative study of
of lighting energy via daylighting, at the same time large window naturally ventilated and gas lled windows for hot climates. Energy Convers
area also lets in large amount of unwanted solar radiation. The Manage 2009;50:1691703.
combination between daylighting and solar shading requires extra [16] Ismail Kamal AR, Salinas Carlos T, Henriquez Jorge R. Comparison between
PCM lled glass windows and absorbing gas lled windows. Energy Build
attentions. 2008;40:7109.
In cooling-dominant climates, employing several popular [17] Manz H, Brunner S, Wullschleger L. Triple vacuum glazing: heat transfer and
energy-efcient designs on window can reduce a large amount of basic mechanical design constraints. Sol Energy 2006;80:163242.
[18] Chow Tin-Tai, Li Chunying, Lin Zhang. Innovative solar windows for cooling-
solar heat gain while still retain a satisfactory level of daylighting. demand climate. Sol Energy Mater Sol Cell 2010;94:21220.
Among the window designs discussed in this paper, the low-e glaz- [19] Bojic Milorad, Yik Francis. Application of advanced glazing to high-rise
ing is the best choice considering both thermal and daylighting residential buildings in Hong Kong. Build Environ 2007;42:8208.
[20] Assem EO, Al-Mumin AA. Code compliance of fully glazed tall ofce building in
performance, while double-layer glazing performs the worst. The
hot climate. Energy Build 2010;42:11005.
comprehensive performance of overhang is better than that of [21] Fang Yueping, Eames Philip C, Norton Brian, Hyde Trevor J, Zhao Junfu, Wang
interior blind. But the adjustability of blind makes it a competitive Jinlei, et al. Low emittance coatings and the thermal performance of vacuum
selection. glazing. Sol Energy 2007;81:812.
[22] Aldawoud Abdelsalam. Conventional xed shading devices in comparison to
Orientation and geography location can make signicant affec- an electrochromic glazing system in hot, dry climate. Energy Build
tions on the thermal and daylighting performance of window 2013;59:10410.
designs. In cooling-dominant climates, all the window designs per- [23] Lee ES, Tavil A. Energy and visual comfort performance of electrochromic
windows with overhangs. Build Environ 2007;42:243949.
forms better on the east and west orientations, while the worst [24] Dussault Jean-Michel, Gosselin Louis, Galstian Tigran. Integration of smart
performance occurs on the north orientation. In areas with low lat- windows into building design for reduction of yearly overall energy
itudes, the difference among orientations is quite obvious. As the consumption and peak loads. Sol Energy 2012;86:340516.
[25] Inoue Takashi, Ichinose Masayuki, Ichikawa Naoyoshi. Thermotropic glass
latitude rises, the difference becomes insignicant. with active dimming control for solar shading and daylighting. Energy Build
It is also discovered that the louvers reectivity is the key factor 2008;40:38593.
that affects the blinds comprehensive performance. The higher the [26] Lin Lu, Law Kin Man. Overall energy performance of semi-transparent single-
glazed photovoltaic (PV) window for a typical ofce in Hong Kong. Renew
reectivity is, the better the blind performs. Energy 2013;49:2504.
Though low-e glazing can achieve an excellent thermal and [27] Chow TT, Fong KF, He W, Lin Z, Chan ALS. Performance evaluation of a PV
daylighting performance, there still exist possible uncomfortable ventilated window applying to ofce building of Hong Kong. Energy Build
2007;39:64350.
features such as overheating and glare. Searching for advanced
[28] Chow Tin-Tai, Qiu Zhongzhu, Li Chunying. Potential application of see-
glazing materials with better thermal and visual properties will through solar cells in ventilated glazing in Hong Kong. Sol Energy Mater Sol
still be the focus of the future. Cell 2009;93:2308.
[29] Chow Tin-Tai, Li Chunying. Liquid-lled solar glazing design for buoyant
water-ow. Build Environ 2013;60:4555.
Acknowledgement [30] Chow TT, Lin Z, He W, Chan ALS, Fong KF. Use of ventilated solar screen
window in warm climate. Appl Therm Eng 2006;26:19108.
[31] Jonsson Andreas, Roos Arne. Visual and energy performance of switchable
The work described in this paper was nancially supported by windows with antireection coatings. Sol Energy 2010;84:13705.
the Research Grants Council of Hong Kong (Project No. 522613). [32] Li Danny HW, Lam Joseph C. Evaluation of lighting performance in ofce
buildings with daylighting controls. Energy Build 2001;33:793803.
[33] Li Danny HW, Lam Tony NT, Wong SL. Lighting and energy performance for an
References ofce using high frequency dimming controls. Energy Convers Manage
2006;47:113345.
[34] Li Danny HW, Tsang Ernest KW. An analysis of daylighting performance for
[1] Nielsen TR, Duer K, Svendsen S. Energy performance of glazing and windows.
ofce buildings in Hong Kong. Build Environ 2008;43:144658.
Sol Energy 2000;69:13743.
[35] Bodart M, De Herde A. Global energy savings in ofces buildings by the use of
[2] Menzies GF, Wherrett JR. Windows in the workplace: examining issues of
daylighting. Energy Build 2002;34:4219.
environmental sustainability and occupant comfort in the selection of multi-
[36] Li Danny HW, Cheung KL, Wong SL, Lam Tony NT. An analysis of
glazed windows. Energy Build 2005;37:62330.
energy-efcient light ttings and lighting controls. Appl Energy 2010;87:
[3] Aydin Orhan. Conjugate heat transfer analysis of double pane windows. Build
55867.
Environ 2006;41:10916.
[37] Galasiu Anca D, Atif Morad R, MacDonald Robert A. Impact of window blinds
[4] Aydin Orhan. Determination of optimum air-layer thickness in double-pane
on daylight-linked dimming and automatic on/off lighting controls. Sol Energy
windows. Energy Build 2000;32:3038.
2004;76:52344.
[5] Tian Cheng, Chen Tingyao, Yang Hongxing, Chung Tse-ming. A generalized
[38] Athienitis AK, Tzempelikos A. A methodology for simulation of daylight room
window energy rating system for typical ofce buildings. Sol Energy
illuminance distribution and light dimming for a room with a controlled
2010;84:123243.
shading device. Sol Energy 2002;72:27181.
[6] Ochoa Carlos E, Aries Myriam BC, van Loenen Evert J, Hensen Jan LM.
[39] Chaiwiwatworakul Pipat, Chirarattananon Surapong, Rakkwamsuk Pattana.
Considerations on design optimization criteria for window providing low
Application of automated blind for daylighting in tropical region. Energy
energy consumption and high visual comfort. Appl Energy 2012;95:23845.
Convers Manage 2009;50:292734.
[7] Tsikaloudaki K, Laskos K, Theodosiou Th, Bikas D. Assessing cooling energy
[40] Lee ES, Selkowitz SE. The New York Times Headquarters daylighting mockup:
performance of windows for ofce building in the Mediterranean zone. Energy
monitored performance of the daylighting control system. Energy Build
Build 2012;49:1929.
2006;38:91429.
[8] Gasparella Andrea, Pernigotto Giovanni, Cappelletti Francesca, Romagnoni
[41] Kim Ji-Hyun, Park Young-Joon, Yeo Myoung-Souk, Kim Kwang-Woo. An
Piercarlo, Baggio Paolo. Analysis and modeling of window and glazing systems
experimental study on the environmental performance of the automated
energy performance for a well-insulated residential building. Energy Build
blind in summer. Build Environ 2009;44:151727.
2011;43:10307.
[42] Inoue Takashi. Solar shading and daylighting by means of autonomous
[9] Singh MC, Garg SN. Energy rating of different glazing for Indian climates.
responsive dimming glass: practical application. Energy Build 2003;35:
Energy 2009;34:198692.
46371.
[10] Bojic M, Yik F, Sat P. Energy performance of windows in high-rise residential
[43] Li Danny HW, Lam Joseph C, Lau Chris CS, Huan TW. Lighting and energy
buildings in Hong Kong. Energy Build 2002;34:7182.
performance of solar lm coating in air-conditioned cellular ofces. Renew
[11] Poirazis Harris, Blomsterberg Ake, Wall Maria. Energy simulations for glazed
Energy 2004;29:92137.
ofce buildings in Sweden. Energy Build 2008;40:116170.
228 Y. Huang et al. / Applied Energy 134 (2014) 215228

[44] Ghisi Enedir, Tinker John A. Evaluating the potential for energy savings on [53] Tabares-Velasco Paulo Cesar, Christensen Craig, Bianchi Marcus. Verication
lighting by integrating bre optics in buildings. Build Environ and validation of EnergyPlus phase change material model for opaque wall
2006;41:161121. assemblies. Build Environ 2012;54:18696.
[45] Sullivan R, Lee ES, Selkowitz S. A method of optimizing solar control and [54] Henninger Robert H, Witte Michael J, Crawley Drury B. Analytical and
daylighting performance in commercial ofce building. Proc ASHRAE Conf comparative testing of EnergyPlus using IEA HVAC BESTEST E100E200 test
Therm Perform Exterior Envelops Build 1992:3139. suite. Energy Build 2004;36:85563.
[46] Inanici Mehlika N, Nur Demirbilek F. Thermal performance optimization of [55] Yun Gyeong, Kim Kang Soo. An empirical validation of lighting energy
building aspect ratio and south window size in ve cities having different consumption using the integrated simulation method. Energy Build
climatic characteristics of Turkey. Build Environ 2000;35:4152. 2013;57:14454.
[47] Kontoleon KJ, Bikas DK. Modeling the inuence of glazed openings percentage [56] Alstan Jakubiec J, Reinhart Christoph F. A method for predicting city-wide
and type of glazing on the thermal zone behavior. Energy Build 2002;34: electricity gains from photovoltaic panels based on LiDAR and GIS data
38999. combined with hourly Daysim simulations. Sol Energy 2013;93:12743.
[48] Al-Homoud MS. Optimum thermal design of ofce buildings. Int J Energy Res [57] Hong Kong Government. Code of practice for overall thermal transfer value in
1997;21:94157. buildings; 1995.
[49] Johnson CA, Besant RW, Schoenau GJ. Economic preferred window orientation [58] Singapore Government. BCA green mark for non-residential building version
and optimum fenestration design of a non-daylit and daylit large ofce NRB/3.0; 2008.
building for different climate conditions and different billing structures. [59] The U.S. Department of Energy. U.S. Department of Energy commercial
ASHRAE Trans 1990;96:2333. reference building models of the national building stock; 2008.
[50] Miyazaki T, Akisawa A, Kashiwagi T. Energy savings of ofce buildings by the [60] Hong Kong Government. Building energy code; 2007.
use of semi-transparent solar cells for windows. Renew Energy 2005;30: [61] Zhang Yufan, Barrett Peter. Factors inuencing occupants blind-control
281304. behavior in a naturally ventilated ofce building. Build Environ 2012;54:
[51] Goia Francesco, Haase Matthias, Perino Marco. Optimizing the conguration of 13747.
a faade module for ofce buildings by means of integrated thermal and [62] Van Den Wymelenberg Kevin. Patterns of occupant interaction with window
lighting simulations in a total energy perspective. Appl Energy 2013;108: blinds: a literature review. Energy Build 2012;51:16576.
51527. [63] Enshen Long. Are the relative variation rates (RVRs) approximate in different
[52] Zhou YP, Wu JY, Wang RZ, Shiochi S, Li YM. Simulation and experimental cities with the same increase of shape coefcient? Build Environ 2005;
validation of the variable-refrigerant-volume (VRV) air-conditioning system in 40:47380.
EnergyPlus. Energy Build 2008;40:10417.

S-ar putea să vă placă și