Sunteți pe pagina 1din 2

St.

Petersburg Fire & Rescue


Prevention Division
400 Dr. Martin Luther King Jr. St. S
St. Petersburg, FL 33701-4472
Office 727 893-7064
Fax 727 892-5011

Occupant Name: Push Ultra Lounge Inspection Date: 1/4/2017


Address: 128 3 Street South InspectionType: Reinspection
Contacts: Phillip Sinclair Inspected By: Marie Brumer
727-893-7540
727-871-7874 marie.brumer@stpete.org

478-731-2237

Occ. Sq. Ft.: 7025
Suite: Second Floor & Rooftop
Insp. Result Location Code Set Code
FL NFPA 01 13
10.2.5 - OWNER/OCCUPANT RESPONSIBILITY Maintain
Fail - Cleared Floor 1 Chapter 10 General Safety
systems and testing paperwork.
Requirements

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13
Fail - Cleared Floor 1 Chapter 10 General Safety 10.19.3.2 - Sprinkler head clearance from storage.
Requirements

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13
Fail - Cleared Floor 1 11.1.2 - Electric, installation and maintenance
Chapter 11 Building Services

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13 11.1.5.2 - Excerpt: Multiplug adapters shall not be used as a
Fail - Cleared Floor 1
Chapter 11 Building Services substitute...

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13 11.1.7.6 - Excerpt: Extension cords shall not be used as a
Fail - Cleared Floor 1
Chapter 11 Building Services substitute...

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13
Fail - Cleared Floor 1 11.1.10 - Open Electrical Boxes
Chapter 11 Building Services

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13
Fail - Cleared Floor 1 Chapter 13 Fire Protection 13.3.3.2 - Sprinkler inspect, tested, and maintained
Systems

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 01 13
13.3.3.5.1.8 - Sprinklers - Altered finish (paint, rust,
Fail - Cleared Floor 1 Chapter 13 Fire Protection
coatings...)
Systems

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 101 13
Fail - Cleared Floor 1 7.2.1.8.1 - Open Doors
Chapter 7 Means of Egress

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 101 13 7.2.2.4.1.6 - Existing stairs and ramps permitted to have one
Fail - Cleared Floor 1
Chapter 7 Means of Egress handrail.

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 101 13
Fail - Cleared Floor 1 7.9.2.1 - Emergency Illumination
Chapter 7 Means of Egress

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 101 13
Fail - Cleared Floor 1 7.10.9.2 - Exit Signs, Testing
Chapter 7 Means of Egress

Image: checkmark.gif
Violation cleared on 1/4/2017
FL NFPA 101 13
Fail - Cleared Floor 1 Chapter 13 Existing Assembly 13.7.9.3.1 - Occupancy Load Posting
Occupancies

Image: checkmark.gif
Violation cleared on 1/4/2017

Per City Ordinance 13-121 you will be billed for this inspection. The responsibility for compliance with all laws and
codes of the state of Florida and the City of St. Petersburg remains with the property owner and/or occupant. This
notice does not preclude future requirements for compliance.
Thank you for your cooperation in keeping your business and our community safe! If you have any questions, please
contact the Fire Prevention office at 727-893-7064.