Sunteți pe pagina 1din 10

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance


Test
SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A. TEST PROCEDURE AND CHECKLIST

The initial battery capacity test and commissioning records are pertinent
to the maintenance and optimum operational life of the battery. All
commissioning data shall be dated, recorded, and maintained in a
permanent file to facilitate required future maintenance and
interpretation of the operating data. The following data shall be
maintained in a permanent record file:
a) Initial battery capacity test performed in accordance with IEEE 450 SAES-P-103
A1
(for lead acid), IEEE 1106 (for nickel cadmium), or IEEE 1188 (for VRLA) Sec. 10.1
as applicable.
b) The initial resistance values of the intercell connections.
c) The initial individual cell voltages and specific gravity measurements.

Check that the Vented lead-acid cells are meeting the design, 17-SAMSS-511
A2
performance, and test requirements of IEC 60896-11. Sec. 8

As part of the battery, Saudi Aramco shall witness the battery


17-SAMSS-511
A3 manufacturer local representative performimg a capacity test at the
Sec. 17.2
installation site.

Check that the electrolyte level of each cell is between the high and low
SAES-P-103
A4 level marks imprinted on the cell case.
Sec. 3.2
IEEE Std 450, Annex E (d)

Check thoroughly each battery cell jar, cell jar cover, and seal (jar-to-
cover seal, post-to-cover seal) for deterioration (acid leakage, cracking, SAES-P-103
A5
crazing-spiderweb effect, distortion, etc.). Sec. 3.2
IEEE Std 450,Annex E (e)

Check thoroughly the plates in each cell for sulfation. SAES-P-103


A6
IEEE Std 450, Annex E (f) Sec. 3.2

Check the plates in each cell for the proper color that indicates a fully
SAES-P-103
A7 charged battery based on the manufacturers information.
Sec. 3.2
IEEE Std 450, Annex E (g)

Check through, the clear battery jar case, the plates, the bus bar
connection to each plate, and the bus bar connection to the post of each
battery cell for corrosion and other abnormalities. Inspect the lower part SAES-P-103
A8
of the post seals and the underside of the cover for cracking or Sec. 3.2
distortion.
IEEE Std 450, Annex E (h)

Check that all cells of the battery are properly numbered. SAES-P-103
A9
IEEE Std 450, Annex E (l) Sec. 3.2

Page 1 of 10
Check that each battery cell vent, flame arrestor, and dust cap is present
SAES-P-103
A10 and inspect each for damage.
Sec. 3.2
IEEE Std 450, Annex E (m)

Page 2 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Perform test that Batteries are delivering a minimum 90% of their rated
ampere-hour capacity at the initial site-commissioning test. Batteries 17-SAMSS-511
A11
delivering less than 90% of the rated capacity need to be returned to the Sec. 17.2.2
vendor for replacement.

If resistance readings obtained are more than 20% above the installation
value or above a ceiling value established by the manufacturer, or if SAES-P-103
A12
loose connections are noted, retorque and retest. Sec. 3.2
IEEE Std 450, Sec. 5.3.1(c)

Initial conditions:
Equalize the battery if recommended by the manufacturer and then SAES-P-103
A13
return it to float for a minimum of 72 hours. Sec. 3.2
IEEE Std 450, Sec. 7.2(a)

Check all battery connections and ensure that all resistance readings are
SAES-P-103
A14 correct for the system.
Sec. 3.2
IEEE Std 450, Sec. 7.2(b)

Record the specific gravity and float voltage of each cell or float current
SAES-P-103
A15 of the string and float voltage of each cell just prior to the test.
Sec. 3.2
IEEE Std 450, Sec. 7.2(c)

Record the electrolyte temperature of 10% or more of the cells to


SAES-P-103
A16 establish an average temperature (suggested every sixth cell).
Sec. 3.2
IEEE Std 450, Sec. 7.2(d)

Record the battery terminal float voltage. SAES-P-103


A17
IEEE Std 450, Sec. 7.2(e) Sec. 3.2

Take adequate precautions (such as isolating the battery to be tested


from other batteries and critical loads) to ensure that a failure will not SAES-P-103
A18
jeopardize other systems or equipment. Sec. 3.2
IEEE Std 450, Sec. 7.2 (f)

Test length:
The performance and acceptance tests are presented in Sec. 7.5 (IEEE
450) and the duration is recommended to be approximately the same as
SAES-P-103
A19 the duty cycle. These tests may not confirm the ability of the battery to
Sec. 3.2
meet its duty cycle, particularly if very-high-rate, short-duration loads
determine the battery size.
IEEE Std 450, Sec. 7.3.1

Test discharge rate:


The discharge rate for a capacity test depends upon the type of capacity
test selected. For the acceptance test or performance test, the discharge SAES-P-103
A20
rate should be a constant-current or constant-power load based on the Sec. 3.2
manufacturers rating of the battery for the selected test length.
IEEE Std 450, Sec. 7.3.2

Acceptance, modified performance, and performance tests:


Disconnect the charging source, connect the load bank to the battery,
start the timing, and continue to maintain the selected discharge rate. If
SAES-P-103
A21 the charging source cannot be disconnected, the current being drawn by
Sec. 3.2
the load must be increased to compensate for the current being supplied
by the charging source to the battery.
IEEE Std 450, Sec. 7.5(c)

Page 3 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Maintain the discharge rate until the battery terminal voltage decreases
to a value equal to the minimum average voltage per cell as specified by SAES-P-103
A22
the design of the installation (e.g., 1.75 Vdc) times the number of cells. Sec. 3.2
IEEE Std 450, Sec. 7.5(d)

Read and record the individual cell voltages and the battery terminal
voltage. The readings should be taken while the load is applied at the
SAES-P-103
A23 beginning of the test, at specified intervals, and at the completion of the
Sec. 3.2
test. There should be a minimum of three sets of readings.
IEEE Std 450, Sec. 7.5(e)

If one or more cells is approaching reversal of its polarity (+1 V or less)


and the test nears the 9095% expected completion time, continue the SAES-P-103
A24
test until the specified terminal voltage is reached. Sec. 3.2
IEEE Std 450, Sec. 7.5(f)

If earlier in the test an individual cell is approaching reversal of its


polarity (+1 V or less) but the terminal voltage has not yet reached its SAES-P-103
A25
test limit, the test should be stopped. Sec. 3.2
IEEE Std 450, Sec. 7.5(g)

Observe the battery for intercell connector heating. SAES-P-103


A26
IEEE Std 450, Sec. 7.5(i) Sec. 3.2

Restoration:
Disconnect all test apparatus. Recharge the battery and return it to SAES-P-103
A27
normal service. Sec. 3.2
IEEE Std 450, Sec. 7.7

Specific gravity readings are based on a temperature of 77F (25C).


The readings should be corrected for the actual electrolyte temperature
and level (see B.3). For each 3F (1.67C) above 77F (25 oC), add 1 SAES-P-103
A28
point (0.001) to the reading. Subtract 1 point for each 3F (1.67 oC) Sec. 3.2
below 77F (25 oC).
IEEE Std 450, Annex B. 2

Effect of electrolyte level:


The specific gravity of the electrolyte in a cell will increase with a loss of
water due to electrolysis or evaporation. When specific gravity readings
are being taken, the electrolyte levels should also be measured and
recorded. The battery manufacturer will provide a gravity correction
SAES-P-103
A29 factor for the particular cells involved. However, if the electrolyte level is
Sec. 3.2
between the high and low level marks and the temperature corrected
specific gravity of the electrolyte is within the manufacturers nominal
specific gravity range, it is not necessary to correct the specific gravity of
the battery for electrolyte level.
IEEE Std 450, Annex B. 3

Effect of water additions:


When water is added to a cell, it tends to float on top of the electrolyte
because its specific gravity is 1.000 in comparison to 1.215 nominal for
the electrolyte in most batteries. If the cells are in a normal float charge SAES-P-103
A30
condition, there is very little mixing of the electrolyte due to gassing. In Sec. 3.2
certain cell types it may take 68 weeks or longer for complete mixing to
occur. The specific gravity should be read before adding water.
IEEE Std 450, Annex B. 4

Page 4 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Test all post-to-post and terminal connections for proper resistance after
SAES-P-103
A31 all terminal connections are completed and prior to use of the battery.
Sec. 3.2
NEMA PE 1-2003, Sec. 2.5.10

Page 5 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

B. TEST EQUIPMENT AND MATERIALS CRITERIA

1. Ranges of measuring devices: The instruments used shall enable the values of voltage and current to be measured. The caliber of these
instruments and the measuring methods shall be chosen so as to ensure the accuracy specified for each test. For analogue instruments this implies
that readings shall be taken in the last third of the graduated scale. (Ref: IEC 60896-11, Sec. 12.1.1)

2. Voltage measurement: The instruments used for voltage measurement shall be voltmeters of an accuracy class equal to 0,5 or better. The
resistance of the voltmeters used shall be at least 1 k/V. See IEC 60051or IEC 60485. (Ref: IEC 60896-11, Sec. 12.1.2)

3. Current measurement: The instruments used for current measurement shall be ammeters of an accuracy class equal to 0,5 or better. The entire
assembly of ammeter, shunt and leads shall be of an accuracy class of 0,5 or better. See IEC 60051 or refer to IEC 60359. (Ref: IEC 60896-11, Sec.
12.1.3)

4. Temperature measurement: For measuring temperature, thermometers shall be used having a suitable measuring range in which the value of each
graduated division is not in excess of 1 C. The absolute accuracy of the instruments shall be at least 1 C. (Ref: IEC 60896-11, Sec. 12.2)

5. Electrolyte density measurement: For measuring electrolyte densities, hydrometers or other instruments shall be used with scales so graduated
that the value of each division is not in excess of 5 kg/m3. The absolute accuracy of the instruments shall be at least 5 kg/m3.
(Ref: IEC 60896-11, Sec. 12.3)

6. Time measurement: For measurement of time, the instruments accuracy shall be 1% or better. (Ref: IEC 60896-11, Sec. 12.4)

7. The test equipment calibration cycle shall not exceed twelve months.
Schedule Q, Att. IV, Sec. 7

C. TEST RESULTS

D. CONCLUSIONS

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Specific gravity shall be in accordance with manufacturer's NETA ATS 2009


D1
recommended values. 7.18.1.1.3.1.1

Electrolyte level shall be at the manufacturer's recommended reference NETA ATS 2009
D2
point. 7.18.1.1.3.1.1

NETA ATS 2009


D3 Cell voltage shall be in accordance with manufacturer's published data.
7.18.1.1.3.2.4

Consult the battery manufacturer for cell internal ohmic values in excess NETA ATS 2009
D4
of 25% between identical cell that are in fully charge state. 7.18.1.1.3.2.6

Page 6 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Test results are acceptable and in accordance with Saudi Aramco Schedule Q
D5
Engineering Standards and contractual requirements. Att. II Sec.1.3

Page 7 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance Test SATR-P-3103 30-Apr-13 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule Q Quality Requirements (Pro Forma Contract), February 2008
2. SAES-P-103, UPS and DC Systems, 11 July 2012
3. Acceptance Testing Specifications - NETA (2009)
4. IEC 60896-11 Stationary Lead-Acid Batteries (Vented types) General Requirements and Methods of Tests, (2002)
5. NEMA PE 1 Uninterruptible Power Systems (UPS) - Specification and Performance Verification, (1-2003)
6. IEEE Std 450 Vented Lead-Acid Batteries for Stationary Applications, 2010
7. 17-SAMSS-511 Stationary Storage batteries, 11 July 2012

ATTACHMENT(S):
1. Attachment - 1 IEC-60896-11, Table A.1 and A.2 Test recommendation for stationary batteries

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Name, Title, Department,
Company, Initials and Name, Initials and Date:
Date:

QC Inspector PID Representative


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Page 8 of 10
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) REV 7 31-Mar-13

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

UPS/DC Vented Lead-Acid Wet Cell, Jobsite Acceptance


Test
SATR-P-3103 30-Apr-13 ELECT-

Attachment 1 - IEC 60896-11

Page 9 of 10
Page 10 of 10

S-ar putea să vă placă și