Sunteți pe pagina 1din 20

7800 SERIES

Relay Modules
CHECKOUT AND TEST
This publication provides general checkout and troubleshooting procedures for the 7800 SERIES Relay Modules.

SYSTEM CHECKOUT CAUTION


IMPORTANT Equipment Malfunction or Damage Hazard.
Perform all Static Checkout Procedures in the Each relay module type is unique. Using existing
applicable relay module installation instructions wiring on a relay module change can cause
before starting these procedures. equipment damage.
Make wiring changes when a relay module is replaced
with a different 7800 SERIES Relay Module to
WARNING sequence burner.
Explosion Hazard.
Can cause serious injury or death. IMPORTANT
Do not allow fuel to accumulate in the combustion 1. If the system fails to perform properly, note the
chamber for longer than a few seconds without fault code, fault message, equipment status, and
igniting to prevent danger of forming explosive mixture sequence time on the display. Then refer to the
Close manual fuel shutoff valve(s) if flame is not Troubleshooting section.
burning at end of specified time. 2. Repeat all required Checkout tests after all
adjustments are made. All tests must be satisfied
with the flame detector(s) in their final position.
WARNING
Electric Shock Hazard.
Can cause serious injury or death.
Equipment Recommended
1. Use extreme care while testing system. Line S7800A Keyboard Display Module
voltage is present on most terminal connections Volt-ohmmeter (1M ohm/volt minimum sensitivity) with:
when power is on. 0-300 Vac capability.
2. Open master switch before removing or installing 0-6000 ohm capability.
7800 SERIES Relay Module or Keyboard Display 0-10 Vdc capability.
Module connector.
Checkout Summary
Make sure all manual fuel shutoff valve(s) are closed before
starting initial lightoff check and Pilot Turndown tests. Table 1 provides an overview of checkout steps performed for
each applicable system.
Do not put the system in service until you have satisfactorily
completed all applicable tests in this section and any others See Installation Instructions for location of component parts
recommended by the original equipment manufacturer.. and/or Q7800 Specifications for terminal locations.

Limit trial for pilot to ten seconds. Limit the attempt to light
main burner to two seconds after fuel reaches burner nozzle.
Do not exceed manufacturer nominal lightoff time.

U.S. Registered Trademark


Copyright 1998 Honeywell Inc. All Rights Reserved 65-0229-1
7800 SERIES RELAY MODULES

Table 1. Checkout Steps and Applicable 7800 Series Systems.


Piloted Infrared Flame Flame Rod Ultraviolet Flame
Checkout Step Systems DSI Systems Detectors Systems Detectors
Preliminary Inspection X X X X X
Flame Signal Measurement X X X X X
Initial Lightoff Check for X
Proved Pilot
Initial Lightoff Check for X
Direct Spark Ignition
Pilot Turndown Test X
Ignition Interference Test X
Hot Refractory Saturation X
Test
Hot Refractory Hold-in X X X X X
Test
Ignition Spark Pickup X
Response to Other X
Ultraviolet Sources
Flame Signal with Hot X X X X X
Combustion Chamber
Safety Shutdown Tests X X X X X

Preliminary Inspection INITIAL LIGHTOFF CHECKS


Perform the following inspections to avoid common problems.
Make certain that: Proved Pilot Systems
1. Wiring connections are correct and all terminal screws Perform this check on all installations that use a pilot. It
are tight. should immediately follow the preliminary inspection.
2. Flame detector(s) is clean, installed and positioned
properly. Consult the applicable Instructions. NOTE: Low fuel pressure limits, if used, could be open. If so,
3. Combination of amplifier and flame detector(s) is bypass them with jumpers during this check.
correctly used. See the amplifier specifications.
4. Plug-in amplifier and purge card (if required) are 1. Open the master switch.
securely in place. 2. Make sure that the manual main fuel shutoff valve(s) is
5. Burner is completely installed and ready to fire; consult closed. Open the manual pilot shutoff valve. If the pilot
equipment manufacturer instructions. Fuel lines are takeoff is downstream from the manual main fuel
purged of air. shutoff valve(s), slightly open the manual main valve to
6. Combustion chamber and flues are clear of fuel and supply pilot gas flow. Make sure the main fuel is shut off
fuel vapor. just upstream from the burner inlet, or disconnect power
7. Power is connected to the system disconnect switch from the automatic main fuel valve(s).
(master switch). 3. Close the master switch and start the system with a call
8. Lockout is reset (reset button) only if the Relay Module for heat by raising the setpoint of the operating
is powered. controller, see the relay module sequence. The 7800
9. Run/Test Switch (if present) is in RUN position. Series Relay Module should start the INITIATE
10. System is in STANDBY condition. STANDBY message sequence.
is displayed in the S7800 Keyboard Display Module. 4. Let the sequence advance to PILOT IGN (status is
11. All limits and interlocks are reset. displayed on the Keyboard Display Module, if used),
PILOT LED turns on, ignition spark should occur and
Flame Signal Measurement the pilot should light. If the pilot ignites, the FLAME LED
is energized. Go to step 7.
See instructions provided with the amplifer. 5. If the pilot flame is not established in ten seconds (four
seconds if configuration jumper JR1 is clipped), safety
shutdown occurs. Let the sequence complete its cycle.
6. Push the reset pushbutton, and let the system recycle
once. If the pilot still does not ignite, make the following
ignition/pilot adjustments:
a. Open the master switch and remove the 7800
Series Relay Module from the subbase.

65-02291 2
7800 SERIES RELAY MODULES

b. On the subbase, jumper L1 to the ignition 17. Shut down the system by opening the burner switch or
terminal; refer to the appropriate wiring diagram by lowering the setpoint of the operating controller.
to determine the proper terminal. Disconnect the Make sure the main flame goes out. There may be a
leadwire to the pilot valve if it is connected to the delay due to gas trapped between the valve(s) and
same terminal. burner. Make sure all automatic fuel valve(s) close.
c. Close the master switch to energize only the 18. Restart the system by closing the burner switch and/or
ignition transformer. raising the setpoint of the operating controller. Observe
d. If the ignition spark is not strong and continuous, that the pilot is established during PILOT IGN and the
open the master switch and adjust the ignition main burner flame is established during MAIN IGN
electrode spark gap setting to the manufacturer within the normal lightoff time.
recommendation. 19. Measure the flame signal. Continue to check for the
e. Make sure the ignition electrodes are clean. proper signal through the RUN period. Check the signal
f. Close the master switch and observe the spark. at both High and Low Firing Rate positions and while
g. After a continuous spark is obtained, open the modulating, if applicable.
master switch and add a jumper on the subbase 20. Run the burner through another sequence, observing
from terminal L1 power to the pilot terminal 8 or the flame signal for:
21. Reconnect the leadwire from the pilot valve if a. Pilot flame alone.
it was disconnected in step b. b. Pilot and main flame together.
h. Close the master switch to energize both the c. Main flame alone (unless monitoring an
ignition transformer and the pilot valve. intermittent pilot). Also observe the time it takes
i. If the pilot does not ignite and if the ignition spark to light the main flame. Ignition of main flame
is still continuous, adjust the pressure regulator should be smooth.
until a pilot is established. 21. Make sure all readings are in the required ranges
j. When the pilot ignites properly and stays ignited, before proceeding.
open the master switch and remove the jumper(s) 22. Return the system to normal operation.
from the terminals of the subbase.
k. Check for adequate bleeding of the fuel line. NOTE: After completing these tests, open the master switch
l. Reinstall the 7800 Series Relay Module on the and remove all test jumpers from the subbase
subbase, close the master switch, and then return terminals, limits/controls or switches.
to step 4.
7. When pilot ignites, measure the flame signal. If the pilot Direct Spark Ignition Systems
flame signal is unsteady or approaching the 1.25 Vdc
minimum value, adjust the pilot flame size or detector This check applies to gas and oil burners not using a pilot. It
sighting to provide a maximum and steady flame signal. should immediately follow the preliminary inspection. Refer to
8. Recycle the system to recheck lightoff and pilot flame the appropriate sample block diagram of field wiring for the
signal. ignition transformer and fuel valve(s) hookup.
9. When the MAIN LED turns on, make sure the automatic
main fuel valve is open; then smoothly open the manual NOTE: Low fuel pressure limits, if used, could be open. If so,
main fuel shutoff valve(s) and watch for main burner bypass them with jumpers during this check.
flame ignition. When the main burner flame is
established, go to step 16. 1. Open the master switch.
10. If the main burner flame is not established within five 2. Complete the normal ready-to-fire checkout of the fuel
seconds or the normal lightoff time as specified by the supply and equipment as recommended by the
equipment manufacturer, close the manual main fuel equipment manufacturer.
shutoff valve(s). 3. Close all manual main fuel shutoff valve(s). Check that
11. Recycle the system to recheck the lightoff and pilot the automatic fuel valve(s) is closed. Make sure fuel is
flame signal. not entering the combustion chamber.
12. Smoothly open the manual fuel shutoff valve(s) and try 4. Close the master switch and start the system with a call
lightoff again. (The first re-attempt may have been for heat by raising the setpoint of the operating
required to purge the lines and bring sufficient fuel to controller; see the relay module sequencing. The
the burner.) program sequence should start the INITIATE sequence.
13. If the main burner flame is not established within five 5. Let the sequence advance through PREPURGE (if
seconds or the normal lightoff time specified by the applicable). Ignition spark should occur when the PILOT
equipment manufacturer, close the manual main fuel LED turns on. Listen for the click of the first stage fuel
shutoff valves(s). Check all burner adjustments. solenoid valve(s). The relay module locks out and the
14. If the main burner flame is not established after two ALARM LED turns on.
attempts: 6. Let the 7800 Series Relay Module complete its cycle.
A. Check for improper pilot size. 7. Open the manual fuel shutoff valve(s).
B. Check for excess combustion air at low fire. 8. Push the reset button and the relay module recycles the
C. Check for adequate low fire fuel flow. program sequence through PREPURGE (if applicable).
D. Check for proper gas supply pressure. 9. When the PILOT LED turns on, make sure that the first
E. Check for proper valve operation. stage burner flame is established. If it is, go to step 15.
F. Check for proper pilot flame positioning. 10. If the first stage burner flame is not established within
15. Repeat steps 8 and 9 to establish the main burner four seconds, or within the normal lightoff time specified
flame; then go to step 16. by the equipment manufacturer, close the manual fuel
16. With the sequence in RUN, make burner adjustments shutoff valve(s), and open the master switch.
for flame stability and Btu input rating. 11. Check all burner adjustments.

3 65-02291
7800 SERIES RELAY MODULES

12. Wait about three minutes. Close the master switch, If using AMPLI-CHECK or self-checking amplifier and 1M
open the manual fuel shutoff valve(s), and try to light off ohm/volt meter, the flame signal fluctuates every time the
the burner again. The first attempt may be required to amplifier does a self-check or a shutter check.
purge the lines and bring sufficient fuel to the burner.
13. If the first stage burner flame is not established within NOTE: Low fuel pressure limits, if used, could be open. If so,
four seconds, or within the normal lightoff time specified bypass them with jumpers during this test.
by the equipment manufacturer, close the manual fuel
shutoff valve(s), and open the master switch. 1. Open the master switch.
14. If necessary, repeat steps 11 through 13 to establish 2. Close the manual main fuel shutoff valve(s).
the first stage burner flame. Then go to step 15. 3. Connect a manometer (or pressure gauge) to measure
15. When the first stage burner flame is established, the pilot gas pressure during the turndown test.
sequence advances to RUN. Make burner adjustments 4. Open the manual pilot shutoff valve(s).
for flame stability and input rating. If a second stage is 5. Close the master switch and start the system with a call
used, go to step 18. for heat. Raise the setpoint of the operating controller.
16. Shut down the system by opening the burner switch or The 7800 Series sequence should start, and
by lowering the setpoint of the operating controller. PREPURGE (if applicable) should begin.
Make sure the burner flame goes out and all automatic 6. After the PILOT LED turns on in interrupted pilot
fuel valves close. applications, set the Run/Test Switch to the TEST
17. If used, remove the bypass jumpers from the low fuel position to stop the sequence. The FLAME LED comes
pressure limit and subbase. on when the pilot ignites.
18. If a second stage is used, make sure the automatic
second stage fuel valve(s) opened. Check the lightoff as NOTE: If the sequence does not stop, reset the
follows (or go to step 19): system and make sure you set the Run/Test
a. Open the manual second stage fuel valve(s). Switch to TEST within the first eight seconds
b. Restart the system by raising the setpoint of the of the PILOT IGN sequence.
operating controller.
c. When the first stage burner flame is established, IMPORTANT
watch for the automatic second stage fuel You have 0.8 second or three seconds, depending
valve(s) to open. Observe that the second stage on PFEP selected, to position the Run/Test Switch to
lights off properly. the TEST position to stop the sequence after the
d. Make burner adjustments for flame stability and start of the PILOT IGN period.
input rating.
e. Shut down the system by lowering the setpoint of 7. Turn down the pilot pressure very slowly, reading the
the operating controller. Make sure the burner manometer (or pressure gauge) as it drops. Stop
flame goes out and all automatic fuel valves instantly when the FLAME LED goes out. Note the
close. pressure. The pilot is at the minimum turndown position.
f. Go to step 19. Immediately turn up the pilot pressure until the FLAME
19. Restart the system by closing the burner switch and/or LED comes on again or the flame signal increases to
raising the setpoint of the operating controller. Observe 1.25 Vdc.
that the burner flame is established during PILOT IGN,
within the normal lightoff time specified by the NOTE: If there is no flame for fifteen seconds with the
equipment manufacturer. RUN/TEST switch in the TEST position, the
20. Measure the flame signal. Continue to check for the relay module locks out.
proper signal through the RUN period. Check the signal
at both high and low firing rate positions and while 8. Repeat step 7 to verify the pilot gas pressure reading at
modulating. Any pulsating or unsteady readings require the exact point the FLAME LED light goes out.
further attention. 9. Increase the pilot pressure immediately until the
21. Make sure all readings are in the required ranges FLAME LED comes on, and then turn it down slowly to
before proceeding. obtain a pressure reading just above the dropout point
or until the flame signal increases to 1.25 Vdc.
NOTE: On completing these tests, open the master 10. Set the Run/Test Switch in the RUN position (if used)
switch and remove all test jumpers from the and let the sequence proceed. When the MAIN LED
subbase terminals, limits/controls or switches. turns on, make sure the automatic main fuel valve(s)
opens; then smoothly open the manual main fuel
22. Return the system to normal operation. shutoff valve(s) (or any other manually-opened safety
shutoff valve(s), if used) and watch for main burner
ignition. If the main burner flame is established, go to
step 18.
PILOT TURNDOWN TEST (ALL
INSTALLATIONS USING A PILOT) NOTE: This step requires two people, one to open the
manual valve(s) and one to watch for ignition.
Perform this check on all installations that use a pilot. The
purpose of this test is to verify that the main burner can be lit 11. If the main burner flame is not established within five
by the smallest pilot flame that can hold in the flame amplifier seconds, or within the normal lightoff time specified by
and energize the FLAME LED. Clean the flame detector(s) to the equipment manufacturer, close the manual main
make sure that it detects the smallest acceptable pilot flame. fuel shutoff valve(s) and open the master switch. If the
lightoff is rough, the pilot flame size is too small.

65-02291 4
7800 SERIES RELAY MODULES

12. Close the master switch to recycle the burner and stop Hot Refractory Hold-in Test
the sequence in the PILOT period by using the Run/
Test Switch. (Rectifying Photocell, Infrared Detectors,
13. Increase the pilot flame size by increasing its fuel flow
until a smooth main flame is accomplished. Ultraviolet Detectors)
14. Reposition the flame scanner sight tube or use orifices This condition can delay response to flame failure and also
until the pilot flame signal voltage is in the range of 1.25 can prevent a system restart if hot refractory is detected.
to 1.50 Vdc.
15. When the main burner lights reliably with the pilot at Infrared (lead sulfide) detectors can respond to infrared rays
turndown, disconnect the manometer (or pressure emitted by a hot refractory, even when the refractory has
gauge) and turn up the pilot gas flow to that visibly ceased to glow. Infrared radiation from a hot refractory
recommended by the equipment manufacturer. is steady, but radiation from a flame has a flickering
16. If used, remove the bypass jumpers from the subbase characteristic. The infrared detection system responds only to
terminals, limits/controls, or switches. flickering infrared radiation; it can reject a steady signal from
17. Run the system through another cycle to check for hot refractory. The refractory steady signal can be made to
normal operation. fluctuate if it is reflected, bent or blocked by smoke or fuel
18. Return the system to normal operation. mist within the combustion chamber. Be careful when
applying an infrared system to verify its response to flame
only.
IGNITION INTERFERENCE TEST The ultraviolet detector can respond to hot refractory above
(ALL FLAME RODS) 2300F (1371C).

Ignition interference can subtract from (decrease) or add to 1. Operate the burner until the refractory reaches its
(increase) the flame signal. If it decreases the flame signal maximum temperature (Infrared Only).
enough, it causes a safety shutdown. If it increases the flame If the installation has a multi-fuel burner, burn the
signal, it could cause the FLAME LED to come on when the heavier fuel that is most likely to reflect, bend or
true flame signal is below the minimum acceptable value. obscure the hot refractory steady infrared radiation
2. When the maximum refractory temperature is reached,
Start the burner and measure the flame signal with both close all manual fuel shutoff valves, or open the
ignition and pilot (or main burner) on, and then with only the electrical circuits of all automatic fuel valves.
pilot (or main burner) on. Any significant difference (greater 3. Visually observe when the burner flame or FLAME LED
than .5 Vdc) indicates ignition interference. goes out. If this takes more than three seconds, the
infrared detector is sensing hot refractory.
To Eliminate Ignition Interference 4. Immediately terminate the firing cycle. Lower the
setpoint to the operating controller, or set the Fuel
1. Make sure there is enough ground area. Selector Switch to OFF. Do not open the master switch.
2. Be sure the ignition electrode and the flame rod are on
opposite sides of the ground area. NOTE: Some burners continue to purge oil lines
3. Check for correct spacing on the ignition electrode: between the valves and nozzles even though
a. 6000V systems1/16 to 3/32 in. (1.6 to 2.4 mm). the fuel valves are closed. Terminating the
b. 10,000V systems1/8 in. (3.2 mm). firing cycle (instead of opening the master
4. Make sure the leadwires from the flame rod and ignition switch) allows purging the combustion
electrode are not too close together. chamber. This reduces a buildup of fuel vapors
5. Replace any deteriorated leadwires. in the combustion chamber caused by oil line
6. If the problem cannot be eliminated, consider changing purging.
the system to an ultraviolet flame detection system.
5. If the detector is sensing hot refractory, correct the
Hot Refractory Saturation Test condition by one or more of the following procedures:
a. Add an orifice plate in front of the cell to restrict
(All Infrared Detectors) the viewing area of the detector.
Start the burner and monitor the flame signal during the b. Resight the detector at a cooler, more distant part
warmup period. A decrease in signal strength as the of the combustion chamber. Make sure the
refractory heats up indicates hot refractory saturation. If detector properly sights the flame.
saturation is extreme, the flame signal drops below 1.25 Vdc c. Try lengthening the sight pipe or decreasing the
and the system shuts down as though a flame failure pipe size (diameter).
occurred.
For details, refer to the detector Instructions and the
If hot refractory saturation occurs, the condition must be equipment Operating Manual. Continue adjustments until hot
corrected. Add an orifice plate in front of the cell to restrict the refractory hold-in is eliminated.
viewing area, lengthen the sight pipe or decrease the pipe
size (diameter). Continue adjustments until hot refractory
saturation is eliminated.

5 65-02291
7800 SERIES RELAY MODULES

9. If the detector is relocated or resighted, or the amplifier


IGNITION SPARK RESPONSE TEST is replaced, repeat all required Checkout tests.
(ALL ULTRAVIOLET DETECTORS)
Test to make certain that the ignition spark is not actuating
the FLAME LED: SAFETY SHUTDOWN TESTS
1. Close the pilot and main burner manual fuel shut-off
valve(s).
(ALL INSTALLATIONS)
2. Start the burner and use the Run/Test Switch (if Perform these tests at the end of Checkout, after all other
available) to stop the sequence in the PILOT IGN tests are completed. If used, the external alarm should turn
period. Ignition spark should occur, but the flame signal on. Press the RESET pushbutton on the relay module to
should not be more than 0.5 Vdc. restart the system.
3. If the flame signal is higher than 0.5 Vdc and the 1. Opening a Preignition Interlock during the STANDBY or
FLAME LED does come on, consult the equipment PREPURGE period (only for RM7800, EC/RM7840,
operating manual and resight the detector farther out RM7838B, EC7810, EC7820, EC/RM7830, EC/
from the spark, or away from possible reflection. It may RM7850).
be necessary to construct a barrier to block the ignition a. *Preignition ILK* fault is displayed on the
spark from the detector view. Continue adjustments Keyboard Display Module. Fault code 10 or 33 is
until the flame signal due to ignition spark is less than displayed to denote the fault.
0.5 Vdc. b. Safety shutdown occurs.
2. Opening a Lockout Interlock during PREPURGE,
NOTE: The Honeywell Q624A and Q652A,B Solid State PILOT IGN, MAIN IGN or RUN period (only for
Spark Generators prevent detection of ignition spark RM7800, EC/RM7840, RM7838B, EC7810, EC7820,
when properly applied with C7027, C7035, C7044 or EC/RM7830, EC/RM7850).
C7061 Ultraviolet Flame Detectors. The Q624A and a. *Lockout ILK* fault is displayed on the Keyboard
Q652B are only for use with gas pilots; the Q652A is Display Module. Fault code 11 or 12 or 21 or 29 is
only for oil applications. displayed to denote the fault.
b. Safety shutdown occurs.
Response To Other Ultraviolet Sources 3. Detection of flame 40 seconds after entry to STANDBY
from RUN, fault code 9. Detection of flame from ten
Some sources of artificial light (such as incandescent or seconds up to 30 seconds into PREPURGE time.
fluorescent bulbs, mercury sodium vapor lamps and daylight) a. Simulate a flame to cause the flame signal
produce small amounts of ultraviolet radiation. Under certain voltage level to be at least 1.25 Vdc for 40
conditions, an ultraviolet detector responds to these sources seconds after entry to STANDBY from RUN and
as if it is sensing a flame. To check for proper detector also simulate a flame signal for 10 seconds to
operation, check the Flame Failure Response Time (FFRT) 30 seconds for PREPURGE.
and conduct Safety Shutdown Tests under all operating b. *Flame Detected* fault is displayed on the
conditions. Keyboard Display Module. Fault code 9 or 15 or
18 is displayed to denote the fault.
Flame Signal With Hot Combustion Chamber c. Safety shutdown occurs.
4. Failure to ignite pilot.
(All Installations) a. Close pilot and main fuel manual shutoff valve(s).
1. With all initial start-up tests and burner adjustments b. Cycle burner on.
completed, operate the burner until the combustion c. Automatic pilot valve(s) should be energized but
chamber is at the maximum expected temperature. the pilot cannot ignite.
2. Observe the equipment manufacturer warm-up d. *Pilot Flame Fail* fault is displayed on the
instructions. Keyboard Display Module. Fault code 28 is
3. Recycle the burner under these hot conditions and displayed four or ten seconds, depending on the
measure the flame signal. Check the pilot alone, the jumper configuration selection for Pilot Flame
main burner flame alone, and both together (unless Establishing Period (PFEP) after the pilot valve(s)
monitoring only the pilot flame when using an is energized to denote the fault.
intermittent pilot, or only the main burner flame when e. Safety shutdown occurs.
using DSI). Check the signal at both High and Low 5. Failure to ignite main (only interrupted pilot application).
Firing Rate positions and while modulating, if a. Open the manual pilot valve(s); leave the main
applicable. fuel manual shutoff valve(s) closed.
4. Check the FFRT of the flame amplifier and relay b. Depress the RESET button.
module. c. Start the system.
5. Lower the setpoint of the operating controller and d. The pilot should ignite and the flame signal
observe the time it takes for the burner flame to go out. should be at least 1.25 Vdc but the main burner
This should be within the maximum FFRT. cannot light.
6. If the flame signal is too low or unsteady, check the e. The flame signal should drop below 1.25 Vdc
flame detector temperature. Relocate the detector if the within the FFRT of the amplifier and the relay
temperature is too high. module after the interrupted pilot goes out.
7. If necessary, realign the sighting to obtain the proper f. *Main Flame Ign.* fault is displayed on the
signal and response time. Keyboard Display Module. Fault code 19 is
8. If the response time is still too slow, replace the Plug-in displayed to denote the fault.
Flame Signal Amplifier. g. Safety shutdown occurs.

65-02291 6
7800 SERIES RELAY MODULES

6. Loss of flame during RUN. The KDM displays a sequence status message indicating:
a. Open the main fuel manual shutoff valve(s) and STANDBY, PURGE, PILOT IGN, MAIN IGN, RUN and
open manual pilot shutoff valve(s). POSTPURGE. The selectable messages also provide visual
b. Depress the RESET button. indication of current status and historical status of the
c. Start the system. Start-up should be normal and equipment such as: Flame Signal, Total Cycles, Total Hours,
the main burner should light normally. Fault History, Diagnostic Information and Expanded
d. After the sequence is in the normal RUN period Annunciator terminal status (if used). With this information,
for at least ten seconds with the main burner most problems can be diagnosed without extensive trial and
firing, close the manual main fuel shutoff valve(s) error testing.
to extinguish the main burner flame. (On
intermittent pilot applications, also, close the pilot Table 2 provides the sequence and status hold messages.
manual shutoff valve.) Table 3 is a summary of all relay module fault messages, fault
e. The flame signal should drop below 1.25 Vdc codes, and troubleshooting suggestions. In addition,
within the FFRT of the amplifier and the relay Diagnostic Information and History Data are available to
module after the main flame and/or pilot goes out. assist in troubleshooting the relay module.
f. *Main Flame Fail* fault is displayed on the
Keyboard Display Module. Fault code 17 is The relay module provides diagnostic information to aid the
displayed to denote the fault. service mechanic in obtaining information when
g. Safety shutdown occurs. (EC/RM7890, EC/ troubleshooting the system. Information available in the
RM7895, RM7896 relay modules will recycle if Diagnostic Information includes Device Type, Device Suffix,
jumper JR2 is intact, then lock out on failure to Software Revision, Manufacturing Code, Flame Amplifier
light the pilot.) Type, Flame Failure Response Time, Selectable Jumper
7. Opening a Preignition Interlock after the first five Configuration Status, Run/Test Switch Status and Terminal
seconds of POSTPURGE. Status.
a. Open the main fuel manual shutoff valve(s) and
open manual pilot shutoff valve(s). Diagnostic Information Index
b. Depress the RESET button.
c. *Preignition ILK* fault is displayed on the The relay module monitors input/output terminals and can
Keyboard Display Module. Fault code 33 is display the status of the terminal at the KDM (see Table 2)
displayed to denote the fault. (example: Pilot Valve T8 1). See the applicable relay module
d. Safety shutdown occurs. installation instructions for a complete terminal description
and number. The display shows the actual status of the
IMPORTANT terminal. If voltage is detected at the terminal, 1 is displayed,
1. If the relay module fails to shut down on any of but if no voltage is detected at the terminal, 0 is displayed.
these tests, take corrective action; refer to
Troubleshooting and the relay module diagnostics Historical Information Index
and return to the beginning of all Checkout tests. The relay module has nonvolatile memory that allows the
2. When all Checkout tests are completed, reset all Relay Module to retain historical information for the six most
switches to the original status. recent lockouts. Each of the six lockout files retains the cycle
when the fault occurred, the hour of operation when the fault
occurred, a fault code, a fault message and burner status
TROUBLESHOOTING when the fault occurred.

System Diagnostics IMPORTANT


Some older relay modules can not operate without a
Troubleshooting control system equipment failures is easier KDM, extension cable assembly with KDM or a Data
with the relay module self-diagnostics and first-out ControlBus Module installed.
annunciation. In addition to an isolated spst alarm relay
(audible annunciation), the relay module provides visual SERVICE NOTES:
annunciation by displaying a fault code and fault or hold 1. If the KDM is scrambled, remove and reinstall the
message at the S7800 Keyboard Display Module (standard KDM, and reset the 7800 Relay Module.
on RM7800 and RM7838A,B devices; optional on all others). 2. Reset the 7800 Series Relay Module by pressing the
The relay module provides 127 diagnostic messages for RESET pushbutton on the 7800 Series Relay
troubleshooting the system (see Table 3). Module, or pressing a remote reset pushbutton wired
through the KDM, Data ControlBus Module or
Self-diagnostics of the relay module enables it to detect and Remote Reset Module. A power-up reset causes an
annunciate both external and internal system problems. Fault electrical reset of the relay module but does not
messages, such as interlock failures, flame failures and false reset a lockout condition.
flame signals are displayed at the KDM, and annunciated at 3. Use the access slots on the sides of the Q7800A,B
the 7800 SERIES Relay Module by the ALARM LED. to check terminal voltage.
4. Maximum ambient operating temperature of a
C7012E,F; Series 1 through 6, is reduced to
125F because of the duty cycle operation of the
relay module.

7 65-02291
7800 SERIES RELAY MODULES

Table 2. Keyboard Display Module Sequence and Status Hold Messages.


Sequence Status
INITIATE mm:ss The Keyboard Display Module (KDM) indicates the burner status, INITIATE, a stabilization period
for the relay module to check for any fluctuations in ac line voltage inputs or control inputs on
power up or during normal operation. The timing of the INITIATE period is either two seconds or
ten seconds, depending on the model, before entering STANDBY.
If the relay module is in an INITIATE HOLD status, the following conditions could exist:
INITIATE HOLD: The KDM indicates the burner status and that it is waiting for excess line noise to clear up, which
(AC Frequency/Noise) prevents sufficient reading of the line voltage inputs. The burner sequence does not advance into
STANDBY until the excess line noise ceases or a line frequency error occurs; this is caused by
using a 60 Hz device on a 50 Hz line, or vice versa on devices with a date code earlier than 9804,
is corrected.
INITIATE HOLD: The KDM indicates the burner status and that ac line power has momentarily dropped out. The
(AC Line Dropout) burner sequence does not advance into STANDBY until the ac line voltage has stabilized
throughout the INITIATE sequence.
INITIATE HOLD: The KDM indicates the burner status and that line frequency is faster than the expected value.
(AC Frequency) The burner sequence does not advance into STANDBY until the line frequency returns to the
proper value; this is perhaps caused by using a 60 Hz device on a 50 Hz line for devices with a
date code earlier than 9804.
INITIATE HOLD: The KDM indicates the burner status and that low line voltage (10% lower than rated voltage) has
(Low Line Voltage) occurred. The burner sequence does not advance into STANDBY until the line voltage is at a
sufficient level for proper operating parameters.
STANDBY The KDM indicates the burner status, STANDBY. The burner can be placed in STANDBY by
opening the burner switch or if the operating controller indicates its setpoint is satisfied. If a
demand is present for burner operation, the burner sequence does not advance from STANDBY
to PURGE until the recycle limits close. If an Expanded Annunciator is connnected, the display
messages are enhanced.
If the relay module is in a STANDBY HOLD status, the following conditions could exist:
STANDBY HOLD: The KDM indicates the burner status and that a flame is detected. A demand is present for burner
F/G (Flame Detected) operation. The sequence does not advance to PREPURGE until the flame signal clears. If the
flame signal does not clear within 40 seconds, the relay module locks out.
STANDBY HOLD: T20 The KDM indicates the burner status and that the Preignition Interlock is not closed. A demand is
(Preignition Interlock) present for burner operation, but the burner sequence does not advance to PREPURGE until the
Preignition Interlock proves closed. If this time exceeds a 30 second hold, the relay module locks
out.
STANDBY HOLD: T7 The KDM indicates the burner status and that the Lockout Interlock is closed. A demand is
(Lockout Interlock) present for burner operation, but the burner sequence does not advance to PREPURGE until the
Lockout Interlock proves open. If this time exceeds the 120 second hold, the relay module locks
out.
STANDBY HOLD: T7 The KDM indicates the burner status and that the Running Interlock is closed. A demand is
(Running Interlock) present for burner operation, but the burner sequence does not advance to PREPURGE until the
T17 for EC/RM7810, Running Interlock proves open. If this time exceeds the 120 second hold, the relay module locks
7820, 7830, 7850 out.
devices
PURGE The KDM indicates the burner status, PURGE, which is the period of time the blower motor is
running before the Ignition period. The timing of the PURGE period is selectable.
If the relay module is in a PURGE HOLD status, the following conditions could exist:
PURGE HOLD: T19 The KDM indicates the burner status and that the High Fire Switch is not closed. The firing rate
(High Fire Switch) motor is driving to its PURGE rate position. If this time exceeds four minutes and fifteen seconds,
the relay module locks out.
PURGE DELAY: T19 The KDM indicates the burner status and that the High Fire Switch is jumpered. The High Fire
(High Fire Switch Switch is bypassed, welded or otherwise prematurely closed. The system automatically adds 30
Jumpered) seconds to allow the firing rate motor additional drive time to reach or near the open damper
position before starting the PURGE sequence.
PURGE HOLD: TEST The KDM indicates the burner status and that the Run/Test Switch is in the TEST position. The
(Run/Test Switch) sequence does not continue until the Run/Test Switch is placed in the RUN position.
NOTE: Normal sequences are in bold type, while abnormal sequences are in regular type. This table is for all 7800 SERIES
Relay Modules so all listed steps may not apply to the unit installed.

65-02291 8
7800 SERIES RELAY MODULES

Table 2. Keyboard Display Module Sequence and Status Hold Messages (continued).

Sequence Status
If the relay module is in a PURGE HOLD status, the following conditions could exist (continued):
PURGE HOLD: T18 The KDM indicates the burner status and that the Low Fire Switch is jumpered. The Low Fire
(Low Fire Switch Switch is bypassed, welded or otherwise prematurely closed. The system automatically adds 30
Jumpered) seconds to allow the firing rate motor additional drive time to reach or near the closed damper
position before starting the ignition sequence.
PURGE HOLD: F/G The KDM indicates the burner status and that a flame is detected. The burner sequence does not
(Flame Detected) advance through PREPURGE because a flame is detected as being present. The sequence holds
waiting for the flame signal to clear. If the time exceeds 30 seconds, the relay module locks out.
PURGE HOLD: T18 The KDM indicates the burner status and that the Low Fire Switch is not closed. The firing rate
(Low Fire Switch) motor is driving to its Low Fire position in preparation for Ignition Trials. If this time exceeds four
minutes and fifteen seconds, the relay module locks out.
PURGE HOLD: T7 The KDM indicates the burner status and that the Running Interlock is not closed. The sequence
(Running Interlock) does not advance to ignition until the Running Interlock proves closed. If this time exceeds 30
seconds, the relay module locks out.
PILOT IGN mm:ss The KDM indicates the burner status, PILOT IGN, and the timing of the PILOT IGN trial begins, in
seconds. During this period, the relay module permits the pilot valve to open and the pilot flame
to establish.
If the relay module is in a PILOT HOLD status, the following condition could exist:
PILOT HOLD: TEST The KDM indicates the burner status, PILOT IGN, and that the Run/Test Switch is in the TEST
(Run/Test Switch) position. The sequence does not continue until the Run/Test Switch is placed in the RUN
position.
MAIN IGN mm:ss The KDM indicates the burner status, MAIN IGN, and the timing of the MAIN IGN trial begins, in
seconds. During this period, the relay module permits the main valve to open and the main flame
to establish.
RUN The KDM indicates the burner status, RUN, which is the period of time after the Ignition Trials and
before the operating controller setpoint is reached. During this time, the burner is firing under
control of the firing rate control.
If the relay module is in a RUN HOLD status, the following condition could exist:
RUN LOWFIRE: TEST The KDM indicates the burner status and that the Run/Test Switch is in the TEST position.
(Run/Test Switch) Normal modulation or operation does not continue until the Run/Test Switch is placed in the RUN
position.
POSTPURGE mm:ss The KDM indicates the burner status, POSTPURGE, which is the period of time after the RUN
period when the blower motor continues to run. The timing of the POSTPURGE period is fifteen
seconds.
Waiting for The KDM has power but is waiting to receive a signal from the relay module to continue
connection... operation.
RESET/ALARM TEST The KDM indicates the burner status, RESET/ALARM TEST. This condition indicates that the
reset button is pressed. If it is held for more than four seconds, the alarm output is energized. The
alarm output is de-energized when the reset button is released.
Additional Sequence Status Information When An Expanded Annunciator Is Connected To The Relay Module:
BURNER OFF: T6 The KDM indicates the Burner Switch is not closed. The burner sequence does not advance to
(Burner Switch) PREPURGE until the Burner Switch closes.
STANDBY The KDM indicates the burner status, STANDBY, and that the Operating Control is not closed.
The burner sequence does not advance to PREPURGE until the Operating Control closes.
STANDBY HOLD: T6 The KDM indicates the burner status, STANDBY, and that a limit is not closed. The burner
(EA Hold Message) sequence does not advance to PREPURGE until one or all limits close downstream from the
Operating Control.
STANDBY HOLD: T6 The KDM indicates the burner status, STANDBY, and that the control input is not closed. The
(Circuit Fault) burner sequence does not advance to PREPURGE until the control input closes.

NOTE: Normal sequences are in bold type, while abnormal sequences are in regular type. This table is for all 7800 SERIES
Relay Modules so all listed steps may not apply to the unit installed.

9 65-02291
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary.


Fault Code System Failure Recommended Troubleshooting
Fault 1 No card is plugged into the 1. Make sure the purge card is seated properly.
*No Purge Card* purge card slot. 2. Inspect the purge card and connector on the relay module for
damage or contaminants.
3. Reset and sequence the relay module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
Fault 2 Excess noise or device 1. Check the relay module and display module connections.
*AC Frequen/Noise* running on slow ac. 2. Reset and sequence the relay module.
Fault 3 Ac line dropout detected. 3. Check the relay module power supply and make sure that both
*AC Line Dropout* frequency and voltage meet the specifications.
Fault 4 Device running on fast ac. 4. Check the backup power supply, as appropriate.
*AC Frequency*
Fault 5 Low ac line detected.
*Low Line Voltage*
Fault 6 Purge card timing changed 1. Make sure the purge card is seated properly.
*Purge Card Error* since card was initially read. 2. Inspect the purge card and connector on the relay module for
damage or contaminants.
3. Reset and sequence the relay module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
Fault 7 Flame sensed when flame 1. Check wiring and correct any errors. Make sure that flame
*Flame Amplifier* not present. sensor wires are in separate conduits. Check for noise
coupling into the flame detector leadwires.
2. Make sure that flame detector and flame amplifier are
compatible.
3. Remove the flame amplifier and inspect connections. Reseat
the amplifier.
4. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier and/or the flame
detector.
Fault 8 Flame sensed when no 6. If the fault persists, replace the relay module.
*Flame Amp/Shutr* signal expected during
shutter-check or Ampli-
Check versions.
Fault 9 Flame sensed when shutter 1. Check that flame is not present in the combustion chamber;
*Flame Detected* open and no flame is correct any errors.
expected during STANDBY. 2. Check wiring and correct any errors. Make sure that flame
sensor wires are in separate conduits. Check for noise
coupling into flame detector leadwires.
3. Remove the flame amplifier and inspect its connections.
Reseat the amplifier.
4. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier and/or the flame
detector.
6. If the fault persists, replace the relay module.
Fault 10 Preignition Interlock fault 1. Check wiring and correct any errors.
*Preignition ILK* during STANDBY 2. Check Preignition Interlock switches to assure proper
*EC/RM7800, 7840, 7838B functioning.
only). 3. Check fuel valve operation.
4. Reset and sequence the relay module; monitor the Preignition
Interlock status.
5. If the code persists, replace the relay module.
(continued)

65-02291 10
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 11 Running Interlock powered at 1. Check wiring to make sure that interlocks are connected
*Running ILK On* improper sequence point. properly between terminals 6 and 7. Correct any errors.
2. Reset and sequence the relay module.
3. If the fault persists, measure the voltage between terminals 6
and G (ground), then terminals 7 and G. If there is line supply
voltage present at terminal 6 when the controller is off, the
controller switch may be bad or is jumpered.
Fault 12 Lockout Interlock powered at 4. If steps 1 through 3 are correct and there is line supply
*Lockout ILK On* improper point in sequence. voltage present at terminal 7 when the controller is closed
and the fault persists, check for a welded or jumpered
Running Interlock, Lockout Interlock, or Airflow Switch.
Correct any errors.
Fault 13 Combustion airflow interlock 5. If steps 1 through 4 are correct and the fault persists, replace
*Airflow Sw. On* fault during STANDBY. the relay module.
Fault 14 High Fire Interlock Switch 1. Check wiring and correct any errors.
*High Fire Sw.* failure to close during 2. Reset and sequence the relay module.
PREPURGE. 3. Use either the manual motor potentiometer to drive the motor
to the High Fire position or use the Run/Test Switch option,
if available. Sequence to Prepurge drive to High Fire and
place in the Test position. Adjust the High Fire Switch while
in this state to make sure that it closes properly.
4. Measure the voltage between terminal 19 and G (ground)
while in the Prepurge drive to High Fire state. Line supply
voltage should be present. If not, the switch adjustment is
incorrect and/or the switch is defective and needs replacing.
5. Reset and sequence the relay module. If line supply voltage
was present between the High Fire Switch and terminal 19,
and the fault still persists, replace the relay module.
Fault 15 Flame sensed when no flame 1. Check that the flame is not present in the combustion
*Flame Detected* is expected during chamber; correct any errors.
STANDBY. 2. Make sure that the flame amplifier and flame detector are
compatible.
3. Check wiring and correct any errors.
4. Remove the flame amplifier and inspect the connections.
Reseat the amplifier.
5. Reset and sequence the relay module.
6. If the code reappears, replace the amplifier and/or the flame
detector.
7. If the fault persists, replace the relay module.
Fault 16 No-flame detected during 1. Measure the flame signal. If one exists, make sure it meet
*Flame-Out Timer* Pilot Flame Establishing specifications. Make any necessary burner adjustments using
Period. manufacturer instructions.
2. Make sure that the flame amplifier and flame detector are
compatible.
3. If the code reappears, replace the amplifier and/or the flame
detector.
4. If the fault persists, replace the relay module.
Fault 17 Main flame failure during RUN 1. Inspect the main fuel valve(s) and connection(s).
*Main Flame Fail* after flame is established and 2. Make sure that the fuel pressure is high enough to supply
on for at least 10 seconds. fuel to the combustion chamber.
3. Check the flame detector sighting for adequate flame signal
throughout the burner firing rate.
(continued)

11 65-02291
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 18 Flame sensed when shutter is 1. Check that flame is not present in the combustion chamber.
*Flame Detected* open and no flame is expected Correct any errors.
during PREPURGE. 2. Make sure that the flame amplifier and flame detector are
compatible.
3. Check the wiring and correct any errors. Make sure F and G
wires are in individual conduits and protected from stray
noise pickup.
4. Remove the flame amplifier and inspect the connectors.
Reseat the flame amplifier.
5. Reset and sequence the relay module.
6. If the code reappears, replace the flame amplifier and/or the
flame detector.
7. If the fault persists, replace the relay module.
Fault 19 Flame was lost during MFEP or 1. Inspect the main fuel valve(s) and connection(s).
*Main Flame Ign.* the first 10 seconds of the RUN 2. Make sure that the fuel pressure is high enough to supply
state. fuel to the combustion chamber.
3. Make sure the flame detector is positioned to obtain the
required flame signal strength; reset and recycle.
Fault 20 Low Fire Interlock switch failure 1. Check wiring and correct any errors.
*Low Fire Sw. Off* to close during PREPURGE. 2. Reset and sequence the relay module.
3. Use either the manual motor potentiometer to drive the
motor to the Low Fire position or use the Run/Test Switch
option, if available. Sequence to Prepurge drive to Low Fire
and place in the Test position. Adjust the Low Fire Switch
to make sure that it closes properly.
4. Measure the voltage between terminal 18 and G (ground)
while in the Prepurge drive to Low Fire state. Line supply
voltage should be present. If not, the switch adjustment is
incorrect and/or the switch is defective and needs
replacing.
5. Reset and sequence the relay module. If line supply voltage
was present between the Low Fire Switch and terminal 18,
and the fault still persists, replace the relay module.
Fault 21 Running Interlock fault during 1. Check wiring; correct any errors.
*Running ILK* PREPURGE. 2. Inspect the fan; make sure there is no blockage of the air
intake and that it is supplying air.
3. Make sure the Interlock Switches are working properly and
that all switch contacts are free of contaminants.
Fault 22 Lockout Interlock fault during 4. Reset and sequence the relay module to PREPURGE (place
*Lockout ILK* PREPURGE. the Run/Test Switch in the Test position, if available).
Measure the voltage between terminals 7 and G (ground).
Line voltage should be present.
Fault 23 Combustion airflow interlock 5. If steps 1 through 4 are correct and the fault persists,
*Airflow Switch* fault during PREPURGE. replace the relay module.
Fault 24 The flame interlock (relay 1. Check for F leadwire routing. Make sure routing is in its
*Call Service* module) was on when it should conduit and isolated from noise-producing circuits.
be off.
Fault 25 The flame interlock (relay
*Call Service* module) was off when it should
be on.
Fault 26 The Manual Open Valve Switch 1. Check wiring and correct any errors.
*Man-Open Sw. Off* was off when it should be on 2. Make sure that the Manual Open Valve Switch is fully open.
(RM7838B only). 3. Make sure that the Manual Open Valve Switch is
functioning properly and that the switch contacts are free
from contaminants.
4. Reset and sequence the relay module.
5. Make sure that the Manual Open Valve Switch provides an
electrical path when closed. Verify that the relay module is
receiving power at terminal 17.
6. If steps 1 through 5 are correct and the fault persists,
replace the relay module.
(continued)

65-02291 12
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 27 Start Switch was on during 1. Start Switch held on too long.
*Start Switch On* PREPURGE (RM7838A, 2. Check wiring; verify that Start Switch is correctly connected.
RM7838B only). 3. Make sure that the Start Switch is functioning properly and that
the switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE; set the
Run/Test Switch to Test. Make sure there is no power at
terminal 6 during PREPURGE.
5. If steps 1 through 3 are correct and the fault persists, replace
the relay module.
Fault 28 Pilot flame failure. 1. Check pilot valve wiring and operation. Correct any errors.
*Pilot Flame Fail* 2. Check fuel supply.
3. Check pilot pressure and repeat pilot turndown test.
4. Check ignition transformer electrode, flame detector, flame
detector sighting and flame amplifier.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
Fault 29 Lockout Interlock fault. 1. Check wiring; correct any errors.
*Lockout ILK* 2. Inspect the fan; make sure that there is no blockage of the air
intake and that it is supplying air.
3. Make sure that the Lockout Interlock Switches are working
properly and that all switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE (place the
Run/Test Switch in the Test position, if available). Measure the
voltage between terminals 7 and G (ground). Line voltage
should be present.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
Fault 30 Running Interlock fault. 1. Inspect the Running Interlocks, including the Airflow Switch,
*Running ILK* and the connections. (continued)
2. Make sure that the Running Interlocks, including the Airflow
Switch, are functioning properly and that switch contacts are
free of contaminants.
3. Reset and sequence the relay module to PREPURGE. Set the
Run/Test Switch, if available, to Test. Measure the voltage
between terminal 7 and G (ground). Line voltage should be
present.
4. If steps 1 through 3 are correct and the fault persists, replace
the relay module.
Fault 31 Low Fire Interlock Switch 1. Check wiring; correct any errors.
*Low Fire Sw. Off* failure to close during RUN 2. Reset and sequence the relay module.
(RM7838B only). 3. Use either the manual motor position to drive the motor to the
Low Fire position, or use the Run/Test Switch option, if
available. Sequence to Run drive to Low Fire and place in the
Test position. Adjust the Low Fire Switch while in this state to
make sure it is closing properly.
4. While in Run, drive to Low Fire state, measure the voltage
between terminal 18 and G (ground). Line voltage should be
present. If not, the switch adjustment is incorrect and/or the
switch is defective and needs replacement.
5. Reset and sequence the relay module. If line voltage was
present between the Low Fire Switch and terminal 18 and the
fault persists, replace the relay module.
(continued)

13 65-02291
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 32 Combustion Airflow 1. Check wiring; correct any errors.
*Airflow Switch* Interlock fault. 2. Inspect the fan; make sure there is no blockage of the air intake
and it is supplying air.
3. Make sure the Airflow Interlock Switches are working properly
and all switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE. Place the
Run/Test Switch in the Test position, if available. Measure the
voltage between terminals 7 and G (ground). Line voltage
should be present.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
Fault 33 Preignition interlock fault. 1. Check wiring; correct any errors.
*Preignition ILK* 2. Inspect the Preignition Interlock switches and make sure they
function properly.
3. Check fuel valve operation. Valve must close within five
seconds.
4. Reset and sequence the relay module.
5. During STANDBY or PREPURGE, measure the voltage between
terminal 20 and G (ground). For EC/RM7810, 7820, 7830, 7850,
check voltage between terminal 17 and G. Line voltage should
be present. If not, the Preignition Interlock switches can be
defective and need replacing.
6. If the fault persists, replace the relay module.
Fault 34 CTL input was energized at 1. Check wiring; correct any errors.
*Control On* the wrong time for the relay 2. Reset and sequence the relay module.
module. This fault implies a 3. If fault persists, replace the relay module.
field wiring error.
Fault 35 Safety relay was off when it 1. Reset and sequence the relay module. If fault repeats, replace
*Call Service* should be on or a fuse has relay module, but be sure to test for excessive loads on
blown. appropriate terminals described by fault code.
Fault 36 Main valve terminal was off 2. If fault does not repeat on next cycle check for electrical noise
*Call Service* when it should be on. being coupled into the relay module through the loads on
appropriate terminals described by the fault code.
Fault 37 Pilot (ignition) valve terminal 3. If fault persists, replace the relay module.
*Call Service* was off when it should be
on.
Fault 38 Ignition terminal was off
*Call Service* when it should be on.
Fault 39 V2S valve terminal (usually
*Call Service* terminal 21) was off when it
should be on.
Fault 40 Safety relay was on when it
*Call Service* should be off.
Fault 41 Main valve terminal was on
*Main Valve On* when it should be off. WARNING
Fault 42 Pilot (ignition) valve terminal Explosion Hazard.
*Pilot Valve On* was on when it should be Can cause explosion, serious injury or death.
off. 1. Remove system power, turn off fuel supply.
Fault 43 Ignition terminal was on 2. Check for wiring errors that could provide power to
*Ignition On* when it should be off. terminals described by the fault. Correct any errors.
Fault 44 V2S valve terminal, used as 3. Re-power system; reset and sequence the relay module.
*Pilot Valve 2 On* a pilot, is on when it should 4. If fault persists, replace the relay module.
be off. 5. When fault is corrected, turn on fuel supply.
(continued)

65-02291 14
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 45 Low Fire Interlock switch failure 1. Check wiring; correct any errors.
*Low Fire Sw. Off* to close or stay closed. 2. Reset and sequence the relay module.
3. Use either the manual motor position to drive the motor to
the Low Fire position, or use the Run/Test Switch option, if
available. Sequence to Run, drive to Low Fire and place in
the Test position. Adjust the Low Fire Switch while in this
state to make sure it is closing properly.
4. While in Run, drive to Low Fire state, measure the voltage
between terminal 18 and G (ground). Line voltage should
be present. If not, the switch adjustment is incorrect
and/or the switch is defective and needs replacement.
5. If steps 1 through 4 are correct and the fault still persists,
replace the relay module.
Fault 46 This fault indicates: 1. Remove power to the device.
*Flame Amp Type* a. The Flame Failure Response 2. Reseat the flame amplifier and reset and sequence the relay
Time (FFRT) or TYPE input module.
from the amplifier changed 3. For EC/RM7890 only; make sure that Jumper JR2 is
while the device was completely clipped if a three-second FFRT amplifier is
powered; or being used. If Jumper JR2 is intact (relight option is
b. A standard amplifier was selected), use 0.8 second FFRT amplifier.
used in a pilot valve 4. For RM7838B only; make sure that a Shutter Check Flame
application; or Amplifier is being used with the Pilot Valve Hold option
c. A three-second FFRT selected.
Amplifier was used with the
relight option on the
RM7890 Relay Module.
Fault 47 The configuration jumpers differ 1. Inspect the jumper connections. Make sure that clipped
*Jumpers Changed* from the sample taken at startup. jumpers are completely removed.
2. Reset and sequence the relay module.
3. If fault persists, replace the relay module.
Fault 48 V2S valve terminal, used as a
*Delayed MV On* delayed main valve, was on when WARNING
it should be off. Explosion Hazard.
Can cause explosion, serious injury or death.
1. Remove system power, turn off fuel supply.
2. Check wiring; correct any errors.
3. Inspect the V2S Fuel Valve and its connections.
Make sure the switch is working correctly and is not
jumpered or welded.
4. Reset and sequence the relay module.
5. If fault persists, replace the relay module.
Fault 49 The manual open switch was on
*Man-Open Sw. On.* when it should be off. WARNING
Explosion Hazard.
Can cause explosion, serious injury or death.
1. Remove system power, turn off fuel supply.
2. Check wiring; correct any errors.
3. Inspect the Manual-Open Switch and its
connections. Make sure the switch is working
correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If fault persists, replace the relay module.
Fault 50 The sequence logic detected a 1. Inspect the jumpers and refer to the installation instructions
*Jumpers Wrong* combination of jumpers that is for compatible jumper configurations.
illegal for the sequence eg, if it is 2. Make sure that clipped jumpers are completely removed.
correct to clip Jumper JR1 or 3. Reset and sequence the relay module.
Jumper JR2, but not both, this 4. If fault persists, replace the relay module.
fault would be used when both
are clipped (RM7888 only).

(continued)

15 65-02291
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 51 Flame signal value is too high 1. Make sure that flame detector and flame amplifier are
*Flame Too Strong* to be valid. compatible.
2. Remove the flame amplifier and inspect the connections. Reset
the flame amplifier.
3. Reset and sequence the relay module.
4. Check the flame detector sighting position, reset and cycle.
5. Verify that no ignition noise is present in the F lead due to wire
routing.
6. Measure the flame strength. Verify it meets specifications. If
not, refer to the flame amplifier and/or flame detector checkout
procedures.
7. If the code reappears, replace the flame amplifier and/or the
flame detector.
8. If the fault persists, replace the relay module.
Fault 52 Pilot Valve 2 (terminal 21) was 1. Inspect terminal 21 and connections. Make sure that the valve
*Call Service* off when it should be on. is operating properly.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
Fault 53 Lockout Input fault 1. Check wiring; correct any errors.
*Lockout Switch* (EC/RM7810, 7820, 7830, 2. Inspect the Lockout Switch to make sure it is working
7850 only). properly.
3. Reset and sequence the relay module. During STANDBY or
PREPURGE, measure the voltage between terminal 20 and G
(ground). Supply voltage should be present. If not, the
lockout switch is defective and needs replacing.
4. If the fault persists, replace the relay module.
Fault 54 Combustion pressure switch 1. Check wiring; correct any errors.
*Comb. Pressure* fault (Fulton pulse only). 2. Inspect the Combustion Pressure Switch to make sure it is
working correctly.
3. Reset and sequence the relay module.
4. During STANDBY or PREPURGE, measure the voltage
between terminal 20 and G (ground). Supply voltage should
be present. If not, the Combustion Pressure Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
Fault 55 Purge fan switch is on when it 1. Check wiring; correct any errors.
*Purge Fan Sw. On* should be off (Fulton pulse 2. Inspect the Purge Fan Switch terminal 18 and its connections.
only). Make sure the switch is working correctly and is not jumpered
or welded.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 56 Block intake fault 1. Check wiring; correct any errors.
*Block Intake* (Fulton pulse only). 2. Inspect the Block Intake Switch and make sure it is working
properly.
3. Reset and sequence the relay module.
4. During PREPURGE, measure the voltage between terminal 7
and G (ground). Supply voltage should be present. If not, the
Block Intake Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
Fault 57 Purge Fan Switch is off when 1. Inspect the Prepurge Fan Switch terminal 18 and the
*Purge Fan Sw. Off* it should be on (Fulton pulse connections. Make sure the switch is working properly.
only). 2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
Faults 58 - 66 Unused faults
*Call Service*
Fault 67 L1 and L2 1. Check L1 and L2 for proper line phasing.
*AC Phase* miswired/exchanged
(EC/RM7810, 7820, 7830,
7850 only).
(continued)

65-02291 16
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).

Fault Code System Failure Recommended Troubleshooting


Fault 68 Preignition Interlock fault. 1. Check wiring; correct any errors.
*Preignition ILK* 2. Inspect the Preignition Interlock switches and make sure
they work properly.
3. Check fuel valve operation. Valve must close within five
seconds.
4. Reset and sequence the relay module.
5. During STANDBY or PREPURGE, measure the voltage
between terminal 17 and G (ground). Supply voltage should
be present. If not, the Preignition Interlock switches are
defective and need replacing.
6. If the fault persists, replace the relay module.
Fault 69 - 70 Unused faults.
*Call Service*
Fault 71 Low Fire Switch closed, High 1. Check firing rate position switches (usually in Modutrol
*Dynamic LFS* Fire Switch must be open Motor) for proper operation.
(EC/RM7850 only). 2. Check wiring, correct any errors.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 71 Limit input (terminal 7) is off 1. Check limits to make sure they are satisfied after resetting.
*Limits Complete* when it should be on (RM7888 2. Check electrical connections to terminal 7 of wiring
only). subbase.
3. Reset relay module.
4. If the fault persists, replace the relay module.
Fault 72 High Fire Switch closed; Low 1. Check firing rate position switches (usually in Modutrol
*Dynamic HFS* Fire Switch must be open Motor) for proper operation.
(EC/RM7850 only). 2. Check wiring, correct any errors.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 72 Special Function 2 Input 1. Check operation of Special Function 2 of PLC.
*Spec.Func.2* (terminal 17) is off when it should 2. Check electrical connection to terminal 17 of wiring
be on. subbase and confirm presence of supply power when
Special
Function 2 is activated.
3. Reset relay module.
4. If the fault persists, replace the relay module.
Fault 73 Special Function 3 Input 1. Check operation of Special Function 3 of PLC.
*Spec.Func.3* (terminal 19) is off when it should 2. Check electrical connection to terminal 19 of wiring
be on. subbase and confirm presence of supply power when
Special
Function 3 is activated.
3. Reset relay module.
4. If the fault persists, replace the relay module.
Fault 75 Flame Indication Feedback 1. Remove wire to terminal 21 and reset relay module.
*Flame Proven (terminal 21) either on when it 2. If the fault persists, replace relay module.
Feedback* should be off or off when it 3. Reconnect wire to terminal 21. If the fault returns, verify
should be on. wiring.
Fault 76 - 93
*Accessory Fault*
Fault 94 - 104
*Call Service*
Fault 105 Relay Module self-test failure. 1. Reset and sequence the relay module.
*Call Service* 2. If the fault reappears, remove power from the relay module
Fault 106 Relay Module self-test failure. and reapply the power; reset and sequence the relay
*Call Service* module.
3. If the fault persists, replace the relay module.
Fault 107 Relay Module flame signal
*Call Service* crosscheck failure.
(continued)

17 65-02291
7800 SERIES RELAY MODULES

Table 3. Hold and Fault Message Summary (continued).


Fault Code System Failure Recommended Troubleshooting
Fault 109 Negative cycle test failed, 1. Make sure a good earth ground connection exists at the
*Call Service* earth ground absent or line installation site and all earth ground connections are complete
voltage phasing improper. and correct.
2. Make sure the relay module and all loads operate at the same
line voltage phase.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 110 The configuration jumpers 1. Inspect the jumper connections. Make sure they match the
*Call Service* differ from stored values. original selection and clipped jumpers are completely
removed.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
4. Configuration jumpers must be selected prior to 200 hours of
operation. If configuration jumpers are changed after 200
hours of operation, lockout 110 occurs. Relay module cannot
be reset and must be replaced.
Fault 111 Relay Module configuration 1. Inspect the jumper connections. Make sure they match the
*Call Service* jumper test failure. original selection and clipped jumpers are completely
removed.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
Fault 112 - 126 Relay Module self-test 1. Reset and sequence the relay module.
*Call Service* failure. 2. If the fault persists, replace the relay module.
Fault 127 Safety relay feedback circuit 1. Reset and sequence the relay module.
*Call Service* was in an improper state. 2. If the fault persists, replace the relay module.

65-02291 18
7800 SERIES RELAY MODULES

19 65-02291
7800 SERIES RELAY MODULES

Home and Building Control Home and Building Control


Honeywell Inc. Honeywell Limited-Honeywell Limite
Honeywell Plaza 155 Gordon Baker Road
P.O. Box 524 North York, Ontario
Minneapolis MN 55408-0524 M2H 3N7
Printed in U.S.A. on recycled
paper containing at least 10%
65-02291 G.R. Rev. 4-98 20 paper fibers.
post-consumer www.honeywell.com