Sunteți pe pagina 1din 3

Article 440 Air Conditioning and Refrigerating Equipment Page 1 of 3

Article 440 Air Conditioning and Refrigerating Equipment

By Mike Holt for EC&M Magazine

Knowledge of Article 440 requirements is increasingly in hot demand.

Long-time EC&M reader Joe Territo, president of Territo Electric in Ocoee, FL, knows the importance of Article
440 and its growing role in facilities. A Territo client operates a multi-story building that exists for one purpose:
to make and supply chilled water to nearby customers. Chilled water buildings have been popping up in cities
across the country. And they have something in common with data centers, clinical labs, temperature-controlled
industrial enclosures, and probably your own office-they come under Article 440, because they use electrically
driven air-conditioning and refrigeration equipment that has a hermetic refrigerant motor-compressor.

What is a hermetic refrigerant motor-compressor? It's a combination consisting of a compressor and motor
enclosed in the same housing. These have no external shaft or shaft seals, and the motor operates in the
refrigerant.

Article 440 does not cover such household appliances as room air-conditioners, household refrigerators and
freezers, drinking water coolers, or beverage dispensing machines, because these are appliances and must
comply with Article 422.

Disconnecting Means

Article 440 requires you to locate the disconnecting means within sight of, and readily accessible from, the air-
conditioning or refrigerating equipment (Figure 440-2). "Within sight" means visible from, and not more than 50
ft from, each other [Article 100] (Figure 440-4). You can install the disconnecting means on or within the air-
conditioning or refrigerating equipment-but not on the access panels (Figure 440-3).

This requirement has two exceptions:

1. You can lock the switch open if the equipment is essential to an industrial process and the installation
meets certain requirements.
2. Where a plug and receptacle serve as the disconnecting means, they must be accessible. But they need
not be readily accessible.

Circuit Protection

The requirements for protecting the branch-circuit conductors, control apparatus, and circuits supplying
hermetic refrigerant motor-compressors against short circuits and ground faults are in [440.22].

The size and type of the short-circuit and ground-fault protection device for air-conditioning and refrigeration
equipment are often marked on the equipment nameplate. The manufacturer calculates these ratings per
[440.22] and [440.32] (Figure 440-5).

If the equipment nameplate specifies "Maximum Fuse Size," use a one-time or dual-element fuse. If the
nameplate specifies "HACR Circuit Breaker," use an HACR-rated circuit breaker [110.3(B)].

Short-circuit and ground-fault protection cannot exceed the nameplate ratings. If the equipment does not have

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML/Article-440-Air-Conditio... 7/5/2012
Article 440 Air Conditioning and Refrigerating Equipment Page 2 of 3

a nameplate specifying the size and type of protection device, how do you size those devices? That depends
on whether you are sizing for multiple motors or a single motor.

Rating for Equipment. Where the equipment incorporates more than one hermetic refrigerant motor-
compressor, or a hermetic refrigerant motor-compressor and other motors or other loads, size the equipment
short-circuit and ground-fault protection with the "largest load" method. The rating of the branch-circuit short-
circuit and ground-fault protective device cannot exceed the largest motor-compressor short-circuit ground-fault
protection device plus the sum of the rated-load currents of the other compressors.

Size the branch-circuit conductors at 125 percent of the larger motor-compressor current plus the sum of the
rated-load currents of the other compressors [440.33].

One Motor-Compressor. The short-circuit and ground-fault protection device for motor-compressor conductors
must be capable of carrying the starting current of the motor. Also, the protection device cannot exceed 175
percent of the equipment load current rating.

If the protection device sized at 175 percent is not capable of carrying the starting current of the motor-
compressor, you can use the next larger protection device if it does not exceed 225 percent of the motor-
compressor current rating.

Test your knowledge with this question: What size conductor and protection must you have for a 24A motor-
compressor on a 240V circuit (Figure 440-6)?

a. 10 AWG, 40A
b. 10 AWG, 60A
c. A or B
d. none of these

Answer: (a) 10 AWG, 40A protection.

Here's how we arrive at that answer:

Step 1: Size the branch-circuit conductor [Table 310.16 and 440.32].

24A x 1.25 = 30A, 10 AWG, rated 30A at 60C [110.14(C) and Table 310.16].

Step 2: Size the branch-circuit protection [240.6(A) and 440.22(A)].

24A x 1.75 = 42A, next size down protection = 40A.

If a 40A protection device is not capable of carrying the starting current, you can size the protection device up
to 225 percent of the equipment load current rating (24A x 2.25 = 54A, next size down 50A).

Conductor Sizing

Size these branch-circuit conductors no smaller than the spec on the equipment nameplate. If the equipment
does not have a nameplate specifying the branch-circuit conductors, size the conductors per [440.32] (Figure
440-5).

One Motor-Compressor. Suppose your equipment is not marked with minimum circuit ampacity. For each
single motor compressor, use a branch-circuit conductor ampacity not less than 125 percent of the motor-
compressor current. Protect branch-circuit conductors against short circuits and ground faults between 175
percent and 225 percent of the rated-load current. See [440.22(A)].

Several Motor-Compressors. Conductors that supply several motor-compressors must have an ampacity of not

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML/Article-440-Air-Conditio... 7/5/2012
Article 440 Air Conditioning and Refrigerating Equipment Page 3 of 3

less than 125 percent of the highest-rated motor-compressor current of the group plus the sum of the rated-
load currents of the other compressors. Protect these conductors against short circuits and ground faults per
[440.22(B)(1)].

Room Air-Conditioners

The rules in Part VII of Article 440 apply to window or in-wall type room air-conditioner units that incorporate a
hermetic refrigerant motor-compressor rated not over 40A, 250V, 1. These units are common in homes,
hotels, and mobile shelters such as construction trailers. But, you'll see them in many other applications as
well.

When calculating branch-circuit requirements, you can consider a room air-conditioner to be a single motor unit
only if the installation meets the four conditions listed in [440.62(A)]. You must make three branch-circuit
determinations:

Conductor and Protection Size. Branch-circuit conductors for a cord-and-plug-connected room air-conditioner
rated not over 40A at 250V must have an ampacity of not less than 125 percent of the rated-load currents
[440.32].

Maximum Load on Circuit. Where the room air-conditioner is the only load on a circuit, the marked rating of the
air-conditioner cannot exceed 80 percent of the rating of the circuit [210.23(A)].

Other Loads on Circuit. The total rating of a cord-and-attachment-plug-connected room air-conditioner cannot
exceed 50 percent of the rating of a branch-circuit where lighting outlets, other appliances, or general-use
receptacles are also supplied [210.23(B)].

Room Air-Conditioning Disconnecting Means

The supply cord for room air-conditioning equipment cannot be longer than 10 ft for 120V units or 6 ft for
equipment rated 208 through 240V. An attachment plug and receptacle can serve as the disconnecting means
for a room air-conditioner, provided (Figure 440-7):

1. The manual controls on the room air-conditioner are readily accessible and within 6 ft of the floor, or
2. An approved manually operable switch is in a readily accessible location within sight from the room air-
conditioner.

Unless you have special certification, your work on refrigerant systems does not include breaking refrigerant
seals or working with the refrigerant itself. But it does include properly applying Article 440 to protect circuits
and ensure reliable operation of the equipment. Whether you are keeping beverages cold at your local
convenience store or keeping tissues alive at a medical clinic, your knowledge of Article 440 will allow you to do
the job right.

Copyright 2002 Mike Holt Enterprises,Inc.


1-888-NEC-CODE (1-888-632-2633)

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML/Article-440-Air-Conditio... 7/5/2012

S-ar putea să vă placă și