Introduction of New Product

1600AF MCCB
For power distribution
- The highest breaking capacity
- Optimum coordination technique (Cascading & discrimination)
- Powerful engineering tools

For protection of motor & its control device


- Optimal overload protection

For controlling and disconnecting circuits

For extensive applications


- Wide range of optimized auxiliaries
and accessories

MCCB OCR Accessory


1600AF, 3&4pole
Icu: 50/70/150kA
N, A, P, S type Outer: 16 type
Ics: 100(75)%Icu
L/S/I/G Inner: 5 type
Icw: 25kA/1s
Thermal, Ammeter, Easy connection
Ui: 1000V
Power, Harmonic
Uimp: 8kV
Cat. A, B
TS1600 Rating

Type TS1000 TS1250 TS1600

Ampere frame 1000 1250 1600


Pole 3, 4 3, 4 3, 4
Rated current,(A) In -5~40C 800, 1000 1250 1600
50C 800, 1000 1250 1560
65C 800, 1000 1240 1420
Rated insulation voltage, (V) Ui 1000 1000 1000
Rated impulse withstand voltage, (kV) Uimp 8 8 8
Rated operational Ue AC50/60Hz 690 690 690
voltage, (V) DC - - -
Rated short-circuit breaking capacity N H L N H N H
IEC60947-2 Rated ultimate short-circuit AC50/60Hz 220/240V 55 75 200 55 75 55 75
(sym) breaking capacity, (kA) (Icu) 380/415V 50 70 150 50 70 50 70
440V/460V 50 65 130 50 65 50 65
480/500V 40 50 100 40 50 40 50
660/690V 35 45 50 35 45 35 45
DC 250V 2P - - - - - - -
500V 2P - - - - - - -
750V 3P - - - - - - -
Rated service breaking capacity, %Icu
100% 75% 100% 100% 75% 100% 75%
(Ics)
Rated short-circuit making capacity, AC50/60Hz 1s 25 25 12 25 25 25 25
(kA) (Icw) 3s - - - - - -
Overriding instantaneous protection kA peak 50 50 - 50 50 50 50
Isolation
Category B B A B B B B
Mechanical life (operations) 10000 10000 10000
(Life cycle) Electrical life (operations) 440V In/2 6000 6000 4000 5000 5000 5000 5000
In 5000 5000 3000 4000 4000 2000 2000
690V In/2 4000 4000 3000 3000 3000 2000 2000
In 2000 2000 2000 2000 2000 1000 1000
Pollution degree 3 3 3
Dimension (mm) d a (3p/4p) 210/280
c2
a c1
b 327
c1 155.5
b

c2 162.7
d 185.3
Weight (kg) 3P 13
4P 16.8

Ordering
MCCB

TS1600 N A 1600A 3P - -
Ampere frame Type Rated current N phase way (4Pole) Connection type
1000 N Normal 800A L N-R-S-T - Standard
TS 1250 H High 1000A R R-ST-N Rear
REAR
1600 L Current Limiting 1250A Connection
Switch- 1600A
NA disconnector

Trip relay Poles


N Normal 3P 3Pole
A Ammeter 4P 4Pole
P Power meter
S Supreme meter
Trip relay types

Classification N type A type P type S type

Externals

Current L / S / I / G / Thermal L / S / I / G / Thermal L / S / I / G / Thermal(Continuous) P type


protection ZSI(Protective coordination) ZSI(Protective coordination)
Earth leakage (Option) Earth leakage(Option) P type
Over/Under current
Other
- Over/Under frequency
protection
Unbalance(Voltage/Current)
Reverse power
Current (R / S / T / N) 3 Phase Voltage/Current 3 Phase Voltage/Current
RMS/Vector RMS/Vector
Power(P, Q, S), PF(3-Phase) Power(P, Q, S), PF(3-Phase)
Energy(Positive/Negative) Energy(Positive/Negative)
Measurement - Frequency, Demand Frequency, Demand
function Voltage/Current harmonics
(1st~63th)
3 Phase Waveforms
THD, TDD, K-Factor
Fine adjustment for long/short P type
Fine adjustment - -
time delay/instantaneous/ ground
Overload protection relays P type
: DO (Alarm)
Pre Trip Alarm -
(Ground fault is not available
when using Pre trip alarm)
3DO (Fixed) 3DO (Programmable) P type
Digital Output -
L, S/I, G Alarm Trip, Alarm, General
Compliance with IEC60255-3 P type
IDMTL setting - -
SIT, VIT, EIT, DT
Modbus/RS-485 Modbus / RS-485 Modbus / RS-485
Communication -
Profibus-DP Profibus-DP Profibus-DP
Self Power Self Power AC/DC 100~250V AC/DC 100~250V
- Power source works over 30% - Power source works over 30% DC 24~60V DC 24~60V
current of In (one pole) current of In (one pole)
Power supply - External power source are Basic protection function(L / S / I / G)
required for comm. is still under normal operation
AC/DC 100~250V without control power.
DC 24~60V
RTC timer Available Available Available Available
Long time delay N type N type N type
LED for
Short time delay/
trip info.
Instantaneous
Ground fault
10 records 256 records 256 records
Fault recording - (Fault/Current/Date and Time) (Fault/Current/Date and Time) Last fault wave
recording (3 Phase)
Event recording - - 256 records(Content, Status, Date) P type
Operating Reset button Reset, Menu A type A type
button Up/Down, Left/Right, Enter
Trip relay

N G 0

Trip relay type Communication & protection Control voltage & frequency

000 Without trip relay

N G 0
N Normal G Ground fault + L/S/I/G 0 Self-Power, 60Hz
* L/S/I/G configuration as standard 5 Self-Power, 50Hz
-with LED indicators
-without output contacts
* Ground fault system by vector sum

A G 0
A Ammeter G Ground fault 0 Self-Power, 60Hz
Z Without comm. + Earth leakage (<30A) 1 AC/DC 100V~250V, 60Hz
E Without comm. + Earth leakage (>30A) 2 DC 24V~60V, 60Hz
C Comm. 5 Self-Power, 50Hz
K Comm. + Earth leakage (<30A) 6 AC/DC 100V~250V, 50Hz
X Comm. + Earth leakage (>30A) 7 DC 24V~60V, 50Hz
* L/S/I/G configuration as standard
* Ground fault system by vector sum(G,C)
* Earth leakage system
- Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)
- E,X: External CT - Private ZCT applied(faullt current >30A)
* Comm. and output contacts DO NOT work under self-power condition.

P C 1
P Power meter C Ground fault + Com 1 AC/DC 100V~250V, 60Hz
K Comm. + Earth leakage (<30A) 2 DC 24V~60V, 60Hz
X Comm. + Earth leakage (>30A) 6 AC/DC 100V~250V, 50Hz
A Comm. + Pre-trip alarm 7 DC 24V~60V, 50Hz
* L/S/I/G configuration as standard
* Ground fault system by vector sum
* Earth leakage system
- K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)
- X: External CT - Private ZCT applied(faullt current >30A)
* Applicable to generator protection purpose

S C 1
S Supreme meter C Ground fault + Com 1 AC/DC 100V~250V, 60Hz
K Comm. + Earth leakage (<30A) 2 DC 24V~60V, 60Hz
X Comm. + Earth leakage (>30A) 6 AC/DC 100V~250V, 50Hz
A Comm. + Pre-trip alarm 7 DC 24V~60V, 50Hz
* L/S/I/G configuration as standard
* Ground fault system by vector sum
* Earth leakage system
- K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)
- X: External CT - Private ZCT applied(faullt current >30A)
* Applicable to generator protection purpose

Note) 1. L/S/I/G configuration as standard


2. Ground fault, earth leakage and pre-trip alarm functions are alternative.
3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition.
4. Voltage module should be required for P and S types(supplied seperately)
Characteristic curves

Long-time delay (L) Short-time delay (S)


5000 5000
2000 2000

Ir = 0.4...1 In
1000 1000

500 500 Isd = 1.5...10 Ir

200 200

100 100

50 50
40 tr = 0.5...20s 40
30 30
20
20 20
12 10
10
8

t(s) 5 4
t(s) 5
4 4
3 3
2
2 2

1
1 1

0.5
0.4 0.4 0.4 I2t ON 0.4
0.3 0.3 0.3 0.3

0.2 0.2 0.2 0.2


I2t OFF

0.1 0.1 0.1


0.1

0.05
0.05 0.05

0.02 0.02

0.01 0.01
0.5

0.7

10

20
0.5

0.7

10

20

Ir Ir

Instantaneous (I)
Ground fault (G) IDMTL
100 10000

50 5000
40
30
2000
20

Ig = 0.2...1 In EIT
1000
10

500
5 VIT
4
3
200
2

100
SIT
t(s) 1 t(s)
I2t ON 50

0.4 0.4 0.4

0.3 20
0.3 0.3
DT
0.2 0.2 0.2
10

I2t OFF
0.1 0.1 0.1
5

0.05
0.05
2
Ii = 2...15 In

0.02 1

0.01 0.05
0.5

0.7

10

20
0.05
0.07
0.1

0.2

0.3
0.4
0.5

0.7

3
4
5

10

In Ir
Dimensions

Front Type Front Type Busbar


307 404
Insulation barrier 267 362
250 320 115.7 77 77 77 77 18 115.7
Plate protection Insulation barrier
2525 50 25 25 25 25 25 16.5
15
25 25 Plate protection
Mounting hole

11
25
Mounting hole

11
11
283.5
5.5
5.5
5.5

283.5
5.5
212
270
327

212
270
327
C
L C
L C
L

212
270
327
374
404
212
270
327
374
404
C C C

37.2
L L L

37.2
70 70 70 70 70
199 269 47.5
Trip button
210 280 115.7 70 70 70 70 70 47.5
149.8 Trip button
199 269 115.7
152.5
210 280 149.8
155.5
152.5
162.7 155.5
190.6 162.7
190.6
16.5

16.5

Rear Type Panel drilling

114.7 84
210 280 43.5 3P 4P
199 Insulation barrier 269 14

Mounting hole
4- 5.5 4- 5.5 or M5
or M5
283.5

15

212
212
212
258

372
212
258

135

C C C
42

L L L
37.2

199 269
Trip button
115.7
149.8
152.5
155.5
162.7
190.6
31

31
11

11

25 25
44
44 70 70 Insulation barrier 70 70 70

Front panel cutting

3P 4P 3P 4P
95

95
15
15

199

199
119

119

67 67 200 200

LS constantly endeavor to improve our products so that information in this HEAD OFFICE
catalog is subject to change without notice. LS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do,
431-848, Korea
Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
Susol 1600AF MCCB / October.2010 Printed in korea STAFF