16MM TOP & BOT

TOR @ 150 C/C


SECTION OF CULVERT
G.L

12 TOP & BOT 300


TOR @ 150 C/C

VERT ON EACH FACE


12 TOR @ 150 C/C STR

HORZ ON EACH FACE


10 TOR @ 200 C/C STR 1250

12 TOR @ 150 C/C (ALT)


12 TOR @ 150 C/C STR
AT TOP & BOTTOM
450

10 TOR @ 200 C/C STR


AT TOP & BOTTOM 300

P.C.C. 1:3:6 100

300

100 200 300 1000 300 200 100

TYP. REINE DETAILS OF CULVERT

NOTES:- M/s. PUSHPGIRI CONSTRUCTIONS


1. ALL DIMENSIONS ARE IN MM AND LEVELS ARE IN METERS.
CIVIL WORKS FOR CONSTRUCTION OF 22KV
2. UNLESS OTHERWISE STATED ALL CONCRETE FOR R.C.C. WORK GIS PANEL ROOM, POWER CABLE TRENCH
SHALL BE IN M-20 GRADE TO GIVE STRENGTH OF 20N/mm2 AT 28 DAYS AND METAL SPREADING AT 220/ 22KV
3. ALL STEEL USED FOR R.C.C. SHALL BE HIGH YIELD STRENGTH MULUND SUBSTATION
DEFORMED BARS (TOR STEEL) CONFIRMING TO IS 1786 (GRADE Fe 415)
SUCH BARS ARE DENOTED BY SYMBOL
( TYP. REINE DETAILS OF CULVERT)
4. ALL CONCRETE FOR R.C.C. WORK SHALL BE MACHINE MIXED
AND VIBRATED WITH VIBRATOR DRAWN CHECKED RECOMMEND DRG NO. SR.NO
5. CLEAR CONCRETE COVER TO REINFORCING BARS BE AS FOLLOWS 02
a) PILE CAP 50MM ON BOTTOM/ SIDE. b) COLUMNS 50MM. c) PILE 50MM
APPROVED DATE SCALE PGC/MULUND/02
6. MINIMUM LAP LENGTH SHALL BE 47 TIMES THE BAR DIAMETER REV.NO
LAPS SHALL BE STAGGERED AND NEVER LOCATED AT ONE PLACE. 01
7. IF DUE TO SITE CONDITIONS OR PRACTICAL DIFFICULTIES IN
EXECUTING THE WORK, ANY CHANGES ARE REQUIRED IN
DESIGN / DRAWING, THE SAME SHALL BE REFERRED TO THE
APPROVING AUTHORITY