Sunteți pe pagina 1din 5

Sr.

# Clause Non-Conformances Recommendations Responsibility Target Date


Rubber mats must always be placed in
An electric panel was not provided with
front of electrical DBs and panels in order
rubber mat in front of it located in HT
Electrical to prevent electrocution while working on
1 room of Power House. And safe distance 30-5-2017
Safety them. And a safe working distance must
was also not marked around a step up
be clearly marked around suck high
transformer located in the same area.
tension areas.
No emergency light and exit sign was All such areas must have emergency lights
installed on the door of engines hall and and exit door signage installed to facilitate
in the basement of Power House. safe and orderly evacuation in case of any
Emergency And access to few fire extinguishers was emergency. Lights and sign EHS
2 Responsibility, Access for Fire extinguisher
Action Plan found blocked due to placement of And access to all fire fighting equipment
unnecessary tools and items in front of and installations must always be cleared
them near Work Shop of Power House maintained clear and in an unobstructed
located in Engine Hall. manner.
No flammable chemical should be placed
Flammable chemicals were found placed / in high temperature areas and all
Chemicals stored in engines hall of Power House chemicals must possess hazard rating and
3 24-5-2017
Safety without secondary containments, hazard MSDS and must be placed within
ratings and MSDS. respective secondary containments in
order to avoid spillages.
No combustible material should be placed
or store in such areas in order to avoid fire
Combustible material was found placed 24-5-2017
4 Fire Safety hazard. And all oily rags must be
on floor in Work Shop of Power House.
contained within designated drums or
containments.
5 Hot Work Welding plant was found left unattended All employees must be instructed to place
Issue / Revision No. 00 Issue Date: March 02, 2009 Page 16/1
INTERNAL AUDIT REPORT EHS-FR-112

on a site of Power House while the the equipment and tools at their respective
relevant labor was at rest. locations before leaving the area.
All active sites must have an up to date
An expired work permit was found
work permit displayed on the site and all
displayed on a site of Power House and
6 PTW relevant hazards must be clearly marked on Sectional Head ok
hazards were not clearly identified on
the work permits along with necessary
another work permit in the same area.
precautionary / safety measures.
A monkey ladder leading to cooling
All monkey ladders must have a cage
7 Work at Height towers was found not provided with 31-5-2017
starting from the height of 7 feet.
cage at Power House.
All ASTs must be provided with gauges
and overfill devices in order to avoid any
Overfill devices and gauge was missing
accident while loading and unloading
on an acid storage tank located at Power
operations.
House.
8 AST Safety All overfill devices and gauges must be Sectional Head 31-5-2017
HFO was found excessively spilled in
regularly checked and changed in case if
secondary containment of HFO storage
not functioning properly in order to avoid
tanks located at Power House.
spillages during loading and unloading
operations.
Unsafe and exposed electrical
All electrical connections must be secured
Electrical connections were found in an electrical
9 in order to prevent the hazard of fire or Sectional Head ok
Safety DB located in control room of Power
electrocution.
House.
No compressed gas cylinder should be
Cylinders A compressed gas cylinder was found placed or stored inside such high
10 Sectional Head not related to PG
Safety placed inside Boiler hall. temperature areas in order to avoid any
serious accident like fire or explosion.
Multiple chemical containers were All chemical containers must be properly
Chemicals found placed without secondary labeled with product name, hazard rating
11 Sectional Head not related to PG
Safety containments and hazard labeling in a and MSDS. And must be placed within
store located in front of Boiler House. respective secondary containments
Issue / Revision No. 00 Issue Date: March 02, 2009 Page 17/1
INTERNAL AUDIT REPORT EHS-FR-112

All such stations must always possess


12 Hazard Necessary signage was missing on the MSDS, hazard rating, no smoking sign
main SNGPL station located adjacent to and emergency contact numbers clearly Sectional Head not related to PG
Communication
the gate leading to hostels. displayed.

Issue / Revision No. 00 Issue Date: March 02, 2009 Page 18/1