Sunteți pe pagina 1din 3

Chapter C12

SEISMIC DESIGN REQUIREMENTS FOR


BUILDING STRUCTURES

C12.3.3.3 Elements Supporting Discontinuous revised requirement is intended to quantify the


Walls or Frames importance of redundancy. The NEHRP Commen-
The purpose of the special load combinations is tary points out that many non-redundant structures
to protect the gravity load-carrying system against have been designed in the past using values of R that
possible overloads caused by overstrength of the were intended for use in designing structures with
lateral force-resisting system. Either columns or higher levels of redundancy. In other words, the use
beams may be subject to such failure, therefore, both of the R factor in the design has led to slant in design
should include this design requirement. Beams may in the wrong direction. The NEHRP Commentary
be subject to failure due to overloads in either the indicates that the source of the revised factor is
downward or upward directions of force. Examples Technical Subcommittee 2 of the NEHRP Provisions.
include reinforced concrete beams, the weaker top
laminations of glulam beams, or unbraced anges of C12.4.3 Seismic Load Effect Including
steel beams or trusses. Hence, the provision has not Overstrength Factor
been limited simply to downward force, but instead to Some elements of properly detailed structures are
the larger context of vertical load. A remaining not capable of safely resisting ground-shaking
issue that has not been fully addressed in this edition demands through inelastic behavior. To ensure safety,
is clarication of the appropriate load case for the these elements must be designed with sufcient
design of the connections between the discontinuous strength to remain elastic. The 0 coefcient approxi-
walls or frames and the supporting elements. mates the inherent overstrength in typical structures
The connection between the discontinuous having different seismic force-resisting systems. The
element and the supporting member must be adequate special seismic loads, factored by the 0 coefcient,
to transmit the forces for which the discontinuous are an approximation of the maximum force these
element was designed. For example, where the elements are ever likely to experience. This standard
discontinuous element is required to comply with the permits the special seismic loads to be taken as less
special loads specied in Section 12.4.3, as is the case than the amount computed by applying the 0
for steel columns in braced and steel moment frames, coefcient to the design seismic forces when it can be
its connection to the supporting member will also be shown that yielding of other elements in the structure
required to be designed to transmit the same forces. will limit the amount of load that can be delivered to
These same special seismic loads are not required for the element. As an example, the axial load in a
shear wall systems and, as such, the connection column of a moment-resisting frame will derive from
between the shear wall and the supporting member the shear forces in the beams that connect to this
would only need to be designed to transmit the loads column. The axial loads due to lateral seismic action
associated with the shear wall and not the special need never be taken as greater than the sum of the
seismic loads. shears in these beams at the development of a full
structural mechanism, considering the probable
C12.3.4 Redundancy strength of the materials and strain-hardening effects
This standard introduces a revised redundancy (for frames controlled by beam hinge-type mecha-
factor for structures in Seismic Design Categories D, nisms this would typically be 2Mp/L, where for steel
E, and F to quantify redundancy. The value of this frames Mp is the expected plastic moment capacity of
factor is either 1.0 or 1.3. This factor has an effect of the beam as dened in the AISC Seismic Specica-
reducing the R factor for less redundant structures, tion and for concrete frames, Mp would be the
thereby increasing the seismic demand. The factor is probable exural strength of the beam, where L is the
specied in recognition of the need to address the clear span length). In other words, as used in this
issue of redundancy in the design. The National section, the term capacity means the expected or
Earthquake Hazards Reduction Program (NEHRP) median anticipated strength of the element, consider-
Commentary Section 5.2.4 explains that this new ing potential variation in material yield strength and

479
CHAPTER C12 SEISMIC DESIGN REQUIREMENTS FOR BUILDING STRUCTURES

strain-hardening effects. When calculating the tion exibility may be included as part of the model
capacity of elements for this purpose, material of the structure, but doing so is not required. Where
strengths should not be reduced by capacity or foundation exibility is not considered, the foundation
resistance factors. elements and the base of the structure may be rigidly
restrained. The rigid restraints should be consistent
with the design of the structure. As an example,
C12.6 ANALYSIS PROCEDURE SELECTION consider a moment frame building without a basement
and with moment-frame columns supported on
Table 12.6-1 provides the permitted analysis proce- footings designed to support shear and axial loads,
dures for all seismic design categories. The table is i.e., pinned column bases. For such a building, the
applicable only to buildings without seismic isolation base is the level at the top of the footings. If founda-
(Chapter 17) or passive energy devices (Chapter 18). tion exibility is not considered, the columns should
The four basic procedures provided in Table be restrained horizontally and vertically, but not
12.6-1 are Equivalent Lateral Force (ELF) analysis rotationally. Consider a moment-frame building with
(Section 12.8), modal response spectrum (MRS) a basement and the base dened as the level closest to
analysis (Section 12.9), and linear response history grade. For this building, horizontal restraint may be
(LRH) analysis and nonlinear response history (NRH) provided at the level closest to grade, as long as the
analysis. Requirements for performing response diaphragm is designed to transfer the shear out of the
history analysis are provided in Chapter 16 of the moment frame. Because the columns extend through
standard. Nonlinear static pushover analysis is not the basement, they may also be restrained rotationally
provided as an approved analysis procedure in and vertically at this level. However, many times it is
ASCE 7-05. better to extend the model through the basement and
The ELF method is allowed for all SDC B and C provide the vertical and rotational restraints at the
buildings, and for all SDC D, E, and F buildings, with foundation elements, which is more consistent with
the following two exceptions: the actual building geometry.
Regular structures with height > 160 ft (48.8 m) and
C12.8.4.1 Inherent Torsion
T > 3.5Ts
Where earthquake forces are applied concurrently
Structures with height < 160 ft (48.8 m) and with one
in two orthogonal directions the 5 percent displace-
or more of the following irregularities: torsion,
ment of the center of mass should be applied along a
extreme torsion, soft story, extreme soft story,
single orthogonal axis chosen to produce the greatest
weight (mass), or vertical geometric.
effect, but need not be applied simultaneously along
Ts = SD1/SDS is the period at which the horizontal two axes (i.e., in a diagonal direction).
and descending parts of the response spectrum Most diaphragms of light-frame construction are
intersect (Figure 11.4-1). The value of Ts will depend somewhere between rigid and exible for analysis
on the Site Class because SDS and SD1 include such purposes, that is, semirigid. Such diaphragm behavior
effects. When ELF is not allowed, the analysis must is difcult to analyze when considering torsion of the
be performed using modal response spectrum or structure. As a result, it is believed that consideration
response history analysis. of the amplication of the torsional moment is a
ELF is not allowed for buildings with the listed renement that is not warranted for light-frame
irregularities because the procedure is based on an construction.
assumption of a gradually varying distribution of mass Historically, the intent of the Ax term was not to
and stiffness along the height and negligible torsional amplify the natural torsion component, only the
response. The basis for the 3.5Ts limitation is that the accidental torsion component. There does not appear
higher modes become more dominant in taller build- reason to further increase design forces by amplifying
ings (Lopez and Cruz 1996, Chopra 2007), and as a both components together.
result, the ELF method may underestimate the design
base shear and may not correctly predict the vertical C12.11.2 Anchorage of Structural Walls and
distribution of seismic forces in taller buildings. Transfer of Design Forces into Diaphragms
There are numerous instances in U.S. earthquakes
C12.7.1 Foundation Modeling of tall, single-story, and heavy walls becoming
This section provides direction as to how to treat detached from supporting roofs, resulting in collapse
the interface between the structure and soils. Founda- of walls and supported bays of roof framing

480
MINIMUM DESIGN LOADS

(Hamburger and McCormick 1994). The response sheathed with materials other than wood structural
involves dynamic amplication of ground motion by panels, whereas the minimum R factors for Categories
response of vertical system and further dynamic B and C are 1.5 and 2.0, respectively.
amplication from exible diaphragms. The design Where the roof framing is not perpendicular to
forces for seismic design category D and higher have anchored walls, provision needs to be made to transfer
been developed over the years in response to studies both the tension and sliding components of the
of specic failures. It is generally accepted that the anchorage force into the roof diaphragm. Where a
rigid diaphragm value is reasonable for structures wall cantilevers above its highest attachment to, or
subjected to high ground motions. For a simple near, a higher level of the structure, the reduction
idealization of the dynamic response, these values factor based upon height within the structure,
imply that the combined effects of inelastic action in (1 + 2z/h)/3, may result in a lower anchorage force
the main framing system supporting the wall, the wall than appropriate. In such an instance, using a value of
(acting out of plane), and the anchor itself correspond 1.0 for the reduction factor may be more appropriate.
to a reduction factor of 4.5 from elastic response to an
MCE motion and therefore the R value associated
with nonlinear action in the wall or the anchor itself is REFERENCES
3.0. Such reduction is generally not achievable in the
anchorage itself, thus it must come from yielding Chopra, A. K. (2007). Structural Dynamics,
elsewhere in the structure, for example, the vertical Prentice Hall, Upper Saddle River, NJ
elements of the seismic force resisting system (SFRS), Hamburger, R. O., and McCormick, D. L. (2004).
the diaphragm, or walls acting out of plane. The Implications of the January 17, 1994, Northridge
minimum forces are based upon the concept that less Earthquake on Tilt-Up and Masonry Buildings with
yielding will occur with smaller ground motions and Wood Roofs, Proceedings, 63rd Annual Convention,
less yielding will be achievable for systems with Structural Engineers Association of California, Lake
smaller R factors, which are permitted in Seismic Tahoe, Calif., 243255.
Design Categories B and C. The minimum R factor in Lopez, O. A., and Cruz, M. (1996). Number of
Seismic Design Category D is 3.25, excepting Modes for the Seismic Design of Buildings,
cantilever column systems and light-frame walls Earthquake Engrg. and Struct, Dyn., 25(8), 837856.

481

S-ar putea să vă placă și