Documente Academic
Documente Profesional
Documente Cultură
Table of Contents
Guide to using the QDC part .................................................................................................................. 3
Chapter 1 Preliminary....................................................................................................................... 6
1 Name of QDC part ......................................................................................................................... 6
2 Purpose .......................................................................................................................................... 6
3 Application ..................................................................................................................................... 6
4 Requirements of BCA not varied ................................................................................................. 6
5 Referenced documents ................................................................................................................. 6
6 Definitions ...................................................................................................................................... 8
Chapter 2 Performance criteria and acceptable solutions.......................................................... 13
Appendix A1 Requirements for external debris protection............................................................ 48
Appendix A2 Specification: Simulated windborne debris impact testing for external fabric of
cyclone shelters .............................................................................................................................. 51
Appendix A3 Specification: Simulated wind pressure testing for external fabric of cyclone
shelters .............................................................................................................................. 53
Appendix B Standardised site and building signage...................................................................... 54
Appendix C Ventilation specifications: Venturi ducts .................................................................... 55
Appendix D Specifications: Diesel generators................................................................................ 56
Uninterruptible power source......................................................................................................... 57
Appendix E Specification: Central battery systems ....................................................................... 58
Appendix F Dynamic thermal simulation and CFD simulation assessment ................................. 59
Appendix G Ductwork connectivity with natural ventilation devices ............................................ 61
Appendix H Required elements of a cyclone shelters fire and evacuation plan ......................... 62
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
Guide to using the QDC part
Overview
This guide is intended to provide information that will help readers to understand and
apply the Queensland Development Code, part 3.8 Cyclone shelters (the QDC part).
The guide does not form part of the QDC part.
The Queensland Development Code (or QDC) is the part, or aspects of the parts, of the
document called Queensland Development Code published by the department.
The chief executive of the department may amend the QDC, including by adding
another part to it or replacing a part of it. However, an amendment does not take effect
until the chief executive publishes the amendment on the departments website and a
regulation approves the amendment.
A provision approving the addition of the QDC part to the QDC is set out in the Building
Regulation 2006, part 8, division 1. The provision (section XXYY) states that the
approval takes effect on X XXX 2017. Therefore, the QDC part takes effect on that day.
The QDC part applies to buildings that are proposed to be used as cyclone shelters
under a local government disaster management plan. Under the Building Regulation
2006 (section XX), a building must not be referred to as a cyclone shelter unless it
meets certain criteria (Note: The criteria will be added to this paragraph once the
wording of the amendment to the Building Regulation 2006 has been finalised).
How to comply with the QDC generally and the QDC part in particular
Under section 14 of the Building Act 1975 (Building Act), building work complies with the
QDC only if it complies with all relevant performance criteria under the QDC. The building
work complies with a relevant performance criteria only if it achieves a relevant building
solution under the QDC for the performance criteria.
The QDC part contains 28 performance criteria and 51 acceptable solutions. Under
section 14 of the Building Act, a relevant building solution for any of the performance
criteria can be achieved by
(a) complying with the relevant acceptable solution for the performance criteria; or
(b) formulating an alternative solution that complies with the performance criteria or
is shown to be at least equivalent to the relevant acceptable solution; or
4 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
The BCA contains performance requirements that building work must comply with. It also
contains building solutions for those requirements in the form of deemed-to-satisfy
provisions.
Under section 35 of the Building Act, if a part of the QDC is inconsistent with the BCA,
the part prevails to the extent of the inconsistency. This section allows the QDC part to
vary particular requirements in the BCA. In particular, section 35 allows the QDC part to
vary performance requirements in the BCA by setting performance criteria that replace or
vary those performance requirements. The section also allows the QDC part to vary the
relevant building solutions for particular performance requirements by setting acceptable
solutions that differ from the deemed-to-satisfy provisions for those performance
requirements.
A cyclone shelter is rarely dedicated solely for the purpose of an emergency shelter, and
usually operates during normal occupancy with a different type of use. Regardless of the
classification that applies for the buildings normal use under the BCA, the building
classification applicable while the building or part is operating as a cyclone shelter will be
a class 9b.
In assessing the compliance of the building against the requirements of the BCA, the
building certifier will apply both the classification that is applicable for the buildings normal
use and the classification of 9b as applicable while the building is operating as a cyclone
shelter, if this classification is different to that applying for the normal use.
This QDC part provides for additional requirements relevant to the use as a cyclone
shelter that vary, or apply in addition to, the requirements of the BCA for a class 9b
building. Where an aspect of the BCA is not varied specifically by this QDC part, the
provisions of the BCA for both the class 9b cyclone shelter use and the classification
applying for the normal use continue to apply.
Referral agency
The Queensland Fire and Emergency Service (QFES) has jurisdiction as an advice
agency where an alternative solution is proposed for the fire safety system under this
QDC part. This includes performance criteria P3.3, P4.0, P4.1, P4.2 and P4.3.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
5 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Associated requirements
The following legislation includes requirements that apply to cyclone shelters as defined
under the QDC part. These requirements are additional to the requirements in the QDC
part.
Building Act 1975
Building Code of Australia (BCA)
Building Regulation 2006
Sustainable Planning Act 2009
Sustainable Planning Regulation 2009.
Cyclone shelters are designed to be operated as part of a local or regional disaster
management response to a tropical cyclone event. Other legislation, such as the Disaster
Management Act 2003, applies to the operational activities of cyclone shelters.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
6 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Chapter 1 Preliminary
1 Name of QDC part
This part of the Queensland Development Code (this QDC part) may
be cited as the Queensland Development Code, part 3.8 Cyclone
shelters.
NoteThis QDC part takes effect on X XXX 2017. See the Building Regulation 2006,
section XX.
2 Purpose
The purpose of this QDC part is to provide additional and varied
technical building requirements to those in the BCA that apply to
cyclone shelters.
3 Application
This QDC part is applicable to buildings or parts of buildings that are
proposed to be used as a cyclone shelter under a local government
disaster management plan.
5 Referenced documents
The table below sets out the number, year of commencement and
title of each Australian Standard referred to elsewhere in this QDC
part.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
7 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Including Amendment 1
AS/NZS 1999 Methods for fire tests on building materials,
1530.3 components and structures Simultaneous
determination of ignitability, flame propagation,
heat release and smoke release
AS/NZS 2012 Specification for preservative treatment Part 3
1604.3 Plywood
AS 1668.2 2012 The use of ventilation and air conditioning in
buildings Mechanical ventilation in buildings
Including Amendment 1
AS 1670.1 2015 Fire detection, warning, control and intercom
systems Systems design, installation and
commissioning Fire
AS 1670.4 2015 Fire detection, warning, control and intercom
systems Systems design, installation and
commissioning Sound systems and intercom
systems for emergency purposes
AS 1692 2006 Steel tanks for flammable and combustible
liquids
Including Amendment 1
AS/NZS 1768 2007 Lightning protection
AS 2293.1 2005 Emergency escape lighting and exit signs for
buildings Part 1: System design, installation and
operation
Including Amendment 1
AS 2293.3 2005 Emergency escape lighting and exit signs for
buildings Part 3: Emergency escape luminaires
and exit signs
AS 2419.1 2005 Fire hydrant installations, Part 1: System design,
installation and commissioning
Including Amendment 1
AS 2441 2005 Installation of fire hose reels
Including Amendment 1
AS 2444 2001 Portable fire extinguishers and fire blankets
Selection and location
AS/NZS 2015 Plumbing and drainage Stormwater drainage
3500.3
AS 3600 2009 Concrete structures
Including Amendment 1 and 2
AS 3700 2011 Masonry structures
Including Amendment 1
AS 4040.0 1992 Methods of testing sheet roof and wall cladding
Introduction, list of methods and general
requirements
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
8 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
6 Definitions
acceptable solution see the Building Act, section 14.
baffled entry means an entry door permitting entry during high wind
conditions, protected by screening to avoid debris loads impacting the
entry door.
Building Code of Australia (BCA) see the Building Act, section 12.
Note
The BCA forms part of the National Construction Code Series published by the body
known as the Australian Building Codes Board.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
9 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
cyclone shelter, for the purposes of this QDC part, means a building
or part of a building that:
Note see the Building Regulation 2006, section XX, for the definition of cyclone
shelter as it applies outside this QDC part.
design flood event means the applicable flood event for design
based on an annual probability of exceedance of 1:500.
design storm tide event means the applicable storm tide event as
determined in accordance with P1.0 and A1.0.0 of this QDC part.
exit has the same meaning as set out in the BCA, volume 1, and
where debris screens including doors or gates are incorporated as
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
10 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
fire and evacuation plan means the fire and evacuation plan required
for the building by s104E of the Fire and Emergency Services Act 1990
with the elements listed in Appendix H.
NOTE If conditions during a tropical cyclone do not exceed the wind speeds at which
lockdown is required, the total occupancy period may not include a lockdown period.
maximum flood level, for a design flood event, means a flood event
affecting the site having an annual probability of exceedance of 1:500,
and includes the backwater effects of a relevant design storm tide
event for sites in a storm tide hazard area.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
11 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
mean higher high water means the average height of the higher high
waters over a 19-year period. For shorter periods of observation,
corrections are applied to eliminate known variations and reduce the
result to the equivalent of a mean 19-year value.
NoteA cyclone shelter is intended for a total occupancy period of 36 hours made up of
the following:
The occupancy period does not include the time taken by the LDMG to set up the shelter
and ready it for operation prior to the point at which evacuees are accepted.
probable maximum flood level means the flood level determined for
the largest conceivable flood event, determined from the probable
maximum precipitation and catchment characteristics.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
12 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
shelter space means all spaces within the cyclone shelter required to
support the operation of the shelter, except for the diesel generator
enclosure and the toilet amenities.
storm tide height means the water height derived from the effect on
coastal water of a storm surge combined with the normally occurring
astronomical tide.
wave effect means the combined effect of wave set-up and wave run-
up occurring in frontal areas along the coastline subject to ocean
waves during a tropical cyclone.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
13 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
1 Siting
Performance criteria
P1.0
A cyclone shelter must be designed and constructed to resist the impacts
of
(a) storm tide hazard;
(b) river and creek flood hazard.
Acceptable solution
A1.0.0
(1) A cyclone shelter in a storm tide hazard area must have a minimum floor
level determined from the following
(a) the sum of 1:10,000 AEP storm tide height (AHD), Mean Higher High
Water (AHD) and wave effect (frontal area only); and
(b) be increased to the next 0.5 m increment in AHD above the level
determined in (a).
Acceptable solution
A1.0.1
(1) A cyclone shelter in a flood hazard area must have a floor level above the
greater of
(a) the design flood event maximum flood level; or
(b) the probable maximum flood level less 1 m; or
(c) where flooding with a water flow velocity greater than 3m/s may occur,
the probable maximum flood level; and
(d) the design flood event in (a) shall have an annual probability of
exceedance of 1:500.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
14 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P1.1
A cyclone shelter must be located so that it avoids, to the degree necessary,
the impacts of built and natural hazards during a tropical cyclone.
Acceptable solution
A1.1.0
(1) The minimum distance a cyclone shelter may be located from
(a) a tree with a mature trunk diameter of greater than 100mm, is the
mature height of the tree.
(b) buildings or structures, is the maximum height of the buildings or
structures.
Vehicle access
Performance criteria
P1.2
A cyclone shelter must be located so that it is provided with suitable access
for vehicles and pedestrians prior to and after cyclone events.
Acceptable solution
A1.2.0
(1) A cyclone shelter must be provided with vehicular access that
(a) provides set-down for car and bus passengers within 200m of the
cyclone shelters primary entry point; and
(b) where located within the site, provides all-weather sealed access for
a vehicle with a GVM of 15 tonnes.
(2) Passenger set-down areas in (1) must be capable of being accessed and
left in forward gear.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
15 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
2 Design actions
Wind actions
Performance criteria
P2.0
A cyclone shelter must be designed and constructed, to the degree
necessary, to resist the impacts of wind actions associated with severe
tropical cyclones.
Acceptable solutions
A2.0.0
(1) The magnitude of wind actions on a cyclone shelter in accordance with the
BCA must be determined using
(a) an annual probability of exceedance of the design event for safety
of 1:10 000; and
(b) an annual probability of exceedance for serviceability limit state of
1:50; and
(c) for AS/NZS1170.2, internal wind pressures that are calculated on
the basis of a large dominant opening existing on one wall only.
A2.0.1
(a) internal fabric, including walls and ceilings, that resists the internal
wind pressures calculated using AS/NZS1170.2 and A2.0.0; and
(c) imperforate lining materials, where used under the roof to satisfy
A2.0.2(1)(b), that are designed with a net pressure coefficient
between the lining and the roof cladding of 0 or -0.3, where
AS/NZS1170.2 does not require a more severe net pressure
coefficient to be used; and
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
16 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(g) roof sheeting that is mechanically screw fixed with cyclone washers
to resist design wind pressures.
A2.0.2
(a) evidence from a registered testing authority that the assembly has
been subjected to the tests specified in Appendix A3 after
withstanding the tests specified in Appendix A2; or
(b) where roof or wall cladding has not been tested in accordance with
Appendix A2 prior to the tests specified in Appendix A3, the
addition of an imperforate lining material designed to resist the wind
loads; or
(e) for reinforced concrete blockwork with all cores filled, design in
accordance with AS3700.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
17 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
A2.0.3
(1) Roof and wall bracing for a cyclone shelter shall be provided such that
(a) the design loads in each direction are resisted by a minimum of two
spatially separated roof and wall bracing systems; and
A2.0.4
(1) Where plywood is used as an imperforate lining material under
A2.0.2(1)(b), the plywood must be suitable for use in hazard class H3
exposure conditions as referred to in AS/NZS1604.3.
Performance criteria
P2.1
A cyclone shelter must be designed and constructed, to the degree
necessary, to resist the impacts of windborne debris.
Acceptable solution
A2.1.0
(1) Elements forming the external fabric of a cyclone shelter, including
windows, doors, roller doors, louvered openings, wall and roof cladding,
debris screens and the like, must
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
18 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(d) where an entry door is protected by a baffled entry, that door may
be designed to resist design debris impact load B only.
A2.1.1
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
19 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
A2.1.2
(a) prevent the debris missile described in design debris impact load A
from impacting the external face of the door from any angle,
including after a single rebound at any angle from another wall; and
(2) For A2.1.2(1)(a), where a missile impacts a wall of the baffled entry at an
angle of 90 or less to the face of the wall, the potential rebound trajectory
must be taken to occur at any angle from 90 to 180 to the wall.
Performance criteria
P2.2
A cyclone shelter must be designed and constructed, to the degree
necessary, to resist the additional imposed loading of debris build-up and
the like on horizontal exposed surfaces.
Acceptable solution
A2.2.0
(1) For the purposes of designing the roof membrane and supporting structure
in accordance with the BCA, the applicable uniformly distributed imposed
loading under AS/NZS1170.1 must be
(a) the greater of
(i) the uniformly distributed imposed loading as determined
under AS/NZS1170.1 for the design use; and
(ii) a uniformly distributed imposed load of 1.8kPa.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
20 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P2.3
Where elements providing structural support to a cyclone shelter are
located below the design flood level within a storm tide or flood hazard
area, the elements must be designed and constructed, to the degree
necessary, to resist the impacts of wave and water flow actions.
Acceptable solution
A2.3.0
(1) For determining the applicable loads on the building structure in
accordance with the BCA
(a) water loads below the design event water level must be determined
in accordance with section 15 of AS5100.2; and
(b) where the element is exposed to a design storm tide event water
loads due to design storm tide event must include the effect of
waves, and be calculated for an annual probability of exceedance of
not less than 1:2000; and
(c) where the element is exposed to a design flood event (river and
creek) water loads must include the effect of debris mats 1.2m
thick and log impact, and be calculated for an annual probability of
exceedance of not less than 1:500; and
(d) where the element is exposed to both design storm tide event and
design flood event water loads must include the effect of waves,
debris mats 1.2m thick and log impact, and be calculated for a
combined annual probability of exceedance of not less than 1:500.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
21 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Building signage
Performance criteria
P3.0
Acceptable solution
A3.0.0
(b) be located
(2) Signage in A3.0.0(1)(b)(iii) must be fixed between 1.2m and 2.1m above the
entry points finished ground surface level.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
22 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P3.1
Acceptable solution
A3.1.0
(1) At least one entry point to a cyclone shelter must consist of either
(4) Entry doors to a cyclone shelter in A3.1.0 (1) must be fitted with door
handles that are
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
23 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(d) with at least 100mm of the handle length located between 900mm and
1100mm from the entrys finished ground surface level.
Performance criteria
P3.2
Acceptable solution
A3.2.0
(1) The following floor surfaces must have a slip resistance not less than
classification R11 or P4 as determined by AS4586:
(a) the area extending internally 2m from the primary entry point and for
the full width of the entry points door.
(b) the area extending internally 2m from the entry point in A3.1.0 and for
the full width of that entry points door.
(2) Walls and ceilings in a cyclone shelter must be light in colour and have
(a) for walls, at least 50% of their area with a minimum luminous
reflectance value of 60%; and
(3) A cyclone shelter must incorporate a path of travel for people with
disabilities complying with AS 1428.1 between the following areas
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
24 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(d) amenities.
Acceptable solution
A3.2.1
(1) For the purposes of the deemed-to-satisfy provisions of the BCA and
acceptable solutions of the QDC, the number of occupants accommodated
in the shelter area within a cyclone shelter must be determined by
(a) calculating the number obtained by dividing the floor area of each
part of the shelter area by 1.2m2, excluding any spaces set aside
for
NoteOccupancy for other areas within the shelter space of a cyclone shelter, such as
kitchen spaces, office and registration areas, storage spaces and the like, is determined
by applying the provisions of the BCA, clause D1.13.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
25 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Egress
Performance criteria
P3.3
Acceptable solution
A3.3.1
(1) Where required exits in a cyclone shelter are fitted with additional
restraints, they must be
(a) capable of being locked in the open position at all times other than
during the lockdown period; and
(b) capable of being engaged in the closed position during the lockdown
period.
(3) If keys are used in conjunction with locking mechanisms in A3.3.1 (1) or
(2), they must
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
26 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
4 Fire safety
Performance criteria
P4.0
NOTE If a fire occurs within the building during lockdown conditions, the LDMG may determine that
conditions external to the building are not suitable to permit evacuation. In this case, the risk of a fire
developing to a size that presents a risk to the occupants during lockdown conditions must be reduced.
Acceptable solutions
A4.0.0
A4.0.1
The shelter area must have a minimum ceiling height of 6m for a minimum of
80% of the floor area.
A4.0.2
(1) All rooms and spaces within a building containing a cyclone shelter must
be
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
27 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(a) capable of being accessed from within the shelter space without travel
outside the building, so that occupants are able to attempt to
extinguish a fire in that area; or
(b) separated from all spaces functioning as part of the cyclone shelter by
fire-resisting construction having a minimum FRL of 120/120/120.
A4.0.3
(1) Within a cyclone shelter, fire hazard properties of materials must comply
with BCA volume 1, specification C1.10 and
(a) for Table 3 of BCA Specification C1.10, the shelter space is a specific
area; and
(i) be non-combustible; or
A4.0.4
(1) Ancillary use areas of a high fire hazard in cyclone shelters must
(2) The ancillary use areas in A4.0.3(1) include, but are not limited to
(a) laboratories.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
28 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(e) laundries, if the equipment includes gas fired dryers or the like.
(3) If supplied, all gas to the cyclone shelter must be able to be turned off
before the pre-lockdown period.
Management procedure
A4.0.5
Separation of equipment
Performance criteria
P4.1
A cyclone shelter must prevent the spread of fire from and to services and
equipment having a high fire hazard or a potential for explosion, or required
to be capable of continued operation during the occupancy period.
Acceptable solution
A4.1.0
(1) The following services and equipment must be separated from the cyclone
shelter space and each other by construction elements achieving a
minimum FRL of 120/120/120 in accordance with BCA volume 1,
specification A2.3
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
29 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P4.2
Occupants in a cyclone shelter must be provided with automatic warning
on the detection of smoke so that appropriate actions can be undertaken
in the event of a fire.
Acceptable solution
A4.2.0
(1) A cyclone shelter must be provided with
(a) a smoke detection and alarm system and fire indicator panel
complying with AS 1670.1; and
(b) an occupant warning system complying with clause 3.22 of AS1670.1,
and incorporating
(i) a device located at the FIP or MECP, providing the ability to
make voice announcements over the warning speaker
system; and
(ii) a warning speaker system having speech intelligibility
complying with AS1670.4, section 4.3.8; and
(iii) the ability to provide an alert signal prior to the evacuation
signal; and
(c) a separate detection zone for each room where the main source of
required ventilation is provided by natural ventilation; and
(d) zone isolation switches located at the fire indicator panel to enable
isolation of rooms in (c).
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
30 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P4.3
A cyclone shelter must be provided with services and equipment to allow
occupants to undertake initial attack on a fire during a tropical cyclone
event.
Acceptable solution
A4.3.0
(1) Fire hose reels serving a cyclone shelter must
(a) comply with AS 2441; and
(b) be located within the building; and
(c) be located so that coverage is provided to all spaces within the cyclone
shelter without the need to travel outside the building; and
(d) be located so that the hose does not need to pass through fire or
smoke doors, except for doors referred to in A4.0.4(1) and A4.1.0(1).
(2) Any part of the fire hose reel system located externally to the building must
be capable of resisting the loads in A2.0.0 and A2.1.0.
NOTE Fire hose reels serving parts of the building other than the cyclone shelter may be
located outside the building, provided that they are protected in accordance with A4.3.0(2).
(3) In addition to the town mains connection, a water storage tank must be
provided for a fire hose reel system within a cyclone shelter, and must
(a) have a minimum capacity of 5,000 litres; and
(b) be provided with a pump that is connected to the diesel generator
power supply in A7.0.2.
(4) The storage in A4.3.0(3) may be provided within the same tanks as the
water storage provided in A8.0.0, provided that
(a) suitable backflow prevention devices are provided; and
(b) the minimum 5,000 litre capacity is in addition to the amount required
under A8.0.0.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
31 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A4.3.1
(1) Fire extinguishers complying with AS 2444 must be provided to cyclone
shelters in accordance with Table 2.
Table 2: Type, number and location of fire extinguishers
Type Size Rating Number Location
Water 9.1 litre 3A 2 Adjacent to each hose
reel
1 Within cyclone shelter
dedicated office
Dry 4.5kg 4A:20B:E 2 Within cyclone shelter
chemical dedicated office
1 Adjacent to a generator
room
1 Adjacent to a battery
room
1 Per 300m2 of floor area
and within 15m travel
distance to any point in
the building
Carbon 5.0kg 5B:E 1 Adjacent to a battery
dioxide room
1 Adjacent to any
communication/server
room
(2) A minimum 1m2 fire blanket complying with AS 2444 must be provided to
any kitchen within a cyclone shelter.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
32 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
External weatherproofing
Performance criteria
P5.0
A cyclone shelter must be designed and constructed, to the degree
necessary, to resist rainfall events associated with a severe tropical
cyclone.
Acceptable solution
A5.0.0
(1) The stormwater drainage system for a cyclone shelter must be designed in
accordance with AS/NZS3500.3 to cater for a design rainfall event with an
average recurrence interval of 500 years.
(2) The roof of a cyclone shelter must
(b) not include any penetrations through the roof sheeting for
downpipes, gutters and similar rainwater goods; and
Ventilation generally
Performance criteria
P5.1
A cyclone shelter must be provided with ventilation that
(a) complies with the BCA, volume 1, FP4.3, FP4.4 and FP4.5; and
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
33 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Verification Method
CV5.1
Compliance with P5.1 to ventilate a cyclone shelter during the occupancy period
is verified if the ventilation system meets the dynamic thermal and computational
fluid dynamic simulation assessment set out in Appendix F.
Acceptable solution
A5.1.0
Performance criteria
P5.2
The shelter area of a cyclone shelter used by occupants must
(a) be provided with ventilation that will maintain adequate air quality
during the occupancy period; and
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
34 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.0
(a) for supply air, ventilation rates not less than 10 L/s/m2 of outside
air; and
(b) for exhaust air, ventilation rates not less than 11 L/s/m2; and
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
35 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.1
(1) Fans used for supply air, exhaust air and circulation of air to shelter
spaces must be configured so that, for areas greater than
(a) 250m2, failure of any one fan within the ventilation system does not
result in a reduction of minimum ventilation rate by more than 55%;
or
(b) 500m2, failure of any one fan within the ventilation system does not
result in a reduction of minimum ventilation rate by more than 35%.
(2) Supply air distribution outlets forming part of a ventilation system must
be
(a) configured so that 90% of the floor area served is not greater than
12m from a supply air outlet measured from the outlet; and
(3) Exhaust air intake locations must not be located lower than two thirds the
height of the occupied space.
(4) Fans used for circulation of air must be capable of operating during the
lockdown period.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
36 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.2
(1) During the lockdown period, a cyclone shelter must be provided with
natural ventilation through
(a) natural ventilation devices located at its external parts that are
connected to the inside parts by
(3) The area of natural ventilation devices located on the external parts of a
cyclone shelter must be provided in accordance with Table 4.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
37 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.3
Acceptable solution
A5.2.4
Acceptable solution
A5.2.5
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
38 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(a) so that at least 90% of the internal floor area of the building served
by the ventilation system is within 20m of an internal opening; and
(b) in accordance with Table 5; and
(c) in accordance with Figure 1.
Figure 1
C
X
X
B
Legend
A 120
= Internal openings
X 1/16 x (A + B + C + D + E)
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
39 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.6
(1) Amenities areas, during both pre-lockdown and post lockdown periods,
must
(a) be provided with mechanical exhaust systems in accordance with
AS 1668.2; and
(b) discharge vertically above the roof in the following locations
(i) outside the line of external walls; and
(ii) at the lowest end of any roof slope; or
(iii) along a barge-end; and
(c) have fans capable of operating on both generator and mains
power.
(2) Amenities areas, under lockdown conditions must
(a) be provided with a venturi suction system complying with Appendix
C; and
(b) be capable of modulation through manual interaction.
(3) Mechanical exhaust systems in A5.2.6(1) must not operate during the
lockdown period.
Acceptable solution
A5.2.7
(1) Diesel generator areas, under both pre-lockdown and post lockdown
conditions, must
(a) be provided with mechanical exhaust systems in accordance with
AS 1668.2; and
(b) discharge vertically above the roof in accordance with A5.2.6 (2);
and
(c) have fans capable of operating on both generator and mains
power.
(2) Diesel generator areas, under lockdown conditions, must be provided with
natural ventilation through natural ventilation devices connected to the
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
40 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A5.2.8
(1) Central battery areas, under both pre-lockdown and post lockdown
conditions, must
(a) be provided with mechanical exhaust systems in accordance with
AS 2676.2; and
(b) discharge vertically above the roof in accordance with A5.2.6 (2);
and
(c) have fans capable of operating on both generator and mains
power.
(2) Mechanical exhaust systems for central battery areas must not operate
under lockdown conditions.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
41 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
(3) Under lockdown conditions, central battery areas must be provided with a
venturi suction system complying with Appendix C.
Lighting
Performance criteria
P6.0
A cyclone shelter must be provided with lighting that
Acceptable solution
A6.0.0
(1) Artificial lighting within a cyclone shelter must be connected to mains and
diesel generator electricity supply and provide a minimum of
(a) 400 lux in spaces used for
(i) the application of first aid.
(ii) food preparation and cooking.
(iii) office and administrative activities for the operation of
the cyclone shelter.
(b) 160 lux to all other areas including amenity areas.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
42 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Acceptable solution
A6.0.1
Emergency lighting
Performance criteria
P6.1
Acceptable solution
A6.1.0
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
43 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Power distribution
Performance criteria
P7.0
A cyclone shelter must be designed and constructed with electrical services
and equipment appropriate to the use of the building.
Acceptable solution
A7.0.0
Lightning protection
Performance criteria
P7.1
Acceptable solution
A7.1.0
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
44 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Emergency power
Performance criteria
P7.2
Acceptable solution
A7.2.0
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
45 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P8.0
A cyclone shelter must be designed and constructed to include a water
storage facility so that water suitable for human consumption, food
preparation, food utensil washing and personal hygiene appropriate to the
number of occupants during the design occupancy period is capable of being
stored prior to the occupancy period.
Acceptable solution
A8.0.0
(1) A cyclone shelter must be provided with tanks suitable for water storage
that
(a) provide the volumes in Table 6; and
(b) are connected to serve hand washing, drinking fountains and
kitchen facilities within the cyclone shelter during the occupancy
period; and
(c) are located in a space inside the cyclone shelter; and
(d) are fitted with pumps connected to a diesel generator complying
with A7.0.2 to provide pressure for delivery of the stored water; and
(e) have bypass valves installed to permit the stored water to gravity
flow to services in the event of a diesel generator failure.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
46 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
NOTE During the periods when the building is used for its normal occupancy, it is not necessary for
the cyclone shelter water tanks to be at full capacity or service the listed features, provided
that the tanks are able to be readily deployed to serve the occupancy period.
Ancillary provisions
Kitchen amenities
Performance criteria
P9.0
A cyclone shelter must be provided with suitable spaces in the building to
facilitate basic food and medicaments storage and preparation.
Acceptable solution
A9.0.0
(1) A cyclone shelter must be provided with a kitchen space for the
preparation and serving of food.
(2) A kitchen space must
(a) be located adjacent to the primary entry point to the cyclone shelter
and have access from the foyer; and
(b) have a floor area calculated on the basis of 2.5 m2 per 100 persons
or a minimum of 13m2, whichever is the greater; and
(c) incorporate a hand wash basin no more than 5m from any part of a
bench used for the preparation of food; and
(d) have a minimum of two 10 amp, general purpose electrical outlets
connected to the mains and diesel generator power source.
(3) Benches in kitchen spaces must
(a) for the serving of food
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
47 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Office facilities
Performance criteria
P9.1
Acceptable solution
A9.1.0
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
48 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Performance criteria
P9.2
A cyclone shelter must be provided with a suitable space within a room for
the provision of first aid activities.
Acceptable solution
A9.2.0
Chair store
Performance criteria
P9.3
A cyclone shelter must be provided with suitable storage space for chairs for
use during the design occupancy period.
Acceptable solution
A9.3.0
(1) A cyclone shelter must be provided with a room for the storage of chairs.
(2) A room for the storage of chairs must have a minimum floor area
calculated on the basis of 4m2 per 100 occupants or part thereof.
Appendix A1 Requirements for external debris protection
A1.1 Debris impact loading
The external fabric of a cyclone shelter must be constructed to resist the impact
of design debris impact load A and design debris impact load B.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
49 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
External building fabric elements, including windows, doors, roller doors, louvered
openings, wall and roof cladding, debris screens and the like, must comply with
the test specifications in Appendix A2 and A3.
All glass in the external building fabric must be laminated.
The impact load trajectories to be resisted by building elements are described in
Table A1.
Table A1
Roof fascias and Horizontal A+B Soffits, fascias and barges are
barges exempt from debris impact loads
if external walls that resist the
loads extend to the underside of
Eaves soffits flat Vertical A+B the upper roof sheeting.
or downward
sloping from wall
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
50 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
51 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
NOTE Testing carried out in accordance with James Cook University Cyclone Testing Station
Technical Note No.4. Simulated Windborne Debris Impact Testing of Building Envelope
Components is considered to satisfy this Appendix.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
52 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
53 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
NOTE an appropriate test rig and test method is described in James Cook University, Cyclone Testing
Station Technical Note No.2 Simulated Wind Load Testing of Roof and Wall Cladding Systems.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
54 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
55 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
Venturi ductwork system must be sized based upon a friction loss of no greater
than 0.6 Pa/m utilizing the air flow rates that would otherwise be applicable for a
mechanical exhaust system provided in accordance with AS1668.2.
Ducts and their fixings located outside the building must resist the gust ultimate
wind pressure defined in A2.0.0 including local pressure factors.
The top of the venturi duct must be located in a region of the roof subject to
negative pressure for all wind directions.
The venturi duct projection above the roof level must be minimised to reduce
wind loads on the duct and fixings.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
56 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
The emergency generator must be provided with adequate fuel storage for 24
hour continuous operation at full rated load. Fuel storage must be via steel
tank(s) with integral secondary containment and fuel shut off systems.
A fuel polishing system must be provided to maintain fuel life for long storage
periods.
The emergency generator is to start upon sense of power failure and provide
supply to nominated emergency equipment within 30 seconds of loss of power.
An automatic transfer switch must be provided to switch to generator power in
the event of mains power failure. The automatic transfer switch must also revert
to mains power should it be restored.
The diesel generator must be located within the shelter building, in a dedicated
room, have access from within the building without the need to exit the building,
and have external access in addition to the internal access.
The generator must be provided with the following controls:
key operated local engine start/stop control
controls for auto/off/manual/load test
emergency manual shutdown
speed indicator, kW meter, frequency meter, ammeter, kVAR meter,
power factor meter, and hours run meter
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
57 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
The minimum power demand per DGPO must be determined for the essential
equipment to be connected.
Notes:
1. The devices connected to the nominated power outlets should be low wattage to conserve
the UPS power supply.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
58 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
59 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
60 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
The mean 10 minute wind speed at the start of pre-lockdown simulation must be
10 km/hr increasing linearly to 70 km/hr at lockdown and maintained at this speed
during lockdown.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
61 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
AD 0.25 ANVD KT
where:
AD = area of ductwork connecting natural ventilation devices to internal
openings (m2)
ANVD = area of natural ventilation device (m2)
KT = the aggregate loss co-efficient of proposed ductwork fittings (bends,
transitions, offsets, plenums, expansions, contraction) connecting the
natural ventilation device to the internal opening, determined with a
Reynolds number correction value of 1.0.
The minimum internal cross-sectional area of the ductwork connecting the natural
ventilation devices to internal openings must be not less than 20% the size of the
natural ventilation device.
Ductwork connecting natural ventilation devices to internal openings must be
limited to 20 m in length.
The use of turning vanes in ductwork is not permitted.
Internal openings must have a face area determined by:
AIO 0.5 ANVD
where:
AIO = area of internal opening (m2)
ANVD = area of natural ventilation device (m2)
P = pressure drop (Pa) of a 1 m2 reference sample of the internal opening
with a face velocity of 3.5 m/s.
The internal opening must not have an area of less than 30% of the natural
ventilation device area.
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017
62 Queensland Development Code, Part 3.8 Cyclone shelters
______________________________________________________________
3. The proposed maintenance schedule for the cyclone shelters fire safety
installations.
(b) a simple and legible diagram of the building, drawn to a reasonable scale,
indicating the cyclone shelters evacuation routes, required exits and
assembly points; and
______________________________________________________________
Publication date: 10 March 2017
Commencement date: XX XXX 2017