Sunteți pe pagina 1din 2

GENERAL Valve Tag Number 25MAC10AA201/202/203 25EGC30AA201

25GMA20AA201
Equipment protected HP steam pipe FUEL OIL LINE HTF-Oily
wastewater pipe
Positioning pipe PIPE PIPE
Case
Equipment/Pipe Tag 25MAC10BR004 25EGC30BR001 25GMA20B
R201
Full Nozzle/Semi Nozzle
Safety or Relief SAFETY RELIEF SAFETY
Conv, Bellows Pilot Op.
Bonnet Type
CONN. Size inlet Outlet 6''/10'' 10''/10''
Flange Rating or Screwed BW BW
Type of Facing
MATERIALS Body and Bonnet BY SUPPLIER BY SUPPLIER
Seat and Disc BY SUPPLIER BY SUPPLIER
Resilent Seat Seal BY SUPPLIER BY SUPPLIER
Guide and Rings BY SUPPLIER BY SUPPLIER
Spring BY SUPPLIER BY SUPPLIER
Bellows BY SUPPLIER BY SUPPLIER
OPTIONS Cap: Screwed or Bolted
Lever: Plain or Packed
Test Gag
BASIS Code API520&ASME I API520&ASME I API520&ASME I
Fire
FLUID DATA Fluid and State Steam Oil HTF-Oily wastewater
Required Capacity ??m3/s ( ??kg/s) ??m3/s ( ??kg/s)
65m3/h
Mol. Wt. Oper.sp.Gr
Oper. Press Set. Press 11/14bar.a. 12/12.6 2.5/2.6bar.a
Oper. Temp. Rel. Temp 288/380 Ambient temperature Ambient
temperature
Back pressure Constant BY SUPPLIER BY SUPPLIER
Variable BY SUPPLIER BY SUPPLIER
Total BY SUPPLIER BY SUPPLIER
Allowable Overpressure 3% Set.Pre 3% Set.Pre
Overpressure factor
Compressibility Factor
Latent Heat of Vaporization
Ratio of Specific Heat
Operating Viscosity
Barometric pressure
Calc.Area mm2 BY SUPPLIER BY SUPPLIER
Selected Area mm2 BY SUPPLIER BY SUPPLIER
Orifice Designation (1) BY SUPPLIER BY SUPPLIER
Manufacturer
Model No
NOTES "(1) - Orifice sizing is considering a PSV witout rupture disk
(2) - Materials will be determinated by supplier. Equipment provision (BW) is on
SA-182 F1 material quality
(3) - Variable back pressure considered for ASME I is 10% of the set pressure (M
aximum allowed for conventional valves)
(4)- The formula used for sizing liquid discharge case is based on the ASME VIII
certification. The estimated coefficient Kd is 0.65, to be confirmed by valve s
upplier.
(5)The backpressure suffered by te safety valve must comprehend the pressure los
ses in the line to the silencer and silencer s pressure loss.So balances valves ar
e required for this application.Balances valves are suppled by the supplier."