Reciprocating
Compressor
(any design)
Flow sheet symbol
1763
106
trols. The nomenclature for the symbols in the equation is as
follows:
h = differential head (ft or m)
H = polytrophic compressor head (ft or m)
K1,2,3 = flow constant
Compressor inlet ow, ft3/min
R = gas constant
104
Electric motor, T1 = inlet temperature
gear driven u = rotor tip speed (ft/s or m/s)
W = weight flow (lbm/hr or kg/hr)
Z = gas compressibility factor
= motor torque (ft lbf or J)
103
0 2 4 6 8 10 12 14 18 20 22 24 26 28 = head coefficient
Compressor speed, thousand RPM = angular velocity (radians/hr)
= density of gas (lb/ft or kg/m )
3 3
Speed Governor Classification
FIG. 8.15c
The speed and flow capacity ranges of standard compressor drives
* lb = 0.45 kg
(top) and the classification of speed governors (bottom). PSI = 6.9 kPa = 0.069 BAR
240
220
The operating ranges of the most popular drives are I
200 rve S4 (4)
shown in Figure 8.15c. Also given in the lower part of the Cu
180
figure is the definition of some two-speed governors. Regu-
y
Discharge pressure (PSIA)*
nc
II Constant
lation error is the percentage of the difference in speed
cie
rve
72%
160 pressure
Cu
E
120
nc
cie
(5)
nc
E
ge l
100
cie
%
Sur
y
78
nc
80
cie
%
(3)
76
S3
CENTRIFUGAL COMPRESSORS 60
%
74
ve
40 c ur
tem n)
The Compression Process Sy s ictio
20 s tl y fr
(mo
The centrifugal compressor is a machine that converts the
0 1 2 3 4 5 6 7 8 9 10 11 12
momentum of gas into a pressure head.
Flow (103 lbm/hr)*
*For SI units see Section A.1
n
n n 1
H= = ZRTI , [( PD /PI ) 1] 8.15(1)
w n 1 FIG. 8.15d
The operating point is located where the centrifugal compressor
curves cross the system curve of the process. The system curve can
Equation 8.15(1) is the basis for plotting the compressor be a constant pressure one (horizontal line), a mostly friction one,
curves and for understanding the operation of capacity con- or any other.
3
2
1 4 7
Pressure
Pressure
Pressure
5 8
6 9
2 1 4 7
3
Power
Power
Power
5
6 8
9
Capacity Capacity Capacity
(a) (b) (c)
FIG. 8.15f
The efficiencies of discharge throttling (left), suction throttling (center), and variable speed control (right).
* lb = 0.45 kg
TABLE 8.15h PSI = 6.9 kPa (0.069 BAR)
Compressor Performance Parameters as a Function of Throt- 240
tling Method
220
Control Operation S1
Valve Compressor Above 200 ve I
Cur speed
P(PSI) Efficiency Surge By 180 100 %
ve II
E 74%
y
76% ciency
Suction throttling mostly 12.2 77% 347% s
nc
80%
y
cie
nc
friction system 120 V
ve I
cie
E
Cur eed
E
(4)
Discharge throttling mostly 122 72% 148% 100 sp
70%
78%
t
imi
friction system
80
ge l
Sur
60 ve
cur
ystem
40 s
tion
fric (2)
surge is less likely in a mostly friction system than in a ostly
20 M
constant-pressure system under suction throttling control.
0 1 2 3 4 5 6 7 8 9 10 11 12
Flow (103 lbm/hr)*
Discharge Throttling A control valve on the discharge of the *For SI units see Section A.1
centrifugal compressor may also be used to control its capacity.
In Figure 8.15d, if the flow is to be reduced from 9600 lbm/hr FIG. 8.15i
(4320 kg/hr) at point (1) to 5900 lbm/hr (2655 kg/hr), the Control of centrifugal compressor capacity by speed variation.
compressor must follow curve I and therefore operate at point
(4), at 190 psia (1.3 MPa) discharge pressure and 72% effi-
ciency. However, the mostly friction system curve at this
3700 lbm/hr (1665 kg/hr). The intersection with the mostly
capacity requires only 68 psia (0.5 MPa) and the rest of the
friction system at point (5) represents a flow change of only
pressure is wasted through the discharge control valve. The
9600 7800 = 1800 lbm/hr (810 kg/hr).
surge flow (at S4) is 4000 lbm/hr (1800 kg/hr), and the com-
pressor is therefore operating at 5900/4000 = 148% of surge.
Variable Speed The pressure ratio developed by a centrif-
Thus, surge is more likely to occur in a mostly friction system
ugal compressor is related to the tip speed in the following
when discharge throttling is used than when suction throttling
manner:
is used.
Table 8.15h compares the valve pressure drops, efficien-
cies, and surge margins of suction and discharge throttling. ZRTI
u 2 /2 g = [( P /P )( n 1/ n ) 1] 8.15(2)
(n 1/ n) D I
Inlet Guide Vanes This method of control uses a set of
adjustable guide vanes on the inlet to one or more of the From this relation the variation of discharge pressure with
compressor stages. By prerotation or counter-rotation of the speed may be plotted for various percentages of design speed,
gas stream relative to the impeller rotation, the stage is as shown in Figure 8.15i. The obvious advantage of speed
unloaded or loaded, thus lowering or raising the discharge control from a process viewpoint is that both suction and
head. The effect is similar to suction throttling as illustrated discharge pressures can be specified independently of the
in Figure 8.15d (curves II and III), but less power is wasted flow.
because pressure is not throttled directly. Also, the control is The normal flow is shown at point (1) for 9700 lbm/hr
two-directional, since it may be used to raise as well as to (4365 kg/hr) at 142 psia (0.98 MPa). If the same flow is
lower the band. It is more complex and expensive than throt- desired at a discharge pressure of 25 psia (173 kPa), the speed
tling valves but may save 10 to 15% on power and is well is reduced to 70% of design, shown at point (2). In order to
suited for use on constant-speed machines in applications achieve the same result through suction throttling with a
involving wide flow variations. pressure ratio of 10:1, the pressure drop across the valve
The guide vane effect on flow is more pronounced in would have to be (142 25)/10 = 11.7 psi (81 kPa), with the
constant discharge pressure systems. This can be seen in attendant waste of power, as a result of throttling. This is in
Figure 8.15d (curve II), where the intersection with the con- contrast with a power saving accomplished with speed con-
stant pressure system at point (2) represents a flow change trol, because power input is reduced as the square of the
from the normal design point (1) of 9600 5900 = speed.
PD psia
(9600 8100)/9600 = 16%. 510
500 Operating conditions
490 A B C D E
Surge Control
P1 274.5 292 278 295 344
480
T1 120 120 100 100 120
The design of compressor control systems is not complete Mw 11.6417 10.6364 10.48 8.3978 7.0
without consideration of surge control, because it affects the k 1.2646 1.2742 1.282 1.2943 1.3
stability of the machine. Surging begins at the positively Z 1.0016 1.0047 1.0027 1.0053 1.01
sloped section of the compressor curve. In Figure 8.15i this
occurs at S1 on the 100% speed curve at 4400 lbm/hr (1980
kg/hr). If the flow never drops below this limit, that will 1800
ensure safe operation for all speeds, but some power will be 1700
wasted at speeds below 100% because the surge limit
1600
decreases at reduced speed.
1500 A
Even for a compressor running at a constant speed, the B
surge point changes as the thermodynamic properties vary at 1400
C
the inlet. This is shown in Figure 8.15j. Although inaccurate 1300
bhp
control of the surge point can put the compressor into deep 1200
D
surge, a conservatively set surge point results in useless recy- 1100
cling and wasted energy. 1000 E
Various schemes to control surge are outlined in the fol- 700 800 900 1000 1100 1200 1300 1400
lowing paragraphs. These include: icfm (suction ow)
M Users
PDT Compressor
Pd
PDT Pd Pi
h Ratio
P relay
PT PY
Pi
Surge valve
m(P) + b
SP FCV
Surge limit Characteristic h
curves for various FT FIC FO
Surge PI
compressor speeds
measurement DA
100%
Pressure increase Pd Pi, PSI
F To vent or
90% recycle
E
Surge valve opens if
h < m(P) + b
80%
D Surge line
70% Compressor
C speeds
60%
120
Guid
Surge e v an
e s ra
ve
limit dial
ur
100%
ec
100
rg
Speed
Su
( PP 1) percent pressure rise
g s
80
sin ane
clo e v
id
Gu
80%
60
40
d
i
(Centrifugal compressor)
20
Inlet ow (ACFM)
0 20 40 60 80 100 120
Volumetric ow at suction conditions, percent
FIG. 8.15m ve
ur
The surge line for an axial compressor is steep at low flows and ec
3 urg
flat at high flows. Pressure rise (PSI) S
Maximum
even if pressure varies, as long as the compressor is at a
Normal va
1
constant speed. As speed is reduced, the surge and choke
lines intersect. Below this intersection, the traditional meth-
Minim
vane settin
ods of surge protection (venting, recycling) are ineffective;
ne setting
um va
only a quick raising of the compressor speed can bring the
machine out of surge.
ne set
g
This is similar to the situation when the compressor is
(Axial compressor)
being started up. As the operating point is moving on the ting
load curve (Figure 8.15p), it must pass through the unstable
region on the left of the surge curve as fast as possible in Inlet ow (ACFM)
order to avoid damage from vibration.
FIG. 8.15n
Flow Measurement The two critical components of a surge When guide vanes are used for throttling, both the centrifugal and
1
control loop are the flow sensor and the surge valve. Both the axial compressors surge curve bends over.
must be fast, accurate, and reliable.
Flow oscillations under surge conditions occur on a cycle
of little more than a second. The flow transmitter should be streamlined flow tube-type sensor. Noise will also be reduced
fast enough to detect these. The time constants of various if the low-pressure tap of the d/p cell is connected to a pie-
1
transmitter designs are as follows: zometric ring in the venturi-type flow tube (Figure 8.15q). The
addition of straightening vanes will also contribute to the
Pneumatic with damping: Up to 16 sec reduction of noise.
Electronic d/p: 0.21.7 sec Antisurge control usually requires a flow sensor on the
Diffused silicone d/p: Down to 0.005 sec suction side of the compressor. If good, noise-free flow mea-
surement cannot be obtained on that side, a corrected dis-
Only the diffused silicone-type sensor design is fast charge side differential pressure reading (hd) can be substi-
enough to follow the precipitous flow drop that occurs at the tuted. Equation 8.15(3) can be used to obtain the suction side
beginning of surge or the oscillations during surge. Measure- differential pressure (hs) from readings of (hd) and the suc-
ment noise is another serious concern, because it necessitates tion plus discharge pressures and temperatures (Ps, Pd, Ts,
a greater margin between the surge and the control lines. Noise and Td):
can be minimized by the use of 20 pipe diameters of upstream
and 5 diameters of downstream straight runs around the hs = hd(Pd/Ps)(Ts/Td) 8.15(3)
100%
Speed
100%
ve
ur
r ve
Surge
ec
80%
e cu
rg
Speed
Su
e
80%
g
rv
Sur
Speed
Cu
Vertical portion
e
60% ok
Speed Ch
40% Load curve 60%
Speed Speed
Stonewall
Static
Divergent outlet
Surge Control Valves Surge valves are usually fail-open,
linear valves that are tuned for fast and precise throttling.
Because the valve is the weak link in the total surge protection
system, and because testing and maintenance cannot be done
on-line if only one valve is used, total redundancy is recom-
mended. Each of the two parallel surge valves should be sized Annular chambers
for the full flow of the compressor but for only 70% of the
discharge pressure. This pressure reduction is caused by the FIG. 8.15q
flow reversals during surge. Herschel venturi with annular pressure chamber.
TABLE 8.15r
Venturi, Flow Tube, and Flow Nozzle Inaccuracies (Errors) in Percent of Actual Flow for Various Ranges of Beta Ratios and
Reynolds Numbers
Line size, inches Pipe Reynolds Number Range Inaccuracy, Percent of
Flow Sensor (1 in. = 25.4 mm) Beta Ratio for Stated Accuracy Actual Flow
2 10 to 1 10 0.75%
1 5 6
Herschel standard Cast 432 0.300.75
2 10 to 2 10 1.5%
5 6
Welded 848 0.400.70
8 10 to 8 10 0.5%
2 4 6
Proprietary true venturi Cast 296 0.300.75
8 10 to 8 10 1.0%
4 6
Welded 1120 0.250.80
8 10 to 1 10 1.0%
3 4 6
Proprietary flow tube Cast 348 0.350.85
7 10 to 4 10 1.0%
4 6 7
ASME flow nozzles 148 0.200.80
1
No longer manufactured because of long laying length and high cost.
2
Badger Meter Inc.; BIF Products; Fluidic Techniques Inc.; Primary Flow Signal Inc.; Tri-Flow Inc.
3
ABB Instrumentation; Badger Meter Inc.; BIF Products; Preso Industries.
4
BIF Products; Daniel Measurement and Control.
Surge Large solenoid close more slowly than it opened. Such fast-opening, slow-
control opens when closing designs can respond to the first precipitous drop in
signal deenergized flow and thus can prevent the second surge cycle from devel-
Interlock
2 S2
#2 oping. It is important not to slow the speed of valve opening
Large too much, because quick throttling is still required.
air supply 1:1 Vent
The valve must also respond quickly to the control signal
Solenoid Enlarged
vents when tap and throttle quickly in either direction. In order to speed up
deenergized the air movement into and out of the actuator, the vent and
2 Vent signal ports on the actuator are both drilled out, an air booster
S1 Position
O ZT feedback is installed, and a large-capacity path is established between
E S Posit.
I/P I signal the booster and the actuator. In order to reduce the dead band
D
Vent of the 1:1 booster, it is advisable to use a signal range of
Gas from Liner To vent or 630 PSIG instead of the usual 315 PSIG.
compressor globe recycle The bypass needle valve around the booster in Figure 8.15s
discharge FO is required because without it the volume on the outlet of the
positioner would be much smaller than on the outlet of the
FIG. 8.15s booster. This would allow the positioner to change the input
A well-designed surge control valve will have a positioner, a large
to the booster faster than the booster could change its output,
air supply with a one-to-one booster repeater with bypass, vent
solenoids, and position feedback. (Adapted from Reference 1.) resulting in a limit cycle. This limit cycle is eliminated by
the addition of the adjustable bypass.
All surge valves should be throttle-tested before ship-
ment. It is also desirable to monitor the surge valve opening
Globe valves (Section 6.19) are preferred to rotary through the use of a position transmitter.
designs because of hysteresis and breakaway torque consid-
erations. Boosters (Figure 8.15s) can cut the sum of prestroke Surge Control Curves As was shown in Figure 8.15l, a par-
dead time and full-scale stroking to under 1 sec. Actually, abolic surge curve with a positive slope will appear as a
valves as large as 18 in. have been made to throttle to any straight line on a P vs. h plot. The purpose of surge control
1
position in under a half-second. is to establish a surge control line to the right of the actual
Digital valves (Section 6.18) are even faster: They can surge line, so that corrective action can be taken before the
stroke in 0.1 sec without any overshoot. Their limitations are machine goes into surge. Such a control system is shown in
in the plugging of the smaller ports and in the difficulty of Figure 8.15t.
inspecting them. The biased surge control line is implemented through a
Positioners are frequently required to reduce hysteresis biased ratio relay (PY), which generates the set point for
(packing friction), dead band (boosters), disc flutter (butterfly FIC as follows:
valves), and overshoot; they are also often needed just to
provide the higher air pressure required by piston actuators.
SP = m(P) + b 8.15(4)
Figure 8.15s shows some of the main components of a
1
surge control valve. The electronic control signal is con-
where
verted to a pneumatic one by the I/P converter, and this
SP = desired value of h in inches H2O
pneumatic signal is sent to the positioner through a three-
way solenoid (S1). The output signal from the positioner is m = slope of the surge line at the operating point
sent simultaneously into a booster relay (1:1) and an adjust- P = compressor pressure rise in psi
able bypass. The output from the booster relay is connected b = bias of the surge set point in inches H2O
by short- and large-diameter tubes to the valve actuator with
an enlarged pressure tap and to the large venting solenoid The offset between the surge and the control lines should
(S2). Some of the operational features of the system are as be as small as possible for maximum efficiency, but it must
described below. be large enough to give time to correct upsets without vio-
6
When interlock #2 is de-energized, requiring instanta- lating the surge line. The slower the upsets and the faster
neous full opening of the surge valve (because of discharge the control loop, the less offset is required for safe operation.
line blockage or other reasons), S1 vents the positioner inlet In a good design, the bias b is about 10%, but in bad ones,
and S2 vents the actuator top-work. Because S2 is large, air as disturbances get faster or instrument slower, it can grow
removal is fast and the valve opens quickly. On return to to 20%.
normal, both solenoids are energized. This closes S2 and A second line of defense is the backup interlock FSL. It
opens S1 to the control signal. is normally inactive, as the value of h is normally above the
Depending on the size or restriction in the line from S1, FIC set point SP. When the surge controller FIC is not fast
air might enter the system more slowly and the valve might enough to correct a disturbance, h will drop below SP. FSL
Compressor dierential P
T Time for surge to develop position
(FIC error to drop to zero)
envelope
Ti Integral setting of FIC
15
To users
105%, so that the valve is closed but the signal is just linger- Tuning the Controller The closed loop ultimate oscillation
ing above the 100% mark without saturation. method cannot be used for tuning the surge loop, because
As soon as h starts dropping toward the set point, the there is a danger of this oscillation triggering the start of
valve should start to open, and it should reach full opening surge. The open loop reaction curve technique of tuning is
before the set point is reached. As soon as h starts dropping, used with both the surge and the throughput controller in
the proportional contribution to the FIC output decreases. If manual. The output of each controller is changed by 10%, and
the approach is slow, the increase in the reset contribution will the resulting measurement response is analyzed on a high-
be greater than the decrease caused by the proportional con- speed recorder, yielding the time constant and the dead time
tribution. Therefore, if h does not drop to SP, the valve slowly of the process (Figure 8.15w).
returns to the closed position. The effect of the internal feed- The tuning settings of the surge controller can be tested
back in the FIC is to activate the integral action only when by first increasing the bias (b in Figure 8.15t) until the surge
the valve is not closed, while keeping the proportional action valve opens and then analyzing the loop response. The FIC
operational all the time. must be so tuned that its overshoot is less than the distance
The main goal of a feedback surge controller is to protect between the FSL and FIC set points (A in Figure 8.15t).
the machine from going into surge. Once the compressor is The throughput controller should be kept in automatic while
in surge, the FIC is not likely to be able to bring it out of the surge controller is tested so that interaction problems
it, because the surge oscillations are too fast for the controller will be noted. Once the surge controller is tuned, it should
to keep up with them. This is why backup systems are not be switched to manual but should remain always in
needed. automatic.
The surge controller is usually electronic, and the more The antireset windup feature is not effective on slow
recent installations tend to be microprocessor-based. Such disturbances, because the integral contribution that increases
digital units can memorize complex, nonlinear surge curves the FIC output outweighs the proportional contribution that
and can also provide adaptive gain, which is a means of lowers it; thus, the valve stays closed until the surge line is
increasing controller gain as the operating point approaches crossed. In order for the ARW to be effective, the time for
the surge curve. In digital controllers, it is desirable to set the controller error to drop from its initial value to zero (T)
the sample time at about one quarter of the period of surge must fall within two limits. It must be slower than the stroking
oscillation, or at 0.3 sec, whichever is shorter. If a flow- time of the surge valve (Tv), but it must be faster than two
1
derivative backup control (Figure 8.15v) is used, the sample integral times of the controller:
time must be 0.05 sec or less, because if it is slower, the
backup system would miss the precipitous drop in flow as Tv < T < 2Ti 8.15(5)
surge is beginning.
If the above requirement cannot be satisfiedbecause,
for example, one of the potential disturbances is a slow clos-
ing discharge valvean anticipator control loop should be
To users
added (Figure 8.15z).
ZSC
Compressor
Adjustable
bias (b) and ratio (m) 2 Surge Protection Backup The purpose of the FIC in
P Figure 8.15t was to protect the compressor from going into
PT PY
mP + b
surge. The feedback surge controller is usually not fast
FSL FSLL 2
Vent enough to bring the machine out of surge once it has devel-
Two redundant
valves with oped, because the surge oscillations are too fast for this
features in
S Figure 8.15s controller. Yet even with the best feedback surge controller
L/L d/dt
SP FO
Surge
measurement P linear design, the machine will go into surge.
h
FT FIC PI This can be intentionally initiated to verify the surge
DA
1 ARW curve, it can be caused by errors or shifts in the surge curve
f(x)
FY < as the unit ages, and it can occur because of misoperation or
failure of either the controller or downstream block and check
Vent
valves. For these reasons, a second line of defensea backup
HIC
systemis required in addition to the surge FIC.
FIG. 8.15v
The backup system usually consists of two subsystems,
In this configuration the interlock backup (FSLL) is triggered by identified as interlocks #1 and #2 in Figure 8.15t. In interlock
measuring the rate of flow change (L/L). If this is done by a digital #2, FSLL detects conditions that will cause the complete
control system, the sample time must be 0.05 sec or less. (Adapted stopping of all forward flow from the compressor; when such
from Reference 1.) a condition is detected, FSLL instantaneously and fully opens
Controlled Manipulated
variable (c) variable (m)
control valve
opening
(%)
Slope = Rr = A/B
%
100 100
Dead time (L) =
Point of C
= 2 minutes
80 inection 80
K Reaction rate (Rr) =
60 A = 16% 60 = A = 10%/min
B
L = 2 min B = 1.6 min
M
40 40 Step change (m) =
m = 10% = 10%
20 20 Steady state
Gain (Kp) = K/m =
0 0 = 3.5
0 1 2 3 4 5 6 7 8 9 10
Time, minutes
FIG. 8.15w
An example of open loop tuning where the settings are determined on the basis of the dead time (L) and reaction rate (Rr) of the controlled
process.
the surge valve. One such condition in Figure 8.15t is sig- This type of backup is called the operating point method.
naled by a closed position limit switch (ZSC) on the block Its advantage is that it takes corrective action before the surge
valve. curve (curve ) is reached. Its disadvantages are that it is not
Interlock #1 in Figure 8.15t provides open-loop backup usable on multistage machines or on systems with recycle and
as follows: The FSL detects an approach to surge that is closer that the protection it provides is lost if PY in Figure 8.15t
than the FIC set point; when it detects such a condition, it fails by dropping its output to zero. For this reason, it is
takes corrective action. Under normal conditions, FSL senses desirable to provide a minimum limit on the output of PY.
an h value that is higher than SP, meaning that the operating The manual loader input (HIC) to the low-signal selector
point is to the right of curve . As surge approaches, the is used during start-up. Because its output passes through the
operating point crosses the control line (curve 4) as h drops low selector, it can increase but cannot decrease the valve
below SP. The FSL is set to actuate interlock #1 when h has opening.
crossed curve . This occurs when the flow has dropped
below the FIC set point by the amount A (usually 5%).
When interlock #1 is actuated, it triggers the signal gen- Flow-Derivative Backup The difference between the oper-
erator FY to drop its output signal to zero and then, when ating point technique of backup (Figure 8.15t) and the flow-
the operating point has returned to the right of curve , derivative method (Figure 8.15v) is that the first method acts
gradually increase it back to 100%. When the FY output before the surge curve is reached, whereas the second is
drops to zero, the low signal selector (in the output of the activated by the beginning of surge. Because flow drops off
FIC) will select it and send it to the valve. This causes the very quickly at the beginning of surge, the instruments that
surge valve to open fully in less than a second, followed by measure the rate of this drop must be very fast.
a slow closure according to the program in the signal gener- If implemented digitally, the sample time of the flow
ator FY. As the FY output rises, it will reach the output of derivative loop must be 0.05 sec or less in order not to miss
the FIC, at which point control is returned from the backup the initial drop in flow. The lead-lag station (L/L) that detects
system to the feedback controller. the rate of flow reduction is adjusted so that the lag setting
will filter out noise and the lead setting will give a large The purpose of the output backup section is to recognize
output when the flow drops. the approach of a surge condition that the feedback controller
The function of interlock #1 is the same as was described (FIC) was unable to arrest and to correct such a condition
in connection with Figure 8.15t. When FSL detects the drop when it occurs. As long as the surge measurement (h) is not
in flow, it causes the signal generator (FY) output to drop to below the set point (SP), no corrective action is needed, and
zero, fully opening the valve within a second. If this action therefore blocks and will set the FIC output modifier
succeeds in arresting the surge, the signal generator output signal (A) to zero. Once h is below SP, the operating point
slowly rises and control is returned to the feedback FIC. is to the left of curve in Figure 8.15t, and the output of
If interlock #1 does not succeed in bringing the machine block in Figure 8.15x is switched to Yes.
out of surge, then after a preset number of oscillations FSLL Next, block checks if the adjustable time delay D1
1
is actuated. This triggers interlock #2, which keeps the surge having typical values of 0.3 to 0.8 sec has passed. If it has
valve fully open until surge oscillations stop. not, signal A remains at its last value. If D1 has passed, A is
The flow derivation method of backup has the advantage increased by an increment X. Typical values of the X incre-
1
of providing protection even if the compressor pressure-rise ment range from 15 to 30%. As A is subtracted from the FIC
instruments (PT, PY) fail, but it also has the disadvantage output signal, this backup loop will open up the surge valve
of not being usable when the flow signal is noisy. at a speed of 1530% per 0.30.8 sec. When h is restored to
above set point, the signal A is slowly returned to zero,
allowing the surge valve to reclose.
Optimized Adaptations of Surge Curve The surge curve shifts The purpose of the set point adaptation loop (blocks
with wear and with operating conditions. Figure 8.15x describes to ) is to recognize shifts in the surge curve and, as a
a surge control loop that recognizes such shifts and automat- response, to move the control line in Figure 8.15t to the
ically adapts to the new curve. The adaptation subroutine right by increasing to total bias b of the ratio relay PY. The
consists of two segments, the set point adaptation section logic of blocks to is similar to that described for blocks
(blocks to ) and the output backup section (blocks to 11 , except that the resulting variable bias signal (b1) is
to 11 ).
added to the fixed bias (b0) to arrive at the adapted new
bias (b). The speed of set point adaptation does not need to
be as fast as the opening of the surge valve. Therefore, the
time delay D2 tends to be longer than D1, and the increment
Users
Y is smaller than X. The purpose of the reset button in block
Compressor P
d is to provide a means for the operator to reset the b1 signal
Scaler back to zero.
P
PT
Pi Fixed bias
b1
+ b0
Bias b Adjustable ratio (m) Override Controls
PY and automatically
Reset 1 +
adapted bias (b) Figures 8.15t and 8.15v show backup and overrides imple-
mented by a low-signal selector on the outlet of the feedback
Increase 2 Leave 3 Leave 4
output output output FIC. Figure 8.15y shows some additional overrides that might
by at last at last m (P) + b
Y% value value
Yes No No
Has 5 6 SP 7 Has 8 User #1
delay Yes h < SP h < SP Yes delay Yes
D2 ? SP ? D1
passed? h h passed? Compressor PT FT
01 External
No No Ratio R/A feedback
Set 9 Leave 10 Increase 11 P PIC
User #N
output output output PT PY
01
at at last by f (x) FT
zero value x%
FSL 1 FY Bias (b)
SP +
Output h +
Surge modier FT FIC < +
SP 02 02 FO
measurement (h) + signal (A) DA
FT FIC FO
HIC SP Vent LAG
FIC FY
Vent h 03 03
D/A
Ratio
P Optimized Load-Following
PT PY
Rate of drop
When a compressor is supplying gas to several parallel users,
External
limiter
feedback
the goal of optimization is to satisfy all users with the min-
VY x PIC imum investment of energy. The minimum required header
>
03 01
pressure is found by the valve position controller (VPC) in
h Figure 8.15aa. It compares the highest user valve opening
SP
h (that identifies the needs of the most demanding user) with
FT FIC < FO
a set point of 90%, and if even the most open valve is not
DA
yet 90% open, it lowers the header pressure set point.
HIC
f(x) This supply-demand matching strategy not only mini-
Vent
FSL 1 FY mizes the use of compressor power but also protects the users
from being undersupplied, because it protects any and all
FIG. 8.15z supply valves from the need to open fully. On the other hand,
The velocity limiter serves to protect against sudden load changes as the VPC causes the user valves to open farther, these valves
by temporarily opening the surge vent valve when the load is quickly not only reduce their pressure drops but also become more
7
dropping. This is achieved by providing VY-03, which, in case of a stable.
sudden drop in h, does not immediately lower x and therefore it (x) The VPC is an integral-only controller, with its integral
is selected by the high selector as the set point. time set for about 10 times that of the PIC. This guarantees
FIG. 8.15bb SP
Protective overrides can be added to optimized load-following con- h FIC
FT FO
trols, so that the system is protected against excessively low pres- 02
DA
Surge
sures on the suction side of the compressor or from overloading the controller Vent
compressors motor drive.
FIG. 8.15cc
The load controller (PIC-01) and surge controller (FIC-02) both
that the VPC will act more slowly than all the user controllers, affect the compressor throughput.
thus giving stable control even if the user valves are unstable.
The external feedback (FB in Figure 8.15aa) protects the VPC
from reset windup when its output is limited or when the PIC (as in Figure 8.15dd), the action of PIC-01 will bring the
has been switched to manual. operating point closer to the surge line. In this case, a conflict
In addition to following the load, it is also necessary to exists between the two loops, because as FIC-02 acts to
protect the equipment. In Figure 8.15bb, one protective over- correct an approaching surge situation, PIC-01 responds by
ride prevents the development of excessively low suction worsening it. The better tuned (narrower proportional band)
pressures (PIC-02), which could result in drawing oil into and faster (electronic or hydraulic speed governors) the PIC-01
the compressor. The other override (KWIC-03) protects from
overloading the drive motor and thereby tripping the circuit
breaker. Vector 1
In order to prevent reset windup when the controller Eect of PIC increasing the
output is blocked from affecting the SIC set point, external vane setting (or speed) in response Surge control line
feedback (EFB) is provided for all three controllers. This to surge valve opening set by FIC02
arrangement is typical for all selective or selective-cascade
PIC01 setpoint
control systems. v e A
ur
ec Vector 2
urg Eect of opening
Pressure rise (PSI)
c
Under abnormal conditions, when point A in ad
Lo
ne set
loop is, the more dangerous is its effect of worsening the loop gain of PIC-01 is 0.5 when FIC-02 is in manual and
approach of surge. the switching of FIC-02 into automatic causes the PIC-01
The throughput controller (PIC-01 in Figure 8.15cc) loop gain to drop to 0.25, the relative gain is 0.5/0.25 = 2.
moves the operating point on the path of the load curve. The Table 8.15ff lists the correct interpretations of the relative
surge controller (FIC-02 in Figure 8.15cc) moves the oper- gain (RG) values.
ating point on the path of the characteristic curve of the If the calculated relative gain values are put in a 2-by-2
compressor at constant speed. If the characteristic curve is matrix, the best pairing of controlled and manipulated vari-
steep, the action of the surge controller will cause a substan- ables is selected by choosing those that will give the least
tial upset in the discharge pressure controlled by PIC-01 amount of conflict. These are the RG values between 0.75
(Figure 8.15cc). If the load curve is flat, the effect of the and 1.5, preferably close to 1.0. The regions of inhibition,
pressure controller on the surge controller will be the greatest. reinforcement, and reversal are shown in Figure 8.15gg.
If the throughput is under flow control, the opposite
effects will be observed. The effect of the surge controller
Decoupling Decoupling is the means of reducing the inter-
on the flow controller will be the greatest when the charac-
action between the surge and the load control loops. If the
teristic curves of the compressor are flat, and the effect of
goal of decoupling is to maintain good pressure control even
the flow controller on the surge controller will be greatest
during a surge episode, the system shown in Figure 8.15hh
when the load curve is steep.
can be used. In this system, as the antisurge controller opens
As shown in Table 8.15ee, whether the loops will assist
the vent valve, a feedforward signal (X) simultaneously
or conflict with each other, both the relative slopes of the
increases the speed of the compressor in proportion. The
load and surge curves and the variable selected for process
negative sign at the summing device is necessary because the
control need to be considered.
surge valve fails to open. If the two vectors shown in
As both loops try to position the operating point on the
Figure 8.15dd are correctly weighed in the summer, the end
compressor map, the resulting interaction can cause the type
of inverse response that was described in Figure 8.15dd, or
it can cause oscillation and noise. The oscillating interaction
is worst if the proportional bands and time constants or peri- Loop becomes Loop becomes
unstable if other sluggish when other Loop becomes If tuned with
ods of oscillation are similar for the two loops. Therefore, if loops are switched loops are switched unstable when other other loops in
to manual; to manual; loops are switched to manual; automatic;
tight control is of no serious importance, one method of
Unstable when other Sluggish when other If tuned with
Closing other loops
reducing interactions is to reduce the response (widen the reverses gain.
loops are switched to loops are switched to other loops in
automatic automatic manual
proportional band) of the load controller. Similarly, the use
No interaction
of slower actuators (such as pneumatic ones) to control com- No direct action,
all eects through other loops
pressor throughput will also reduce interaction, but at the cost
of less responsive overall load control.
Pressure PC FC Antisurge eliminates this bias, because when its time constant has been
controller controller reached, the values of X and Y will be equal and will cancel
each other. Therefore, this decoupler will serve to temporarily
+ desensitize a fast and tightly turned PIC-01 loop, which oth-
x
erwise might worsen the situation by overreacting to a drop
Decoupler
in pressure when the vent valve opens.
FCV SP
FT M SIC PIC PT
ST
Compressor
A Discharge Compressor
FT #1
h1
PV
FC
SP SP
h2 = h1 (K2/K1)
Suction FIC
+ where K1 and K2 are the slopes
of the surge curves.
SP SP
h2
SIC M
FC
PV
ST
FT
FT
FCV
FIG. 8.15ll
FIG. 8.15kk
Two parallel compressors can be so loaded as to keep both of them
When operating multiple compressors in parallel, the total flow
at equal distance from their surge curves. (Adapted from Reference 1.)
(load) can be so distributed among the machines that one is fully
loaded and the other handles the variations in demand.
PIC
to be started, interlock #1 switches item #15 (or #16) to the
01 start position, causing the integrator #6 (or #14) to drive up
To time 1
+ 2 + 5 (by applying supply voltage to the integrator) until PIC-01
delayed PSH
1 > takes over control through the low selector #3 (or #11). The
shut-down 04
logic +
SIC HIC
3 4
+ integrator output will continue to rise and then will stay at
<
01 SP 01
7 +
maximum, so as not to interfere with the operation of the
1 < control loop.
Start + 6 The ratio flow controllers (FFIC-01 and -02) are protected
M
15 from reset windup by receiving an external feedback signal
Stop
through the low selector #7 (or #12), which selects the lower
Compressor
FT #1
of the FFIC output and the ramp signal.
Discharge header
01
FB Interlock #1 is also provided with rotating sequencer
Suction header
FO FFIC
01
logic, which serves to equalize run times between machines
+ 9 SP and protects the same machine from being started and
Total load
Surge stopped frequently. A simple approximation of these goals is
SP
controls +
#1 FFIC achieved if the machine that operated the longest is stopped
Start + 14 02
To time FB and the one that was idle the longest is started.
delayed 16 Stop 12
shut-down
If only one of the compressors is variable-speed, the PIC-
<
logic
1 01 output signal can be used in a split-range manner. For
11 + 13
1 SIC SP HIC + example, if there were five compressors of equal capacity,
<
8 02 02
FSL
switches would be set to start an additional constant-speed
<
03 unit as the output signal rises above 20, 40, 60, and 80% of
Surge M its full range. The speed setting of the one variable-speed
controls FT
#2 02 compressor is obtained by subtracting from the PIC output
Compressor the sum of the flows developed by the constant-speed
#2
machines and multiplying the remainder by 5. The gain of 5
is the result of the capacity ratio between that of the individ-
FO
ual compressor and the total.
FIG. 8.15mm
A flow-balancing bias can be superimposed on direct pressure con- Multi-Inlet Compressor Control
trol. This control system can distribute the load between the two
machines in the order of their efficiencies. (Adapted from These compressors most often are refrigeration compressors.
Reference 3.) The main problem here is to keep the process temperatures,
which are controlled by the evaporators, within tolerable
limits. This is achieved by controlling the vapor temperature
in Figure 8.15mm. Here a high-speed integrator (item #5) is (by quenching) in a feedforward manner, based upon the
used on the summed speed signals to ensure a correspondence amount of recycle flow or recycle valve position. A typical
between the PIC output signal and the number of compressors control scheme to control a three-inlet compressor is shown
(and their loading) used. The integrator responds in a fraction in Figure 8.15nn.
of a second and therefore does not degrade the speed of
response of the PIC loop. Installation
Figure 8.15mm also illustrates the automatic starting and
stopping of individual compressors as the load varies. When A check valve in the discharge line as close to the compressor
the total flow can be handled by a single compressor or when as possible will protect it from surges. On motor-driven com-
any of the surge valves open, FSL-03 triggers the shutdown pressors, it is helpful to close the suction valve during starting
logic interlock circuit #1 after a time delay. to prevent overload of the motor. After the unit is operating,
Operation with an open surge valve would be highly it should be brought to stable operating range as soon as
inefficient, because the recirculated gas is redistributed possible to prevent overheating.
among all the operating units. When a compressor is to be The recycle valve control should be fast opening and slow
stopped, item #15 (or #16) is switched to the stop position, closing to come out of surge quickly and then stabilize the
causing the integrator #6 (or #14) to drive down until it flow. The transmitter ranges should be such that the recycle
overrides the control signal in low selector #3 (or #11) and valve is able to open in a reasonable amount of time with
reduces the speed until the unit is stopped. reasonable proportional and integral control constants of the
Automatic starting of an additional compressor is also antisurge controller. The importance of proper controller tun-
initiated by interlock #1 when PSH-04 signals that one of the ing cannot be underestimated. Typical settings are PB = 50%,
compressors has reached full speed. When a compressor is I = 13 sec/repeat.
PT PIC
After
cooler
Motor Compressor
Recycle line
FCV FCV
FT TT PT TT PT PIC
PIC
PT
Suction scrubber
Suction scrubber
Suction Suction Suction
PCV PCV PCV
Quench line
FIG. 8.15nn
Control strategy for a multiple inlet compressor.
Lube and Seal Systems A typical lube oil system is shown in Panel alarms on low oil level, low oil pressure (or flow), and
Figure 8.15oo. Dual pumps are provided to ensure the unin- high oil temperature are provided. A head tank provides oil
terrupted flow of oil to the compressor bearings and seals. for coasting down in case of a power failure.
The design of these systems is critical, because failure
of the oil supply could mean a shutdown of the entire process.
In cases in which the process gas cannot be allowed to contact
Head TAH
tank TSH the oil, an inert gas seal system may be used. This is shown
FAL PI
in Figure 8.15pp for a centrifugal compressor with balanced
seals.
Filters FSL
TJR
Coolers PCV
Compressor
PI
PSL LAL
M M PDCV
PAL
LG LSL Seal
Oil FI
gas
sump
TI
TC
Dryer
14 outlet
(96.6) temperature
PIC TRC
12 Vent
Discharge pressure, PSIG (kPa)
(82.8)
10 Curve II
(69.0)
To dryer
(1,550 rpm) Silencer
8
(55.2) (2) M
6 Curve I Rotary
(41.4) (1,420 rpm) blower
4
(27.6) (1) FIG. 8.15rr
The blower discharge pressure can be controlled by venting the
2
(13.8) excess gas that is not required by the process.
0 10 20 30 40 50 60 70 80
(0.005)(0.009)(0.014)(0.019)(0.024)(0.028)(0.030)(0.038)
Inlet ow ACFM (m3/s)
into the suction on pressure control. This is shown in
FIG. 8.15qq Figure 8.15ss, where suction pressure control is used on a
The rotary compressor is a positive displacement machine. At con- rotary filter, maintaining the proper drainage of liquor from
stant inlet flow, the discharge pressure rises if the speed is increased, the cake on the drum.
while at constant speed, the flow drops as the discharge pressure
The optimization of rotary compressors will be discussed
rises.
later, together with that of reciprocating compressors.
The rotary compressor is essentially a constant-displacement, The reciprocating compressor is a constant-volume, variable-
variable-discharge pressure machine. Common designs discharge pressure machine. A typical compressor curve is
include the helical-screw, the lobe, the sliding vane, and the shown in Figure 8.15tt, for constant-speed operation. The
liquid ring types. The characteristic curves for a lobe-type curve shows no variation in volumetric efficiency in the
unit are shown in Figure 8.15qq. As shown by curves I and design pressure range, which may vary by 8 PSIG (53.6 kPa)
II, the inlet flow varies linearly with the speed of this positive- from unloaded to fully loaded.
displacement machine. The volumetric inefficiency is a result of the clearance
The small decrease in capacity at constant speed with an between piston end and cylinder end on the discharge stroke.
increase in pressure is a result of gas slippage through impel- The gas that is not discharged reexpands on the suction
ler clearances. It is necessary to compensate for this by stroke, thus reducing the intake volume.
small speed adjustments as the discharge pressure varies. For The relationship of speed to capacity is a direct ratio,
example, when the compressor is operating at point 1, it because the compressor is a displacement-type machine. The
3
delivers the design volume of 66 ACFM (1.9 m /m) and 3.5
PSIG (24 kPa). In order for the same flow to be maintained
when the discharge pressure is 7 PSIG (48 kPa), the speed
must be increased from 1420 rpm to 1500 rpm at point 2 by Bleed
the flow controller in the discharge line. Suction pressure
In addition to speed variation, the discharge flow can also control valve PIC
be adjusted by throttling the suction, the bypass, or the vent Slurry Vent
line from the rotary blower. Vent throttling of the excess gas knock Separator
Vacuum
is shown in Figure 8.15rr in a process where the discharge line
out
[~] pot
is throttled by a temperature controller. This can be a dryer
M
application, where the temperature of the outlet gas is con- Liquid Liquid
trolled to prevent product degradation and to provide the ring waste
Rotary compressor
proper product dryness. In other systems, instead of venting,
drum lter Seal
the gas is returned to the suction of the blower under pressure Washed
solids liquid
control.
An important application of the liquid ring rotary com- FIG. 8.15ss
pressor is in vacuum service. The suction pressure is often The suction pressure control of a liquid ring-type rotary compressor
the independent variable and is controlled by bleeding gas is illustrated here.
typical normal turndown with gasoline or diesel engine driv- FIG. 8.15vv
ers is 50% of maximum speed, in order to maintain the torque The five steps in a constant-speed, positive displacement compressor
within acceptable limits. with five-step unloading.
On/Off Control
In three-step unloading, capacity increments are 100, 50,
For intermittent demand, where the compressor would waste or 0% of maximum flow. This method of unloading is accom-
power if run continuously, the capacity can be controlled by plished by the use of valve unloading in the double-acting
starting and stopping the motor. This can be done manually piston. At 100%, both suction valves are closed during the
or by the use of pressure switches. Typical switch settings discharge stroke. At 50%, one suction valve is open on the
are on at 140 PSIG (1 MPa), off at 175 PSIG (1.2 MPa). This discharge stroke, wasting half the capacity of the machine.
type of control would suffice for processes in which the At 0%, both suction valves are held open on the discharge
continuous usage is less than 50% of capacity, as shown in stroke, wasting total machine capacity.
Figure 8.15uu, where an air mix blender uses a rapid series
For five-step unloading, a clearance pocket is used in
of high-pressure air blasts when the mixer becomes full. The
addition to suction valve control. The capacity can be 100,
high-pressure air for this purpose is stored in the receiver.
75, 50, 25, or 0% of maximum flow. This is shown in
Figure 8.15vv. At 100%, both suction valves and the clear-
Constant-Speed Unloading ance pocket are closed. At 75%, only the clearance pocket is
open. At 50%, only one suction valve is open on the discharge
In this type of control, the driver operates continuously, at
stroke. At 25%, one suction valve and the clearance pocket
constant speed, and one varies the capacity in discrete steps
are open. At 0%, both suction valves are opened during the
by holding suction valves open on the discharge stroke or
discharge stroke.
opening clearance pockets in the cylinder. The most common
The use of step unloading is most common when the
schemes are three- and five-step unloading techniques. The
larger number of steps saves horsepower because it more driver is inherently a constant-speed machine (Figure 8.15ww),
closely matches the compressor output to the demand.
To
Aftercooler
blender M
Air
M Reciprocating Unloader receiver
Compressor compressor
Air
receiver
FIG. 8.15ww
FIG. 8.15uu Constant-speed capacity control of a reciprocating compressor, pro-
On/off control of a reciprocating compressor. vided with pneumatic unloading.
this will energize the time delay (TR) and will open the water Load- M1 TR
Run 6
Unload
solenoid valve (WSV) if neither the air temperature (ATSH) APSL TR M
2 7
nor the cooling water temperature (WTSH) is high. 7" on delay USV
After 7 sec, TR-1 opens. Assuming that this time delay TR Control
8
was sufficient for the oil pressure to build up, the opening of Annunc.
9
TR-1 will have no effect, because OPSL will have closed in
the meantime. FIG. 8.15yy
If the opening of WSV resulted in a cooling water flow The local/remote switch is wired to allow stand-alone or integrated
greater than the minimum setting of the low water flow compressor operation.
2
10 13 1R1
Compressor #1 Wire #10 to #19
Compressor #2 Wire #20 to #29 1R1-2 ATA-1
R1
Compressor #3 Wire #30 to #39, and so on
Wires #1
17 from 14 1R2 reset
In this system, the first digit of the wire number indicates compressor
1R2-2 WTA-1
the compressor, and the second digit describes the function #1
of the wire. Immediately knowing, for example, that wire R1-1
number 45 comes from compressor #4 and serves to signal 19 15 1R3
a low water flow condition on that machine simplifies check- 1R3-2 WFA-1 #1
out and start-up. run
TABLE 8.15ccc
System Performance when ASPL-A Is Set to Close at 90 psig, APSL-B Is
Set to Close at 85 psig, and the Differential Gap Is Set at 10 psid
Pressure in
Air Receiver APSL-A APSL-B Lead
(psig) Contact Contact Compressor Lag Compressor
Ho No O #1
Wires to 2-position Wires to Compressor
switch with selector
compressor compressor #1 10
A 4 sets of B #2 12
A on contacts
B on #3 16
standby 30 17
standby A0 18
A0 Lead A B0 10
10
A7 B7
B 20
Lead B loaded B0
APSL-A 30
4TR-2 20
FIG. 8.15eee
addition of a three-position off selector switch, illustrated The wiring of an off selector switch that can be used to identify
in Figure 8.15eee. With the addition of the off-selector, any the common spare compressor, or the compressor that is undergoing
2
of the compressors can be selected for load, lag, or off duties, maintenance from among a set of three compressors.
just by turning these conveniently located switches.
Depending on the position of the off selector, the iden- Ten (10) incoming wires from
tities of Compressors A and B in Figure 8.15ddd will be as each compressor
follows: Compressor status
#1 #2 #3
Compressor running
Selected Compressor Compressor
High air temperature
Off A B
Silence
For an integrated three-compressor system, only 30 wires 2 Lead and o
A B1 3
need to be run if the remote annunciator is included. Without selector
remote alarms, only 15 wires are needed (5 per compressor). Lead O
Compressor on standby
The front face of a remote control cabinet of a three-compressor Loading
status
lead-lag system is illustrated in Figure 8.15fff. Compressor is loaded
Large Systems From the building blocks discussed in the FIG. 8.15fff
previous paragraphs, an integrated remote controller can be The faceplate of the control panel that can be used to operate an
2
configured for every compressor combination. Figure 8.15ggg integrated three-compressor system.
Compressor nine compressors and can also select the order in which they
APSL-F
F
are to come on.
FIG. 8.15ggg Wired or Digital Bus From the previous discussion it can be
In large, multiple-compressor systems, a priority selector can be seen that the building-block approach to compressor control
used to change the order of priorities of the compressors within the system design is very flexible. Any number of stand-alone
2
system. compressors can be integrated into automatic load-following
control systems, with complete flexibility for priority, lead-lag,
or off selection. The logic blocks described can be imple-
illustrates how six stand-alone compressors might be inte- mented either in hardware or in software. All wires and termi-
grated into a single load-following system. nals can be prenumbered to minimize installation errors.
As the system pressure drops below 90 psig, APSL-A The potential benefits of compressor control system inte-
closes, starting the first compressor. As the load rises, causing gration are listed below:
the system pressure to drop further, more switches will close,
until at 80 PSIG all six switches will be closed and all six
1. Unattended, automatic operation relieves operators for
compressors will be running.
other tasks.
The priority selector shown in Figure 8.15ggg is pro-
2. Automatic load-following eliminates the possibility of
vided for the convenient reconfiguration of compressor
accidents caused by the loss of the air supply.
sequencing. When the selector is in position #1, as the load
increases, the compressors will be started in the A, B, C, D, 3. Because the supply and the demand are continuously
E, F order. When switched to position #2, the sequence and automatically matched, the energy cost of opera-
becomes C, D, E, F, A, B. In position #3, the sequence is E, tion is minimized.
F, A, B, C, D.
If a system consists of nine compressors, and full flexi- If priority or lead-lag switching is under computer con-
bility in integrated remote control is desired, the faceplate of trol, this would also make the digital implementation of the
a control cabinet might look like Figure 8.15hhh. With this system more desirable. On the other hand, if a dedicated,
system, the operator can set the lead, lag, or off status for all hard-wired system is preferred, because it is more familiar
Microprocessor
Recycle
FCV valve
FIG. 8.15iii
A digital unit controller that is connected to the compressor I/O by a digital bus is well suited for both compressor optimization and for
integrating the compressor controls into the total control system of the plant.
to the average operator, hardware implementation can be the 5. Baumeister, T. (ed.), Marks Standard Handbook for Mechanical Engi-
proper choice. neers, 8th edition, New York: McGraw-Hill, 1978, pp. 1453.
6. Waggoner, R. C., Process Control for Compressors, paper given at
Houston Conference of ISA, October 1114, 1976.
7. Baker, D. F., Surge Control for Multistage Centrifugal Compressors,
CONCLUSIONS Chemical Engineering, May 31, 1982, pp. 117122.
Buzzard, W. S., Controlling Centrifugal Compressors, Instrumentation Hiller, C. C., and Glicksman, L. R., Improving Heat Pump Performance via
Technology, November 1973. Compressor Capacity ControlAnalysis and Test, Vol. 1, Massachu-
Byers, R. H., Snider, M., and Brownstein, B., Simulator to Test Compressor setts, January 1976.
Research Facility Control System Software, Military Electronics Kolnsberg, A., Reasons for Centrifugal Compressor Surging and Surge
Defense Expo 80, Geneva, Switzerland: Interavia, 1980, pp. 140153. Control, Journal of Engineering for Power, ASME, January 1979,
Carrier Corp., Air Conditioning News, Syracuse, NY: Carrier Corp., May pp. 7986.
12, 1980, pp. 3, 12. Langill, A. W., Jr., Microprocessor-Based Control of Large Constant-Speed
Centrifugal Compressors, Bulletin 8282-C, Woodcliff Lake, NJ: Ingersoll- Centrifugal Compressors, Advances in Test Measurement, Vol. 19,
Rand Co., 1972. Research Triangle Park, NC: ISA, 1982.
Cheremisinoff, N. P., Compressors and Fans, Prentice Hall, 1992. Liptk, B. G., Compressor Control, Control Magazine, June 1999.
Compressibility Charts and their Application to Problems Involving Pres- Moellenkamp, G., Scott, J., and Farmer, F., Compressor Station Minicom-
sure-Volume-Energy Relations for Real Gases, Bulletin P-7637, puter System for Control, Monitoring, and Telemetry, 13th World Gas
Mountainside, NJ: Worthington-CEI Inc., 1949. Conference, Paper IGU/C, London, England: International Gas Union,
Compressor Handbook for the Hydrocarbon Processing Industries, Hous- 1976.
ton, TX: Gulf Publishing Co., 1979. Neerken, R. F., Compressors in Chemical Process Industries, Chemical
Cooke, L. A., Saving Fuel at Pipeline Compressor Station, Instrumentation Engineering, January 20, 1975.
Technology, November 1977. Nisenfeld, A. E., and Cho, C. H., Parallel Compressor Control, Australian
Davis, A., Keegan, P. J., and Peltzman, E., Variable Capacity Compressor Journal of Instrumentation and Control, December 1977, pp. 108112.
Controller, Report No. DOE/CS/35224-T1, U.S. Dept. of Energy, Nisenfeld, A. E., and Cho, C. H., Parallel Compressor Control: What Should
1979. be Considered, Hydrocarbon Processing, February 1978,
Dussourd, J. L., Pfannebecker, G., Singhania, S. K., and Tramm, P. C., pp. 147150.
Considerations for the Control of Surge in Dynamic Compressors Rammler, R., Advanced Centrifugal Compressor Control, ISA/93 Techni-
Using Close Coupled Resistances, in Centrifugal Compressors and cal Conference, Chicago, September 1924, 1993.
Pump Stability, Stall, and Surge, 1976, pp. 128.
Rammler, R., Energy Savings through Advanced Centrifugal Compressor
Dwyer, J. J., Compressor Problems: Causes and Cures, Hydrocarbon
Performance Control, Advances in Instrumentation, Vol. 37, 1982.
Processing, January 1973.
Rammler, R., and Langill, A. W., Jr., Centrifugal Compressor Performance
Elliott Multistage Compressors, Bulletin P-25, Jeannette, PA: Elliott Divi-
Control, Joint Automatic Control Conference, AIChE, 1979,
sion, Carrier Corp., 1973.
pp. 261265.
Engineering Data Book, 9th ed., Tulsa, OK: Natural Gas Processors Sup-
Roberts, W. B., and Rogers, W., Turbine Engine Fuel Conservation by Fan
pliers Association, 1972.
and Compressor Profile Control, Symposium on Commercial Aviation
Fallin, H. K., and Belas, J. J., Controls for an Axial Turboblower, Instru-
Energy Conservation Strategies, National Technical Information Ser-
mentation Technology, May 1968.
vice Document PC A16/MF A01, April 2, 1981, pp. 231256.
Fehervari, W., Asymmetric Algorithm Tightens Compressors Surge Con-
Rutshtein, A., and Staroselsky, N., Some Considerations on Improving the
trol, Control Engineering, October 1977.
Control Strategy for Dynamic Compressors, ISA Transactions,
Filippini, V., Surge Condition and Antisurge Control of a Centrifugal Com-
Vol. 16, 1977, pp. 319.
pressor, Quaderni Pignone, No. 5.
Shinskey, F. G., Process Control, Application, Design, and Tuning, 4th ed.,
Gas Properties and Compressor Data, Form 3519-C, Woodcliff Lake, NJ:
New York: McGraw-Hill Professionals, 1996.
Ingersoll-Rand Co., 1967.
Gravdahl, J. T., et.al., Compressor Surge and Stall, Springer Verlag, May Shinskey, F. G., Interaction between Control Loops, Part II: Negative Cou-
1999. pling, Instruments and Control Systems, June 1976.
Gaston, J. R., Centrifugal Compressor Control, Research Triangle Park, Smith, G., Compressor Surge Control Achieved Using Unique Flow Sen-
NC: ISA Chemical and Petroleum Instrumentation Symposium Pro- sor, Pipeline Gas Journal, December 1978, pp. 42, 4647.
ceedings, 1974. Staroselsky, N., Better Efficiency and Reliability for Dynamic Compressors
Gaston, J. R., Improved Flow/Delta-P Antisurge Control System, Com- Operating in Parallel or in Series, Paper 80-PET-42, New York:
pressor-Engine Workshop, Pacific Energy Association, March 1981, ASME, 1980.
pp. 113. Staroselsky, N., and Ladin, L., Improved Surge Control for Centrifugal
Gupta, B. P., and Jeffrey, M. F., Compressor Controls Made Easy with Compressors,Chemical Engineering, May 21, 1979, pp. 17584.
Microprocessors, Instrument Maintenance and Management, Vol. 13, Van Ormer, H. P., Jr., Air Compressor Capacity Controls: A Necessary Evil,
1979, pp. 6367. Vol. 1. Reciprocating Compressors, Hydraulics and Pneumatics, June
Gupta, B. P., and Jeffrey, M. F., Optimize Centrifugal Compressor Perfor- 1980, pp. 6770.
mance, Hydrocarbon Processing, Computer Optimization, June 1979. Waggoner, R. C., Process Control for Compressors, Advances in Instru-
Hallock, D. C., Centrifugal CompressorsThe Cause of the Curve, Air mentation, Vol. 31, 1976.
and Gas Engineering, January 1969. Warnock, J. D., Are Your Compressors Wasting Energy? Instruments and
Hansen, K. E., et al., Experimental and Theoretical Study of Surge in a Control Systems, March 1977, pp. 4145.
Small Centrifugal Compressor, Journal of Fluids Engineering, Sep- Warnock, J. D., Typical Compressor Control Configurations, Advances in
tember 1981, pp. 391395. Instrumentation, Vol. 31, 1976.
Hassenfuss, F., Compressor Controls Coordinated for Carbon Dioxide White, M. H., Surge Control for Centrifugal Compressor, Chemical Engi-
Line, Oil and Gas Journal, July 31, 1972, pp. 9195. neering, December 25, 1972.