Fire safety in the engine room

Most fires on board ships start in the engine room. This article highlights the main aspects
associated with fire safety of engine rooms, based on observations made during condition
surveys of vessels entered with Gard.
Any fire on board a vessel is a very serious situation. Unless the fire can be quickly put out, there
is a risk of it spreading and gaining momentum to very fast becoming a frightening threat to the
vessel and the lives of those on board. When a fire situation occurs at sea, there is no fire brigade
to call, it is the crew on board who will have the task of fighting the fire, for their own survival
and to save the vessel and its cargo. It is therefore important that officers and crew are prepared
for a fire situation, that they know the means provided for fire-fighting and are able to act with
speed and decision. There are a number of built-in safety features on board a vessel, designed to
limit the risk of fire and the spread of it, and the officers and crew must have full knowledge of
these and maintain their integrity.
Steel separations
One of the reasons for the engine room casing and various decks, bulkheads and staircases being
made of steel is to limit a spread of fire. If there is a fire in the engine room, it is important that
the fire may not readily spread to accommodation, bridge, lifeboat stations and cargo areas.
Likewise, a fire in the cargo areas should not be able to gain access to the engine room, which is
"the heart of the ship", where generators and fire pumps, the means to fight a fire, are located.
Therefore, get to know the built-in fire boundaries and maintain the integrity of such separations.
Be careful when making alterations on board, and be especially aware that when new cables and
pipelines are installed, their passage through steel decks and bulkheads must be made in a fire-
proof way.
Air control
The good working condition of air ventilation fire flaps and the emergency stop of fans is
essential, but so is the crew's full knowledge of other openings to the engine room that may need
to be closed in a fire situation.
During condition surveys Gard Services has repeatedly seen air ventilator fire flaps which can
not be closed and/or secured in closed position. Solidity of fire flaps should be checked and they
should be moved regularly and maintained with grease not to freeze. There should also be means
to secure the flap handles in closed position and the open and closed position should be clearly
marked. If fire flaps can not be secured, the draft of a fire is likely to throw them open.
One should also be aware of all other ways
of air inlets to the engine room, such as
various entrance doors, emergency exits and
skylights. Doors leading to the engine room
from the accommodation are fitted with
devices for automatic closing. It is
important that these are working, and that
doors and doorframes are not damaged,
allowing passage of an air draft. Doorsills
and coamings may be damaged by the
moving of machinery parts to deck through
doors in the engine room, causing
obstructions for the full closing of the door.
Doors should be tested by releasing them
from the open position, to see if they close
fully by the automatic device, and there
The CO should not be used for
should then be no openings between the
2

storage of flammable products


door and the coaming.
and other gear. Access to the
CO room should be limited to
2
Emergency escapes from engine rooms may
authorised personnel, to avoid be arranged by shafts leading to deck and
accidental release. with access doors at various levels. The full
closing of the doors should not be
obstructed by the stretching of loose electric
cables, hoses, etc., and also these doors
should close tightly by their own automatic
means. It must be remembered that such a
shaft, if not kept closed, will provide a draft
from the engine room.
The engine room is a warm place to work, and the sweating crew may often arrange entrance
doors to be kept open by the fitting of hooks, ropes, wedges, etc., to get an additional draft of air.
This is often seen especially on doors leading through the steering gear flat to the poopdeck. In
the case of a fire, such doors may be inaccessible, and the hooks, etc., can not be released to
close the door. Air to the engine room can then not be closed off. Likewise, Gard surveyors often
see skylights at the top of the engine room and removable steel panels for the passing of spare
parts being kept open by steel wire slings, etc. In a fire situation one may not remember that such
items are kept open, and one may not have access to the location to remove the obstructing
devices.
Combustible oil
On board a ship there is fuel oil, lubricating oil, hydraulic oil - all very combustible and the most
likely nourishments of an engine room fire. Gard surveyors have met crew members who do not
consider lubricating oil and hydraulic oil to be fire hazards, as such oils are seen to be difficult to
light. That is, however, only a question of temperature. In an oil fire it is the gas above the liquid
that burns, and if heated sufficiently by a fire, lubricating oil and hydraulic oil also become
volatile and fire-hazardous.
All oil supply systems in the engine room are
constructed in accordance with classification and
SOLAS rules, and there are built-in protections
which the crew should be aware of, understand and
respect. Valves in fuel oil supply lines from day
tanks are fitted with remote controls, operated from
a location outside the engine room casing, so that
fuel supply may be cut in an engine room fire.
These devices are regularly inspected by class, flag
state and port state inspectors and are normally in
good working order. It is also important that such
remote closing arrangements are clearly marked for
the oil supply lines they serve, in order not to close
the fuel to the wrong machinery. One may want to
stop the main engine in a fire situation, but possibly
Fireman equipment should not an auxiliary diesel engine supplying power to
be properly arranged, the fire pumps, for instance.
ready for use, not as shown
in this picture.
One breach of safety which Gard surveyors see on board most vessels they inspect is that the
lower valve of the level glasses of oil tanks is forcibly kept open. Class and state authorities seem
to overlook this item, although it is clearly stated in classification and statutory rules that such a
valve is to close automatically.
A level glass is needed to check the contents of the oil tanks by daily readings. However, level
glasses represent a weakness of the tank integrity, therefore a valve is fitted at the lower end, and
provided with means for automatic closing. Normally such a valve is spring loaded and the crew
member will have to bend down and keep a pressure by hand until the oil has risen in the level
glass. Thick oil may take some time to fill up the level glass, and for the ease of work, crew
members often secure such valves permanently in open position, by steel wire, blocks of wood,
etc., or by ingeniously designed "thumbscrew" fittings. During condition surveys Gard surveyors
find this serious breach of safety on board most of the vessels having oil tanks with level glasses.
Gard Services has also seen that in reports from engine room fires, there is often described a
sudden and inexplicable increase in the power of the fire. One reason for this could be the
breaching of level glasses on oil tanks and lower valves being secured in open position.
Gard's advice on this problem is to fit for instance foot operated valves to the lower end of the
level glass, thus avoiding the need of the crew member to bend down. Superintendents, masters
and chief engineers should make sure that such safety devices are not tampered with and the
crew member should think twice before securing such valves in open position.
All fuel and other oil pipelines should be maintained in good condition, arranged as required by
class and IMO regulations. Gard surveyors occasionally see plastic and rubber hoses being fitted,
instead of metal pipes. Such installations are dangerous and a serious breach of regulations. Any
flexible coupling must be of an approved type and should be inspected regularly.
General cleanliness
For a fire to propagate in an engine room, it needs material for combustion. Oil should not be
allowed to accumulate in drip trays, gutters and bilges, so a high level of cleanliness will
normally be associated with a high level of fire safety. Drain pipes from gutters to oil collecting
tanks should be kept open, oily rags should be disposed of in a correct manner and engines and
floor plates cleaned regularly. Oily remains in bilges and in other areas below floor plates may at
times need chemical cleaning to be removed.
In some ships there is a large collection of used spare parts and items which are "nice to have".
Gard surveyors have seen large collections of plastic sheets, cardboard, wooden planks, used
paint tins, etc., being stored in fire- prone areas. "Good housekeeping" is a key word! Discard
combustible materials, remove outdated equipment that may hinder access in a fire situation and
enforce a high level of cleanliness. It is not particularly smart to store combustible materials
behind an electrical switchboard, close to the exhaust pipe of a diesel engine, in the vicinity of a
boiler furnace, and next to rotating machinery.
Sources of ignition
The sources of heat most likely to start a fire in the engine room are hot exhaust pipe and engine
surfaces, bearings of rotating machinery heating up and defunct electrical equipment. Heat
sources can of course also be introduced by human error, as by for instance dangerous use of
electric tools and welding equipment.
Insulation of exhaust pipes is often found to be
defective, especially in the vicinity of the diesel
engines, where removal of insulation is needed
during engine maintenance. Also, flange
connections and steel supports of exhaust pipes
may often be inadequately insulated, as well as
indicators and other instruments fitted. Look for
signs of hot areas, such as paint discoloration and
reddish rust surfaces. New regulations are now
established, valid for all ships from 1st July this
year.
1

Electrical installations will always represent a


certain risk of sparks and fire, although the risk is
reduced by the use of quality safety devices and
close adherence to valid regulations. When a
Photo shows the oily vessel is delivered from the newbuilding yard, the
surroundings of an FO tank. electrical installation is normally in good
The lower valve of the sight condition, well tested by competent personnel.
glass is secured in fully open Thereafter the authorities' control of electrical
position. installation on board a ship is very lax, far below
the level imposed on land-based industry and
private homes. In reducing the number of crew on
board, the position of electrician has disappeared.
The electrical installation on board a ship is regulated by class and SOLAS rules. A "megger test"
by crew or shipyard and a superficial visual inspection by the class surveyor is often all the
attention the electrical installation receives. Thermographical examinations are considered a
much better means for checking the fire risks of electrical installations, and such technology is
now easy to obtain. 2

Gard surveyors see a lot of dangerous, "home-made", electrical work on board older vessels. It
must be emphasised that only qualified personnel should be allowed to work on electrical
installations, only quality electrical fittings should be used and valid standards should always be
followed.
All rotating machinery may also represent a source of sufficient heat to light a fire, first of all by
bearings of pumps, etc., heating up. Alertness and proper maintenance are key words.
A crankcase explosion is a particular danger when main bearings of a diesel engine crankshaft
become damaged. The premature opening of crankcase doors following an oil mist or high
bearing temperature alarm has been the cause of more than one engine room fire. 3

1 See article "New fire safety regulations in the engine room" in this issue of Gard News.
2 See article "Thermographical examinations of engine rooms" in this issue of Gard
News.
3 See article "Crankcase explosions" in Gard News issue No. 159.

Fire-fighting capabilities
The standard equipment used for fighting a fire in the engine room of a ship is hand-held fire
extinguishers, a large capacity extinguisher, fire pumps and fire hoses, and the fixed fire
extinguishing system. This article will not discuss the advantages and disadvantages of various
extinguishing media, but only highlight some observations made as to the practical use of the
equipment.
Hand-held extinguishers should be in good condition, and stored correctly in locations as
designed on the vessel's Fire Plan. A fire extinguisher is not a place to hang boiler suits, etc., like
Gard surveyors sometimes see. It should be easy to find and readily accessible. When the
extinguisher is found at the inner end of a narrow paint shop or service room, Gard surveyors
usually propose to hang it at the entrance to the room. The extinguishing medium should be
compatible with the most likely fire risk, i.e., oil, electrical, etc., and the extinguisher should be
regularly checked for full content.
The large capacity extinguisher has often been of a type very difficult to move around, so its
location is of interest. Also, during fire exercises, one should test out how to best move the
extinguisher around. Today there are also foam applicators installed which are easier to operate,
with hoses on reels that can be easily rolled out, and which can be connected to any fire hydrant -
a very efficient tool for fighting a limited fire. Again, it is important to have training on how to
put the equipment into use at short notice.
While SOLAS defines the size of fire nozzles, the dimensions of fire hoses have been up to "the
Administration". Some flag Administrations prefer hoses of such large diameter that they are
difficult to roll out before being put under pressure, and may need a very strong crew to handle
under pressure. The best way to roll out the hoses should be studied and as realistic as possible
exercises should be arranged.
Investigations have shown that in many engine
room fires it has taken too long for a decision to
release the fixed fire extinguishing system to be
made, an average of more than 30 minutes since
the fire has been discovered. Often that is much
too long, because the fire may then have taken full
control. As for the fixed fire extinguishing system,
Gard surveyors see more CO2 installations than
any other system in use, and such a system
requires all personnel out of the engine room
before the gas is released. A good reporting and
head counting system is therefore essential in
reducing the time needed for the release.
Decisiveness in the use of the CO2 system and a
full knowledge of how the system is operated are
Do not hang personal gear also key factors. It seems that the costs of refilling
on fire extinguishers. They the CO2 system may sometimes also be a
should be readily accessible consideration, but it should not be. Once manual
and not fouled up. fire fighting has been tried without success, use the
main system before the fire turns catastrophic.
However, do not release the fixed fire-fighting
system in a panic, be aware of what you are doing,
as the system can only be released once.
Finally, it should be mentioned that the fireman outfit required by SOLAS is really a minimum
requirement. Except for equipment seen on board some cruise vessels with professional firemen,
the standard SOLAS equipment will probably not be found very satisfying by a professional
fireman. It is heat reflective only as long as it is not sooted down, for instance. On many vessels
Gard surveyors find that the equipment is on board, still wrapped in its original packing.
Obviously no one has ever tested it out and the equipment is not being used during fire exercises.
It should of course be readily accessible and designated personnel should train in its use and also
know its limitations. We are then back where we started: it is the crew on board a ship that will
have to fight an eventual fire, and their success largely depends on dedication, knowledge and
regular realistic exercises.
.