PSD01
Controlled Switching of
High-Voltage Circuit-Breakers
Controlled
switching

Switching transients Increased system the same instant. As a Controlled switching


reliability as a result of result of the arbitrary Less stresses on the
that occur during the reduced voltage switching instant and the equipment
fluctuations and lower phase shifts of the three Non-controlled closing of
switching of capacitive harmonic stress. phases with respect to a capacitor bank at a
and inductive loads Longer service life of
each other, a tendency voltage peak can result in
for random phase high inrush currents and
result in electrodynamic equipment reducing
positions arises. The over-voltages, which can
switching over-voltages
and dielectric stress on switching transients vary greatly exceed the
and inrush currents.
accordingly in the nominal system values.
the equipment of the Possible replacement individual phases but, in This means that the
of costly, complex general, unfavorable capacitors are heavily
high-voltage system. mechanical auxiliary switching conditions can loaded both mechanically
Controlled switching equipment, such as be expected in at least and dielectrically and age
closing resistors. one phase. prematurely. As a result
with the PSD01 control capacitors can be
The intensity of the Controlled switching
unit from Siemens switching transients allows an individual damaged or destroyed.
during switching optimum switching Closing the contact at
minimizes these operations depends on instant to be set for each the optimal point in time
the phase position at the switching pole. The reduces the load on the
stresses. The following capacitor bank and
point of switching. A switching transients are
advantages arise from circuit-breaker without thereby reduced to a improves the quality of
controlled switching minimum. With circuit- the voltage of the
the use of this control switches the three breakers with three network.
unit: phases at approximately independent drives, each
switching pole receives
an individual switching
command from the
control unit.

U [%] U [%]
200 200

100 100

0 0

1 2

0 20 40 60 80 t [ms] 0 20 40 60 80 t [ms]
Switching a capacitive load
1 Closing time optimized
2 Closing time not optimized

2
Non-controlled energizing loads such as shunt Optimization of the
of a reactor or a reactors or transformers switching instant
transformer close to the means that the circuit- prevents re-ignitions and
voltage zero crossing breaker can interrupt the over-voltages are
may result in a very high small currents before the minimized.
direct current natural zero crossing. In the cases described
component. The This process is known as above, non-controlled
induction flow thus current chopping and making or breaking can
generated saturates the leads to steeply rising lead to increased stress
iron core and induces an over-voltage. This can on the equipment.
inrush current that result in a re-ignition Closing resistors and
presents a high load for across the open breaker reactors that were
the transformer or the contacts if the clearance previously used to
reactor. Controlled at this instant is not reduce these stresses
switching at the voltage sufficient to withstand may no longer be
crest will also prevent the dielectric load. Over- required. Controlled
switching transients from voltages are inevitable. switching offers an
occurring and Controlled switching also economical alternative.
consequently the offers a remedy in this
equipment is protected. case.
Non-controlled de-
energizing of inductive

I [%] I [%]
1000 1000

500 500

0 0

1 2

0 20 40 60 80 t [ms] 0 20 40 60 80 t [ms]
Switching of a transformer
1 Closing time optimized
2 Closing time not optimized

3
Control unit

By taking current values Closing is carried out Integration into the


into consideration, the with an optimal phase substation
PSD01 control unit position relative to the The PSD01 control unit is
optimizes the switching voltage. The phase integrated into the
operations of circuit- position is selected substation control
breakers with respect to based on the actual system so that the
the phase relative to the switching duty so that switching commands
current or voltage. switching transients can that are given for
Controlled switching be avoided. operational reasons are
takes the present When opening small processed. Opening
opening and closing inductive currents, the commands that are
times of the circuit- contact separation is generated by the system
breaker into account. controlled with respect prote ction in case of
Commands from the to the voltage cycle so short circuit are passed
system protction are that the contact directly onto the circuit-
passed directly onto the clearance during breaker. In such cases
circuit-breaker. interruption is sufficiently there is no control of the
large to prevent re- switching instant.
ignition.

Voltage transformer(s) Current transformer(s) Control room System protection

Measuring values
(Busbar/Load) Measuring values Alarms Commands OPEN/CLOSE Commands
Bypass - Only in coordination

Personal Computer PSD01


with the manufacturer!

Commissioning Zero crossing detection


and Calculation of
maintenance Calculation of mechanical operating time
delay time
Data logging and evaluation

Sensors
- Tripping voltage
- Ambient temperature Releases Releases
- Hydraulic pressure (only for hydraulic operating mechanisms) OPEN/CLOSE OPEN
- Reference contact (Protection)
Auxiliary switches
Control voltage

Circuit breaker

4
The functions and To compensate for The Adaptive Control
features of the PSD01 possible deviations in the function allows the
control unit opening and closing of a self-adaptation of the
The PSD01 control unit circuit-breaker, the control unit in response
offers wide-ranging PSD01 control unit offers to changed circuit-
functionalities. It offers two functions to perform breaker properties, for
the possibility to select making and breaking at example, with the help
and set the opening and the optional instant for of reference contacts.
closing instant for each each pole: The reference contacts
switching pole reproduce the closing
The PSD01 or opening of the main
individually. compensates for the contacts of the circuit-
The PSD01 control unit is dependence of the breaker.
suitable for use with all opening and closing
high-voltage circuit- times in opening and
breakers. This includes closing on the ambient
already installed circuit- temperature and the
breakers with a minimum control voltage. With
stability of the opening hydraulically driven
and closing time and a breakers, the drive
sufficiently steep pre- energy (hydraulic
arcing characteristic pressure) is also
curve. compensated. It is
possible to chose
With the help of two between different
separately configured compensation
parameter sets in the characteristics.
control unit it is possible
to control a circuit-
breaker which is used for
two different switching
tasks. Automatic
selection between the
two switching tasks
during operation takes
place via a mode input.

5
Functions

In order to monitor the Data-acquisition of the switching operations parameters


success of the controlled last 4 switching with the help of (e.g. frequency,
switching operations and operations is Windows-compatible voltages, temperature).
the internal functions, performed. The signals software. When the limits are
the PSD01 has a wide for all in- and outputs exceeded or not
Individual detection of
range of monitoring and are recorded. This reached, an alarm
the positions of the
evaluation functions: includes the current signal is displayed.
individual circuit-
and voltage time
Evaluation of up to 4 breaker pole with a Output of error
curves and the process
voltage channels and 3 monitoring function by messages (alarms),
curves of the switching
current channels means of 4 auxiliary e.g. if a switching
commands (inputs
switch inputs. operation is not
Assessment of the from the control room
successfully
effected closing or and outputs on the Data-acquisition of the
performed, if no zero
opening operations is circuit-breaker) and the most important data
crossing of the
possible reference contact from approximately
reference voltage has
signals. The 400 events and
been detected, or if an
oscillograms are placed switching operations
input signal has not
in a buffered memory by means of the
been received.
and are available even History function. In
after supply History, the data are Monitoring of sensors,
interruption. acquired cyclically and hardware, and the
event-controlled and voltage supplies.
Easy graphical
stored in a nonvolatile
evaluation of all Experience
memory.
recorded signals of the
Our years of experience
Option of inputting in the use and
limits for the individual development of control
units have gone into the
development of the
PSD01. The PSD01
control unit has been
subjected to
comprehensive electrical,
mechanical, and climatic
tests. The EMC test in
accordance with IEC
61000 and IEC 60255
and the test for low
noise emission in
accordance with EN
55011 have been passed
successfully. Climatic
and mechanical tests in
accordance with IEC
60068 and IEC 60255
demonstrate unlimited
functionality even under
disruptive environmental
influences.

6
Technical Data

Housing:
42HP/3U HF module support with perforated cover plate
Protection category: IP2
Height: 133.35 mm (3U)
Width: 219 mm (9.5) (269 mm with securing bracket)
Depth: 225 mm
Weight: 4 kg
Ambient conditions:
- 40 C to +70 C
Free air convection, non-condensing
Voltage supply:
Voltage: 42...360 Vdc
Power consumption: 15 W
Mains buffering, protected against polarity reversal, short-circuits, no-load and over-load, monitoring of supply interruption
Analog inputs:
1x temperature 4...20 mA, 24 V
3x oil pressure 4...20 mA, 24 V internal supply
3x reserve 4...20 mA, 24 V

1x control voltage 0...300 Vdc


1x CLOSE-trip voltage 0...300 Vdc same reference dimensions/insulated
1x OPEN-trip voltage 0...300 Vdc

4x voltage transformer 0...212 Vac f 0=1 kHz, R in=2.4 MW, insulated


3x current transformer 12.5 Adc f0=1 kHz, R in=10 mW, insulated, 100 A, 5 ms, Imax=14 Adc
Digital inputs:
1x MODE
1x AUX-close-contact pole A
1x AUX-close-contact pole B
1x AUX-close-contact pole C 32...300 Vdc, Rin=20 kW, protected against polarity reversal, insulated
1x AUX-open-contact poles ABC
1x CLOSE-command
1x OPEN command

3x Reference contact 4...20 mA, 24 V internal supply


Outputs:
3x power outputs CLOSE 24...300 Vdc, 20 A, 2.5 s or 25 A, 200 ms (90C),
3x power outputs OPEN Imax=35 A, short-circuit interrupt time < 10 s

8x relay contact 1 two-way contact, switching capacity 2000 VA


constant current 8 A, operating range 300 Vdc / 0.5 A
8x LED display
Communication interfaces:
DTE/DCE communication

2x EIA RS-232, DTE, 115000/57000 bps, serial modem, SUB-D9


Resolution, sampling rate
10 kHz, 10 Bit, 250 ms, sensor inputs 1 s, 10 Bit
Switching precision: 0.1 ms
System:
16-Bit microcontroller - C167CR, 20 MHz, RTC, 512K SRAM, 512K FLASH, capacitor-buffered
Connection technology:
COMBICOM PHOENIX contact system recommended connection cross-section: 2.5 mm
Type MSTB 2.5/..-STF, 0.2-2.5 mm, AWG 24-12
1 x 6-pole, 8 x 16-pole
Accessories:
1x serial modem cable

7
For Further
Information

Please fax this page to the


Name
following number:
Fax +49 30 386-25867
Position

Company

Street

Postcode/City/Country

Phone/Fax

E-mail

Please send me more information on the following topics:


High-voltage circuit-breakers for outdoor installation, product range
High-voltage circuit-breaker: Type 3AP1/2, 72.5 kV to 420 kV
Live-Tank and Dead-Tank high voltage circuit-breaker technology
High-voltage circuit-breaker: Type 3AT2/3, 245 kV to 550 kV
Hydraulic operating mechanisms for high voltage circuit-breakers
SF6 in power engineering-acting responsibly
Further copies of this brochure

Department
Power transmission and distribution
High-voltage division
Nonnendammallee 104
D-13629 Berlin
E-mail: circuit.breaker@ptd.siemens.de
http://www.ptd.siemens.de/en/circuitbreaker/index.htm

Siemens Aktiengesellschaft Subject to change Bestell-Nr. E50001-U113-A145-V1-X-7600