PSD01
Controlled Switching of
High-Voltage Circuit-Breakers
Controlled
switching
U [%] U [%]
200 200
100 100
0 0
1 2
0 20 40 60 80 t [ms] 0 20 40 60 80 t [ms]
Switching a capacitive load
1 Closing time optimized
2 Closing time not optimized
2
Non-controlled energizing loads such as shunt Optimization of the
of a reactor or a reactors or transformers switching instant
transformer close to the means that the circuit- prevents re-ignitions and
voltage zero crossing breaker can interrupt the over-voltages are
may result in a very high small currents before the minimized.
direct current natural zero crossing. In the cases described
component. The This process is known as above, non-controlled
induction flow thus current chopping and making or breaking can
generated saturates the leads to steeply rising lead to increased stress
iron core and induces an over-voltage. This can on the equipment.
inrush current that result in a re-ignition Closing resistors and
presents a high load for across the open breaker reactors that were
the transformer or the contacts if the clearance previously used to
reactor. Controlled at this instant is not reduce these stresses
switching at the voltage sufficient to withstand may no longer be
crest will also prevent the dielectric load. Over- required. Controlled
switching transients from voltages are inevitable. switching offers an
occurring and Controlled switching also economical alternative.
consequently the offers a remedy in this
equipment is protected. case.
Non-controlled de-
energizing of inductive
I [%] I [%]
1000 1000
500 500
0 0
1 2
0 20 40 60 80 t [ms] 0 20 40 60 80 t [ms]
Switching of a transformer
1 Closing time optimized
2 Closing time not optimized
3
Control unit
Measuring values
(Busbar/Load) Measuring values Alarms Commands OPEN/CLOSE Commands
Bypass - Only in coordination
Sensors
- Tripping voltage
- Ambient temperature Releases Releases
- Hydraulic pressure (only for hydraulic operating mechanisms) OPEN/CLOSE OPEN
- Reference contact (Protection)
Auxiliary switches
Control voltage
Circuit breaker
4
The functions and To compensate for The Adaptive Control
features of the PSD01 possible deviations in the function allows the
control unit opening and closing of a self-adaptation of the
The PSD01 control unit circuit-breaker, the control unit in response
offers wide-ranging PSD01 control unit offers to changed circuit-
functionalities. It offers two functions to perform breaker properties, for
the possibility to select making and breaking at example, with the help
and set the opening and the optional instant for of reference contacts.
closing instant for each each pole: The reference contacts
switching pole reproduce the closing
The PSD01 or opening of the main
individually. compensates for the contacts of the circuit-
The PSD01 control unit is dependence of the breaker.
suitable for use with all opening and closing
high-voltage circuit- times in opening and
breakers. This includes closing on the ambient
already installed circuit- temperature and the
breakers with a minimum control voltage. With
stability of the opening hydraulically driven
and closing time and a breakers, the drive
sufficiently steep pre- energy (hydraulic
arcing characteristic pressure) is also
curve. compensated. It is
possible to chose
With the help of two between different
separately configured compensation
parameter sets in the characteristics.
control unit it is possible
to control a circuit-
breaker which is used for
two different switching
tasks. Automatic
selection between the
two switching tasks
during operation takes
place via a mode input.
5
Functions
6
Technical Data
Housing:
42HP/3U HF module support with perforated cover plate
Protection category: IP2
Height: 133.35 mm (3U)
Width: 219 mm (9.5) (269 mm with securing bracket)
Depth: 225 mm
Weight: 4 kg
Ambient conditions:
- 40 C to +70 C
Free air convection, non-condensing
Voltage supply:
Voltage: 42...360 Vdc
Power consumption: 15 W
Mains buffering, protected against polarity reversal, short-circuits, no-load and over-load, monitoring of supply interruption
Analog inputs:
1x temperature 4...20 mA, 24 V
3x oil pressure 4...20 mA, 24 V internal supply
3x reserve 4...20 mA, 24 V