Electrical safety

...always one step ahead

A-ISOMETER
IRDH275, IRDH375, IRDH575
Whichever IT system you have,
the A-ISOMETERs IRDH275 / 375 / 575 will monitor them all
T H E N E W D E V I C E FA M I LY A - I S O M E T E R I R D H 2 7 5 , I R D H 3 7 5 A N D I R D H 5 7 5

The use of unearthed power sup-


plies (IT systems) is of the essence
in all electrical installations where
high operating safety and reliabi-
lity is paramount. IRDH275/375/575
- the new family of innovative
A-ISOMETERs is exactly adapted
to the requirements of modern
power supply systems. The new
AMPPlus measuring principle allows
exact measuring of the insulation
resistance, even in extended IT
systems and installations including
variable-speed drives.

A solution that helps


to keep the costs low
Comprehensive information and
clear indication via a plain text
display and yet simple-to-use
makes this device family stand
out where safety is important.
Time is gained and expensive
interruptions can be avoided
thanks to advance information. Front view of the A-ISOMETER IRDH575, IRDH375 and IRDH275

IRDH... speak in plain language


All text messages are displayed as plain text on the illumi-
nated display and are emphasized by brightly lit LEDs.

IRDH... inform at the press of a button


Additional information such as system leakage capacitance,
parameter values etc. are immediately available at the press
of a button.

IRDH... simple to operate


The user-friendly menu structure and large keys makes the
device simple to operate.

Variable installation
The panel-mounting enclosure is easy-to-install into the fascia of a switch-
board. In this way, the entire information is available to the user at a
glance. Terminal cover and shock-hazard protected connection termi-
nals provide additional protection. The IRDH275 series is designed for
installation into a switchgear cubicle (DIN rail).
The modular system
Time gained thanks to flexibility

Basic function
The A-ISOMETER IRDH275/375
measure the insulation resistance
and indicate the measured value
on the display. If the measured
value falls below the preset value,
an alarm message is provided.

Basic function of the IRDH275

Monitoring several
interconnected
IT systems
Only one A-ISOMETER may be
active in each IT system. The
A-ISOMETERs IRDH275B/375B
can be configured accordingly so
that this requirement will always
be met when several IT systems
are interconnected. The RS485
interface (BMS protocol) provides
the necessary information exchan-
ge between the A-ISOMETERs.
Monitoring of several interconnected IT systems

Insulation monitoring
with automatic fault
location (EDS)
If an insulation fault occurs, it must
be localized and eliminated in order
to guarantee operating safety. For
fast, automatic localization of the
faulty circuit, the IRDH575 and the
insulation fault evaluator EDS47...-
12 with the appropriate measuring
current transformers are combined
to provide a complete insulation
Insulation monitoring with automatic fault location (EDS)
fault location system.
For various application fields
Techniques that convinces

Application fields
Industrial systems with variable-
speed drives
Power generation and distri-
bution
Industry Traffic engineering Traffic engineering etc.

IRDH275 / 375 / 575 series Technical features


Monitor Insulation monitoring with prewarning and
the insulation resistance in all IT systems main alarm for universal use in all IT systems
the functional safety through automatic self monitoring Adjustable response value 1 k ...10 M
- System and earth connection - system functions
AMPPlus measuring principle for AC,DC and
Signal AC/DC IT systems of up to 793 V,extendable via
a drop in insulation resistance coupling devices (not for IRDH575)
- prewarning - main alarm
Monitoring of system functions, system and
Inform
earth connection
via plain LC text display
- actual insulation resistance - system leakage capacitance Automatic adaptation to system leakage
- faulty conductor (DC) - parameter values capacitances

Internal and external test and reset button


IRDH275B / 375B / 575 series Illuminated plain text display:
Additional functions 2x 16 characters (IRDH275/375)
4x 16 characters (IRDH575)
Data memory
Historical memory to store alarm text messages with date and time Alarm LEDs
Communication - prewarning
- main alarm
RS485 interface (BMS protocol)
- system monitoring
Current output 0/4 . . . 20 mA
additional features of IRDH575
ISONET function
- insulation fault location
For interconnection of several IT systems - common alarm, fault located
Decoupling relays
Separately adjustable alarm relays in N/O and
N/C operation
IRDH575 series RS485 interface (BMS protocol)
The IRD575 series in combination with EDS47...-12 evaluators and
measuring current transformers can be extended to an automatic Panel mounting (optional) in IP 65 (IRDH375)
insulation fault location system. or in IP 42 (IRDH575)
Location DIN rail mounting (IRDH275)
Insulation faults in electrical installations with up to 708 subcircuits
Enclosure for installation into standard distri-
No disconnection of the electrical installation bution panels
Information IRDH375 = 72 x 144 mm (H x B)
Indication of the faulty subcircuit IRDH575 = 96 x 144 mm (H x B)
Technical data
F U N C T I O N S A N D C H A R A C T E R I S T I C S AT A G L A N C E

Series
Type IRDH275 IRDH375 IRDH575
Application field
Nominal voltage range Un 3(N)AC 0 ... 793 V, DC 0 ... 650 V 3(N)AC 0 ... 793 V, DC 0 ... 650 V 3(N)AC/DC 20 ... 575 V/340 ... 760 V
Frequency range fn DC 0.2 ... 400 Hz DC 0.2 ... 400 Hz DC 50 ... 400 Hz
System leakage capacitance Ce < 150 (500) F < 150 (500) F < 150 (500) F
Nominal voltage range Un (extendable) x x --
Application
Main circuits AC,3(N) AC/DC x x x
Control circuits AC/DC x x x
Diode-decoupled systems x x x
Interconnected IT systems x x x
Response values/contacts
Number of response values 2 2 2
Response value 1 k ... 10 M 1 k ... 10 M 1 k ... 10 M
Contact main alarm 1 changeover contact (or system fault) 1 changeover contact 1 changeover contact
Contact prewarning 1 changeover contact 1 changeover contact 1 changeover contact
Contact (1 changeover contact) -- system fault system fault/EDS alarm
Communication
Measured value display/parameter two-line LC display two-line LC display four-line LC display
Alarm LEDs 3 3 5
Function keys 4 4 4
RS485 interface BMS protocol (B version) BMS protocol (B version) BMS protocol
Current output 0 ... 400 A(0/4 ... 20 mA B version) 0 ... 400 A(0/4 ... 20 mA B version) 0/4 ... 20 mA
General features
Measuring principle AMPPLUS AMPPLUS AMPPLUS
Test/reset button internal/external internal/external internal/external
Fault memory x x x
Indication faulty conductors L+/L- x x x
Connection monitoring system/PE system/PE system/PE
Historical memory B version B version x
Isometer disconnecting relays B version B version x
Insulation fault location
Test current adjustable -- -- 1 ... 50 mA
Indication -- -- faulty conductors
Evaluators -- -- EDS470/473-12

Right to modifications reserved!


A SUMMARY
IRDH 375 series OF THE FUNCTIONS
MONITORING TECHNICAL
4 insulation resistance in all ungrounded (IT) systems CHARACTERISTICS
4 system and earth connection 4two-step insulation monitoring for
4 system functions universal use in all IT systems
4 functional safety due to automatic self monitoring
4adjustable response value
SIGNALLING 1kOhm10 MOhm
4 A drop in insulation resistance 4AMPplus measuring principle for
8prewarning 8main alarm AC, DC and AC/DC IT systems up to
690 V, extendable via coupling
INFORMATION devices
4 via LC text display 4continuous monitoring of system
8current insulation resistance 8faulty conductor (DC polarity)
functions and system and earth
8system leakage capacitance 8parameter settings
connection
4automatic adaptation to system
IRDH 375 B series leakage capacitances
Additional functions: 4internal and external test and
reset button
DATA MEMORY
4 historical memory to store alarm text messages with date and time 4illuminated LC text display:
8 2 x16 characters (IRDH 375)
8 4 x16 characters (IRDH 575)
COMMUNICATION
4 RS485 interface (BMS protocol) 4alarm LEDs - IRDH 375-
4 current output 0/4 20mA 8 prewarning
8 main alarm
IT SYSTEM MANAGER 8 system monitoring
4 automatic decoupling of Isometers in interconnected systems supplementary functions-IRDH575-
8 insulation fault location
8 common alarm fault located
IRDH 575 series 4separately adjustable alarm relays
in N/O / N/C operation
The IRDH 575 series in combination with EDS47..-12 evaluators and
measuring current transformers can be extended to provide an 4RS485 interface
automatic insulation fault location system. 4shock hazard protected terminals

DETECTING 4front plate mounting optional


4 insulation fault location in electrical installations cover for IP65
with up to 708 sub circuits 4enclosure for installation into
4 without disconnection of circuits standard distribution panels
8 IRDH 375 =72 x144 mm (HxW)
INFORMATION 8 IRDH 575 = 96x144 mm (HxW)
4 indication of the faulty sub circuit Rights to modification reserved