Documente Academic
Documente Profesional
Documente Cultură
HE EXPOSURE TO
42
Digital Object Identifier 10.1109/MIAS.2009.932345 CREATAS
1077-2618/09/$25.002009 IEEE
Protection Association (NFPA) 70E OSHA initially used the National
and IEEE 1584 arc-flash incident Electrical Code (NEC) as a basis for
energy equations and the results ob- OSHA INITIALLY electrical regulations. Because the NEC
tained using the proposed simplified largely does not address employee
calculations. USED THE safety, it became apparent that a new
Awareness of the various hazards standard was needed. As a result, on 7
caused by an arc flash has increased NATIONAL January 1976, a new NFPA electrical
significantly over the past two deca- standards development committee was
des. The regulations, standards, re- ELECTRICAL formed. This group was given the task
search, and application guidelines of assisting OSHA in preparing stan-
focus on reducing the exposure of CODE (NEC) AS dards specifically addressing electrical
personnel to burn injuries associated A BASIS FOR safety. The Committee on Electrical
with arc-flash events in low-voltage Safety Requirements for Employee
(LV) and medium-voltage (MV) appli- ELECTRICAL Workplaces published the first edition
cations. Currently, the NFPA 70E of NFPA 70E in 1979. The initial
Standard for Electrical Safety in the REGULATIONS. edition covered installation safety
Workplace [1] and the IEEE 1584 requirements. Three subsequent edi-
Guide for Performing Arc-Flash Hazard tions over the next decade added sec-
Calculations [2], [3] have the same tions on safety-related work practices
goal, protecting individuals who must work on or near and safety-related maintenance requirements. OSHA used
energized electrical equipment. However, the philosophi- this work to create many of its regulations applying to
cal approaches used by these two groups to estimate the electrical safety.
arc-flash hazards are different. For many who are required Title 29 of the Code of Federal Regulations (CFR), Sub-
to apply and follow the standards, the arc-hazard calcula- part S, addresses electrical safety requirements that are nec-
tions and the interpretations, at times, can be confusing, essary for the practical safeguarding of employees in their
particularly when there are discrepancies among the meth- workplaces [4]. It was not until 1991 that OSHA added
ods being used. It has been widely accepted in the power words acknowledging arc flash as an electrical hazard. The
industry that there is a need to perform additional research fifth edition of the NFPA 70E, published in 1995, became
and refine the arc-flash calculation methods to more effec- the first standard specifically addressing the arc-flash haz-
tively manage the hazard. ard. This printing included requirements for protective
This article focuses primarily on the arc-flash incident clothing and defined a flash-protection boundary. The next
energy calculations currently being used. Following a two revisions focused on detailed arc-flash hazard analysis,
Constants
2
47
Summary of incident energy calculations.
assorted variables was investigated. This fault current, for voltages less than
is to be emphasized; no effort has been 480 V, in closed configurations, could
made in this article to validate the equa- ONE OF THE MOST be approximated by the simplified
tions presented in the IEEE Standard IMPORTANT AND equation of a straight line given by (as
1584. The approach is demonstrated on shown in Figure 3)
the equations derived for LV and MV ESSENTIAL
systems. A discussion of three cases fol- Ia 0:6 Ibf : (10)
lows: 1) system voltages 480 V and ELEMENTS OF AN
below, 2) system voltages below 600 V, Using information extracted from
and 3) system voltages over 1,000 V. ARC-FLASH the IEEE 1584 test results database,
These voltage values were selected so arcing current and three-phase bolted
that some comparison could be made HAZARD fault current data corresponding to
with the experimental results provided ANALYSIS IS THE voltages less than 480 V are plotted
in the IEEE Standard 1584. (scatter plot) in Figure 4.
ESTIMATION OF A line representing (10) is super-
System Voltages 480 V and Below imposed over the IEEE 1584 test
Equations (3) and (5) were evaluated THE INCIDENT data. Test points on the scatter plot
for different conductor gap distances are grouped into three shaded areas as
on a 480-V system with a box configu- ENERGY. identified. Group 3 is of particular
ration as shown in Figure 3. interest because of the wide variation
Figure 3 reveals that a worst case in arcing current levels observed for
relationship between the arcing current and the bolted fault currents more than 100 kA. This is attributed to
the test procedure, which investigated a broad range of
conductor gap distances varying from 7 to 32 mm. Fig-
ure 3 reveals that the incident energy equation models
Arcing Versus Bolted Fault Current
(480 V, Box Configuration)
the increasing influence of conductor gap distance at
70 higher fault current levels. The simplified approach does
G = 10 mm G = 25 mm G = 40 mm
not account for this because only the worst case was con-
60 sidered, i.e., a conductor gap of 10 mm. Nevertheless, all
Arcing Fault Current (kA)
50
of the data points fall beneath this line, confirming that
la = 0.6 lbf this simple linear equation could be used as a worst case
approximation of the relationship between the arcing
IEEE INDUSTRY APPLICATIONS MAGAZINE MAY j JUNE 2009 WWW.IEEE.ORG/IAS
40
current and bolted fault current, for voltages less than
30
480 V, in closed configurations. It will be interesting to
20 see whether this simplification could be proven by addi-
tional testing.
10 Next, the sensitivity of the normalized incident energy
0
to the conductor gap distance was evaluated using (6) and
0 20 40 60 80 100 (7). Results for ungrounded or high-resistance grounded
Bolted Fault Current (kA) systems are shown in Figure 5. Ungrounded systems are
3 featured in this study because our investigation con-
Sensitivity to gap between conductors: 480 V and below. firmed other literature, which states that typically an
G = 10 mm G = 25 mm G = 40 mm
Arcing Fault Current (kA)
50 25
la = 0.6 lbf
40 20
En = 0.43 la
3 15
30
2 10
20
1 5
10
0
0 0 10 20 30 40 50 60
0 20 40 60 80 100 Arcing Current (kA)
Bolted Fault Current (kA)
4 5
48
Scatter plot of IEEE 1584 LV test data: 480 V and below. Sensitivity to gap between conductors: 480 V and below.
ungrounded system results in the incident energy level Taking the worst case shown on the graph, as before, a
thats about 30% greater than that of a solidly grounded simplified expression for the incident energy is derived:
system [16]. Taking the worst case, as depicted on the
graph later, in a similar approach as before, a simplified En 0:43 Ia : (15)
equation for the incident energy is derived as follows:
Finally, using the procedure previously described, the
En 0:43 Ia : (11) incident energy calculation derived for this case is sum-
marized as
Last, the incident energy is calculated using (8). Con-
tinuing to simplify the equations using the worst case E 4:14 Ibf (t): (16)
approach, the working distance (D) is set to 457 mm
(18 in) and the value of 1.641 is selected for the distance System Voltage More Than 1,000 V
exponent (x) for G 25 mm. It should be noted that A similar approach was used to evaluate the incident
selecting the worst case condition for the distance expo- energy calculations for voltages more than 1,000 V
nent could be problematic. It has been shown that the using the IEEE 1584 equations listed as (4) and (5). Fig-
procedure adopted to calculate the incident energy using a ures 911 detail the data used to develop the simplified
distance exponent can give anomalous results [17], and it equations.
should be further investigated. Because this is a LV system Interpreting the information on the graphs gives the
being evaluated, 1.5 is used for the calculation factor (Cf ). equations that follow:
The incident energy calculation shown with the values
selected for the variables follows: Ia 0:95 Ibf , (17)
En 0:60 Ia : (18)
E 1:5 En (t=0:2) (610=457)1:641 : (12)
To conclude this process, the incident energy for an
Combining (10) to (12) results in a simplified form of ungrounded system is calculated using (8). The working
the incident energy equation:
70
Arcing Versus Bolted Fault Current Normalized Incident Energy Versus Arcing Current
(600 V, Box Configuration) (600 V, Ungrounded)
90 40
80 G = 10 mm G = 25 mm G = 40 mm
Normalized Energy (J/cm2)
Arcing Fault Current (kA)
35 G = 10 mm G = 25 mm G = 40 mm
70
30
60 En = 0.43 la
la = 0.8 lbf 25
50
20
40
15
30
10
20
5
10
0 0
0 20 40 60 80 100 0 10 20 30 40 50 60 70 80
Bolted Fault Current (kA) Arcing Current (kA)
6 8
49
Sensitivity to gap between conductors: 600 V and below. Sensitivity to gap between conductors: 600 V and below.
distance (D) is set to 457 mm (18 in), (0.1 s), then the expressions become
and the value of 2.000 is selected for as follows:
the distance exponent (x). Because ONE OF THE
the voltage of the system being eval- E 0:31 (Ibf ),
uated is greater than 1 kV, 1.0 is used DRAWBACKS OF (21)
for Cf . Equation (19) summarizes E 0:41 (Ibf ): (22)
USING THE NFPA
this approach:
70E APPROACH IS Figure 12 shows that all the avail-
E 1:0 En (t=0:2) (610=457)2:000 : able data points fall below the lines
(19) THE POTENTIAL TO representing the equations derived
for the 480- and 600-V cases, indi-
Combining (17)(19) results in a OVERPROTECT cating that the simplified approach
simplified form of the incident energy results in conservative estimates for
equation: THE WORKERS. the incident energy levels in a LV
system when compared with the
E 5:1 (Ibf ) (t): (20)
available test data.
As an additional means of verification, the simpli-
Verification of Results Derived for the LV Case fied version of the equations presented in this article
To check the validity of the simplified approach presented are compared with the results derived from the NFPA
in this article, average incident energies and bolted fault 70E and IEEE 1584 incident energy equations. NFPA
currents data from the IEEE 1584 test database are plot- 70E incident energy levels were derived using (2) and
ted for voltages under 1,000 V. The values selected corre- IEEE 1584 (3) and (5)(8) were used to calculate the
spond to arc durations of approximately six cycles (100 incident energy levels. Figure 13 provides a summary
ms). If the time in (13) and (16) is set equal to 100 ms of the calculations in a graphical form, confirming that
Arcing Versus Bolted Fault Current Normalized Incident Energy Versus Arcing current
45 (Undergrounded)
60
40
G = 23 mm G = 53 mm
Arcing Fault Current (kA)
35 50 G = 103 mm G = 153 mm
IEEE INDUSTRY APPLICATIONS MAGAZINE MAY j JUNE 2009 WWW.IEEE.ORG/IAS
30 la = 0.95 lbf 40
25 En = 0.6 la
20 30
15 20
10
10
5
0 0
0 5 10 15 20 25 30 35 40 45 0 20 40 60 80 100
Bolted Fault Current (kA) Arcing Current (kA)
9 11
System voltage more than 1 kV. Sensitivity to gap between conductors: More than 1 kV.
Arcing Versus Bolted Fault Current Incident Energy Versus Bolted Fault Current
IEEE 1584 Test Data Under 1 kV 40
Sample Size: 148 35
45
Incident Energy (cal/cm2)
E = 0.41 lbf
Arcing Fault Current (kA)
40 30 (600 V)
35
25
30 la = 0.95 lbf
25 20 E = 0.31 lbf
20 15 (480 V)
15 10
10
5 5
0 0
0 5 10 15 20 25 30 35 40 45 0 20 40 60 80 100
Bolted Fault Current (kA) Bolted Fault Current (kA)
10 12
50
Scatter plot of IEEE 1584 MV test data. Validation of simplified approach.
the simplified approach
gives conservative val- Incident Energy Versus Bolted Fault Current
ues in most cases. The IEEE 1584, NFPA 70E, and Simplified Method
NFPA hazard or risk cat- Calculation Comparison
egories are also shown on 35
the figure for reference. E = 0.41 lbf E = 0.31 lbf
30 Hazard Risk Category 4 (480 V)
(600 V)
Discussion of Results
Using the calculations described in the arc-flash stan- 800 IEEE 1584
dards, the NFPA 70E approach typically produces more 700 Simplified (>1 kV)
conservative estimates (higher values) for the incident 600
energy in the cases explored for this study. One of the
500
drawbacks of using the NFPA 70E approach is the poten-
400
tial to overprotect the workers. Using a sensitivity analy-
300
sis, the alternative method proposed in this article
200
produces more conservative estimates of the potential
incident energy exposure than the IEEE 1584-2002 100
equations. This is to be expected as the method is based 0
0 20 40 60 80 100 120
on some simplifications of the IEEE 1584-2002 equa-
Arc Duration (Cycles)
tions. However, the estimates for incident energy
gleaned from the approximations are less conservative 14
51
than the NFPA 70E calculations. Comparison of incident energy calculations.
Conclusions Acknowledgments
This article has reviewed the incident The authors wish to acknowledge the
energy equations used in the NFPA 70E THE Power Systems Energy Research Cen-
standard as well as the empirically based CALCULATIONS ter (PSerc) for helping to support this
equations of the IEEE 1584 document. A research. PSerc is an Industry Univer-
simplified quick assessment approach has ARE USED TO sity Cooperative Research Center (pre-
been proposed for performing incident viously a National Science Foundation
energy calculations. ESTABLISH THE Center).
The question is then, which
method should be used? This issue is PERSONAL References
complex, because research focused on [1] Standard for Electrical Safety in the Workplace,
modeling arc-flash events and predict- PROTECTIVE NFPA 70E-2004.
[2] IEEE Guide for Performing Arc-Flash Hazard
ing incident energy levels is still in its EQUIPMENT Calculations, IEEE 1584-2002.
infancy. As emphasized in this article, [3] IEEE Guide for Performing Arc-Flash Hazard
real arc-flash exposures are very diffi- REQUIRED FOR Calculations-Amendment 1, IEEE 1584a-2004.
[4] Title 29 of the Code of Federal Regulations
cult to predict because of their ran-
dom complex nature and the large A WORKER. (29 CFR). Part 1910: General Industry;
Safety Standards for Electrical Systems and
number of variables involved. Further Safety-Related Work Practices, Occupa-
complicating matters are the varied tional Safety and Health Administration
working conditions and actual equipment configurations (OSHA) Standards, Washington, DC.
encountered. [5] R. Lee, The other electrical hazard: Electrical arc blast burns, IEEE
Trans. Ind. Appl., vol. IA-18, no. 3, pp. 246251, May/June 1982.
The incident energy information derived from an arc- [6] R. Lee, Pressures developed from arcs, IEEE Trans. Ind. Appl.,
flash study is used to help develop strategies for minimiz- vol. IA-23, no. 4, pp. 760764, July/Aug. 1987.
ing burn injuries. Effectively modeling a large-scale power [7] R. L. Doughty, T. E. Neal, T. A. Dear, and A. H. Bingham, Testing
system, analyzing and accurately calculating the energy update on protective clothing and equipment for electric arc expo-
sure, in IEEE PCIC Conf. Rec., 1997, pp. 323336.
released during an arc-fault event is the cornerstone of an [8] R. L. Doughty, T. E. Neal, and H. L. Floyd, Predicting incident
arc-flash hazard analysis. NFPA 70E incident energy cal- energy to better manage the electric arc hazard on 600 V power
culations are based on theoretical concepts and from mod- distribution systems, IEEE Trans. Ind. Appl., vol. 36, no. 1,
els derived using very limited test data. Similarly, IEEE pp. 257269, Jan./Feb. 2000.
1584 includes a theoretically derived model developed for [9] R. A. Jones, D. P. Liggett, M. Capelli-Schellpfeffer, T. Macalady, L.
F. Saunders, R. E. Downey, L. B. McClung, A. Smith, S. Jamil, and
three-phase, open-air systems, applicable for any voltage. V. J. Saporita, Staged tests to increase awareness of arc-flash hazards
In other words, both standards use Lees article [5] as the
IEEE INDUSTRY APPLICATIONS MAGAZINE MAY j JUNE 2009 WWW.IEEE.ORG/IAS