A short circuit is an electrical fault where a conductive path (usually of low impedance) is formed between two or
more conductive parts of an electrical system (e.g. phase-phase, phase-earth, phase-neutral, etc). This article looks at
the nature of short circuits and tries to break down and explain the constituent parts of fault currents. Note that the
terms "short circuit" and "fault" are often used interchangeably.
In most networks, a short circuit is similar to the closing transient of an RL circuit, where the R and L components
are the impedances of the source(s). The transient characteristics of short circuit currents vary depending on whether
they are near or far from synchronous generators. The sections below describe the two general types of short circuits:
X
d
is the generator direct-axis subtransient reactance ()
X
d
is the generator direct-axis transient reactance ()
Xd is the generator synchronous reactance ( )
T
d
is the generator subtransient time constant (s)
T
d
is the generator transient time constant (s)
Ta is the aperiodic time constant (s)
From the above equation, it can be seen that the short circuit current can be broken up into an aperiodic current (dc
component of the short circuit):
E 2
t/ta
e
X
d
https://wiki.openelectrical.org/index.php?title=Anatomy_of_a_Short_Circuit 1/5
6/7/2017 Anatomy of a Short Circuit - Open Electrical
And a series of three damped sinusoidal waveforms corresponding to the following distinct stages:
1 1 t/t
This period typically lasts 10 to 20ms from the start of the fault. The subtransient reactance is due to the flux casued
by the stator currents crossing the air gap and reaching the rotor surface or amortisseur / damper windings.
1 1 t/t
https://wiki.openelectrical.org/index.php?title=Anatomy_of_a_Short_Circuit 2/5
6/7/2017 Anatomy of a Short Circuit - Open Electrical
This period typically lasts 100 to 400ms after the subtransient period. The transient reactance occurs when all the
damping currents in the rotor surface or amortisseur / damper windings have decayed, but while the damping currents
in the field winding are still in action.
1
(3) Steady-state component: E2 sin(t)
Xd
The steady-state occurs after the transient period when all the damping currents in the field windings have decayed,
and essentially remains until the fault is cleared.
Putting these all together, we get the familiar near-to-generator short circuit waveform:
https://wiki.openelectrical.org/index.php?title=Anatomy_of_a_Short_Circuit 3/5
6/7/2017 Anatomy of a Short Circuit - Open Electrical
Zsc
https://wiki.openelectrical.org/index.php?title=Anatomy_of_a_Short_Circuit 4/5
6/7/2017 Anatomy of a Short Circuit - Open Electrical
E 2
(2) A steady state component: sin(t + )
Zsc 2
During the transient period, the peak transient current is typically 1.5 to 2.5 times higher than the peak steady state
current.