Sunteți pe pagina 1din 21

PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG

DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22A : DISTURBANCE FAULT RECORDER


NO DESCRIPTION REQUIREMENT PROPOSED AND GUARANTEE
1 Name : DFR (Disturbance Fault Recorder) DFR (Disturbance Fault Recorder)
2 Manufacture, country of manufacture : to be mentioned Qualitrol / Hathaway
3 Type : IDM+
4 Input :
Analog AC Input : Min. 16 18
Channel : (8 current, 8 voltage) 8 Current, 8 Voltage (2 Spare)
Voltage : 100/3 volt or according to existing secondary voltage 1003 Volt or According to existing secondary voltage
Current : 1 A or 5 A (compatible with eksisting) 1 A or 5 A (compatible with eksisting)
Burden : 1 VA < 0.5 VA
Error : 0.5 % 0.1% of full scale
Digital input : min. 16 channels for double busbar 64 Channels Modular and can be for double busbar
min. 24 channels for one and half breaker 64 Channels for one and half breaker
Wet & Dry Contact, Normally Open or Close Input, wet & dry contact, normally open or close input selectable by
Trigger on Active & return to normal software
5 Pre-Recording Time : 0.4 Sec (Adjustable) Pre-fault : Minimum 10ms - 10s (adjustable)
6 Recording Time : 10 Sec (Adjustable) 50 Sec (adjustable)
7 Recording
Analog
Voltage Element : Enable Enable
Current Element : Enable Enable
Digital Element : Enable Enable
8 Triger
- RMS Level Triger : V, I, P, Q, f V, I, P, Q, f
- Reated of change : V, I, f V, I, f
- Sub Cycle (For Power Quality) : Yes Yes
- Zero and Negatife Sequence. : Yes Yes
9 Contact : - Contact Input Debounce 20 msec Contact Input Debounce 0-1000 ms (adjustable), 1 ms in step
- Contact Rating relay 125 VDC or eksisting Contact Rating relay 35 to 250 VDC
10 Sampling rate : Min 128 samples per cycle (Selectable) 512 samples per cycle (32, 64, 128, 256, or 512 Selectable)

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 1 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22A : DISTURBANCE FAULT RECORDER


NO DESCRIPTION REQUIREMENT PROPOSED AND GUARANTEE
11 Power Quality Record:
Harmonic Recording. : According to IEC 61000-4-7 According to IEC 61000-4-7
Ability to measure harmonic and THD current and Ability to measure harmonic and THD current and voltage (up to
voltage (up to 40 thd) 50 thd rank)
Voltage Quality
- Range High : 105-125% Vn Step 0.1% 100.1 - 190 % Vn Step 0.1 %
- Range Low : 50-95 % Vn Step 0.1 % 0.1 - 99.9 % Vn Step 0.1 %
- Accuracy : 0.5 % of reading 0.1% of full scale
Current Quality
- Range High : Min 15xIn Step 0.1% Min. 20 x In Step 0.1 %
- Range Low : Min 0.01xIn Step 0.1 % 0.01 x In Step 0.1 %
- Accuracy : 0.5 % of reading 0.1% of full scale
Sag and Swells. : Yes (IEC 61000-4-30) Yes (IEC 61000-4-30 )
Flicker. : Yes (IEC 61000-4-15) Yes (IEC 61000-4-15 )
Frequensi.
- Range : -10%fn up to 5%fn. -10 % fn up to 5% fn
- Accuracy : 0.5 % 0.1% of full scale
Voltage unbalance
- Range : 1-5 % 1-5%
- Accuracy : 1% 0.15%
P&Q Accuracy : 0.5 % 0.2 % of power full scale
12 Memory Capacity (internal/external) : 16 MB- With Battery Backed RAM 16 GB Compact flash es standard
(Including Power Quality Data Loger). (for max.16 channels Analog, 32 events & min storage (for max. 18 channels Analog, 64 events & min storage for 10
for 10 days Power Quality Data) Days Power Quality Data)
Hard Disk (Ekternal disk/host PC) : 80 GB 80 GB (Host PC) / substation
13 Printer With Recording Paper : Yes Yes (one / substation)
(suitable for regular paper and cartridge)
14 Resolution Power Of A/D Conversion : 16 Bit 16 bit for Voltage and 20 bit for Current

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 2 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22A : DISTURBANCE FAULT RECORDER


NO DESCRIPTION REQUIREMENT PROPOSED AND GUARANTEE
15 Internal Clock
Base clock : Crystal Oscillator Yes
Date/time (year,month,day, hour, Minute, second) : Yes Yes
Stability up to 40 C : 0.1 sec/day Comply, Accuracy 100 ns with GPS Internal
16 Starting Unit : available Available
17 Fault Recorder Indication : available Available
18 Free Contacts (for alarm/watchdog) : available Available
19 External Time Sync. Facilities : GPS, IRIG-B port (include GPS & accessory). Internal module GPS, IRIG B port (include GPS & accessory
Accuracy 10 s. Accuracy 100 ns
20 Front Panel Key Pad And Display (Meter and status : Host PC (internal/external) Included Front Panel with 7 button Key Pad And LCD Display
Indication) (Meter and status Indication)
21 Automatic & Multitasking For Recording Printing, : Yes Yes
Transmit & Diagnostic
22 Cross Trigger & Time Sync For More Than One Fault : Yes Yes
Recorder
23 Self Test Mode : Yes Yes
24 Communication for Remote Down Load : Ethernet port, TCP/IP Ethernet Port, TCP/IP, USB, RS 232 (Serial)
25 Power Consumption
Standby : 150 VA 40 VA
Operating : 300 VA 40 VA
26 Insulating Resistance At 500 V Dc : 10 MW Comply
27 Dielectric Test For 50 Hz, 1 Min : 2000 V rms Tested to 2.5 kV (IEC 60255-5 Clause 6)
28 Voltage Withstand Surge : According to IEC 255-5-5 According to IEC 255-5-5
29 Electro Static Discharge : According to IEC 60255-22-2 According to IEC 60255-22-2
30 Vibration and Shock Test : According to IEC 60255-21-1,2 Vibration IEC 60255-21-1
Shock Test IEC 60255-21-2
31 Environment
- Operating Themperature. : 10-50C -5 to 50C
- Humidity : 90% 10-95% non condensing

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 3 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22A : DISTURBANCE FAULT RECORDER


NO DESCRIPTION REQUIREMENT PROPOSED AND GUARANTEE
32 Others :
Mounting : 19 Rack Mountable or moveable 19 Rack Mountable
Current probe and R Shunt (Direct Connection from CT) : High Class Accuracy High Class Accuracy
8 channel current probe (according number of bay and 8 Channel Internal Current Probe
current transformer ratio) / DFR and cable min 20 meter

Software - Original CD software of DFR&PQ - Original CD software of DFR&PQ


(For Operation and Maintenance) (For Operational and Maintenance ) (For Operational and Maintenance )
/Calibrating). /Calibrating).
- Minimum 3 years free upgrade. - Minimum 3 years free upgrade.
- Enable For Window XP. - Enable For Window XP.
- Coexist with another software (no crash/conflict) - Coexist with another software (no crash/conflict)

- Have ability to remote download, include - Have ability to remote download, include
automatic download, remote setting automatic download, remote setting
- Has help function. - Has help function.
- Have ability to Analyze Fault. - Have ability to Analyze Fault.
- Have ability to Analyze Power Quality. - Have ability to Analyze Power Quality.
Printer : Enable Enable
33 Data Loader With minimum requirement : With minimum requirement :
Microsoft Lastest Version Microsoft Windows 7 or Windows 10
Intel Core i5 Intel Core i5
RAM 4 GB RAM 4 GB
Hard Disk 500 GB Hard Disk 500 GB
Camera 1.3 MP Camera 1.3 MP
DVD-CDRW Combo Drive DVD-CDRW Combo Drive
Max 14"1 WXGA Max 14"1 WXGA
LAN/i.Link (IEEE1394)/SD Card slot/4 USB 2.0 . LAN/Modem/i.Link (IEEE 1394)/SD Card Slot/4 USB 2.0
port port, internal & external
Have communication port compatible with fault recorder
Have communication card.
34 Manual Book : Original Manual Book in english or bahasa (hard and Original Manual Book (hard and soft copy)
soft copy)
35 Guarantee : Min 3 (three) years free of charge Min 3 (three) years free of charge

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 4 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22A : DISTURBANCE FAULT RECORDER


NO DESCRIPTION REQUIREMENT PROPOSED AND GUARANTEE
36 Type and routine test certificates : required Yes
37 Catalog, drawing and other references : required Yes

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 5 of 21


A Signal Digital Input (1 DFR untuk 2 Bay)
- DFR dengan Fasilitas 64 Digital Input untuk bay Line 500 kV minimal harus terdiri dari :
Main 1 Protection Operated ( Distance 1) : LP A OPRT
Main 2 Protection Operated ( Distance 2 ) : LP B OPRT
DEF 1 Operated : DEF A
DEF 2 Operated : DEF B
CB 7Ax/Bx phasa A open : 7Ax/Bx R OPEN (ex: 7A1 R OPEN)
CB 7Ax/Bx phasa B open : 7Ax/Bx S OPEN
CB 7Ax/Bx phasa C open : 7Ax/Bx T OPEN
CB 7ABx phasa A open : 7ABx R OPEN
CB 7ABx phasa B open : 7ABx S OPEN
CB 7ABx phasa C open : 7ABx T OPEN
A/R 1 In Progress : A/R 1 OPRT
A/R 2 In Progress : A/R 2 OPRT
Carrier send from Distance Main 1 : LP A SEND
Carrier send from Distance Main 2 : LP B SEND
Carrier send from DEF Main1 : DEF A SEND
Carrier send from DEF Main 2 : DEF B SEND
Carrier Receive to Distance Main 1 : LP A RCV
Carrier Receive to Distance Main 2 : LP B RCV
Carrier Receive to DEF 1 : DEF A RCV
Carrier Receive to DEF 2 : DEF B RCV
Trip phasa R : TRIP R
Trip phasa S : TRIP S
Trip phasa T : TRIP T
Send DTT : DTT SEND
Receive DTT. : DTT RCV
CCP 1 operated : CCP A OPRT
CCP 2 operated : CCP B OPRT
CBF/SZP 1 7Ax/Bx Trip : CBF/SZP A 7Ax/Bx OPRT
CBF/SZP 1 7Ax/Bx Trip : CBF/SZP A 7Ax/Bx OPRT
CBF/SZP 2 7ABx Trip : CBF/SZP B 7ABx OPRT
CBF/SZP 2 7ABx Trip : CBF/SZP B 7ABx OPRT
CB Pole Discapancy : CB DISCRAPANCY
-DFR dengan Fasilitas 32 Digital Input untuk bay line 500 kV minimal harus terdiri dari:
Main 1 Protection Operated ( Distance 1) : LP A OPRT
Main 2 Protection Operated ( Distance 2 ) : LP B OPRT
CB 7Ax/Bx open : CB 7Ax/Bx OPEN
CB 7ABx open : CB 7ABx OPEN
A/R In Progress : A/R OPRT
Carrier send from Distance Main 1 : LP A SEND
Carrier send from Distance Main 2 : LP B SEND
Carrier send from DEF Main1/DEF2 : DEFA/B SEND
Carrier Receive to Distance Main 1 : LP A RCV
Carrier Receive to Distance Main 2 : LP B RCV
Carrier Receive to DEF 1/DEF2 : DEF A/B RCV
Send DTT : DTT SEND
Receive DTT : DTT RCV
CCP Operated : CCP OPRT
CBF/SZP 7Ax/7Bx Trip : CBF/SZP 7Ax/7Bx OPRT
CBF/SZP 7ABx Trip : CBF/SZP 7ABx OPRT

-DFR dengan Fasilitas 64 Digital Input untuk bay IBT 500 kV minimal harus terdiri dari :
Main 1 Protection Operated : MAIN PROT A
Main 2 Protection Operated : MAIN PROT B
REF 500 kV Operated : REF 500 OPRT
REF 150 kV Operated : REF 150 OPRT
Back Up Protection 500 kV Operated : OC 500 OPRT
Back Up Protection 150 kV Operated : OC 150 OPRT
Over Voltage Operated : OV OPRT
Bucholz Operated : BUCHOLZ
Jansen Operated : JANSEN
Thermal Relay Operated : THERMAL
Sudden Pressure Operate : SUDDEN PRESS
PMT 7ABx Open. : 7ABx OPEN
PMT 7ABx Close. : 7ABx CLOSE
PMT 7Ax or 7Bx Open. : 7Ax or 7Bx OPEN.
PMT 7Ax or 7Bx Close. : 7Ax or 7Bx CLOSE
PMT 150 kV Open : 150 kV OPEN
PMT 150 kV Close : 150 kV CLOSE
CCP 1 Operated. : CCP 1 OPRT
CCP 2 Operated : CCP 2 OPRT
CBF/SZP 1 7Ax or 7Bx Trip. : CBF/SZP 1 7Ax or 7Bx OPRT.
CBF/SZP 1 7Ax or 7Bx Trip. : CBF/SZP 1 7Ax or 7Bx OPRT
CBF/SZP 2 7ABx Trip. : CBF/SZP 2 7ABx OPRT
CBF/SZP 2 7ABx Trip. : CBF/SZP 2 7ABx OPRT
Spare. :
Spare. :
Spare :
Spare. :
Spare. :
Spare. :
Spare. :
Spare :
Spare. :

-DFR dengan Fasilitas 32 Digital Input untu bay IBT 500 kV minimal harus terdiri dari :
Main 1 Protection Operated : MAIN PROT A
Main 2 Protection Operated : MAIN PROT B
Back Up Protection 500 kV Operated : OC 500 OPRT
Back Up Protection 150 kV Operated : OC 150 OPRT
Over Voltage Operated : OV OPRT
Bucholz Operated : BUCHOLZ
Jansen Operated : JANSEN
Thermal Relay Operated : THERMAL
Sudden Pressure Operate : JANSEN
PMT 7ABx Open. : 7ABx OPEN
PMT 7Ax or 7Bx Open. : 7Ax or 7Bx OPEN.
PMT 150 kV Open : 150 kV OPEN
CCP 1 Operated. : CCP A OPRT
CCP 2 Operated : CCP B OPRT
CBF/SZP 7Ax/7Bx or B Trip. : CBF/SZP 7Ax/7Bx or B OPRT
CBF/SZP 7ABx Trip. : CBF/SZP 7ABx OPRT
- DFR dengan Fasilitas 64 Digital Input untuk 2 bay Line 150 kV (One & A Half Breaker) minimal harus terdiri dari :
Main 1 Protection Operated (Line Current/Distance 1) : LP OPRT
Back 2 Protection Operated (OCR Back Up) : OC OPRT
A/R 1 In Progress : A/R OPRT
Carrier send from Distance : LP SEND
Carrier Receive to Distance : LP RCV
Trip phasa A : TRIP R
Trip phasa B : TRIP S
Trip phasa C : TRIP T
CB 5Ax/Bx phasa A open : CB 5Ax/Bx R OPEN
CB 5Ax/B xphasa B open : CB 5Ax/Bx S OPEN
CB 5Ax/Bx phasa C open : CB 5Ax/Bx T OPEN
CB 5ABx phasa A open : CB 5ABx R OPEN
CB 5ABx phasa B open : CB 5ABx S OPEN
CB 5ABx phasa C open : CB 5ABx T OPEN
CBF/SZP 5Ax/5Bx Trip : CBF/SZP 5Ax/5Bx OPRT
CBF/SZP 5ABx Trip : CBF/SZP 5ABx OPRT
CCP 1 operated : CCP 1 OPRT
Send DTT : DTT SEND
Receive DTT. : DTT RCV.
CB Pole Discrapancy : CB DISCRAPANCY
Spare. :
Spare. :
Spare. :
Spare :
Spare. :
Spare. :
Spare. :
Spare. :
Spare :
Spare. :
Spare. :
Spare :
- DFR dengan Fasilitas 32 Digital Input untuk 2 bay Line 150 kV (One & A Half Breaker) minimal harus terdiri dari :
Main Protection Operated : LP OPRT
Back 2 Protection Operated (OCR Back Up) : OC OPRT
A/R 1 In Progress : A/R OPRT
Carrier send from Distance : LP SEND
Carrier Receive to Distance : LP RCV
CB 5Ax/Bx phasa A open : 5Ax/Bx R OPEN
CB 5Ax/B xphasa B open : 5Ax/Bx S OPEN
CB 5Ax/Bx phasa C open : 5Ax/Bx T OPEN
CB 5ABx phasa A open : 5ABx R OPEN
CB 5ABx phasa B open : 5ABx S OPEN
CB 5ABx phasa C open : 5ABx T OPEN
CBF/SZP 5Ax/5Bx Trip : CBF/SZP 5Ax/5Bx OPRT
CBF/SZP 5ABx Trip : CBF/SZP 5ABx OPRT
CCP operated : CCP OPRT
Send DTT : DTT SEND
Receive DTT. : DTT RCV.

- DFR dengan Fasilitas 64/32 Digital Input untuk 2 bay Line 150 kV (Double Bus) minimal harus terdiri dari :
Main Protection Operated : LP OPRT
Back 2 Protection Operated (OCR Back Up) : OC OPRT
A/R 1 In Progress : A/R OPRT
Carrier send from Distance : LP SEND
Carrier Receive to Distance : LP RCV
Trip phasa A : TRIP R
Trip phasa B : TRIP S
Trip phasa C : TRIP T
CB phasa A open : CB R OPEN
CB phasa B open : CB S OPEN
CB phasa C open : CB T OPEN
CBF/SZP Trip : CBF/SZP OPRT
Send DTT : DTT SEND
Receive DTT. : DTT RCV
Spare :
Spare. :
- DFR dengan Fasilitas 64 Digital Input untuk bay IBT/Trafo 150 kV (One & A Half Breaker) minimal harus terdiri dari :
Main Protection (DIFF) Operated. : MAIN PROT OPRT
Main Protection (REF HV) Operated. : REF HV OPRT
Main Protection (REF LV) Operated. : REF LV OPRT
Back Up Protection HV Operated. : OC HV OPRT
Back Up Protection LV Operated. : OC LV OPRT
Over Voltage Operated. : OV OPRT
Bucholz Operated. : BUCHOLZ
Jansen Operated. : JANSEN
Thermal Relay Operated. : THERMAL
Suddent Pressure Operated. : SUDDENT PRES
CB HV 5Ax/5Bx Open. : 5Ax/5Bx HV OPEN
CB HV 5Ax/5Bx Close. : 5Ax/5Bx HVCLOSE
CB HV 5ABx Open. : 5ABx HV OPEN
CB HV 5ABx Close. : 5ABx HV CLOSE
CB LV Open : CB LV OPEN
PMT LV Close. : PMT LV CLOSE.
CCP Operated : CCP OPRT
CBF/SZP 5Ax/5BxTrip : CBF/SZP 5Ax/5Bx OPRT
CBF/SZP 5ABxTrip : CBF/SZP 5ABx OPRT
CBF/SZP LV Trip. : CBF/SZP LV OPRT
Spare. :
Spare. :
Spare. :
Spare. :
Spare :
Spare. :
Spare. :
Spare. :
Spare. :
Spare :
Spare. :
Spare. :
- DFR dengan Fasilitas 32 Digital Input untuk bay IBT/Trafo 150 kV (One & A Half Breaker) minimal harus terdiri dari :
Main Protection (DIFF) Operated. : MAIN PROT OPRT
Main Protection (REF HV) Operated. : REF HV OPRT
Main Protection (REF LV) Operated. : REF LV OPRT
Back Up Protection HV Operated. : OC HV OPRT
Back Up Protection LV Operated. : OC LV OPRT
Over Voltage Operated. : OV OPRT
Bucholz Operated. : BUCHOLZ
Jansen Operated. : JANSEN
Thermal Relay Operated. : THERMAL
Suddent Pressure Operated. : SUDDENT PRES
PMT HV 5Ax/5Bx Open. : 5Ax/5Bx OPEN
PMT HV 5ABx Open. : 5ABx HV OPEN
PMT LV Open : CB LV OPEN
CCP Operated : CCP OPRT
CBF/SZP 5Ax/5BxTrip : CBF/SZP 5Ax/5Bx OPRT
CBF/SZP 5ABxTrip : CBF/SZP 5ABx OPRT

- DFR dengan Fasilitas 32 Digital Input untuk bay IBT/Trafo 150 kV (Double Bus) minimal harus terdiri dari :
Main Protection (DIFF) Operated. : MAIN PROT OPRT
Main Protection (REF HV) Operated. : REF HV OPRT
Main Protection (REF LV) Operated. : REF LV OPRT
Back Up Protection HV Operated. : OC HV OPRT
Back Up Protection LV Operated. : OC LV OPRT
Over Voltage Operated. : OV OPRT
Bucholz Operated. : BUCHOLZ
Jansen Operated. : JANSEN
Thermal Relay Operated. : THERMAL
Suddent Pressure Operated. : SUDDENT PRES
CB HV Open. : CB HV OPEN
CB HV Close : CB HV CLOSE
CB LV Open : CB LV OPEN
CB LV Close : CB LV CLOSE
CBF/SZP Trip : CBF/SZP OPRT
Spare : Spare
B Sensor
1. 3UV channel : 80%Vn
2. 1OV channel : 105%Vn
3. 3OC channel : 120% In CT Line or 100% In Trafo
4. 1OC channel : 0.2-0.6%In
5. Uf Channel : 49 Hz
6. Of Channel : 51 Hz
C Duration
1. Pre Fault : 100 ms
2. Fault : Flexible
3. Post Fault : 100 ms
PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22b : FAULT RECORDER PANEL


No DESCRIPTION REQUIRED PROPOSED AN
1. Manufacturer / country of origibn to be mentioned DFR PANEL
2. Type to be mentioned PT. Nobi Putra Angkasa
3. Quantity 1 unit 1 unit
4. Panel type Indoor, equipped with front door (safety glass door) and rear door (according to Indor, equipped with front door (safety glas
available space) space

5. Dimension (H x W x D) 2200 x 800 x 800 mm or refer to existing size


( HxWxD) 2200 x 600 x 800 mm or refer to
6. Panel Protection Index IP 53
IP 55
7. Colour Paint RAL 7032 or refer to existing colour
RAL 7032
8. Earthing Yes
Yes
9. Heating Installed a heating resistor, controlled by a thermostat for panel.
Haeter and Thermostat
10. Lighting Supplied with a light fitting (20 Watt), controlled by door switch. Supplied with a light fitting (20 Watt), contr
11. Material of cubicle Steel sheet with thickness 2 mm. Steel sheet with thickness 2 mm (non corro
Alumunium special alloy 6061-T6
12. Cable wiring for In 1 A or 5 A Function Colour Type and Size
Control Grey NYAF 1.5 mm2 Comply
DC Supply Grey NYAF 2.5 mm2 Comply
AC 220 V Yellow NYAF 2.5 mm2 Comply
AC from PT Red (R), Yellow (S), Blue (T), Black (N) NYAF 2.5 mm 2
Comply
AC from CT Red (R), Yellow (S), Blue (T), Black (N) NYAF 4 mm2 NYAF 4 mm (for use R Shunt)

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 14 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22b : FAULT RECORDER PANEL


No DESCRIPTION REQUIRED PROPOSED AN
Ground Green-Yellow NYAF 4 mm 2
Comply

13. Wiring marking The marking is hot marker type; All cores of all wires must have marked at both ends Comply
which each end is indicating the terminal start and end numbers.

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 15 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22b : FAULT RECORDER PANEL


No DESCRIPTION REQUIRED PROPOSED AN
14. Terminal block For CT 6 mm with short link (equal Phoenix)
2
6 mm with short link (with Weidmuller
or 2.5 mm with Entrelec (for current us
For PT 4 mm2 with open link (equal Phoenix) 4 mm2 with open link (equal Phoenix or
For 2.5 mm2 with knife switch (equal Phoenix) 2.5 mm with knife switch (equal Phoen
Control
15. Wiring and cabling way Use wiring ducts. Use wiring ducts.
16. Others

- Auxiliary relay Yes


- Test Block for each relay Socket plug with 14 x 2 (in and out) terminals Socket plug with 14 x 2 (in and out)
terminals
For CT 4 terminals For CT 4 terminals
For PT 4 terminals For PT 4 terminals
For DC supply 2 terminals For DC supply 2 terminals
Tripping 2 terminals Tripping 2 terminals
Alarm 2 terminals Alarm 2 terminals
- Test plug for each panel 1 unit 1 unit
- NFB PT 3 Pole + auxiliary contact Min 6 Amp.
MCB PT 6 Amp
- NFB DC 2 Pole + auxiliary contact Min 20 Amp.
MCB DC 6 Amp or 20 Amp
- NFB AC 1 Pole + auxiliary contact Min 2 Amp.
MCB AC 6 Amp
17. Drawing :
- Approval drawing Submitted Submitted
- As built drawing 3 (three) sets 3 (three) sets
18. Factory Test Witness by user Witness by user

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 16 of 21


PEMBANGUNAN GIS 150 KV SUMMARECON GADING SERPONG
DAFTAR ISIAN 4 : TECHNICAL PARTICULARS AND GUARANTEES

TPG. 4.22b : FAULT RECORDER PANEL


No DESCRIPTION REQUIRED PROPOSED AN
- Individual test
- Function test

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 17 of 21


SED AND GUARANTEED

ety glass door) and rear door ( according to available)

refer to existing size .

t), controlled by door switch

on corrosive) with

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 18 of 21


SED AND GUARANTEED

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 19 of 21


SED AND GUARANTEED
muller or Entrelec or equal Phoenix for R Shunt)
rrent use CT Probe external)
oenix or with weidmuller or Entrelec)
l Phoenix or with weidmuller or Entrelec)

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 20 of 21


SED AND GUARANTEED

BIDDER'S SIGNATURE(............................................) MANUFACTURER'S SIGNATURE(...........................................) 21 of 21

S-ar putea să vă placă și