Sunteți pe pagina 1din 2

VOLUMEN CIRCUITO HIDRAULICO

1 Volumen agua colectores


Tipo de colector n colectores Volumen (l)/captador Volumen total (l)
Plano 25 2.5 62.5
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
62.5 62.5

2 Volumen agua intercambiadores


Dato 25 25

3 Volumen agua tuberias de cobre


Dimetro Longitud Volumen unitario Volumen total
(mm) (m) (l/m) (l)
12 0 0.093 0.00
15 0 0.151 0.00
18 0 0.254 0.00
22 5 0.311 1.56
28 16 0.531 8.50
35 0 0.809 0.00
42 0 1.15 0.00
54 0 2.03 0.00
63 0 3.09 0.00
80 0 4.4 0.00
100 0 7.73 0.00

Total 10.05 10.05

Total volumen en circuito ( l ) 97.55


Presin mnima del circuito primario (kg/cm2) 1.50
Presin mxima del circuito primario (kg/cm2) 3.50 Factor de presin (Fp)= 2.35
Distancia desde parte superior de captadores hasta vaso de expansin (m) 2 Vaso de expansin cerrado con membrana (l) = 9.86
CALCULO DE PERDIDAS DE CARGA EN CIRCUITOS HIDRAULICOS
Caudal(l/h.m2) 50
Areaunitariacaptador 1.91
Nmerodecaptadores 2
Nbaterasenserie 1 (1, si todas en paralelo)
Caudalglobal(l/h) 191
Caudalunitario(l/h) 95.5

1 PERDIDAS DE CARGA EN TUBERIAS Y ACCESORIOS


Nmero Nmero Longitud Caudal Dimetro ext Velocidad Dimetro int mm.c.a./m mm.c.a. mm.c.a. N vlv. N codos N T90 N vlv. Longitud Total tramo
tramo captadores (m) (l/h) (mm) (m/s) (mm) tramo acumulado retencin esfera equivalente (m) accesorios (mm.c.a.)
1 45 15 4297.5 42 0.95 40 26.36 395.42 395.42 1 6 2 2 16.58 437.07
2 1 15 95.5 22 0.08 20 0.67 10.04 405.46 0 2 0 1 1.49 1.00
3 1 10 95.5 22 0.08 20 0.67 6.69 412.15 0 2 0 1 1.49 1.00
4 5 7 477.5 22 0.42 20 13.18 92.28 504.43 0 0 1 0 0.90 11.87
5 10 7 955 28 0.50 26 13.26 92.81 597.25 0 0 1 0 1.10 14.59
6 15 5 1432.5 35 0.47 33 8.80 43.98 641.23 0 0 1 0 1.52 13.37
7 20 5 1910 35 0.62 33 14.99 74.93 716.16 0 0 1 0 1.52 22.78
8 25 50 2387.5 42 0.53 40 8.88 443.79 1,159.94 0 0 1 0 1.75 15.53
9 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
10 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
11 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
12 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
13 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
14 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
15 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
16 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
17 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
18 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
19 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
20 0 0 0 0 0.00 0 0.00 0.00 1,159.94 0 0 0 0 0.00 0.00
Total prdidas de carga en tuberias (mm.c.a. 1,159.94 Total prdidas de carga en valvu 517.20

2 PERDIDAS DE CARGA EN COLECTORES

N de colectores por batera 2


Longitud de la base del colector (m) 1
Dimetro de tubera exterior del colector 22
Caudal batera colectores 191.00
Prdida de carga longitud del captador (mmca) 10
Velocidad (m/s) 0.17
Dimetro interior 20
mmca/m 2.42

Prdidas de carga en colectores (mm.c.a.) 14.83

3 PERDIDAS DE CARGA EN INTERCAMBIADOR

De tablas (mm.c.a.) 1500 1,500.00

Total prdidas de carga (mm.c.a.) 3,191.97