Transformer Data:
Rated capacity = 73 MVA
HV side rated voltage (at nominal tap) = 110 kV
HV side rated voltage (at lowest tap) = 123.75 kV
HV side rated voltage (at highest tap) = 88 kV
LV side rated voltage = 15 kV
Vector Group = YNyn0 (d5)
Transformer impedance = 30.31% at 73MVA
At HV side-110KV
=
3
73000
=
3 110
110 = 383.1506
At HV side-123.75 KV
75
=
3 123.75
75000
=
3 123.75
123.75 = 340.5783
At HT Side- 88KV
75
88 =
3 88
75000
=
3 88
88 = 478.9383
CT selection is 500:1
AT LT Side-15KV
75
=
3
75000
=
3 15
= 2809.771
% = 30.31
HT:
=
% 3
73000
=
30.31% 3 110
= 1264.106
LT:
=
% 3
73000
=
30.31% 3 15
= 9270.113
Relay Setting (Primary of Transformer)
Our CT ratio on Primary is 500:1
383.1506
Secondary Current = = = 0.766301
500
= = 100% = 1
1264.106
500
= =
1
= 2.53
(0.02 1)
=
0.14
= 0.2
For I>>,
= 8
= 8 1 = 8( 8 500 = 4000)
= 0
Earth setting,
> = =
= .
= .
= =
> % = .
= = > = 100% = 1
9270.113
= 4000
1
= 2.317528
(0.02 1)
=
0.14
2.3175280.02 1
= 1.2
0.14
= 0.145
FOR I>>,
= 8
= 0
Earth setting,
We have neutral to ground resistance at secondary of this transformer, NGR is current limiter device.
NGR=5.31 ohms
=
3
1000
= 13.8
3 5.31
= 1500.458
Our CT at Secondary side is 4000:1, we select 10% to 20% of Current of NGR as our >,
= 10%
150
> = 0.0375
4000
=
1500
= = 10
150
TMS,
(0.2 1)
=
0.14
100.02 1
= 1.4
0.14
= 0.471285
Our Relay setting at secondary side will be,
> = 1
= 0.145
= 1.2
= 8
= 0
= 0.0375
= 0.471285
We have NGR=5.1ohms
Voltage=13.8KV
= 10%
150
> = 0.5
300
> 1.10
= 10%
> = 0.1 1500 = 150
150
> = 0.5
300
> 1.40
Transformer Data:
Rated capacity = 73 MVA
HV side rated voltage (at nominal tap) = 110 kV
HV side rated voltage (at lowest tap) = 123.75 kV
HV side rated voltage (at highest tap) = 88 kV
LV side rated voltage = 15 kV
Vector Group = YNyn0 (d5)
Transformer impedance = 30.31% at 73MVA
At HV side-110KV
=
3
73000
=
3 110
110 = 383.1506
CT Ratio 500:1,
383.1506
110 = = 0.766301
500
At HV side-123.75 KV
75
=
3 123.75
75000
=
3 123.75
123.75 = 340.5783
CT Ratio is 500:1,
340.5789
123.75 =
500
123.75 = 0.68115
At HT Side- 88KV
75
88 =
3 88
75000
=
3 88
88 = 478.9383
CT selection is 500:1
478.9383
88 =
500
88 = 0.957877
1 1
= 2/(( ) + (( ))
123.75 88
2
=
1 1
( ) + (88)
123.75
= 102.8571
73000
=
(3 102.8571)
= 409.7583
123.75
=
409.7583 340.5783
= 100%
409.7583
= = 16.883%
CT is 500:1,
7583
= 409.
500
= 0.819517
At 123.75KV,
123.75
123.75 =
0.6811
=
0.819517
123.75 = 0.835992
At 88KV,
88
88 =
0.957877
=
0.819517
88 = 1.168722
88 = 88
= 1.168722 1
88 = 0.168722
88 = 0.168722
88 = 0.168722 0.819517
88 = 0.138271
88 = 88 + 1
= 1.168722 + 1
88 = 2.168722
88 = 2.168722 0.819517
88 = 1.777305
123.75 = 123.75
= 0.835992 1
123.75 = 0.164008
123.75 = 0.164008
= 0.164008 0.819517
123.75 = 0.134407
123.75 = 123.75 +
= 0.835992 + 1
123.75 = 1.835992
123.75 = 1.835992
AT LT Side-15KV
75
=
3
75000
=
3 15
= 2809.771
CT Ratio is 4000:1
So,
2809.771
=
4000
= 0.702443
>= 0.2
123.75 = 1.835992
As per definition,
0.2
=
2.5
= 8
1
2
3
.
But,
Voltages are 110KV, 123.75KV and 88KV and our calculated voltage 102.8571KV,
At 88KV, Tap is
88 102.8571
= 100%
88
= 16.8831%
At 123.75KV, Tap is
(123.75 102.8571)
= 100%
123.75
= 16.8831%
So keeping this in mind and adding 5% for CT errors, I took initial slope setting as
= 16.8831 + 16.8831 + 5
1 = 38.7662%
1 = 0
I select slope
= %, and our =
I need to select 2 , I put this situation 2 > , I select = 2.1 now equation is
> 2 (2 1 )2 + 1
2 > 6.4
So our = %, and = .
For high set ,
Transformer Data:
Rated capacity = 73 MVA
HV side rated voltage (at nominal tap) = 110 kV
HV side rated voltage (at lowest tap) = 123.75 kV
HV side rated voltage (at highest tap) = 88 kV
LV side rated voltage = 15 kV
Vector Group = YNyn0 (d5)
Transformer impedance = 30.31% at 73MVA
At HV side-110KV
=
3
73000
=
3 110
110 = 383.1506
= 8 383.1506
= 4597.807
CT is 500:1,
4597.807
=
500
= 9.19
2nd condition is about short current, we take 130% of short circuit for differential high stage,
130% 383.1506
=
31.31%
= 1643.338
CT is 500:1,
1643.338
=
500
= 3.2866
= 10