Model: C900 D6
Frequency: 60
Fuel type: Diesel
Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 925 (1156) 835 (1044)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 19.0 31.6 45.2 60.2 15.7 27.9 40.6 54.6
L/hr 72 120 171 228 59 106 154 207
Fuel flow
Maximum fuel flow, L/hr 570
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, C 66
2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS367d-CPGK (5/15)
Air Standby Rating Prime Rating
3
Combustion air, m /min 76.2 71.4
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 196.8 180.0
Exhaust gas temperature, C 481 464
Maximum exhaust back pressure, kPa 10.1
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS367d-CPGK (5/15)
Alternator data
Connection Temp rise C Duty Alternator Voltage
Wye, 3-phase 150/125 C S/P HC6J 380-480V
Ratings definitions
Emergency standby power Limited-time running power Base load (continuous)
(ESP): (LTP): Prime power (PRP): power (COP):
Applicable for supplying power to Applicable for supplying power Applicable for supplying power Applicable for supplying power
varying electrical load for the to a constant electrical load for to varying electrical load for continuously to a constant
duration of power interruption of limited hours. Limited Time unlimited hours. Prime Power electrical load for unlimited
a reliable utility source. Running Power (LTP) is in (PRP) is in accordance with hours. Continuous Power (COP)
Emergency Standby Power (ESP) accordance with ISO 8528. ISO 8528. Ten percent overload is in accordance with ISO 8528,
is in accordance with ISO 8528. capability is available in ISO 3046, AS 2789, DIN 6271
Fuel Stop power in accordance accordance with ISO 3046, and BS 5514.
with ISO 3046, AS 2789, AS 2789, DIN 6271 and
DIN 6271 and BS 5514. BS 5514.