Documente Academic
Documente Profesional
Documente Cultură
Sponsor
substationscommittee
of the
IEEE Power E n g i " g society
Abstract: IEEE C37.123-1991covers the technical requirements for the design, fabrication, testing,
and installation of a gas-insulated substation (GIs); its intent is advisory. This guide discusses
parameters to be supplied by the purchaser and technical requirements for the design, fabrication,
testing, and installation t o be furnished by the manufacturer. Environmental conditions, general
and specific equipment requirements, and a proposal data sheet form are included to aid the user.
Keywords: gas-insulated substation, GIs, GIS equipment, GIS testing, GIS design, GIS
installation
ISBN 1-55937-162-5
No part of this publication may be reproduced in any form,
in a n electronic retrieval system or otherwise,
without the prior written permission of the publisher.
IEEE Standards documents are developed within the Technical
Committees of the IEEE Societies and the Standards Coordinating
Committees of the IEEE Standards Board. Members of the committees
serve voluntarily and without compensation. They are not necessar-
ily members of the Institute. The standards developed within IEEE
represent a consensus of the broad expertise on the subject within the
Institute as well as those activities outside of IEEE that have
expressed an interest in participating in the development of the
standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to produce,
test, measure, purchase, market, or provide other goods and services
related to the scope of the IEEE Standard. Furthermore, the viewpoint
expressed at the time a standard is approved and issued is subject to
change brought about through developments in the state of the art and
comments received from users of the standard. Every IEEE Standard
is subjected to review at least every five years or revision or reafir-
mation. When a document is more than five years old and has not
been reaffirmed, it is reasonable to conclude t h a t its contents, al-
though still of some value, do not wholly reflect the present state of the
art. Users are cautioned to check to determine t h a t they have the latest
edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE.
Suggestions for changes in documents should be in the form of a pro-
posed change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the
meaning of portions of standards as they relate to specific applica-
tions. When the need for interpretations is brought t o the attention of
IEEE, the Institute will initiate action t o prepare appropriate re-
sponses. Since IEEE Standards represent a consensus of all con-
cerned interests, it is important to ensure that any interpretation h a s
also received the concurrence of a balance of interests. For this reason
IEEE and the members of its technical committees are not able t o pro-
vide an instant response to interpretation requests except in those
cases where the matter has previously received formal consideration.
Comments on standards and requests for interpretations should be
addressed to:
Secretary, IEEE Standards Board
445 Hoes Lane
P.O. Box 1331
Piscataway, N J 08855-1331
USA
This guide is issued to aid users in developing and preparing specifications for gas-insulated
substations and equipment; its intent is advisory. The guide covers parameters to be supplied by
the purchaser and technical requirements for the design, fabrication, testing, and installation to
be furnished by the manufacturer. The purchaser should revise any paragraph as appropriate,
delete any paragraph that does not apply t o his or her needs, and incorporate any details to make
the specification conform to his or her standard practices and requirements.
Proposal Data of Section 4, which should be completed by each bidding manufacturer, is provided
in order t o elicit uniform answers from all the providers and t o facilitate technical proposal
evaluation.
J.J.Dodds, Chair
P. C. Bolin M. A. Hick J. E. McConnell
R. H. Bower J. E. Holladay A. Mickevicius
J. A. Buchsbaum A. A. Leibold K. B. Miners
J. L. Charney H. Martensson K. Pettersson
J. Grzan R. Matulic J. F. Quinata
E. I. Hahn B. Sojka
The Gas-Insulated Substations Subcommittee of the IEEE Substations Committee that reviewed
and approved this guide had the following members:
The Accredited Standards Committee on Power Switchgear, C37, that reviewed and approved this
document, had the following members at the time of approval:
The final conditions for approval of this standard were met on January 14, 1991. This standard
was conditionally approved by the IEEE Standards Board on December 6, 1990, with the following
membership:
*Member Emeritus
contmlb
1. I n t r o d u c t i o n ............................................................................................. 7
1.1 Scope .............................................................................................. 7
1.2 References ....................................................................................... 7
1.3 Service Conditions .............................................................................. 9
1.4 Equipment and Service Furnished by the Purchaser ....................................... 9
1.5 Equipment and Services Furnished by the Manufacturer ................................ 10
3. D e t a i l e d R e q u i r e m e n t s ............................................................................... 13
3.1 Circuit Breaker ................................................................................ 13
3.2 Disconnect and Grounding Switches ........................................................ 14
3.3 Gas S y s t e m ..................................................................................... 15
3.4 SFs-to-Air Bushings ........................................................................... 15
3.5 Potheads ......................................................................................... 16
3.6 Transformer and Reactor Bushing Adapters .............................................. 16
3.7 Current Transformers ........................................................................ 16
3.8 Inductive Voltage Transformers ............................................................ 16
3.9 Surge Arresters ................................................................................ 17
3.10 Capacitor Voltage Transformers ............................................................ 17
3.11 Local Control Cabinets ........................................................................ 17
9
IEEE
C37.123-1991 IEEE GUIDE TO SPECIFICATIONS FOR
[SI ANSI C37.12-1981, American National [171 IEEE C37.010-1979 (Reaff. 19881, IEEE Ap-
Standard Guide to Specifications for AC High- plication Guide for AC High-Voltage Circuit
Voltage Circuit Breakers Rated on a Symmet- Breakers Rated on a Symmetrical Current
rical Current Basis and a Total Current Basis (ANSI).4
Basis.
[l8] IEEE C37.011-1979 (Reaff. 1988), IEEE Ap-
[71 ANSI C37.32-1990, American National plication Guide for Transient Recovery Volt-
Standard for Switchgear-High-Voltage Air age for AC High-Voltage Circuit Breakers
Switches, Bus Supports, and Switch Acces- Rated on a Symmetrical Current Basis
sories-Schedules of Preferred Ratings, Man- (ANSI).
ufacturing Specifications, and Application
Guide. [19] IEEE C37.012-1979 (Reaff. 1988), IEEE Ap-
plication Guide for Capacitance Current
[81 ANSI C63.2-1987, American National Switching for AC High-Voltage Circuit
Standard for Electromagnetic Noise and Field Breakers Rated on a Symmetrical Current
Strength, 1 0 KHz to 40 GHz Specifications. Basis (ANSI).
[91 ANSI Y14.15-1966 (Reaff. 1988), American [20] IEEE C37.04-1979 (Reaff. 1988), IEEE
National Standard Electrical and Electronic Standard Rating Structure for AC High-Volt-
Diagrams. age Circuit Breakers Rated on a Symmetrical
Current Basis (ANSI).
[lo1 ANSVNAAMM MBG 531-1988, Metal Bar
Grating Manual. [21] IEEE C37.082-1982 (Reaff. 1988), IEEE
Standard Methods for the Measurement of
[ll] ASTM A123-89, Specification for Zinc Sound Pressure Levels of AC Power Circuit
(Hot-Dip Galvanized) Coatings on Iron and Breakers (ANSI).
Steel Products.2
[223 IEEE C37.09-1979 (Reaff. 1988), IEEE
[121 ASTM A501-88, Specification for Hot- Standard Test Procedure for AC High-Voltage
Formed Welded and Seamless Carbon Steel Circuit Breakers Rated on a Symmetrical
Structured Tubing. Current Basis (ANSI).
1131 ASTM A659-90, Specification for Steel, [231 IEEE C37.1-1987, IEEE Standard Defini-
Sheet and Strip, Carbon (0.16 Maximum t o 0.25 tion, Specification, and Analysis of Systems
Maximum Percent) Hot-Rolled Commercial Used for Supervisory Control, Data Acquisi-
Quality. tion, and Automatic Control.
[141 ASTM D2472-81, Specification for Sulphur [241 IEEE C37.2-1987, IEEE Standard Electrical
Hexafluoride. Power System Device Function Numbers.
U51 IEC 376 (19711, Specification and Accep- [251 IEEE C37.30-1971 (Reaff. 1987), IEEE
tance of New Sulphur H e x a f l ~ o r i d e . ~ Standard Definitions and Requirements for
High Voltage Air Switches, Insulators, and
[16] IEC 517 (1986), Gas-Insulated Metal- Bus Supports (ANSI).
Enclosed Switchgear for Rated Voltages of
72.5 kV and Above. [261 IEEE C37.34-1971 (Reaff. 19871, IEEE
Standard Test Code for High-Voltage Air
'ASTM publications are available from ASTM, Switches (ANSI).
Customer Service Department, 1916 Race Street,
Philadelphia, PA 19103, USA.
31EC publications are available from IEC Sales
Department, Case Postale 131,3 rue de Varemb6, CH 1211,
Geneve 20, SwitzerlandSuisse. IEC publications are also 41EEE publications are available from the Institute of
available in the United States from the Sales Department, Electrical and Electronics Engineers, Service Center, 445
American National Standards Institute, 11 West 42nd Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331,
Street, 13th Floor, New York,hT 10036, USA. USA.
10
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991
[271 IEEE C37.38-1989, IEEE Standard for Gas- 1.2.2 In the event of conflict between the ref-
Insulated Metal-Enclosed Disconnecting, In- erenced standards, the drawings of the user,
terrupter, and Grounding Switches. and his or her specification, or between stan-
dards issued by different authorities, the
[281 IEEE C37.122-1983, IEEE Standard Gas- manufacturer shall notify the purchaser and
Insulated Substations. secure written clarification a s t o what is ac-
ceptable before proceeding with the work.
1291 IEEE C57.13-1978 (Reaff. 1986), IEEE
S t a n d a r d Requirements for I n s t r u m e n t 1.3 Conditions
Transformers (ANSI). 1.3.1 All apparatus shall be capable of
satisfactory operation in t h e following
[301 IEEE C62.2-1987, IEEE Guide for the Appli- environment:
cation of Gapped Silicon-Carbide Surge Ar-
resters for Alternating-Current Systems Environmental:
(ANSI).
Indoor or outdoor:
[311 IEEE C62.11-1987, IEEE Standard for Elevation above sea
Metal-Oxide Surge Arresters for AC Power level: m
Circuits (ANSI). Maximum ambient
temperature:
E321 IEEE 21-1976, IEEE General Requirements Minimum ambient
and Test Procedures for Outdoor Apparatus temperature: -"C
Bushings (ANSI). Humidity (average): %
Wind velocity: km/hr
E331 IEEE 24-1984, IEEE Standard Performance Solar radiation: WIm2
Characteristics and Dimensions for Outdoor Maximum ice loading: mm
Apparatus Bushings (ANSI). Maximum uplift: daN
Maximum impact: daN
[341 IEEE 48-1990, IEEE Standard Test Proce- Seismic:
dures and Requirements for High-Voltage Air quality:
Alternating-Current Cable Terminations Special environmental
(ANSI). considerations:
11
IEEE
C37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR
12
EEE
GAS-INSULATED SUBSTATION EQUIPMENT C37123-1991
13
IEEE
C37.123-1991 IEEE GUIDE TO SPECIFICATIONS FOR
joining enclosures bolted or bonded together provisions shall be made and described to pre-
and grounded. clude the entry of foreign materials into the
2.2.9 As much a s possible, parts shall be of gas space.
standard manufacture with interchangeable 2.2.17 Structures required t o support the
parts and assemblies. equipment, and platforms and walkways for
2.2.10 Pressure relief devices, if required, operation and maintenance access t o operat-
shall be vented to provide a safe environment ing and monitoring devices, shall be designed
for field personnel and equipment during op- to permit access without use of special devices
eration. The bursting pressure of the relief de- or portable ladders. All structures, stairs, plat-
vice shall be effectively coordinated with the forms, and walkways shall conform to OSHA
rated gas pressure and pressure rise due to regula ti o n s.
arcing a s described in the section of IEEE 2.2.18 Ground pad terminals shall be located
(337.122-1983 E281 describing pressurized en- to permit proper connection t o the station
closure requirements. ground grid and to minimize external bus en-
2.2.11 Expansion and installation align- closure voltage gradient to a safe limit.
ment shall be considered in the design of the
bus and the enclosure. If required, expansion
joints shall be provided with compensators for 2.3 Miscellaneous Equipment and Work. The
the enclosure and sliding plug-in contacts for manufacturer shall furnish, but not be limited
the conductor. to providing, the following additional items
2.2.12 Support insulators shall be used to required for a complete installation:
maintain the conductor and enclosure in the
proper relation. There shall be two types of All ladders, platforms, stairs, walk-
support insulators-barrier insulators, which ways, and support necessary t o operate
are employed to isolate gas compartments and and maintain all equipment safely and
nonbarrier insulators, which allow the gas eff i c i en tl y .
pressure t o equalize. All supporting structures for the GIS
2.2.13 Connections between adjacent con- equipment, except concrete foundations
ductor sections shall be made by means of and associated parts such a s anchor
plug-in type contacts. Shields shall be placed to bolts, beams, etc. Sufficient attachment
capture metallic particles that may result from points and equipment loadings to the ap-
contact rubbing. Field welding of the conduc- paratus and concrete foundations shall
tor is not acceptable, except when required for be furnished to ensure successful instal-
special cases of extension, repair, or retrofit. lation, with required clearances, while
2.2.14 Components outside the SFs environ- taking into account thermal expansion
ment shall be installed in weatherproof enclo- and contraction.
sures for outdoor installation. Flexible joints in all equipment sup-
2.2.15 Shipping sections shall be joined in plied a s required to ensure continuity of
the field using either bolted, gasketed flange service d u r i n g t h e r m a l expan-
connections o r welded connections of the en- sion/contraction and vibration. Flexi-
closure. Flanged connections shall have a gas ble joints may also be provided to allow
seal between the flange surfaces. A second more efficient maintenance.
seal ring, sealants, or other suitable means Control and indication systems, includ-
may be used to protect the gas seal from the ex- ing local control cabinets.
ternal environment. Connections, including Grounding provisions for connection t o
bolts and nuts, shall be adequately protected the ground grid of the owner.
from corrosion and shall be easily accessible Wiring and means for wiring between
with the proper tools. individual items of supplier-furnished
2.2.16 Where necessary, and agreed to by the equipment.
purchaser, field-welded connections may be Nameplates for each piece of equipment.
used between major fixed components t o per- Gas system, including density moni-
mit length and angular adjustments t o com- tors and sufficient gas to put the equip-
pensate for construction tolerances. Where ment into service.
field welding is used to join the enclosures, Special tools.
14
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991
(10) External surface preparation and coat- - Functional tests on control and indica-
ing, if specified. Color may affect ther- tion circuits
mal rating. If equipment is derated due - Moisture measurement
t o enclosure color, the user must be in-
formed of the new rating in the proposal. 2.4.3 Field Test. The following field
tests shall be performed a s a minimum
2.4 Tests. The tests shall verify that all com- requirement:
ponents of the GIS perform satisfactorily both
electrically and mechanically a t the specified - Gas leakage test
rating. The tests shall establish t h a t produc- - Operational test
tion sections have been properly assembled - Gas moisture measurement
and that they have essentially the same char- - Resistance test of conductor
acteristics as those sections subjected to design - Current transformer testing
tests. - High-voltage tests
2.4.1 Design or Type Test (Refer to ANSI - Control and installation wiring checks
Standards). The following design test shall - Inductive voltage transformer tests
have been done for the equipment to be
delivered: 2.5 Shipment and Installation
2.5.1 All equipment shall be suitably packed
Impulse withstand voltage [Basic Im- and protected during shipment. Each shipping
pulse Level (BIL) and (Switching Im- unit shall be sealed in a clean, dry condition
pulse Level (SIL) if applicable] with leak-tight shipping covers securely
Power frequency withstand voltage mounted for shipment. All covers t o be re-
Circuit breaker and disconnect switch moved during installation shall be clearly
open -gap withstand voltage marked. Each shipping section shall be care-
Rated continuous-current carrying tests fully sealed and filled with dry gas t o a
Short-time current rating test slightly positive pressure to prevent the en-
Current switching test trance of moisture and contamination. he
Mechanical operation tests supplier shall notify the user whether the ship-
Pressure tests ping sections contain SF6 o r another type of
Circuit breaker tests (refer to ANSI dry gas.
standards) 2.5.2 Components requiring indoor storage
Disconnect switching tests shall be so identified. The manufacturer shall
Instrument transformer tests provide copies of complete, detailed, cus-
tomized instructions for storage, installation,
2.4.2 Production Test. Production tests shall operation, and maintenance of the equipment.
be made in the course of component assembly 2.5.3 Long-term storage instructions shall
and a t the complete or shipping assembly state. be provided, if specified.
Tests shall include a t least the following: 2.5.4 A competent, experienced service
engineer from the manufacturer shall be pre-
Circuit breaker test per IEEE C37.09- sent a t the job site for technical guidance and
1979 E221 direction throughout the installation and test-
Pressure test on all individual enclo- ing of the equipment.
sures and barrier insulators
Gas leak tests of enclosure and barrier
insulators 3.Detailed Requirements
Mechanical operation test
Low-voltage wiring test
Voltage drop measurement of the con- 3.1 Circuit Breakers
ductor and contacts 3.1.1 Circuit breakers shall be the SF6 gas-
Power frequency withstand voltage insulated type, dead tank design, and shall
Partial discharge test of insulators have the ratings a s specified.
and/or shipping sections 3.1.2 The breaker shall have ratings de-
CT and VT tests scribed in IEEE C37.122-1983 [281 and specific
15
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONS FOR
16
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991
voltages of up to 1 0 kV (optional 2.5 kV) or 200 - Each terminal position between adja-
A to be applied t o the conductor without remov- cent breakers.
ing SF6 gas or other components, except for - Each main bus or bus sections.
ground shunt leads.
3.2.11 The listed operation modes shall be Other parts of the GIS shall be divided into a
specified for special grounding applications: suitable number of zones or included in the
above zones.
(1) Fast-acting ground for cable grounding 3.3.7 For single-phase bus construction;
(2) Fault initiating (fast-acting ground) single-phase or three-phase gas pressure and
(3) Current-interrupting capability and density monitoring shall be specified.
recovery voltage for use with parallel 3.3.8 The leakage rate of SF6 gas in kilo-
transmission lines grams from an individual gas zone shall not
exceed 2% per year. The total leakage rate
3.2.12 A voltage test instrument may be spec- from the GIS system shall not exceed 1% per
ified for indicating the presence of voltage on year.
the conductor system. This is accomplished by 3.3.9 Each gas zone shall be furnished with a
measuring the capacitive charge on a ground gas monitoring system consisting of a pres-
electrode. If voltage indication is desired, sure gauge a n d a gas-density continuous
specifications should include Provisions monitoring device provided with two sets of
for t h e Attachment of a Voltage Test adjustable, electrically independent contacts
Instrument. that operate in two stages, as follows:
17
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR
18
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37123-1991
gasketed joint so that the transformer housing can be readily disconnected while the system
is grounded to the GIS enclosure. is being dielectrically tested. The housing
3.8.4 If the transformers are not equipped shall be connected to the metal enclosure of the
with removable links, special covers and any bus system with a flanged, bolted, and gas-
necessary corona shields shall be supplied so keted joint so t h a t the capacitor housing is
that the system can be pressurized and dielec- grounded to the enclosure.
trically t e s t e d a f t e r removal of t h e 3.10.3 At least one special cover and neces-
transformer. sary corona shielding shall be supplied t o
3.8.5 If possible, the voltage transformer permit dielectric testing or system operation
may allow dielectric testing of the equipment with the capacitor-type voltage transformer
with input from the secondary connection with removed.
a special voltage regulator. Removal of the
voltage transformer is not required with this
approach. 3.11 hail Control Cabinets
3.8.6 Primary and secondary terminals 3.11.1 The manufacturer shall furnish one
shall have permanent markings for identifi- local control cabinet for each line terminal (or
cation of polarity, in accordance with IEEE specified sets of line terminals).
C57.13-19781291. 3.11.2 Each cabinet shall be completely fab-
ricated, wired, and assembled a t the factory.
Each cabinet furnished shall be fully equipped
3.9 Surge Arresters and completely wired to the terminal blocks
3.9.1 Arresters shall be of the voltage rating for termination of circuit breaker and discon-
called for in the detailed specifications. IEEE nect switch control, indication, and gas alarm
C62.11-1987[311 may be used as a reference. cables.
3.9.2 Arresters shall be of either the ''plug- 3.11.3 In general, each cabinet shall contain
in" construction or the disconnect-link type the following equipment for control, indicat-
and attached t o the gas-insulated system in ing, and protection of switches, circuit break-
such a manner that they can be readily dis- ers, and associated components:
connected from the system while the system is
being dielectrically tested. The metal housing One control switch for each circuit
of the arrester shall be connected to the metal break er
enclosure of the GIS with a flanged, bolted, and One remote-local switch for each circuit
gasketed joint so that the arrester housing is break er
grounded to the GIS enclosure. One open-close control switch or push-
3.9.3 The ground connection shall be sized button for each motor-operated discon-
for the fault level of the GIs. It shall be insu- nect switch
lated from the GIS enclosure and grounded One open-close control switch or push-
externally to permit periodic maintenance button for each motor-operated ground-
and monitoring of the leakage current. ing switch
3.9.4 If the arresters are not equipped with One or two red indicating lights and one
removable links, special covers and any nec- green indicating light for each circuit
essary corona shields shall be supplied so that breaker, each disconnect and ground-
the system can be pressurized and dielectri- ing switch, or contact position indica-
cally tested after removal of the arrester. tion on the mimic diagram
Control switches for ac and dc supply to
3.10 Capacitor Voltage Transformers each compartment
3.10.1 If required, coupling-capacitor-type One mimic diagram showing connec-
voltage transformers, with the capacitor sec- tions of all furnished equipment
tion including insulator housing, shall be en- One annunciator panel with remote out-
closed in an SFs-filled housing. put contacts
3.10.2 Capacitor voltage transformers shall Terminal blocks and terminations for
be of either the "plug-in" construction or the each gas density relay
disconnect-link type and attached t o the gas- (10) Terminal blocks and terminations for
insulated system in such a manner that they electrical interlock contacts
19
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR
20
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991
4. ProposalData
4.1 Drawings. Time after notification of award when the following drawings and data will be
submitted (in weeks):
IEm
C37323-1991 IEEE GUlDE TO SPECIFICATIONSFOR
4.4EnchureandCond~
Inductance
Capacitance
Resistance enclosure
conductor
Surge impedance
Weight of gas for largest gas zone
Length of bus sections
BusEnclosureData
Type of material
Outside diameter
Wall thickness
Internal pressure at 20 "C
22
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991
48 Disconnect Switches
4 8 Voltage Transformers
23
IEEE
C37123-1991
24