Sunteți pe pagina 1din 22

Recognized 08 an IEEE

American National Standard (ANSI) C37.123-1991

IEEE Guide to Specifications for Gas-Insulated


Substation Equipment

Sponsor
substationscommittee
of the
IEEE Power E n g i " g society

Approved January 14,1991


IEEEStandardSBOard

Approved July 15,1991


American National Standards Institute

Abstract: IEEE C37.123-1991covers the technical requirements for the design, fabrication, testing,
and installation of a gas-insulated substation (GIs); its intent is advisory. This guide discusses
parameters to be supplied by the purchaser and technical requirements for the design, fabrication,
testing, and installation t o be furnished by the manufacturer. Environmental conditions, general
and specific equipment requirements, and a proposal data sheet form are included to aid the user.

Keywords: gas-insulated substation, GIs, GIS equipment, GIS testing, GIS design, GIS
installation

The Institute of Electrical and Electronics Engineers, Inc.


345 East 47th Street, New York,NY 10017-2394,USA

Copyright 0 1991 by the


Institute of Electrical and Electronics Engineers, Inc.
All rights reserved. Published 1991
Printed in the United States of America

ISBN 1-55937-162-5
No part of this publication may be reproduced in any form,
in a n electronic retrieval system or otherwise,
without the prior written permission of the publisher.
IEEE Standards documents are developed within the Technical
Committees of the IEEE Societies and the Standards Coordinating
Committees of the IEEE Standards Board. Members of the committees
serve voluntarily and without compensation. They are not necessar-
ily members of the Institute. The standards developed within IEEE
represent a consensus of the broad expertise on the subject within the
Institute as well as those activities outside of IEEE that have
expressed an interest in participating in the development of the
standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to produce,
test, measure, purchase, market, or provide other goods and services
related to the scope of the IEEE Standard. Furthermore, the viewpoint
expressed at the time a standard is approved and issued is subject to
change brought about through developments in the state of the art and
comments received from users of the standard. Every IEEE Standard
is subjected to review at least every five years or revision or reafir-
mation. When a document is more than five years old and has not
been reaffirmed, it is reasonable to conclude t h a t its contents, al-
though still of some value, do not wholly reflect the present state of the
art. Users are cautioned to check to determine t h a t they have the latest
edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE.
Suggestions for changes in documents should be in the form of a pro-
posed change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the
meaning of portions of standards as they relate to specific applica-
tions. When the need for interpretations is brought t o the attention of
IEEE, the Institute will initiate action t o prepare appropriate re-
sponses. Since IEEE Standards represent a consensus of all con-
cerned interests, it is important to ensure that any interpretation h a s
also received the concurrence of a balance of interests. For this reason
IEEE and the members of its technical committees are not able t o pro-
vide an instant response to interpretation requests except in those
cases where the matter has previously received formal consideration.
Comments on standards and requests for interpretations should be
addressed to:
Secretary, IEEE Standards Board
445 Hoes Lane
P.O. Box 1331
Piscataway, N J 08855-1331
USA

IEEE Standards documents are adopted by the Institute of Electrical


and Electronics Engineers without regard t o whether their adoption
may involve patents on articles, materials, or processes. Such adop-
tion does not assume any liability to any patent owner, nor does i t
assume any obligation whatever to parties adopting the standards
documents.
(This Foreword is not a part of IEEE C37.123-1991,IEEE Guide to Specifications for Gas-Insulated Substation
Equipment.)

This guide is issued to aid users in developing and preparing specifications for gas-insulated
substations and equipment; its intent is advisory. The guide covers parameters to be supplied by
the purchaser and technical requirements for the design, fabrication, testing, and installation to
be furnished by the manufacturer. The purchaser should revise any paragraph as appropriate,
delete any paragraph that does not apply t o his or her needs, and incorporate any details to make
the specification conform to his or her standard practices and requirements.

Proposal Data of Section 4, which should be completed by each bidding manufacturer, is provided
in order t o elicit uniform answers from all the providers and t o facilitate technical proposal
evaluation.

The Working Group K6 on GIS Specifications of the Gas-Insulated Substations Subcommittee of


the IEEE Substations Committee, which prepared and approved this guide, had the following mem-
bers a t the time of the approval:

J.J.Dodds, Chair
P. C. Bolin M. A. Hick J. E. McConnell
R. H. Bower J. E. Holladay A. Mickevicius
J. A. Buchsbaum A. A. Leibold K. B. Miners
J. L. Charney H. Martensson K. Pettersson
J. Grzan R. Matulic J. F. Quinata
E. I. Hahn B. Sojka

The Gas-Insulated Substations Subcommittee of the IEEE Substations Committee that reviewed
and approved this guide had the following members:

R. Matulic, Chair J.F. Quinata, Vice Chair


G. Ahgren J. Grzan A. A. Leibold
P . C. Bolin E. I Hahn K. E. Lewis
R. H. Bower M. A. Hick H. Martensson
U. Brand J. E. Holladay A. Mateuchev
J. A. Buchsbaum C. Hurty J. E. McConnell
R. E. Carberry R. B. Jackson A. Mickevicius
D. R. Carbonnet R. Janezic K. B. Miners
J. L. Charney J. J. Keane P. R. Nannery
F. Y. Chu F. F. Kluge K. Pettersson
T. F. Clark C. Larsson D. J. Poole
N. Cuk L. M. Laskowski R. Snow
D. M. Gallant M. A. Lebow B. Sojka
H. R. Gilden R. C. St. Clair
The following persons were on the Substations Committee of the IEEE Power Engineering Soci-
ety that reviewed and approved this guide for submission to the IEEE Standards Board:

P. R..Nannery, Chair M. L. Holm, Vice Chair


J. B. Cannon, Secretary
W. J. Ackerman K. R. Gilden R. Matulic
B. Y. Afsher J. G n a n T. S . McLenahan
S . J. h o t A. Kaban S . P. Meliopoulos
M. Barbeito M. A. Hick J. O'Hara
J. D. Betz N. G. Hingorani J. T. Orrell
K. L. Black J. E. Holladay J. Oswald
C. J. Blattner D. C. Johnson S . G. Pate1
W. R. Block G. Karady R. J. Perina
P. C. Bolin J. J. Keane T. A. Pinkham
R. H. Bower R. P. Keil J. P. Quinata
S . D. Brown F. F. Kluge D. G. Rishworth
D. E. Buettner D. F. Koenig B. D. Russell
J. C. Burke T. J. Kolenda J. Sabath
R. E. Carbeny A. E. Kollar D. R. Schafer
F. Y. Chu I. H. Kopenen F. C. Schainauskas
E. F. Counsel L. W. Kurtz C. A. Sherry
N. Cuk K. C. Labbe R. C. St. Clair
P. Danfors D. N. Laird J. G. Sverak
F. A. Denbrock L. M. Laskowski W. K. Switzer
W. K. Dick A. A. Leibold E. R. Taylor
C. C. Diemond K. E. Lewis L. F. Volf
P. R. Dolan C. T. Lindenberg R. J. Wehling
L. N.Ferguson K. P. Lips W. M. Werner
G. G. Flaig W. F. Long B. W. Wray
D. L. Garrett R. M. Youngs

The Accredited Standards Committee on Power Switchgear, C37, that reviewed and approved this
document, had the following members at the time of approval:

T. C. Burtnett, Chair C. H. White, Secretary


M. B. Williams, Program Administrator

A. K. McCabe, Executive Vice Chair of High-Voltage Switchear Standards


S.H. Telander, Executive Vice Chair of Low-Voltage Switchgear Standards
D. L. Swindler, Executive Vice Chair of IEC Activities
Organization Represented ..................................................................... Name of Representative
Association of Iron and Steel Engineers ..................................................... J. M. Tillman
Electric Light and Power Group .............................................................. .R. L. Capra (Chair)
M. J. Eckelkamp
K. D. Hendrix
J. H. Provanzana
D. T. Weston
G. R. Brandenberger (Alt.)
T. E. Bruck (Alt.)
M. C. Mingoia (Alt.)
Institute of Electrical and Electronics Engineers ........................................... W. E. Laubach (Chair)
W. F. Hoenigmann
D. M. Larson
E. W. Schmunk
C. A. Schwalbe
R. W. Haas (Alt.)
D. G. Kumbera (Alt.)
R. Matulic (Alt.)
National Electrical Manufacturers Association ............................................ R. A. McMaster (Chair)
T. C. Burtnett
R. H. Miller
R. 0. D. Whitt
H. L. Miller W t . 1
Tennessee Valley Authority ................................................................... R. B. Rotton

Testing Laboratory Group ...................................................................... L. Frier


W. T. OGrady
US Department of Agriculture, REA ......................................................... .H. L. Bowles
Western Area Power Administration .................................................. G. D. Birney
US Department of the Army, Office of the Chief of Engineers.. ............................ W. M. Jones

US Department of the Interior, Bureau of Reclamation ..................................... J. W. Reif


US Department of the Navy, Naval Construction Battalion Center ...................... .R. L. Clark

The final conditions for approval of this standard were met on January 14, 1991. This standard
was conditionally approved by the IEEE Standards Board on December 6, 1990, with the following
membership:

Marco W.Migliaro, Chair James M. Daly, Vice Chair


Andrew G. Salem, Secretary
Dennis Bodson Kenneth D. Hendrix Lawrence V. McCall
Paul L. Borrill John W. Horch L. Bruce McClung
Fletcher J. Buckley Joseph L. Koepfinger* Donald T. Michael*
Allen L. Clapp Irving Kolodny Stig Nilsson
Stephen R. Dillon Michael A. Lawler Roy T. Oishi
Donald C. Fleckenstein Donald J. Loughry Gary S. Robinson
J a y Forster* John E. May, Jr. Terrance R. Whittemore
Thomas L. Hannan Donald W. Zipse

*Member Emeritus
contmlb

SECTION .............................................................................................................................. PAGE

1. I n t r o d u c t i o n ............................................................................................. 7
1.1 Scope .............................................................................................. 7
1.2 References ....................................................................................... 7
1.3 Service Conditions .............................................................................. 9
1.4 Equipment and Service Furnished by the Purchaser ....................................... 9
1.5 Equipment and Services Furnished by the Manufacturer ................................ 10

2 . General Requirements ............................................................................... 10


2.1 Information Required With Proposal ....................................................... 10
2.2 General Description ........................................................................... 11
2.3 Miscellaneous Equipment and Work ....................................................... 12
2.4 Tests ............................................................................................. 13
2.5 Shipment and Installation .................................................................... 13

3. D e t a i l e d R e q u i r e m e n t s ............................................................................... 13
3.1 Circuit Breaker ................................................................................ 13
3.2 Disconnect and Grounding Switches ........................................................ 14
3.3 Gas S y s t e m ..................................................................................... 15
3.4 SFs-to-Air Bushings ........................................................................... 15
3.5 Potheads ......................................................................................... 16
3.6 Transformer and Reactor Bushing Adapters .............................................. 16
3.7 Current Transformers ........................................................................ 16
3.8 Inductive Voltage Transformers ............................................................ 16
3.9 Surge Arresters ................................................................................ 17
3.10 Capacitor Voltage Transformers ............................................................ 17
3.11 Local Control Cabinets ........................................................................ 17

4. Proposal Data ......................................................................................... 19


41 Drawings ....................................................................................... 19
4.2 Weights ......................................................................................... 19
4.3 General Technical Data ...................................................................... 19
4.4 Enclosure and Conductor ..................................................................... 20
4.5 Circuit Breakers ............................................................................... 20
4.6 Disconnect Switches ........................................................................... 21
4.7 Grounding Switches ........................................................................... 21
4.8 Voltage Transformers ........................................................................ 21
4.9 Current Transformers ........................................................................ 22
4.10 Gas-to-Air B u s h i n g s .......................................................................... 22
4.11 Gas System ..................................................................................... 22
IEEE Guide to Specifications for Gas-Insulated
Substation Equipment

1.Introduction 1.1.6 Field assembly costs and maintenance


costs will be considered in bid evaluations.
Ll scope 1.1.7 In order to elicit a complete and uni-
1.1.1 This guide covers the technical re- form response from each bidder, Section 4,
quirements for the design, fabrication, test- Proposal Data, is provided.
ing, a n d installation of a gas-insulated
substation (GIs).
1.1.2 T h e manufacturer shall furnish all 1.2 References
work necessary to provide the complete GIS a s 1.2.1 This guide shall be used in con-
shown on t h e functional one-line diagram, junction with t h e following publications.
which may consist of circuit breakers (CBI, When the following standards are superseded
disconnect switches (DS), maintenance by a n approved revision, the revision shall
ground switches (MGS), fast-acting ground apply.
switches (FGS), voltage transformers (VT),
current transformers (CT), SF6-to-air bush- 111 ANSI A14.3-1984, American National
ings, buses, cable pothead enclosures, trans- Standard Safety Requirements for Fixed
former o r reactor bushing enclosures, Ladders.'
enclosed surge arresters, elbows, bellows,
controls, and supporting structures in applica- [21 ANSI B18.12-1962 (Reaff. 19811, American
ble numbers. All equipment and material National Standard Glossary of Terms for Me-
shall be prefabricated, factory assembled, chanical Fasteners.
tested, and shipped in the largest practical
assemblies. [31 ANSI C2-1990, National Electrical Safety
1.1.3 The assembled equipment shall be ca- Code.
pable of withstanding electrical, mechanical,
and thermal ratings of the specified system. [41 ANSI C37.06-1987, American National
All joints and connections shall be able to Standard AC High-Voltage Circuit Breakers
withstand the forces of expansion, vibration, Rated on a Symmetrical Current Basis-Pre-
contraction, a n d specified seismic require- ferred R a t i n g s a n d Related Required
ments without deformation, malfunction, and Capabilities.
leakage.
1.1.4 The equipment shall be capable of [51 ANSI C37.11-1979, American National
withstanding the specified outdoor or indoor Standard Requirements for Electrical Control
environment. for AC High-Voltage Circuit Breakers Rated
1.1.5 Optimized arrangements are required on a Symmetrical Current Basis or a Total
to reduce installation time, provide ease of op- Current Basis.
erations, minimize maintenance and repair
costs, and facilitate future additions as de-
scribed in the specifications. The proposal
shall include recommended spare parts for
'ANSI publications are available from t h e Sales
reduced outage time in case of a fault, and de- Department, American National Standards Institute, 11
livery time in case of emergency. West 42nd Street, 13th Floor, New York,NY 10036,USA.

9
IEEE
C37.123-1991 IEEE GUIDE TO SPECIFICATIONS FOR

[SI ANSI C37.12-1981, American National [171 IEEE C37.010-1979 (Reaff. 19881, IEEE Ap-
Standard Guide to Specifications for AC High- plication Guide for AC High-Voltage Circuit
Voltage Circuit Breakers Rated on a Symmet- Breakers Rated on a Symmetrical Current
rical Current Basis and a Total Current Basis (ANSI).4
Basis.
[l8] IEEE C37.011-1979 (Reaff. 1988), IEEE Ap-
[71 ANSI C37.32-1990, American National plication Guide for Transient Recovery Volt-
Standard for Switchgear-High-Voltage Air age for AC High-Voltage Circuit Breakers
Switches, Bus Supports, and Switch Acces- Rated on a Symmetrical Current Basis
sories-Schedules of Preferred Ratings, Man- (ANSI).
ufacturing Specifications, and Application
Guide. [19] IEEE C37.012-1979 (Reaff. 1988), IEEE Ap-
plication Guide for Capacitance Current
[81 ANSI C63.2-1987, American National Switching for AC High-Voltage Circuit
Standard for Electromagnetic Noise and Field Breakers Rated on a Symmetrical Current
Strength, 1 0 KHz to 40 GHz Specifications. Basis (ANSI).

[91 ANSI Y14.15-1966 (Reaff. 1988), American [20] IEEE C37.04-1979 (Reaff. 1988), IEEE
National Standard Electrical and Electronic Standard Rating Structure for AC High-Volt-
Diagrams. age Circuit Breakers Rated on a Symmetrical
Current Basis (ANSI).
[lo1 ANSVNAAMM MBG 531-1988, Metal Bar
Grating Manual. [21] IEEE C37.082-1982 (Reaff. 1988), IEEE
Standard Methods for the Measurement of
[ll] ASTM A123-89, Specification for Zinc Sound Pressure Levels of AC Power Circuit
(Hot-Dip Galvanized) Coatings on Iron and Breakers (ANSI).
Steel Products.2
[223 IEEE C37.09-1979 (Reaff. 1988), IEEE
[121 ASTM A501-88, Specification for Hot- Standard Test Procedure for AC High-Voltage
Formed Welded and Seamless Carbon Steel Circuit Breakers Rated on a Symmetrical
Structured Tubing. Current Basis (ANSI).

1131 ASTM A659-90, Specification for Steel, [231 IEEE C37.1-1987, IEEE Standard Defini-
Sheet and Strip, Carbon (0.16 Maximum t o 0.25 tion, Specification, and Analysis of Systems
Maximum Percent) Hot-Rolled Commercial Used for Supervisory Control, Data Acquisi-
Quality. tion, and Automatic Control.

[141 ASTM D2472-81, Specification for Sulphur [241 IEEE C37.2-1987, IEEE Standard Electrical
Hexafluoride. Power System Device Function Numbers.

U51 IEC 376 (19711, Specification and Accep- [251 IEEE C37.30-1971 (Reaff. 1987), IEEE
tance of New Sulphur H e x a f l ~ o r i d e . ~ Standard Definitions and Requirements for
High Voltage Air Switches, Insulators, and
[16] IEC 517 (1986), Gas-Insulated Metal- Bus Supports (ANSI).
Enclosed Switchgear for Rated Voltages of
72.5 kV and Above. [261 IEEE C37.34-1971 (Reaff. 19871, IEEE
Standard Test Code for High-Voltage Air
'ASTM publications are available from ASTM, Switches (ANSI).
Customer Service Department, 1916 Race Street,
Philadelphia, PA 19103, USA.
31EC publications are available from IEC Sales
Department, Case Postale 131,3 rue de Varemb6, CH 1211,
Geneve 20, SwitzerlandSuisse. IEC publications are also 41EEE publications are available from the Institute of
available in the United States from the Sales Department, Electrical and Electronics Engineers, Service Center, 445
American National Standards Institute, 11 West 42nd Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331,
Street, 13th Floor, New York,hT 10036, USA. USA.

10
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991

[271 IEEE C37.38-1989, IEEE Standard for Gas- 1.2.2 In the event of conflict between the ref-
Insulated Metal-Enclosed Disconnecting, In- erenced standards, the drawings of the user,
terrupter, and Grounding Switches. and his or her specification, or between stan-
dards issued by different authorities, the
[281 IEEE C37.122-1983, IEEE Standard Gas- manufacturer shall notify the purchaser and
Insulated Substations. secure written clarification a s t o what is ac-
ceptable before proceeding with the work.
1291 IEEE C57.13-1978 (Reaff. 1986), IEEE
S t a n d a r d Requirements for I n s t r u m e n t 1.3 Conditions
Transformers (ANSI). 1.3.1 All apparatus shall be capable of
satisfactory operation in t h e following
[301 IEEE C62.2-1987, IEEE Guide for the Appli- environment:
cation of Gapped Silicon-Carbide Surge Ar-
resters for Alternating-Current Systems Environmental:
(ANSI).
Indoor or outdoor:
[311 IEEE C62.11-1987, IEEE Standard for Elevation above sea
Metal-Oxide Surge Arresters for AC Power level: m
Circuits (ANSI). Maximum ambient
temperature:
E321 IEEE 21-1976, IEEE General Requirements Minimum ambient
and Test Procedures for Outdoor Apparatus temperature: -"C
Bushings (ANSI). Humidity (average): %
Wind velocity: km/hr
E331 IEEE 24-1984, IEEE Standard Performance Solar radiation: WIm2
Characteristics and Dimensions for Outdoor Maximum ice loading: mm
Apparatus Bushings (ANSI). Maximum uplift: daN
Maximum impact: daN
[341 IEEE 48-1990, IEEE Standard Test Proce- Seismic:
dures and Requirements for High-Voltage Air quality:
Alternating-Current Cable Terminations Special environmental
(ANSI). considerations:

[351 IEEE 80-1986, IEEE Guide for Safety in AC


Substation Grounding (ANSI). 1.4 Equipment and Services Furnished by the
Purchaser. The purchaser shall receive, in-
[361 IEEE Std 315-1975 (Reaff. 1989), IEEE stall, and field test the apparatus specified
Standard Graphic Symbols for Electrical and herein. Installation and field test of the GIS
Electronic Diagrams (ANSI). should be completed under the supervision of
the manufacturer to ensure correct installa-
E371 IEEE 693-1984, IEEE Recommended Prac- tion. The following equipment and services
tices for Seismic Design of Substations shall also be furnished by the purchaser, un-
(ANSI). otherwise specified:

[381 IEEE 837-1989, IEEE Standard for Qualify- Concrete foundations


ing Permanent Connections Used in Substa- Power transformers or reactors, includ-
tion Grounding (ANSI). ing bushings
Surge arresters outside the GIS
[391 NEMA 107-1987, Methods of Measurement
The station ground grid, below ground,
of Radio Influence Voltage (RIV) of High-
and vertical connection risers of ade-
Voltage A p p a r a t u ~ . ~
quate length
60 Hz, a c and dc auxiliary power to
'NEMA publications are available from the National
Electrical Manufacturers Association, 2101 L Street hW, manufacturer-furnished equipment,
Washington, D.C.20037, USA. including:

11
IEEE
C37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR

( a ) Rated dc service voltage V (4) All transformer bushing sulfur hexa-


(b) Minimum dc service fluoride (SFe) enclosures, complete with
voltage -v vibration dampers.
(c) Maximum dc service ( 5 ) All coordination with power-trans-
voltage -v former, cable, and cable-terminator
(d) Rated ac service manufacturers to assure proper electri-
voltage (three-phase) V cal and mechanical interface.
(e) Rated ac service (6) All necessary supports, platforms,
voltage (one-phase) -v stairways, and walkways, including
(6) Supervisory control and data acquisi- embedded steel and anchor bolts needed
tion (SCADA) equipment for attachment.
(7) Conduit or troughs and wiring t o sup- (7) All auxiliary equipment including in-
plier-furnished equipment terlocks; operating mechanisms; and
(8) Gas handling equipment control, monitoring and protective de-
(9) Batteries and battery chargers vices, installed in suitable cabinets.
(10) Protective relaying systems (8) All control cabinets with respective
(11) Transmission-line dead-end termi- mimic buses, internal wiring, and
nations terminations.
(12) Control and power cable trenches (9) All wiring of devices and terminations
(13) Erection labor, with the supervision and internal t o the switchgear and all
assistance of the G I s supplier shielded control cables (and associated
(14) Control house and related equipment or raceways) between the equipment and
building in case of indoor installation, local control cabinets.
including crane (10) Ground buses and ground connection
(15) Job-site unloading and storage pads.
(16) Field welding, if required, with the su- (11) Gas density relays, pressure relief de-
pervision and assistance of the GIS vices, and gas-filling connections.
supplier (12) Initial filling of SFs gas and hydraulic
(1 7) Test equipment, coordinated with the fluid, if required.
GIS supplier (13) Any other equipment not specifically
(18) Specific tertiary bus and other related noted herein but that is necessary for
equipment trouble-free functioning, installation,
(19) High-voltage power cables and pothead and maintenance of the GIS.
connections (14) Technical direction for site assembly
and testing by a competent service
1.5 Equipment and Services Furnished by the engineer .
Manufacturer. The manufacturer shall de- (15) Any special tools, lifting devices, and
sign, manufacture, test, deliver, and guaran- gas manifolds necessary for erection
tee the following services a s required by this that shall be retained by the purchaser
guide: for maintenance purposes.

The complete gas-insulated switchgear,


including the power transformer and 2. General Requirements
line exits with associated circuit
breakers, disconnect and grounding
switches, voltage transformers, and 2.1 Information Required With Proposal
surge arresters. 2.1.1 The proposal shall include general ar-
All metal-enclosed gas-insulated buses rangement drawings and single-line dia-
for interconnecting various switchgear grams, the gas schematic diagram, weights
assemblies. and dimensions, anchor requirements, appro-
All cable terminators, including ter- priate technical data, the bill of material, and
minator support structures, cable box a description of system components.
support structures, and mounting 2.1.2 The proposal shall also include the fol-
insulators. lowing documents:

12
EEE
GAS-INSULATED SUBSTATION EQUIPMENT C37123-1991

Design test data, if required by the tions or protective measures in particularly


purchaser. harsh operating environments.
Insulation coordination study, if re- 2.2.2 The circuit breaker gas zone shall be
quired by the purchaser. independent from all other gas compartments
Seismic study, if required by the and shall meet the rating requirements of
purchaser. IEEE C37.122-1983[28Y and other applicable
Grounding study, if required by the standards referenced in this guide.
purchaser. 2.2.3 Disconnect switches shall be three-
Factory type test reports. phase ( o r single-phase), manually or motor
Documentation on installation proce- operated, and capable of interrupting the
dure a n d sequence, operation, and charging current of the connected GIs bus and
maintenance of the GIs. associated components. Maintenance and
Data on allowable misalignment a t the fast-acting ground switches shall be manual
installation o r required accuracy of or motor operated. Each switch shall be
foundations and anchors. equipped with mechanism-actuated auxiliary
List of recommended spare parts, in- switches for indication of the contact position.
cluding cost and delivery for normal Visual inspection means may be provided, if
and emergency conditions. specified, to observe disconnect and ground
List and cost of special tools, fixtures, switch contact position, along with a mechani-
and lifting devices required for instal- cally connected external position indicator.
lation, operation, and maintenance. Each switch shall have provisions for me-
Availability and cost of high-voltage c h a n i c a l locking a g a i n s t u n w a n t e d
test equipment, if required by the operation.
purchaser. 2.2.4 Electrical interlocks or another suit-
List of previously supplied GIS facilities able scheme shall be furnished t o prevent in-
and their performance to date. correct sequential operation or equipment
Estimated time required to install and malfunction that might result in equipment
to test the equipment. damage or personal injury. Electrical inter-
Field service engineer cost. lock schemes shall be fail-safe t o prevent loss
Training for personnel of the pur- of interlock function upon loss of control
chaser, including cost, duration, and voltage.
material covered. 2.2.5 Control of overvoltages during discon-
Filled-out data sheets of Section 4 of this nector operation shall be included.
guide. Separate data sheets shall be pro- 2.2.6 Heaters (and thermostats, if specified)
vided for each alternative proposal. shall be furnished as required in control cabi-
Listing of exceptions to and deviations nets and equipment housings t o avoid
from this specification. All exceptions condensation.
shall be clearly and separately item- 2.2.7 A single-phase bus shall consist of two
ized. It shall not be necessary for the concentric tubes of high electrical conductivity
purchaser t o examine the standard lit- and mechanical strength, the inner tube being
erature and documents of the manufac- the conductor and the outer tube being the
turer t o determine the existence and solidly grounded enclosure for each isolated
extent of any exceptions or deviations phase. A three-phase bus shall consist of three
from this specification. inner tubes (the conductors) and a single outer
tube (the solidly grounded enclosure for the
bus).
2.2 Description 2.2.8 Conductors shall be made of extruded
2.2.1 The station layout and equipment rat- aluminum or copper tubing suitable for the
ing shall be based on the single-line diagram specified voltage and current ratings. The en-
furnished by the purchaser. Dependent on the closure shall be aluminum or steel with all ad-
station rating, single- or three-phase enclo-
sures may be furnished. The purchaser shall
provide the ratings and any GThe numbers in brackets comespond to those of the
special requirements, such a s spatial limita- references in 1.2.

13
IEEE
C37.123-1991 IEEE GUIDE TO SPECIFICATIONS FOR

joining enclosures bolted or bonded together provisions shall be made and described to pre-
and grounded. clude the entry of foreign materials into the
2.2.9 As much a s possible, parts shall be of gas space.
standard manufacture with interchangeable 2.2.17 Structures required t o support the
parts and assemblies. equipment, and platforms and walkways for
2.2.10 Pressure relief devices, if required, operation and maintenance access t o operat-
shall be vented to provide a safe environment ing and monitoring devices, shall be designed
for field personnel and equipment during op- to permit access without use of special devices
eration. The bursting pressure of the relief de- or portable ladders. All structures, stairs, plat-
vice shall be effectively coordinated with the forms, and walkways shall conform to OSHA
rated gas pressure and pressure rise due to regula ti o n s.
arcing a s described in the section of IEEE 2.2.18 Ground pad terminals shall be located
(337.122-1983 E281 describing pressurized en- to permit proper connection t o the station
closure requirements. ground grid and to minimize external bus en-
2.2.11 Expansion and installation align- closure voltage gradient to a safe limit.
ment shall be considered in the design of the
bus and the enclosure. If required, expansion
joints shall be provided with compensators for 2.3 Miscellaneous Equipment and Work. The
the enclosure and sliding plug-in contacts for manufacturer shall furnish, but not be limited
the conductor. to providing, the following additional items
2.2.12 Support insulators shall be used to required for a complete installation:
maintain the conductor and enclosure in the
proper relation. There shall be two types of All ladders, platforms, stairs, walk-
support insulators-barrier insulators, which ways, and support necessary t o operate
are employed to isolate gas compartments and and maintain all equipment safely and
nonbarrier insulators, which allow the gas eff i c i en tl y .
pressure t o equalize. All supporting structures for the GIS
2.2.13 Connections between adjacent con- equipment, except concrete foundations
ductor sections shall be made by means of and associated parts such a s anchor
plug-in type contacts. Shields shall be placed to bolts, beams, etc. Sufficient attachment
capture metallic particles that may result from points and equipment loadings to the ap-
contact rubbing. Field welding of the conduc- paratus and concrete foundations shall
tor is not acceptable, except when required for be furnished to ensure successful instal-
special cases of extension, repair, or retrofit. lation, with required clearances, while
2.2.14 Components outside the SFs environ- taking into account thermal expansion
ment shall be installed in weatherproof enclo- and contraction.
sures for outdoor installation. Flexible joints in all equipment sup-
2.2.15 Shipping sections shall be joined in plied a s required to ensure continuity of
the field using either bolted, gasketed flange service d u r i n g t h e r m a l expan-
connections o r welded connections of the en- sion/contraction and vibration. Flexi-
closure. Flanged connections shall have a gas ble joints may also be provided to allow
seal between the flange surfaces. A second more efficient maintenance.
seal ring, sealants, or other suitable means Control and indication systems, includ-
may be used to protect the gas seal from the ex- ing local control cabinets.
ternal environment. Connections, including Grounding provisions for connection t o
bolts and nuts, shall be adequately protected the ground grid of the owner.
from corrosion and shall be easily accessible Wiring and means for wiring between
with the proper tools. individual items of supplier-furnished
2.2.16 Where necessary, and agreed to by the equipment.
purchaser, field-welded connections may be Nameplates for each piece of equipment.
used between major fixed components t o per- Gas system, including density moni-
mit length and angular adjustments t o com- tors and sufficient gas to put the equip-
pensate for construction tolerances. Where ment into service.
field welding is used to join the enclosures, Special tools.

14
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991

(10) External surface preparation and coat- - Functional tests on control and indica-
ing, if specified. Color may affect ther- tion circuits
mal rating. If equipment is derated due - Moisture measurement
t o enclosure color, the user must be in-
formed of the new rating in the proposal. 2.4.3 Field Test. The following field
tests shall be performed a s a minimum
2.4 Tests. The tests shall verify that all com- requirement:
ponents of the GIS perform satisfactorily both
electrically and mechanically a t the specified - Gas leakage test
rating. The tests shall establish t h a t produc- - Operational test
tion sections have been properly assembled - Gas moisture measurement
and that they have essentially the same char- - Resistance test of conductor
acteristics as those sections subjected to design - Current transformer testing
tests. - High-voltage tests
2.4.1 Design or Type Test (Refer to ANSI - Control and installation wiring checks
Standards). The following design test shall - Inductive voltage transformer tests
have been done for the equipment to be
delivered: 2.5 Shipment and Installation
2.5.1 All equipment shall be suitably packed
Impulse withstand voltage [Basic Im- and protected during shipment. Each shipping
pulse Level (BIL) and (Switching Im- unit shall be sealed in a clean, dry condition
pulse Level (SIL) if applicable] with leak-tight shipping covers securely
Power frequency withstand voltage mounted for shipment. All covers t o be re-
Circuit breaker and disconnect switch moved during installation shall be clearly
open -gap withstand voltage marked. Each shipping section shall be care-
Rated continuous-current carrying tests fully sealed and filled with dry gas t o a
Short-time current rating test slightly positive pressure to prevent the en-
Current switching test trance of moisture and contamination. he
Mechanical operation tests supplier shall notify the user whether the ship-
Pressure tests ping sections contain SF6 o r another type of
Circuit breaker tests (refer to ANSI dry gas.
standards) 2.5.2 Components requiring indoor storage
Disconnect switching tests shall be so identified. The manufacturer shall
Instrument transformer tests provide copies of complete, detailed, cus-
tomized instructions for storage, installation,
2.4.2 Production Test. Production tests shall operation, and maintenance of the equipment.
be made in the course of component assembly 2.5.3 Long-term storage instructions shall
and a t the complete or shipping assembly state. be provided, if specified.
Tests shall include a t least the following: 2.5.4 A competent, experienced service
engineer from the manufacturer shall be pre-
Circuit breaker test per IEEE C37.09- sent a t the job site for technical guidance and
1979 E221 direction throughout the installation and test-
Pressure test on all individual enclo- ing of the equipment.
sures and barrier insulators
Gas leak tests of enclosure and barrier
insulators 3.Detailed Requirements
Mechanical operation test
Low-voltage wiring test
Voltage drop measurement of the con- 3.1 Circuit Breakers
ductor and contacts 3.1.1 Circuit breakers shall be the SF6 gas-
Power frequency withstand voltage insulated type, dead tank design, and shall
Partial discharge test of insulators have the ratings a s specified.
and/or shipping sections 3.1.2 The breaker shall have ratings de-
CT and VT tests scribed in IEEE C37.122-1983 [281 and specific

15
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONS FOR

ratings in accordance with other applicable break, with motor- o r manual-operating


ANSI standards. mechanisms.
3.1.3 The breaker shall be capable of per- 3.2.3 For motor-operated disconnect
forming t h e specific duty cycle without switches, the control shall be electrically un-
derating. coupled from the drive shaft when the switch is
3.1.4 Each circuit breaker shall be factory operated manually to prevent coincident power
assembled, adjusted, and tested and shall be operation of t h e switch and t h e drive
shipped as a complete single-phase or three- mechanism(s1.
phase unit. 3.2.4 Each disconnect and ground switch
3.1.5 The breaker shall include a suitable shall open or close only due to manual- or mo-
operating mechanism to assure proper open- tor-driven operation. The switch blade shall
ing and closing and shall permit checking not move due to gravity or other means, even if
adjustments and operating characteristics. a part fails. Once initiated, the motor mecha-
The mechanism shall be capable of reclosing nism shall complete an open or close operation
within the range specified in the standards. without requiring the initiating contact to be
3.1.6 Dual trip coils that may be in redun- held closed.
dant electromagnetic construction may be 3.2.5 Each disconnect switch and grounding
specified by the purchaser. switch shall be furnished with electrically in-
3.1.7 Sound-level requirements may be dependent auxiliary switches. The auxiliary
specified by the purchaser. switches shall indicate the position of the
3.1.8 For outdoor applications, each breaker switch blades and shall be provided so that the
shall include a weatherproof control cabinet contacts can be adjusted to be fully engaged
for housing the operating mechanism and all and in proper alignment when in the closed
accessories. Necessary valves and connec- position. Purchaser shall specify number of
tions shall be provided to ensure ease in han- "a" and "b" contacts.
dling the SFs. 3.2.6 Visual verification may be provided, if
3.1.9 Each circuit breaker shall be equipped specified, for each pole of each disconnect
with an operation counter. The preferred ar- switch and grounding switch t o permit visual
rangement for this device is to operate only inspection of each switch blade position. Ex-
during the opening cycle. An indicator that ternal position indicators shall also be
shows the position of the contacts shall be pro- provided.
vided. All gauges, counters, and position 3.2.7 The purchaser shall specify any antic-
indicators shall be readable by an operator ipated duty condition for the ground switches,
standing near the equipment. including the interrupting and/or closing
3.1.10 Each control cabinet for a line termi- duty for ground switches, especially when
nal(s) shall also include the following: connected to parallel transmission lines or
similarly coupled systems. This duty cannot
(1 1 Local-remote switch (optional) normally be performed with a standard
(2) Local-control switch (optional) ground switch and may require a special
design.
3.1.11 Closing resistors, when required, 3.2.8 The purchaser shall specify the ex-
shall meet the rated line-closing switching pected disconnect switch operating capability
surge factor as specified in the applicable in situations where a disconnect switch can be
standards. operated with out-of-phase conditions, such as
synchronizing generators or an inductive po-
32 Disconnect and Grounding Switches tential transformer on the load side of the
3.2.1 Disconnect switches shall be three- switch.
pole, group operated, or single-pole operated, 3.2.9 A manhole or other suitable means of
no-load break, with one operating mechanism opening access shall be provided in each dis-
per three-pole or one operating mechanism per connect-switch and grounding-switch hous-
single-pole position. The purchaser sha!l spec- ing t o allow access t o switch contacts and
ify manual or motor operator. mechanism for repair a n d o r maintenance.
3.2.2 Grounding switches shall be three-pole 3.2.10 A low-voltage test provision may-be
group operated or single-pole operated, no-load supplied with a grounding switch t o permit test

16
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991

voltages of up to 1 0 kV (optional 2.5 kV) or 200 - Each terminal position between adja-
A to be applied t o the conductor without remov- cent breakers.
ing SF6 gas or other components, except for - Each main bus or bus sections.
ground shunt leads.
3.2.11 The listed operation modes shall be Other parts of the GIS shall be divided into a
specified for special grounding applications: suitable number of zones or included in the
above zones.
(1) Fast-acting ground for cable grounding 3.3.7 For single-phase bus construction;
(2) Fault initiating (fast-acting ground) single-phase or three-phase gas pressure and
(3) Current-interrupting capability and density monitoring shall be specified.
recovery voltage for use with parallel 3.3.8 The leakage rate of SF6 gas in kilo-
transmission lines grams from an individual gas zone shall not
exceed 2% per year. The total leakage rate
3.2.12 A voltage test instrument may be spec- from the GIS system shall not exceed 1% per
ified for indicating the presence of voltage on year.
the conductor system. This is accomplished by 3.3.9 Each gas zone shall be furnished with a
measuring the capacitive charge on a ground gas monitoring system consisting of a pres-
electrode. If voltage indication is desired, sure gauge a n d a gas-density continuous
specifications should include Provisions monitoring device provided with two sets of
for t h e Attachment of a Voltage Test adjustable, electrically independent contacts
Instrument. that operate in two stages, as follows:

(1) First Alarm-Refill gas density nor-


3.3 Gas System mally 5% to 10% below the nominal fill
3.3.1 The GIS shall be furnished, if so speci- density.
fied, with sufficient SF6 gas to pressurize the (2) Second Alarm-Minimum gas density
complete system in a sequential approach, one to achieve equipment ratings.
zone or compartment at a time, t o the rated
nominal density. An additional quantity of 3.3.10 Provisions shall be made for connect-
gas shall be furnished as specified. ing pressure gauges, the service cart, and
3.3.2 The SFs gas used shall conform t o moisture instrumentation to each one of the
ASTM D2472-81 [141. gas sections.
3.3.3 The GIS enclosure shall be divided into
several sections separated by gas-tight barrier
insulators. Each section shall be provided with 3.4 SFs-to-& Bushings
the necessary piping and valves to allow isola- 3.4.1 SFg-to-air bushings may be used for
tion, evacuation, and refill of gas without connections between conventional overhead
evacuation of any other section. transmission lines and G I s , between the
3.3.4 A gas schematic diagram shall be transformer and GIS equipment, or other loca-
submitted for approval. It shall include the tions specified by the purchaser.
necessary valves, connections, pressure 3.4.2 Each bushing shall be constructed of
switches, gas monitor system and controls, commercial-grade porcelain o r a n acceptable
indication, orifices, and isolation t o prevent substitute, with all surfaces free from imper-
current circulation. Means of calibrating fections. The color specified by the user shall
density monitors without de-energizing the be gray or brown.
equipment shall be specified. 3.4.3 Bushing connections to a n overhead
3.3.5 The external fixtures shall be made of line or transformer lead shall be NEMA 107-
corrosion-resistant material and shall be 1987 [391 standard 4 hole, 4 in by 4 in alu-
capped where required. minum pad.
3.3.6 For the purpose of gas monitoring and 3.4.4 Each porcelain component o r nonce-
maintenance, the GIS shall be divided into the ramic bushing t h a t has an internal pressure
following individually monitored zones: shall comply with IEEE C37.09-1979 [221.
3.4.5 Bushings may be of the following
- Each power circuit breaker. types:

17
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR

- SF6 single-pressure bushings, which natively, a flexible element may be provided


a r e hollow, S F s - f i l l e d i n s u l a t o r on the transformer side of the SF6-to-oil
columns. bushing.
- SF6 dual-pressure bushings which are 3.6.4 To permit alignment of the bus and the
hollow, SF6-filled insulator columns bushing, the user shall assign responsibility to
with an intermediate barrier such t h a t either the transformer or the GIS supplier to co-
the insulator is at a lower pressure than ordinate their designs.
the nominal gas-zone pressure in the
GIS. 3.7 Current Transformers
- Oil-filled o r dry-type condenser 3.7.1 Each current transformer shall be pro-
bushings. vided so that the enclosure current does not af-
fect the accuracy or the ratio of the device or the
3.5 Potheads conductor current being measured.
3.5.1 If required, SF6 enclosures for cable 3.7.2 Current transformer secondaries shall
potheads shall be provided for connecting the be terminated to shorting terminal blocks.
power cable to the GIs. 3.7.3 I t shall be possible to test each current
3.5.2 The pothead enclosure shall be propor- transformer without the removal of gas.
tioned to permit a dc field test of the connecting 3.7.4 The current transformer location,
cable and shall provide means t o permit such polarity, ratios, and accuracy shall be as
testing. If necessary, i t shall be possible to specified and in accordance with IEEE C57.13-
connect a test bushing. The pothead shall be 1978 [291.
equipped with a removable link to permit cable
and GIS high-voltage tests. 3.8 Inductive Voltage Transformers
3.5.3 To ensure the effectiveness of the cor- 3.8.1 Each voltage transformer shall be dry-
rosion-protection cell in handling power-fre- type, encapsulated, or SF6 insulated and shall
quency fault current within the GIS, the user have the following specified:
and the supplier shall coordinate placement,
ratings, and testing of cell installation. (1) Number of secondary windings
3.5.4 The SF6 pothead enclosure and pothead (2) Number of t a p s in each secondary
support structure shall be equipped with provi- winding
sions for insulation from the cable riser pipe to (3) Ratio of primary voltage t o each sec-
permit cathodic protection on the cable system. ondary winding voltage
(4) Thermal r a t i n g of each secondary
3.6 T r a n s f o r m e r and Reactor Bushing winding
&PM ( 5 ) Thermal rating of primary winding
3.6.1 Enclosure adapters may be rehired to
connect the SF6 bus directly t o the SF6-to-oil 3.8.2 The accuracy classification a t 60 Hz
transformer bushing, bolting directly to a and a t the specified secondary voltage shall be
flange on the bushing, and totally enclosing 0.3 at burdens of W, X, Y, Z, and ZZ, as stated
the insulator and live parts in the SF6 in IEEE C57.13-1978 [291. Burdens may be di-
environment. vided in any proportion between the secondary
3.6.2 The adapter shall have a removable windings, but for accuracy classification the
cover and removable bus link to permit elec- total burden on both windings must not exceed
trically disconnecting the transformer from W, X, Y, Z, or ZZ. Thermal ratings and bur-
the bus, testing of the bus or transformer sepa- dens shall be coordinated with the protection
rately, and removal of the transformer, if system.
require d. 3.8.3 Transformers shall be of either the
3.6.3 The bus enclosure may be insulated plug-in, construction o r the disconnect-link
from the transformer tank t o minimize circu- type and attached to the gas-insulated system
lating currents through the transformer tank. in such a manner that they can be readily dis-
The bus connecting the transformer t o the GIS connected while the system is being dielectri-
may also contain a bellows assembly and cally tested. The metal housing of the
flexible conductor connection to minimize vi- transformer shall be connected to the metal
bration transfer from the transformer. Alter- enclosure of the GIS with a flanged, bolted, and

18
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37123-1991

gasketed joint so that the transformer housing can be readily disconnected while the system
is grounded to the GIS enclosure. is being dielectrically tested. The housing
3.8.4 If the transformers are not equipped shall be connected to the metal enclosure of the
with removable links, special covers and any bus system with a flanged, bolted, and gas-
necessary corona shields shall be supplied so keted joint so t h a t the capacitor housing is
that the system can be pressurized and dielec- grounded to the enclosure.
trically t e s t e d a f t e r removal of t h e 3.10.3 At least one special cover and neces-
transformer. sary corona shielding shall be supplied t o
3.8.5 If possible, the voltage transformer permit dielectric testing or system operation
may allow dielectric testing of the equipment with the capacitor-type voltage transformer
with input from the secondary connection with removed.
a special voltage regulator. Removal of the
voltage transformer is not required with this
approach. 3.11 hail Control Cabinets
3.8.6 Primary and secondary terminals 3.11.1 The manufacturer shall furnish one
shall have permanent markings for identifi- local control cabinet for each line terminal (or
cation of polarity, in accordance with IEEE specified sets of line terminals).
C57.13-19781291. 3.11.2 Each cabinet shall be completely fab-
ricated, wired, and assembled a t the factory.
Each cabinet furnished shall be fully equipped
3.9 Surge Arresters and completely wired to the terminal blocks
3.9.1 Arresters shall be of the voltage rating for termination of circuit breaker and discon-
called for in the detailed specifications. IEEE nect switch control, indication, and gas alarm
C62.11-1987[311 may be used as a reference. cables.
3.9.2 Arresters shall be of either the ''plug- 3.11.3 In general, each cabinet shall contain
in" construction or the disconnect-link type the following equipment for control, indicat-
and attached t o the gas-insulated system in ing, and protection of switches, circuit break-
such a manner that they can be readily dis- ers, and associated components:
connected from the system while the system is
being dielectrically tested. The metal housing One control switch for each circuit
of the arrester shall be connected to the metal break er
enclosure of the GIS with a flanged, bolted, and One remote-local switch for each circuit
gasketed joint so that the arrester housing is break er
grounded to the GIS enclosure. One open-close control switch or push-
3.9.3 The ground connection shall be sized button for each motor-operated discon-
for the fault level of the GIs. It shall be insu- nect switch
lated from the GIS enclosure and grounded One open-close control switch or push-
externally to permit periodic maintenance button for each motor-operated ground-
and monitoring of the leakage current. ing switch
3.9.4 If the arresters are not equipped with One or two red indicating lights and one
removable links, special covers and any nec- green indicating light for each circuit
essary corona shields shall be supplied so that breaker, each disconnect and ground-
the system can be pressurized and dielectri- ing switch, or contact position indica-
cally tested after removal of the arrester. tion on the mimic diagram
Control switches for ac and dc supply to
3.10 Capacitor Voltage Transformers each compartment
3.10.1 If required, coupling-capacitor-type One mimic diagram showing connec-
voltage transformers, with the capacitor sec- tions of all furnished equipment
tion including insulator housing, shall be en- One annunciator panel with remote out-
closed in an SFs-filled housing. put contacts
3.10.2 Capacitor voltage transformers shall Terminal blocks and terminations for
be of either the "plug-in" construction or the each gas density relay
disconnect-link type and attached t o the gas- (10) Terminal blocks and terminations for
insulated system in such a manner that they electrical interlock contacts

19
IEEE
c37123-1991 IEEE GUIDE TO SPECIFICATIONSFOR

(11) Terminal blocks and terminations for transformer


alarm and miscellaneous remote-con- (13) Terminal blocks and terminations for
trol circuits all spare contacts
(12) Terminal blocks and terminations for (14) Terminal blocks and terminations for
all instrument transformer leads. A the external control, instrumentation,
lead shall be installed and terminated and protection of the purchaser
for each t a p of a multiratio current (15) A total of 10% spare terminal blocks

20
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991

4. ProposalData

4.1 Drawings. Time after notification of award when the following drawings and data will be
submitted (in weeks):

General arrangement drawings


Structural plan and details
Foundation loadings for all GIS equipment and
supporting structures
Physical detail drawings (shipping unit)
Electrical schematic and wiring diagrams
Gas schematic diagrams
Grounding arrangement and ground bus details
Erection drawings
Dimensional tolerances, outdoorhndoor X
Y
Z

4.2 Weights (kg, unless otherwise noted)

Circuit breaker 1P or 3P7


Disconnect switch 1P or 3P
Grounding switch 1 P or 3P
Voltage transformer 1P or 3P
SF6-to-Air bushing 1P
Longest section of interconnecting bus 1P or 3P
Interconnecting bus elbow 1P or 3P
Interconnection bus tee 1 P or 3P
Weight of the heaviest piece of equipment to be
handled during construction (name the item)
Estimated total weight of all structural steel
Total estimated weight of all items
4.3 General Technical Data

Rated service voltage (kV, rms)


Rated maximum voltage (kV, rms)
Rated frequency (Hz)
Rated continuous current bus (A, rms)
feeder (A, rms)
Rated short-circuit current (A, rms)
Short time current (A, rms)
Momentary current (A, rms)
Withstand Voltages
Low frequency (kV, rms)
Full wave impulse (BIL) (kV, peak)
Switching impulse (SIL), if required (kV, peak)
Maximum Acceptable Moisture Level
Circuit Breaker (PPMVIB
Compartments where arcing is expected (PPMV)
Compartments where arcing is not expected (PPMV)

71P = single phase; 3P = three phase.


'PPW = Parts per million per volume.
1

IEm
C37323-1991 IEEE GUlDE TO SPECIFICATIONSFOR

4.4EnchureandCond~

Inductance
Capacitance
Resistance enclosure
conductor
Surge impedance
Weight of gas for largest gas zone
Length of bus sections
BusEnclosureData
Type of material
Outside diameter
Wall thickness
Internal pressure at 20 "C

4.5 Circuit Breakers

Voltage range factor


Rated short circuit current symmetrical (A rms)
asymmetrical (A rms)
Rated closing and latching capability (A rms)
Rated interrupting time (60 Hz) (ms)
Rated reclosing time (ms)
Rated permissible tripping delay (SI
Rated operating duty cycle
Type of operating mechanism
Breaker Operating Time (in ms) for Rated Control Voltage and Pressure
Opening time from energization of trip coil to
contact parting
ClosingResistors (if applicable)
Ohmic value of closing resistors per phase (Q)
Insertion time during closing (ms)
Gas Pressures
Pressure at 20 "C of interrupting medium (kPa)
Pressure at 20 "C of insulating medium,
maximum/minimum &Pa)
Maximum Foundation Loading During Operation
For horizontal breakers (N)
For vertical breakers (NI
Motor Capcity
Number and type
Horsepower of each (hp)
Voltage and phase (V)
Current, start/run (A)
Total heater power per three-pole breaker (W)
Control Circuit
Closing voltage range (VI
Maximum closing current (A)
Tripping voltage range (V)
Maximum tripping current (A)
Number of trip coils per pole
Mini" Number of Operations Before the Breaker Must Be
Removed From Service for Maintenance Inspection
No load mechanical

22
IEEE
GAS-INSULATED SUBSTATION EQUIPMENT C37.123-1991

Full load nonfault


Rated short-circuit current
Expected number of hours required to perform
a complete maintenance inspection of one
breaker (including gas handling time)
Maximum guaranteed impact noise level, during
operation, at a point 100 R from the breaker (dB)
Number of breaker operations without motor
operation
Number of full load operations without overheating
the closing resistors (specify the closing duty for
the thermal rating)

48 Disconnect Switches

Rated Full-Wave Impulse Withstand


Across the open gap (kV peak)
Rated 60Hz-1 min Withstand
Across the open gap (kV rms)
Number of switch-operating-mechanism
operations before internal visual inspection
or servicing
Maximum control voltage
Minimum control voltage
Current, startfrun
Maximum opening current
Maximum closing current
Heater power per three-pole switch
Main Current-CarryingContact Material
Base material and specification
Contact insert
Plating material
ControlData for Operating Mechanism
Operating time
Maximum charging current interrupting

4.7 Grounding Switches

Rated close and latch current (A rms)


Number of mechanical operations before internal
visual inspection or servicing
Number of closing operations into energized
bus without damage
Ground switch interrupting capacity, if specified
and agreed (A)

4 8 Voltage Transformers

Name of the manufacturer


Applied test voltage (kV rms)
Power-frequency field test voltage with VT
connected (kV rms)
Ratio of high-voltage to low-voltage windings
Thermal rating of each secondary winding (VA)

23
IEEE
C37123-1991

Thermal rating of the primary winding (VA)


IEEE C57.13-1978 E291 accuracy classification
List burdens for which the above accuracy
classifications apply
Table of current versus time for backfeeding
capacitive current during GIS field tests

4.9 Current "formem

IEEE C57.13-1978 [291 accuracy class


Ratio in terms of primary and secondary current
ratings
Continuous thermal current rating factor
Secondary winding insulation class
Are all current transformers external t o the
GIS enclosures (Ye s/No)
Are CTs split-core type? (Yes/No)

4.10 Gas-to-& Bushing


NOTE: Special BIL and SIL requirements may be specified for the bushing.
Name of the manufacturer
Type designation of the manufacturer
Material
Rated 60Hz Withstand
Dry-1 min (kV rms)
Wet-10 s (kV rms)
ExternalStrikeDistance
Phase-to-ground
Phase-to-phase
External creep distance
Cantilever strength
Acceptable terminal load

4.11 Gas System

Total quantity of SF6 gas to be supplied with the


original equipment (kg)
Total quantity of SF6 gas required per breaker (kg)
Guaranteed maximum SF6 gas leakage rate in
k d y r from the complete GIS
Number of gas monitoring systems included
with the equipment
In service life gaskets
Storage shelf life of gaskets

24

S-ar putea să vă placă și