Documente Academic
Documente Profesional
Documente Cultură
WATER SERVICES
Water supply can either be from the public utility or by private water supply
arrangements.
Borehole
Well
The suitability of water supplied for potable use depends on its purity. Potable
water has to conform to the WHO standards.
Filtration
Sterilization
Softening
The stored capacity shall not exceed the equivalent of 3 days water demand.
Storage tanks can be located at the grand and/or elevated positions.
ii) The reduced line pressure from storage tanks as compared to mains
pressure implies a quieter operation.
Line pressurization
Gravity
Line pressurization
In recent times, the minimum pressure required by modern top range faucets is 1
bar (10m). The mains pressure in most cities of Nigeria is not adequate for this
requirement and a line booster system is usually incorporated. The distribution is
extended directly from the mains supply. In other installations where the
provision of an elevated storage tank is not practical, the booster unit can take
supply from a ground or underground storage tank.
The controls for the line booster unit are effected using a pneumatic system
(pneumatic vessel or membrane pressure tank).
In multi-storey installations where the differential elevation between the tank and
the uppermost fittings (topmost floor) is not adequate, it may become necessary
to install line boosters to serve the upper floors.
The demand for water at sanitary appliances is intermittent and mainly random
but it can peak at some fairly regular times. As such sizing pipes based on the
peak demand is uneconomic. Rather, sizing is carried out based on theoretical
probability of use commonly referred to as demand unit or loading unit.
4. Sum the LU along the pipework to the source (water tank or mains valve).
5. Convert the LU to flow rates using table (this may not be necessary if
sizing graph of figure 2.4 or 2.5 is used.
6. Determine the pressure head H (in metre) of water causing the flow.
7. Estimate the equivalent length EL (in metre) of the pipe run on each flow.
Assume the measured length plus 30% allowance for fitting losses.
9. Depending on the pipe material, choose pipe sizes using Fig 2.4 or 2.5
and the index circuit. Limit flow velocity to less than 2m/s.
10. Size other circuits based on respective H/EL ratio and the limiting velocity.
The hot water requirement for the building can be met by using central hot water
service or decentralized (point-of-use) service.
Central Service
The source of hot water can be gas, diesel or electric boilers. The boilers can be
hot water or steam generators. The hot water can be distribution directly even
though this is not usual. The indirect system is more common in which hot water
or steam from the boiler is used to heat the secondary water system that is used
in the building.
Decentralized Service
This is common in residential dwellings or where the points of use are minimal.
Electricity is the common means of heating. Local electric water heaters (EWH)
come in various sizes 10L, 25L, 50L, 80L, 100L and 125L. The bigger units
with capacities above 50L are used in mini-centralized services. The small units
with capacities of 10L are usually of the instantaneous type.
Hot water distribution pipe works are lagged (insulated) to conserve heat if the
pipes are not buried in the walls.
3. Stein and Reynolds. Mechanical and Electrical Equipment for Buildings, Wiley
ISBN 047156965.