NAMEOFWORK
Part - I
CIVIL WORK
A
COLD STORE WITH PRECOOLING & RIPENING A. MAIN BUILDING
B)
REFRIGERATION SYSTEM
C)
OTHER MACHINARY
TOTAL OF PART II
Part III HT/LT POWER SUPPLY WORK
1.0 TRANSFORMER & HT/LT WORK
2.0 RELATED ELECTRICALS FOR REF. SYSTEM
GRAND TOTAL
Madhya Pradesh State Agricultural Marketing Board
(MP Mandi Board)
63 BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT
AMOUNT
64
Based on Basic Design & Layout by Consultant, the Architectural and Structural Designing of the Civil Works Up to Plinth are in the
Scope of Work of the Bidder
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
A - EARTH WORK.
A-1 Excavation for foundation in earth, soils of all types sand, gravel and soft murum upto a 410 Cum.
depth of 1.5 M including removing the excavated material upto a distance of 100 m
beyond the building area stacking and spreading as directed, dewatering, preparing the
bed for the foundation and necessary back filing, ramming, watering (including shoring
and strutting) etc. complete (Lift up to 2.50 m) Spec. No. BD.A. 1 Page No. 259.
A-2 Excavation for foundation in hard murum including removing the excavated material 200 Cum.
upto distance of 100 m. beyond the building area and stacking and spreading as
directed, dewatering, preparing the bed for the foundation and necessary back filling,
ramming, watering including shoring, strutting complete. (Lift upto 1.50 m.) Spec. No. :
Bd.A 2 Page no. 259.
A-3 Excavation for foundation in hard rock by chiseling, weighing etc. including trimming and R.O Cum.
leveling the bed, removing the excavated material up to a distance of 100 meter beyond
the building area and all lifts, stacking as directed, dewatering and back filling complete.
(Lift up to 1.5 m.) Spec. No. Bd.A6. Page No. 260.
A-4 4 Back Filling in footing with approved excavated materials in 15 cm. To 20 cm. Layers 1500 Cum.
including watering and compaction etc. complete. (above 1.50 Meters lift) Spec. No. 6
Page No. 15.
A-5 4 Filling in plinth and floors with contractor's soil, sand or murum in 15 cm to 20 cm. 1500 Cum.
Layers including watering and compaction etc. complete. Spec. No.7 Page No. 15
A-6 Providing dry trap / granite / quartzite / gneiss rubble stone soling in single layer of 23 500 Sq M.
cm. Thick below Plinth Concrete layer including hand packing and compacting
complete. Spec. No. BD.A. 12. Page No.264.
SUB TOTAL EARTH WORK. Total Rs.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
B - P.C.C. WORK.
B-1 5.3.2 Providing and laying in situ cement concrete (150 mm thk.) M-10/1:3:6 of 432 CUM
trap/granite/quartzite/gneiss metal for foundation including dewatering, form work,
compacting, roughening them if special finish is to be provided, finishing if required and
curing etc. complete (4.42 bag/cum) Spec. No. 3 Page No. 17
C-2 5.3.3 Providing and casting in situ cement concrete M-20 of trap/granite/quartzite gneiss CU.M
metal for reinforced cement concrete columns up to plinth level as per detailed designs
and drawing or as directed including centering, formwork, compacting and finishing the
formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a
smooth and even surface or roughening the surface if special finish is to be provided
and curing etc. complete. (Excluding reinforcement) (7.60 bag/cum) Spec. No. : 4 Page
No.17
Basement 50 cum
Superstructure 6 cum
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
C-3 5.4.1 Providing and casting in situ cement concrete M-20 of trap/granite/quartzite gneiss 92 CU.M
metal for reinforced cement concrete plinth beams as per detailed designs and
drawing or as directed including centering, formwork, compaction and roughening the
surface of special finishing to be proved and curing etc. complete (Excluding
reinforcement). (7.60 bag/cum) Spec. No. 11 Page No.18
Basement 80 cum
C-4 5.4.1 Providing and casting in situ cement concrete M-20 of trap/granite/quartzite /gneiss 70 CUM
metal for reinforced cement concrete floor/ roof beams and slabs and landings as per
detailed designs and drawings, including centering, formwork, compacting and
roughening the surface if special finish is to be provided and curing etc. complete
(Excluding reinforcement). (7.60 bag/cum) Spec No. 11. Page No. 18.
C-9 5.4.10 Providing and fixing in position Mild steel and H.Y.S.D. bar reinforcement of various 45 M.T.
diameters for reinforced cement concrete pile caps, footings, foundation, slabs, beams,
columns, canopies, stair case, newels, chajjas, lintels, pardis, copings, fins arches etc.
as per detailed designs, drawings and schedules including cutting, bending, hookin the
bars, binding with wires or tack welding and supporting as required complete. Spec. No.
: 13. Bd.F17 Page No. 19
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
D - MASONRY WORK.
D-1 6 Providing coursed brick masonry in cement mortar 1:6 in plinth of inner walls / in plinth 152 CUM
of external walls including bailing out water manually, striking joints on unexposed faces
and watering complete. Spec. No. 2 A Page No. 25.
D-2 6 Providing second class burnt Brick masonry with conventional/Indian standard type 110 CUM
bricks in cement mortar 1:6 in superstructure including striking joints, racking out joints,
watering and scaffolding complete. Spec. No. 2B Page No. 25.
D-3 6 Providing second class burnt Brick masonry with conventional/Indian standard type 70 SQM
bricks in cement mortar 1:6 in half brick thick wall including mild steel longitudinal
reinforcement of 2 bars of 6 mm. Diameter at every third course, property bent and
bounded at ends including scaffolding racking out joints and watering complete. Spec.
No. 9 Page No. 26.
D-4 18 Providing internal cement plaster 12 mm. Thk. In single coat in cement mortar 1:5 with 600 SQM
neeru finishing to concrete or brick surfaces, in all positions including scaffolding and
curing complete. Spec. No. : 1.III Page No. 54.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
D-5 18 Providing internal cement plaster 12 mm. Thk. In single coat in cement mortar 1:5 335 SQM
without neeru finishing to concrete or brick surfaces, in all positions including scaffolding
and curing complete. Spec. No. : 1.III. Page No. 54.
D-6 18 Providing sand faced plaster externally in cement mortar using Kharsalia / kasaba or 1100 SQM
similar type of sand, in all positions including base coat of 15 mm. Thick in cement
mortar 1:4 using water proofing compound at 1 kg. Per cement bag, curing the same of
the base than 2 days and keeping the surface of the base coat rough to receive the
sand faced treatment 10 mm. thick in cement mortar 1:4 finishing the surface by taking
out grains and curing for fourteen days scaffolding etc. complete. Spec. No. 9 Page no.
55.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
E - FLOORING.
E-1 Providing and casting in situ m-15 (1:2:4) grade light Reinforced Tremix Flooring 120 2200 SQ.M
mm thick in Cold stores & grading packing hall including providing and binding in
position reinforcements as directed. Casting floor concrete in bays by using girder,
vibrator, vacuum departingmechanical trawling till perfectly leveled, smooth integrated
cement finish is achieved, curing and making good, rate shall include cost of
appropriate concrete hardener, expansion joints bituminous felt and excluding cost of
reinforcement.
E-2 14 Providing and laying polished kotah stone flooring 25 mm to 30 mm thick and 4 cm. To 50 SQ.M
55 cm. Wide in plain pattern on a bed of 1:6 cement mortar including cement float, filling
joints with neat cement slurry, curing, polishing and cleaning complete. Spec. No. 18
Page No. 48.
E-3 14 Providing and fixing in required positions skirting or dado kotah stone slabs 25 mm. To 20 RM
30 mm. Thick and 30 cm. Wide on 1:4 cement plaster including cement float, filling
joints with neat cement slurry, curing, rubbing, polishing and cleaning complete. Spec.
No. 17 Page No. 47.
E-6 Providing sills of polished kotah stone 25 mm. To 30 mm. Thick bed of 1:4 cement RO SQ.M.
mortar including cement float, filling joints with slurry, curing, polishing and cleaning
complete.
E-7 14 Providing 25 mm./30 mm. Thick partitions of machine cut both side polished black/ 8 SQ.M.
brown Granite stone slab of approved shapes, quality and colour for urinals, including
cutting holes of required size in the appropriate places to receive pipes etc. fixing in
cement mortar 1:3 curing and cleaning complete. Spec. No. 17 Page No. 47.
E-9 14 Providing and fixing ceramic tiles of approved quality and size 7 mm thick for dado and 450 SQ.M.
skirting in required position with ready made adhesive mortar of approved quality on
plaster of 1:2 cement mortar including joint filling with white / colour cement slurry
cleaning curing complete. Spec. No.18 Page No. 48.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
Providing and fixing waterproof marine flush door panels for bath and w.c. (8 nos.) with 11 sqm
1 mm thk laminate finish on both sides.
F-2 0 Providing and fixing aluminium sliding window of various sizes as per detailed drawings 5 SQM
fabricated powder coating with or without ventilator including fabrication, glazing with
plain / clear glass panels of approved type and quality, all fixtures and fastening
complete with guard bars 10 cm. center to center. Spec. No. 30. Page No. 37.
F-3 0 Providing and fixing rolling steel shutters fabricated from 18 gauge steel laths with side 18 SQM
guides, bottom rail, brackets, door suspension shafts, including rolling springs, locking
arrangements and housing box at the top including mechanical gear operating
arrangement and one coat of red lead primer and two coat of enyamal paint of
approved shade and quality. Spec. No. 5 Page No. 40.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
F-4 Providing and fixing mosquito proof and fly proof S.S. mesh to windows, ventilators with RO SQM
removable teak wood frame ( 25 mm x 50 mm ) including fixing of mesh of with teak
wood lipping of 12 mm x 50 mm and including painting, l etc. complete. As directed by
Engineer in charge.
F-5 Providing and fixing in position M.S. frame door shutters fixed with fly proof S.S. mesh RO SQM
as per drawing and design and complete with necessary chrome plated fittings and
fixtures and three coats of oil paint etc. complete . As directed by Engineer in charge.
(including teak wood frame)
F-6 Providing and fixing in position 8 S.W.G. wire weld mesh 50 x 50 mm jali in M.S. angle 10 SQM
frame 50 x 50 x 5 as per drawing and design including one coat of primer and two coats
of oil paint as per drawing and instructions of Engineer in charge.
H-2 18 Providing and applying washable oil bound distemper of approved colour and shade to 935 SQM
new surfaces in two coats over a primer coat including scaffolding, preparing the
surfaces complete. Spec. No. 2. Page No. 56.
SUB TOTAL COLOURING WORK. Total Rs.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
I - ANCILLARY WORK.
I-1 0 Providing preconstructional anti termite treatment to all excavated surfaces, back fill in 2400 SQM
immediate contact with foundation, and treating the top surface of plinth filling at the
rate of 5 ltrs. Of emulsion concentrate of 0.5 percent of Chicropyriphox per Sq m. of
surface area with ten years guarantee bond as per I.S. 6313 (part II) -1973 (as per item
No. 22.41, 22,42 and 22,43 of schedule of rates of National Building Organization).
Spec. Sr. No. 7 Page 68.
I-15 Providing and installing in position fabricated M.s. entrance gate (weight approx 50 12 SQM
kg/sq m) including I.S.J. side posts, heavy duty hinges, pad locks, and tower bolts and
including three coats of oil paint to all steel surfaces all as per instructions of Engineer in
charge.
SUB TOTAL ANCILLARY WORK. Total Rs.
J - WATER SUPPLY AND SANITATION.
J-1 Providing and hoisting in position 1 nos. of 10000 ltr capacity P.V.C. water tanks of 1 no.
approved quality and make over a brick masonry platform with plaster and top concrete
complete with all necessary connections as per instructions of Engineer in charge.
J-2 Providing and constructing under ground R.C.C. water tank in M: 250 concrete as per 1 no.
design, inside dimension as 3.0 x 2.0 x 1.5 m with R.C.C. roof slab with inspection
covers, central R.C.C. partition wall, smooth water proof plastering from inside and sand
faced plastering from out side and with all necessary inlet and outlet pipe connections
etc. as per design, drawing and instructions of Engineer in charge.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
J-3 24 Providing and fixing on walls / ceiling / floors, of Diameter given below 'B' class having
embossed as ISI Mark galvanized iron pipes with screwed, sockets, joints and
necessary galvanized iron fittings such as sockets, back nuts, elbows, bends, tees,
reducers, enlargers, plugs, clamps etc. including necessary drilling holes in walls, slabs
etc. and remaking good the demolished portion to restore the same in original condition
neatly and applying anti corrosive primer oil paint and two coats of all painting complete.
Spec. No. 3 Page No. 69.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
J-6 23 Providing and fixing white glazed earthenware half stall type group of three urinals with 1 no.
cistern including P.C.C. soil pipe, C.I. Trap and soil pipe connection upto face of wall
complete. Spec. No. As directed by Engineer in charge. Spec.Sr. No. 34 Page No. 74.
J-7 Providing and laying 100 mm. Diameter half round white glazed stone earthenware 4 RM
pipes in 1:5:10 cement concrete bedding including bends, necessary excavation etc.
complete. As per instruction from Architect
J-8 Providing and fixing white glazed earthenware wash Hand Basin of 55 cm. X 40 cm. 2 no.
Size including single cold water pillar tap / brackets, rubber plugs and brass chain, stop
tap and necessary P.V.C. pipe connections including P.V.C. waste pipe and without
bottled trap upto the outside face of the wall. As per instruction from Architect
J-9 24 Providing and fixing 10 cm. Cast iron Nhani Trap including grating, bend and piece of 4 no.
cast iron pipe upto the outsie face of the wall complete (with 45 cm. Arm). Spec. No. 8
Page No. 70.
J-10 24 Providing and fixing 15 cm. Cast iron Nahani Trap including grating, bend and piece of 2 no.
cast iron pipe upto the outside face of the wall complete (with 45 cm. Arm). Spec. No. 8
Page No. 70.
J-11 Providing and fixing of required diameter cast iron soil / vent / waste pipes with
necessary fixtures and fitting such as bends, tees, single junction, double junction,
slotted vent offsets on walls or in the ground including filling joints with lead with red
lead oil paint coat and two coats of anti corrosive paint including fixing the pipe on walls
by means of nails driven through lugs in wooden holder / battens and supported on
ground floor by C.C. 1:2:4 of 30 cm. x 30 cm. size blocks complete.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
J-12 Providing and fixing 15 cm. X 10 cm. Salt glazed stone ware gully trap in cement 4 no.
concrete 1:4:8 outside the building including cast iron grating in the sink, connecting
glazed stoneware pipe, brick masonry chamber with cast iron grating for the gully trap,
and precast R.C.C. cover with frame fixed with cement mortar.
J-13 Providing and laying 100 mm. Diameter salt glazed stone ware pipes including fittings 4 RM
such as bends, tees, single junction, double junctions, laying, jointing including
excavation and refilling the trenches complete. As per instruction from Architect
J-14 Providing and laying R.C.C. concrete pipes of I.S. N.P. class of 150 mm. Diameter in 25 RM
proper line, level and slope including necessary collars, excavation, laying fixing with
collars in cement mortar 1:1 etc. complete including excavation and refilling the
trenches.
J-15 6 Providing and constructing Brick masonry in cement mortar 1:6 for Inspection Chamber
various sizes given below including 1:4:8 cement concrete foundation, 1:2:4 cement
concrete channels half round S.W.G. pipes, with plastering brick masonry inside and
outside with cement mortar 1:4 and inside neat cement finish including 75 mm. thick
R.C.C. cover etc. complete depth upto 1.20 m. Spec. No. 2. Page No. 25.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
a. 60 cm. X 45 cm. 4 no.
b. 90 cm. X 45 cm. 1 no.
J-16 6 Providing and constructing Brick masonry in cement mortar 1:6 for intercepting chamber 1 no.
90 cm. X 45 cm. Including 1:4:8 cement concrete foundation, 1:2:4 cement concrete
channels half round S.W.G. pipes, channels / half round glazed stone ware intercepting
trap with roding pipe set in 1:4:8 C.C. block with plastering brick masonry inside and out
side with cement mortar 1:$ and inside neat cement finish including 75 mm. thick R.C.C.
cover etc. complete. depth upto 1.20 m. Spec. No. 2 Page No. 25.
J-17 Providing and fixing Hume pipe septic tank 900 mm. Diameter with vent pipe and cap 1 no.
including necessary fittings including excavation and laying. And constructing man holes
chambers with cover on top of the septic tank openings. With plaster etc. complete. As
per instruction from Architect
J-18 Providing soak pit of size 150 cm. X 150 cm. 150 cm. Including excavation and filling 1 no.
with brick bats. As per instruction from Architect
SUB TOTAL WATER SUPPLY AND SANITATION. Total Rs.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
ITEM
NO. DESCRIPTION OF ITEMS. QTY. UNIT RATE
CODE.
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT
AMOUNT, RS
AMOUNT
5 Concrete foundation and grouting as required for metering cubicle with 1 No.
height above ground as per MPEB norms.
MPEB approved electronic TOD meter including liasoning, coordinatio
6 n etc. with MSEB and testing, approvals from authorities as require 1 No.
d.
2-
pole structure with height / clearances as per rules, using RSJ 100 X 11
6 poles ( min. length 9 m.) with 10 mm. thk. base-
plate in M20 PCC 1.5 mtr. deep foundation and 300 mm. dia. muffing, i
7 nterconnection from metering cubicle, 1 set of 3 nos. 11 KV class lighte 1 Job
ning arrestors, 1 set of 11 KV, 200 Amp. single break vertically mounte
d A.B. switch, 1 set of 11 KV D.O. fuses with operating rod, interconnect
ion from DOF to transformer with alkathyne pipe insulated conductor, 11
KV insulators as required, ACSR conductor as required, M.S. channels
, cross-
bracings, supporting structure and all required clamps, connectors, har
dware, accessories, double earthing of 3 nos. LA, 4 P structure, GOD,
DOF using 40 X 6 mm GI flat, complete as per applicable standards, rul
es, norms, guidelines of local authorities, statutory requirements includi
ng liasoning, testing, approvals from all authorities concerned.
All M.S. items to be duly painted with red-
oxide zinc chromate primer and 2 coats of aluminium paint. Portions em
bedded in ground to be painted with 2 coats of bituminous paint
315 KVA, 3 ph. 50 Hz. 11 KV / 433 V transformer as per IS : 2026 and o
ther applicable standards, vector group Dyn11, with off-
circuit tap change switch having constant KVA taps in 6 steps of 2.5 %, l
ow loss grain oriented silicon steel laminations, copper wound with mini
mum class A insulation, ONAN cooling with maximum 50 / 55 deg. temp
8a erature rise of oil / winding, outdoor type HV bushings, LV cable box sui 1 No.
table for 2 nos. 3.5 C X 90 sq. mm. AYFY cables, outdoor type LV neutr
al bushing, radiators, fittings and accessories as per IS including cons
ervator, local winding and oil temperature indicators etc. complete with
first fill of oil as per IS : 335 with 10 % extra for topping up at site, doubl
e earthing of neutral and transformer body using 40 X 6 mm GI conduct
or etc. as per applicable standards, rules, norms, guidelines of local au
thorities, statutory requirements, including liasoning, testing, approvals f
rom all authorities concerned. The job includes the dismantling of the ex
isting transformer at Indapur site and replacing it with new one as specif
ied in the tender along with all necessary accessories. The bidder shall
add on the charges for this work. Please note that the existing transfor
mer is the property of MSAMB and must be handed over back to MSA
MB in working condition.
Same as (8a) above, but of rating 500 KVA and with LV cable box suita
8b RO No.
ble for 3.5C X 150 sq.mm cable. x 3 nos..
400 Amp. 3 pole ACB ( 50 KA ) with earth fault relay, ammeter, voltmete
9 r & indicating lamps in outdoor weather-proof sheet- 1 No.
steel powder coated enclosure having canopy, with terminal extensions,
cable entry & exit boxes suitable for 2 nos. 3.5C X 90 sq.mm AYFY inc
omimg cables as well as 2 nos. 3.5 C x 90 sq. mm. Outgoing cables, m
ounting structure, accessories, hardware etc. including mounting frame,
concrete grouting, double earthing using 40 X 6 mm GI flat, complete a
s per statutory requirements for transformer LV isolation.
10
Earthing stations including test-link as per IS : 3043 using:
a) 600 x 600 x 6mm. GI plate electrode with 50 x 6 mm. GI strip upto g
17 No.
round level.
b) 600 X 600 X 3 mm. copper plate electrode with 25 X 3 mm. copper st 4 No.
rip upto ground level for transformer neutral.
175 KVA, 3ph. & neutral, 50 Hz. 415V, 0.8 pf, heavy duty water-
cooled Diesel - Generator of Kirloskar Cummins make set with cable bo
x suitable for 2 no. 3.5C X 90 sq. mm. AYFY cable, neutral earthing ter
12 minal, heavy duty batteries, engine mounted alternator for battery char 1 No.
ging, manual control panel, local indicators, fuel tank, channel base fra
me, anti-
vibration pads, complete with all required equipment, accessories, fittin
gs, controls, safety devices, exhaust piping, fuel piping, silencer, doubl
e earthing of neutral and body etc. as per applicable standards, rules, n
orms, guidelines of local authorities, statutory requirements, including li
asoning, testing, approvals from all authorities concerned.
Main Power Distribution Board ( PDB): -
Panel shall be totally enclosed cubicle type free standing, floor-
mounting, compartmentalized and modular in construction, expandable
on both sides, fabricated out of 14 gauge CRCA sheet steel duly pretre
ated and painted with 2 coats of red-oxide zinc-
chromate primer and painted with synthetic enamel paint or powder coa
ted.
Panel shall have separate MSEB / DG supply change-
over & incomer section with door interlock and isolated horizontal / verti
cal bus-
13 bar chambers. Bakelite / acrylic shrouds with danger lables shall be pro 1 Set
vided as required to cover live parts and busbars for safety purpose. S
eparate cable-
alleys shall be provided. Component layout in individual modules sh
all be spacious with adequate clearances for ease of operation and mai
ntenance. Capacitor modules when provided shall have adequate cooli
ng arrangement such as louvres at rear and sides. Cable entry shall be
top or bottom as per site conditions. Aluminium anodized labels shall be
provided for components and feeders. 40 x 6 mm GI earth busbar sh
all be provided along panel length with terminals brought out at both en
ds. Necessary foundation frame / pedestal / mounting structure, sheet
metal blanking covers, foundation bolts and all required material / acces
sories etc. shall be included.
Vendor shall submit detailed SLD, G.A. & dimensional drawings, BOM a
nd wiring diagram for Owner's approval. Panel shall be manufactured a
nd tested in an approved manner as per IS:8623 and other applicable s
tandards.
MCC shall consist of following feeders:
A . Change-over section
(ii) 3 Nos. supply on LED type indication lamps with 3 Nos. HRC fuses f
or MSEB and DG supply on indication. 2 sets
(iii) 315 / 5 Amp., 10 VA Y-
ph. CT on MSEB supply side for APFC panel - 1 no.
B. Incomer
(i) 400 Amp ACB ( 50 KA ) with OL, SC, EF protections, operating hand
le and door interlock, etc.- 1 no.
(ii) 0 to 500 V voltmeter, voltmeter selector switch, 3 Nos. HRC fuses
etc. 1 set
50 X 6 mm. main copper busbars with red, yellow, blue, black colour h
eat shrinkable PVC sleeves and mounted on epoxy / SMC insulator sup
ports of tested quality as per IS. Other vertical copper busbars shall be
rated for total compartment rating with current density of 1.5 Amp. per s
q. mm. Minimum size 50 X 6 mm.
Minimum clearance on all sides of each busbar shall be 25 mm.
C. Outgoing Feeders
Cables / wires used for switchgear power connections shall be PVC ins
ulated multi-
strand copper conductor as per IS with current rating atleast 40% more
than feeder FLC. Minimum wire size shall be 2.5 sq. mm. ( to be used u
pto 16 Amp. MCB feeder). For feeder rating above 63 Amp, busbars sh
all be used.
(i) 200 Amp TP MCCB with protections, operating handle and door inte
rlock . neutral link etc. for machine room, and refrigeration systems 1
nos.
(ii) 63 Amp MCB with protections, operating handle and door interlock .
neutral link etc. for Air conditioning system 1 no.
(iii) 100 Amp. MCB with protections, operating handle and door lock, ne
utral link etc for Grading & Packing Hall.
(iv) 100 Amp MCB with protections, operating handle & door lock, neutr
al link etc for complete lighting.
(v) 63 Amp. MCB as spare
14 LT Capacitor APFC Panel 1 Set
Automatic power factor correction compartmentalized, modular, cubicle
type totally enclosed panel generally as per main PDB specification as
under:
A) Incomer :
(i)150 Amp MCCB with OL,SC protections, operating handle, door inter
lock etc. 1 no.
(ii) Supply on LED type indication lamps with HRC fuses 3 nos.
(iii) Auto / Manual switch 1 no.
(iv) APFC relay (Syntron / Sycon make) 1 no.
(v) 0-60 sec. Timer for manual operation 1 set
(vi) 0 to 500 V voltmeter, voltmeter selector switch, 3 Nos. HRC fuse
s etc.- 1 set
(i)25.0 KVAR capacitor module with capacitor, 63 Amp. SFU ( fuse ratin
g as per capacitor mfr. recommendation), 63 Amp. contactor, start, stop
push-
buttons, indication lamp, control fuse switchgear, other components etc.
6 nos.
(ii) 25 KVAR capacitor module as above but without capacitor bank - 2
nos.
(ii) 9 mtr. swaged type medium gauge welded pole as per IS with base
plate, earthing stud, junction- 10 No.
box with MCB, terminals etc., 1 mtr. length lamp bracket, pole cap, wiri
ng from jb to lamp using 2.5 sq.mm. PVC insulated flexible copper wire
etc. complete for 150 W HPSV lamp fixing.
Point wiring from Grading hall LP to switch-board to light / fan-
points in PVC conduits on wall / ceiling inclusive of mains, sub-
mains, sunmica top wooden switch-
board with 5 Amp. piano switch for each light fixture, 650 V grade PVC i
nsulated flexible copper wires as specified below etc. 14 SWG copper e
arth wire to be used from sw. board to fitting. Rate shall be inclusive of
conduit accessories, clamps, saddles, junction boxes, spacers and all r
23 125 No.
equired material.
Wire Sizes
(i) LP to sw. board - 3 nos. 2.5sq.mm.
(ii)Sw. board to light 2 nos. 1.5 sq.mm.
Neutral for individual circuit shall be run separately.
Colour code:- Ph-Red, Neutral - Black, Earth- Green
1 ph. 5 Amp. 2 pin / 3 pin plug socket with piano-
24 switch on sunmica top wooden board including wiring in PVC conduit a 10 No.
s per Item ( 24a ) above in Grading hall & Anter ooms & Reception area
s ).
Structural steel for cable supports, base frames, mounting frames, brac
kets, various other supports, miscellaneous requirements etc. The max
27 imum sizes of sections shall be as under.
a) ISMC 100
b) ISA 75 X 75 X 6
c) 25 X 6 mm M.S. flat
d) 6 mm. thk. chequered plate RO MT
Hume pipes of following ID to be laid below ground including jointing an
28
d sealing of ends to prevent water ingress
a) 300 mm. RO M
b) 250 mm. RO M
c) 200 mm. RO M
d) 150mm. RO M
Providing man hole with masonry chamber and CI cover for laying or wi
29 5 No.
thdrawal of cables in hume pipes.
Providing and laying in 600 mm. (W) X 1000 mm. (D) trench with sand l
30 ayer 150 mm. thick and single brick layer on cable top including refilling RO M
the trench, levelling and providing metal cable markers at 3 mtr. interv
als.
Taking 6 inch bore in rocky soil upto minimum 3 mtr. depth or as req
31 RO No.
uired for GI pipe earth electrode.
32 Fire Fighting and Safety equipment
a) Fire fighting system as per statutory requirement of fire fighting & saf 1 Set
ety department with provision of latest equipments.
b) Portable 5 kg capacity dry type fire extinguisher suitable for electrical 5 No.
fire as per IS and as recommended by TAC.
c) Floor mounted bucket stand with 4 nos 13 litre buckets hung on hoo 2 Set
ks. The stand shall be 1.5 m L x 1.0 m H made out of MS angle frame
duly painted with red oxide primer and 2 coats of red colour finish paint.
d) Antiskid chequered type 415 V grade black rubber mat 1000 mm wid
1 Set
e as per IS 5424 for panels, switches etc.
2 No.
e) First aid box with contents as per standard requirements.
f) Shock treatment chart in English, Hindi and Gujarati with wooden fra
2 No.
me and glass cover.
2 No.
g) Metallic permanently inscribed danger. GAIC 11 KV and 415 V.
h)Insulated hand gloves pairs 11 KV and 415V . 2 No.
TOTAL, RS.
TOTAL IN WORDS:
Panel shall have separate incomer section with door interlock and isolat
ed horizontal / vertical bus-
bar chambers. Bakelite / acrylic shrouds with danger ouver shall be pro
vided as required to cover live parts and busbars for safety purpose. S
eparate cable-alleys shall be provided. Component layout in
(iv) Supply on LED type indication lamp with HRC fuse etc. - 1 set
1 current density of 1.5 Amp. Per sq. mm. Minimum size 25 X 3 mm. 1 Set
c) TP-MCB shall be suitable for motor duty and rating shall be co-
ordinated with OLR rating as per manufacturers recommendations.
TPN isolators (MCB type) suitable for motor duty in outdoor type metal
2 enclosure for motors located outside machine room. 1 set as required 1 Set
3 1 Set
d) 3C X 4 sq.mm. Copper ( 1 run for motors upto 7.5 KW DOL and
2 runs for motors upto 12.5 KW - SD)
3 1 Set
e) 3C X 6 sq.mm. Copper ( 2 runs for motors upto 15 KW - SD)
m) Copper control cables of size 1.5 sq. mm. As per system reqmt.
m) Copper control cables of size 1.5 sq. mm. As per system reqmt.
6 1 Set
a) 32 x 6 mm GI strip (MCC panel )
b) 25 x 3 mm GI strip ( Sub-grid along
cable-trays, motors above 3.7 KW
upto 30 KW, MCB-DBs, lighting
panels etc. )
c) 8 SWG GI wire ( motors upto 3.7 KW, power isolators, JBs, lighting
poles etc.)
d) 12 SWG GI wire ( field eqpt. Like
solenoid valves, LPBS etc.)
e ) 14 SWG Cu wire ( lighting fixtures,
1 ph. Utility-sockets etc.) - 1 set
Lighting Panel
Lighting panel with 32 A DP ELMCB as incoming and 6 A SP-
MCB 6 nos. as outgoing feeders
LP shall be with IP:42 protection, factory fabricated out of CRCA sheet,
powder coated, with metal door, top and bottom removable gland plate
s, universal mounting, complete with copper busbars, earth bus, termin
7 als for looping, cable- 1 No.
ties, shrouds to cover live terminals, front blanking plate with cutout for
MCB operation and all accessories etc. Rate shall be inclusive of mount
ing structure and all required material for installation.
Lighting fixtures
a) 1 x 40 W general purpose box type channel tube fittings with transpa
rent acrylic cover, lamp, mounting hardware, JB for looping, and all acc
essories for ante room as per requirement 1 Set
8
c) Self contained emergency light unit 20 W with sealed re-
chargeable battery, battery-
charger etc. complete in all respects for automatic switch on in case of 2 Set
supply failure.
8
Emergency alarm system (230 VAC) for cold chambers with input sign
als from switches located inside cold chambers near each door. The sy
stem shall comprise of switches, JBs, 150 mm. Gong bell / hooter, visu
al indication to indicate the origin of alarm signal, test / accept / reset pu
11 sh- buttons, UPS ( backup for 1 hour ), necessary wiring and all require 1 Set
d material, accessories.
TOTAL, Rs.
TOTAL, IN WORDS:
Total Amount, Rs.
Total Amount, Rs.
C. PEB WORK
Sr.
No. Description Unit Qty
B) Refrigaretion Machine
Sr.No. Description
Unit Quantity Unit Rate, Rs.
Unit & Air coil unit as per tender specification Capacity 8.5TR
1 Nos. 6
complete with
Codensing Unitref. Piping
& Air coil cabling andtender
unit as per electrical Panels
specification
2 Nos. 2
Capacity in Unit
Codensing 9.5TR Piping
& Air cabling
coil unit andtender
as per electrical Panels of
specification
3 Nos. 8
capacity 7.5 TR TR Piping cabling and electrical Panels
4 SITC Ref. unit for Air conditioning of Packing & Dispatch dock
comprising of Air Cooled Codensing Unit & Air coil unit as per
tender specification of capacity 11.0 TR TR. Including Piping, GI
Ducting with insualtion, SA/ RA Aluminum extruded Grills & Nos. 1
Diffuser, wiring cabling and electrical Panels Temperature
indicators & controllers
7 Ducting & grills and other accessories for Air conditioning Area
Lot 1
TOTAL
Recirculation System:
Chemical Recycling piping with 65 mm dia. pipes of Supreme brand - 7
0m
Inside pipeline with hole with fitting 12 kg. Supreme brand white color
ISI marked with 35 mm thickness 250 Mts
3.1 Ethylene gas emission system as per tech. specs Nos. 1 No.
3.2 Ventilation system as per tech. Specs. set 4 Set
3.3 Steam type Humidifiers capacity 3 to 4 KW set RO
Total Amount
(Rs.)
Total Amount
(Rs.)
Total Amount,
Rs.
AMOUNT
Total Amount
(Rs.)
5 Concrete foundation and grouting as required for metering cubicle with 1 No.
height above ground as per MPEB norms.
MPEB approved electronic TOD meter including liasoning, coordinatio
6 n etc. with MSEB and testing, approvals from authorities as required 1 No.
.
2-
pole structure with height / clearances as per rules, using RSJ 100 X 11
6 poles ( min. length 9 m.) with 10 mm. thk. base-
plate in M20 PCC 1.5 mtr. deep foundation and 300 mm. dia. muffing, in
7 terconnection from metering cubicle, 1 set of 3 nos. 11 KV class lighteni 1 Job
ng arrestors, 1 set of 11 KV, 200 Amp. single break vertically mounted
A.B. switch, 1 set of 11 KV D.O. fuses with operating rod, interconnectio
n from DOF to transformer with alkathyne pipe insulated conductor, 11
KV insulators as required, ACSR conductor as required, M.S. channels,
cross-
bracings, supporting structure and all required clamps, connectors, hard
ware, accessories, double earthing of 3 nos. LA, 4 P structure, GOD, D
OF using 40 X 6 mm GI flat, complete as per applicable standards, rule
s, norms, guidelines of local authorities, statutory requirements includin
g liasoning, testing, approvals from all authorities concerned.
All M.S. items to be duly painted with red-
oxide zinc chromate primer and 2 coats of aluminium paint. Portions em
bedded in ground to be painted with 2 coats of bituminous paint
400 Amp. 3 pole ACB ( 50 KA ) with earth fault relay, ammeter, voltmete
9 r & indicating lamps in outdoor weather-proof sheet- 1 No.
steel powder coated enclosure having canopy, with terminal extensions,
cable entry & exit boxes suitable for 2 nos. 3.5C X 90 sq.mm AYFY inc
omimg cables as well as 2 nos. 3.5 C x 90 sq. mm. Outgoing cables, m
ounting structure, accessories, hardware etc. including mounting frame,
concrete grouting, double earthing using 40 X 6 mm GI flat, complete a
s per statutory requirements for transformer LV isolation.
10
Earthing stations including test-link as per IS : 3043 using:
a) 600 x 600 x 6mm. GI plate electrode with 50 x 6 mm. GI strip upto gr
17 No.
ound level.
b) 600 X 600 X 3 mm. copper plate electrode with 25 X 3 mm. copper st 4 No.
rip upto ground level for transformer neutral.
175 KVA, 3ph. & neutral, 50 Hz. 415V, 0.8 pf, heavy duty water-
cooled Diesel - Generator of Kirloskar Cummins make set with cable bo
x suitable for 2 no. 3.5C X 90 sq. mm. AYFY cable, neutral earthing ter
12 minal, heavy duty batteries, engine mounted alternator for battery char 1 No.
ging, manual control panel, local indicators, fuel tank, channel base fra
me, anti-
vibration pads, complete with all required equipment, accessories, fitting
s, controls, safety devices, exhaust piping, fuel piping, silencer, double
earthing of neutral and body etc. as per applicable standards, rules, nor
ms, guidelines of local authorities, statutory requirements, including lias
oning, testing, approvals from all authorities concerned.
A . Change-over section
(ii) 3 Nos. supply on LED type indication lamps with 3 Nos. HRC fuses f
or MSEB and DG supply on indication. 2 sets
(iii) 315 / 5 Amp., 10 VA Y-
ph. CT on MSEB supply side for APFC panel - 1 no.
B. Incomer
(i) 400 Amp ACB ( 50 KA ) with OL, SC, EF protections, operating hand
le and door interlock, etc.- 1 no.
(ii) 0 to 500 V voltmeter, voltmeter selector switch, 3 Nos. HRC fuses
etc. 1 set
50 X 6 mm. main copper busbars with red, yellow, blue, black colour he
at shrinkable PVC sleeves and mounted on epoxy / SMC insulator supp
orts of tested quality as per IS. Other vertical copper busbars shall be ra
ted for total compartment rating with current density of 1.5 Amp. per sq.
mm. Minimum size 50 X 6 mm.
Minimum clearance on all sides of each busbar shall be 25 mm.
C. Outgoing Feeders
Cables / wires used for switchgear power connections shall be PVC ins
ulated multi-
strand copper conductor as per IS with current rating atleast 40% more
than feeder FLC. Minimum wire size shall be 2.5 sq. mm. ( to be used u
pto 16 Amp. MCB feeder). For feeder rating above 63 Amp, busbars sh
all be used.
(i) 200 Amp TP MCCB with protections, operating handle and door inter
lock . neutral link etc. for machine room, and refrigeration systems 1
nos.
(ii) 63 Amp MCB with protections, operating handle and door interlock .
neutral link etc. for Air conditioning system 1 no.
(iii) 100 Amp. MCB with protections, operating handle and door lock, ne
utral link etc for Grading & Packing Hall.
(iv) 100 Amp MCB with protections, operating handle & door lock, neutr
al link etc for complete lighting.
(v) 63 Amp. MCB as spare
14 LT Capacitor APFC Panel 1 Set
Automatic power factor correction compartmentalized, modular, cubicle
type totally enclosed panel generally as per main PDB specification as
under:
A) Incomer :
(i)150 Amp MCCB with OL,SC protections, operating handle, door interl
ock etc. 1 no.
(ii) Supply on LED type indication lamps with HRC fuses 3 nos.
(iii) Auto / Manual switch 1 no.
(iv) APFC relay (Syntron / Sycon make) 1 no.
(v) 0-60 sec. Timer for manual operation 1 set
(vi) 0 to 500 V voltmeter, voltmeter selector switch, 3 Nos. HRC fuse
s etc.- 1 set
(i)25.0 KVAR capacitor module with capacitor, 63 Amp. SFU ( fuse ratin
g as per capacitor mfr. recommendation), 63 Amp. contactor, start, stop
push-
buttons, indication lamp, control fuse switchgear, other components etc.
6 nos.
(ii) 25 KVAR capacitor module as above but without capacitor bank - 2
nos.
LT cable end termination using heavy duty crimping type lugs, bi-
16 metal treatment in case of connection between dissimilar metals,, brass
nickel plated double compression cable glands, PVC tape, PVC sleev
es etc.
a) 3.5C X 90 sq.mm. - Aluminium 8 No.
b) 4 C X 6 sq.mm. Copper 10 No.
c ) 4C X 4 sq.mm. Copper 10 No.
d) 4C X 2.5 sq.mm. - Copper 75 No.
e) 3 C x 1.5 sq. mm. Copper RO No.
Lighting panels ( LP )
(i) 50 Amp. 4 P-
ELMCB as incomer and 10 Amp. SPMCB - 10 nos. as outgoing feeders
for COLD STORE WITH PRECOOLING & RIPENINGs 3nos.
(ii) 40 Amp. 4P-
20 ELMCB as incomer and 10 Amp. SPMCB - 12 nos. as outgoing feeders 1 Set
for Office, Store, & Machine room 2 no.
iii) 50 Amp. 4 P ELMCB as incomer and 10 Amp. SPMCB for Grading H
all & Despatch dock 1 nos.
iv) 40 Amp. 4P ELMCB as incomer and 10 Amp. SPMCB for Ante room
s 1 & 2 2 nos.
LPs shall be with IP:42 protection, factory fabricated out of CRCA sheet
, powder coated, with metal door, top and bottom removable gland plat
es, universal mounting, complete with copper busbars, earth bus, termi
nals for looping, cable-
ties, shrouds to cover live terminals, front blanking plate with cutout for
MCB operation and all accessories etc. Rate shall be inclusive of mount
ing structure and all required material for installation.
21 Lighting Fixtures / fans
a) 1 x 40 W general purpose box type channel tube fittings with transpar
ent acrylic cover, lamp, mounting hardware, JB for looping, and all acce 100 No.
ssories for packing hall
b) 2 x 40 W general purpose box type channel tube fittings with transpar
ent acrylic cover, lamp, mounting hardware, JB for looping, and all acce 40 No.
ssories for packing hall
(ii) 9 mtr. swaged type medium gauge welded pole as per IS with base
plate, earthing stud, junction- 10 No.
box with MCB, terminals etc., 1 mtr. length lamp bracket, pole cap, wiri
ng from jb to lamp using 2.5 sq.mm. PVC insulated flexible copper wire
etc. complete for 150 W HPSV lamp fixing.
Wire Sizes
(i) LP to sw. board - 3 nos. 2.5sq.mm.
(ii)Sw. board to light 2 nos. 1.5 sq.mm.
Neutral for individual circuit shall be run separately.
Colour code:- Ph-Red, Neutral - Black, Earth- Green
1 ph. 5 Amp. 2 pin / 3 pin plug socket with piano-
24 switch on sunmica top wooden board including wiring in PVC conduit a 10 No.
s per Item ( 24a ) above in Grading hall & Anter ooms & Reception area
s ).
Structural steel for cable supports, base frames, mounting frames, brac
kets, various other supports, miscellaneous requirements etc. The maxi
27 mum sizes of sections shall be as under.
a) ISMC 100
b) ISA 75 X 75 X 6
c) 25 X 6 mm M.S. flat
d) 6 mm. thk. chequered plate RO MT
Hume pipes of following ID to be laid below ground including jointing an
28
d sealing of ends to prevent water ingress
a) 300 mm. RO M
b) 250 mm. RO M
c) 200 mm. RO M
d) 150mm. RO M
Providing man hole with masonry chamber and CI cover for laying or wit
29 5 No.
hdrawal of cables in hume pipes.
Providing and laying in 600 mm. (W) X 1000 mm. (D) trench with sand l
30 ayer 150 mm. thick and single brick layer on cable top including refilling RO M
the trench, levelling and providing metal cable markers at 3 mtr. interv
als.
Taking 6 inch bore in rocky soil upto minimum 3 mtr. depth or as req
31 RO No.
uired for GI pipe earth electrode.
a) Fire fighting system as per statutory requirement of fire fighting & saf 1 Set
ety department with provision of latest equipments.
b) Portable 5 kg capacity dry type fire extinguisher suitable for electrical 5 No.
fire as per IS and as recommended by TAC.
c) Floor mounted bucket stand with 4 nos 13 litre buckets hung on hoo 2 Set
ks. The stand shall be 1.5 m L x 1.0 m H made out of MS angle frame
duly painted with red oxide primer and 2 coats of red colour finish paint.
d) Antiskid chequered type 415 V grade black rubber mat 1000 mm wid
1 Set
e as per IS 5424 for panels, switches etc.
2 No.
e) First aid box with contents as per standard requirements.
f) Shock treatment chart in English, Hindi and Gujarati with wooden fra
2 No.
me and glass cover.
2 No.
g) Metallic permanently inscribed danger. GAIC 11 KV and 415 V.
h)Insulated hand gloves pairs 11 KV and 415V . 2 No.
TOTAL, RS.
TOTAL IN WORDS:
Panel shall have separate incomer section with door interlock and isolat
ed horizontal / vertical bus-
bar chambers. Bakelite / acrylic shrouds with danger ouver shall be pro
vided as required to cover live parts and busbars for safety purpose. S
eparate cable-alleys shall be provided. Component layout in
(iv) Supply on LED type indication lamp with HRC fuse etc. - 1 set
1 current density of 1.5 Amp. Per sq. mm. Minimum size 25 X 3 mm. 1 Set
c) TP-MCB shall be suitable for motor duty and rating shall be co-
ordinated with OLR rating as per manufacturers recommendations.
TPN isolators (MCB type) suitable for motor duty in outdoor type metal
2 enclosure for motors located outside machine room. 1 set as required 1 Set
m) Copper control cables of size 1.5 sq. mm. As per system reqmt.
m) Copper control cables of size 1.5 sq. mm. As per system reqmt.
6 1 Set
a) 32 x 6 mm GI strip (MCC panel )
b) 25 x 3 mm GI strip ( Sub-grid along
cable-trays, motors above 3.7 KW
upto 30 KW, MCB-DBs, lighting
panels etc. )
c) 8 SWG GI wire ( motors upto 3.7 KW, power isolators, JBs, lighting
poles etc.)
d) 12 SWG GI wire ( field eqpt. Like
solenoid valves, LPBS etc.)
e ) 14 SWG Cu wire ( lighting fixtures,
1 ph. Utility-sockets etc.) - 1 set
Lighting Panel
Lighting panel with 32 A DP ELMCB as incoming and 6 A SP-
MCB 6 nos. as outgoing feeders
LP shall be with IP:42 protection, factory fabricated out of CRCA sheet,
powder coated, with metal door, top and bottom removable gland plate
s, universal mounting, complete with copper busbars, earth bus, termin
7 als for looping, cable- 1 No.
ties, shrouds to cover live terminals, front blanking plate with cutout for
MCB operation and all accessories etc. Rate shall be inclusive of mount
ing structure and all required material for installation.
Lighting fixtures
a) 1 x 40 W general purpose box type channel tube fittings with transpar
ent acrylic cover, lamp, mounting hardware, JB for looping, and all acce
ssories for ante room as per requirement 1 Set
8
c) Self contained emergency light unit 20 W with sealed re-
chargeable battery, battery-
charger etc. complete in all respects for automatic switch on in case of 2 Set
supply failure.
Note : Above rates shall be inclusive of all required material / mountin
g accessories eg. Brackets, clamps, M.S. black conduit-
pipes for suspension, ball-socket joints, three point ceiling-
roses, junction-boxes, mounting blocks etc.
Emergency alarm system (230 VAC) for cold chambers with input signa
ls from switches located inside cold chambers near each door. The syst
em shall comprise of switches, JBs, 150 mm. Gong bell / hooter, visual i
ndication to indicate the origin of alarm signal, test / accept / reset push-
11 buttons, UPS ( backup for 1 hour ), necessary wiring and all required m 1 Set
aterial, accessories.
TOTAL, Rs.
TOTAL, IN WORDS: