Sunteți pe pagina 1din 11

Francis Carcia, WA1GFZ

181 Columbia Rd, Enfield, CT 06802: Carcia@sbcglobal.net

High Power Solid State


Broadband Linear Amplifiers,
a Different Approach
The author describes how he modified some surplus amplifier boards to
create broadband RF linear amplifiers.

As a member of the High Performance


Software Defined radio, (HPSDR) group
I found myself in need of an HF amplifier
strip when the PennyLane exciter was
released. The PennyLane exciter produces a
very clean W signal. A two-tone display
yields IMD numbers below 50dBc,
measured per MIL-STD-1311. This test
method is 6dB more conservative than the
PEP method by measuring the difference
between the peaks of the two-tone signals
and the distortion. The two-tone method
adds 6dB, accounting for the time when
both of the two tones are in phase increasing
the peak by 6dB. The plan was to take this
transmit quality and amplify it to a usable
level.
A friend found some amplifier modules
made by Erbtec from surplus MRI equipment
on eBay. They had a power MMIC driving
three push pull FET stages of gain, ending in
a pair of MRF150s. The price was very fair
Figure 1 This photo shows the Erbtec MRI amplifier module, as it was delivered by the
so we picked up a few of them. A schematic eBay vendor.
was purchased from Erbtec. Figure 1 shows
a picture of the module as purchased from
eBay.
It was clear that the heat sink was too to a larger heat sink. The first stage runs current only changes a few milliamps over
small for linear use, and half the board class A at 24V while the driver and final the amplifier temperature operating range.
was filled with digital bias control and step need 48V and a bias source. The LM317 Figure 2 shows a picture of the amplifier
attenuators. The power MMIC was not regulator on the bias side of the board was board mounted on the new heat sink for use
needed since the HPSDR exciter power was moved to a proto board with 4 trim pots and as an HPSDR final amplifier strip.
close to the MMIC output rating. I carefully isolation diodes. There is a thermistor on This amplifier was designed to operate
sawed the board in half and removed the the board near the finals that was integrated around 63MHz, so it would take some
power MMIC. Next I mounted the amplifier into the LM317 control input, to act as changes to get it to function down to
section on a inch copper plate attached bias temperature compensation. The bias 160meters. A number of 0.01mF capacitor

QEX September/October 2015 1


Figure 2 Here is the modified Erbtec amplifier mounted on a larger heat sink, with the initial transformer modifications.

Figure 3 This photo shows the dual 1200W MRI amplifier module I purchased next from eBay.

2 QEX September/October 2015


values were increased to 0.1mF. I set up a a couple years on and off trying all kinds expensive part was the copper heat spreaders.
couple of power supplies on my test bench to of transformers and DC shunt chokes with The poor efficiency on some bands was not
see what the amp would do. Medical grade similar results. I had tried every suggestion all that bad since I only needed about 25W
hardware is very nice to rework without the with the same inconsistent results. of drive. The big amplifier had the same
fear of lifting circuit board traces. The hard Then Dr. Warren Pratt, NRV, sent me efficiency and IMD problem on 15 and
part was done and it should be easy to move a copy of his new predistortion software for 10meters as the smaller one had.
the operating frequency down. The first step use with the HPSDR Hermes transceiver The problem with a push pull amplifier is
was to power the thing up and sweep it down board. I built a current transformer pick up that the output devices do not source current,
from 60MHz to see where the magnetics and installed it into my set up. The current they only sink it. The transformer design
fell apart. The amplifier worked down to transformer required some attenuation in must make up for this. When the output
40meters and up to around 100MHz. The line to avoid overdriving the receiver. The devices are biased in class AB, each device
Final Drain transformer and DC shunt choke system was calibrated using an HP8640B is turned off for over 90 of each cycle.
got pretty warm on 40meters. and Boonton 42B digital power meter. This The device sinking current in conjunction
I thought that if I doubled the turns set up proved far more accurate than the Bird with the transformer must make up for this
on the output transformer and DC shunt 43 wattmeter. The great thing about Warrens inactivity since there is no resonant tank
choke, I could extend the frequency range to software is that you can monitor yourself circuit to provide a flywheel effect, as
160meters. The driver and predriver seemed in real time on the very accurate receiver there is in a single frequency design. I have
to work fine down to 160meters. I added display. I could check my IMD on all bands always felt that shunt fed DC was a band-
one turn to each output transformer winding in about 15minutes. When the predistortion aid for a poor transformer design but didnt
and 4 turns of twisted pair on the DC shunt. software was enabled, all the IMD problems understand why. The transformer should
It all made sense and should work great. I went away so life was almost good, with be able to perform the function of a 180
consulted every application note I had and the third order IMD running in the 45dBc magic T and 1:4 impedance step up in one
gathered all the advice I could find to verify range. device. You would never design a push pull
my modification. I ran my system like this for a while and audio amplifier with an output transformer
Things now got very frustrating, but also found a bigger MRI amplifier to get configured this way. A Push Pull Class AB
interesting. The amplifier would make me up to 1200W PEP output. Figure 3 is a audio amplifier has exactly the same problem
power throughout the HF band but there was picture of the dual 1200W MRI amplifier as a broadband RF amplifier. High-end
something strange going on. On some bands module set up for 80MHz. Figure 4 is my audio output transformers have interleaved
the efficiency and IMD looked good but on 1200W PEP modified MRI Amplifier final. windings as a way to improve coupling and
others, like 15meters, it was quite bad. The (Yes there are low pass filters.) My HPSDR balanced windings.
second harmonic attenuation was poor, so Hermes transceiver and homebrew linear I tested a number of different DC shunt
the performance was clearly not right. I spent amplifier worked quite well. The most chokes and found they had a big effect on

Figure 4 This photo shows the modified 80MHz MRI amplifier with typical broadband transformers and current shunt choke design,
mounted on a larger heat sink with copper heat spreader.

QEX September/October 2015 3


IMD. When a choke had enough reactance about 97% the IMD increased. The typical sleeves replaced the toroid output transformer.
to run at an acceptable temperature on output transformer design does not provide The sleeves provided a convenient layout
160meters, the efficiency and IMD on the this tight coupling, resulting in distortion. with transistors at one end with DC power
higher bands was poor. The Motorola EB104 The Erbtec amplifier has a transmission line and output leads at the other. At 48V, with
amplifier has a small DC shunt choke that transformer with no coupling between the only two secondary turns, this is a problem.
runs very hot. The two windings in a DC primary windings, so the DC shunt fed choke This method has been proven to work at the
Shunt choke do not produce a balanced was necessary to couple the drains. The expense of running higher reactance in the
magnetic field, as claimed. Many designs, uncoupled transformer performed poorly windings in an effort to increase the coupling
including the EB104, add a third winding as a when DC was fed through the shields in an between output devices. This extra primary
source for feedback. A perfect balance would effort to eliminate the DC shunt choke. reactance degrades broadband performance.
yield no feedback. A number of different The typical ham transmitter has two Figure 6 shows schematic diagrams
simulations were tried using LTspice, ferrite sleeves and brass tube primary with of different transformer configurations.
resulting in some common information for a the common center point connected. The The primary connections are shown for
number of configurations. Figure 5 shows the only coupling between drains or collectors simplification. Figure 6A is typically used
simulated current in a DC shunt choke with is the common secondary winding. Adding in 12V amplifiers where two ferrite sleeves
about 1A of DC offset. The two drains of a a DC shunt choke feed helps this coupling. form the transformer with two brass sleeves
push pull amplifier must be tightly coupled to A number of 12V rigs simply connect the for the primary winding. The DC power is
each other for good IMD performance. This transformer primary center tap to the power applied to the center tap. There is no coupling
was true with or without shunt fed power. supply and rely on the 4 or 5 secondary turns between the two output devices until a
Any transformer or DC shunt choke must to couple the drains. When transistors were secondary winding is added. This was found
tolerate some DC imbalance, even if wound low power devices the output transformer to be the least desirable configuration with
as a transmission line transformer. was wound on a toroid that provided tight each side of the push pull acting like a pair
Simulation showed that when the coupling coupling between the output devices. As of single ended amplifiers driving a common
efficiency between drains was reduced below power increased to the 100W level ferrite secondary. There is considerable waveform

Figure 5 This graph is the LTspice simulated phase currents in a DC shunt feed choke, showing the imbalance between phases that creates
the feedback signal.

4 QEX September/October 2015


Ferrite Ferrite 2x 5-1/2" 25 Coax Cables With Feedback Winding

Drain Drain

Power
Transformer With No Coupling Between Output Devices
(A)

Ferrite Ferrite
Drain Drain

Ferrite Ferrite
Sleeve Sleeve

Power
Typical Transformer Design Requiring A DC Shunt Feed
Choke For Coupling
(B)

Ferrite

Power Drain

Drain Power

Balanced And Tightly Coupled Design Drain Output Drain Output


(C) To Balun To Balun

QX1509-Carcia06a
Feedback 48 V DC Feedback 48 V DC

Balanced Antenna Tightly Coupled Design


With Feedback Winding
2x 5-1/2" 25 Coax Cables (E)
QX1509-Carcia06c

2x 5-1/2" 25 Coax Cables

Ferrite Ferrite
Sleeve Sleeve

Ferrite Ferrite
Sleeve Sleeve

Drain Output 48 V DC Drain Output 48 V DC


Drain Output 48 V DC Drain Output 48 V DC To Balun To Balun
To Balun To Balun
Balanced Antenna Tightly Coupled Design
Balanced Antenna Tightly Coupled Design Wired As 1:1 Turns Ratio
(D) (F)
QX1509-Carcia06b QX1509-Carcia06d

Figure 6 Part A shows a transformer with no coupling between the output devices. Part B is a typical transformer design, requiring a DC
shunt feed choke for coupling. Part C is a balanced and tightly coupled transformer design. Part D is a more detailed diagram of a balanced
and tightly coupled transformer design. Part E is a balanced and tightly coupled transformer design that includes a feedback winding. Part F
is a balanced and tightly coupled transformer design that is wired with a 1:1 turns ratio.

QEX September/October 2015 5


distortion of the signal near the positive peak. This actually worked quite well, but had a dual winding of three turns of semi
Also the second harmonic output was quite the additional reactance limited the high ridged line and the DC was fed through
high. When one output device turns off its frequency performance. Both output drains the center conductor. The core was a 0.87
collector or drain voltage can rise well above were tightly coupled to each other with inch type 61 toroid. The center conductor
twice the power supply voltage. This layout a balanced number of turns, limiting the was tiny, so it would never work as a linear
configuration with the devices at one end of stress on the ferrite. Figure 6C combines needing to carry over 10A of DC current.
the sleeves and power at the other looked nice the function of the DC shunt choke and the It was fine for low duty cycle MRI pulse
and efficient but degraded the performance transmission line transformer into a simple service. The module was tested and produced
over a single output core. transformer. The tight coupling between poor performance below 10meters. This
As time went on I introduced the Figure phases produced the cleanest waveform of transformer configuration provided tight
6B configuration as a way to take the all three configurations. The tight coupling coupling between drains on a common core.
DC off the transformer. The DC shunt and short lead lengths also reduced the phase The CERN, Harris, and SD2932
choke provided a method of coupling shift between the device drains. When a 1:2 transformer observations are clearly different
the two output devices to improve the transmission line transformer is wound on a than the typical commercial final. The
transformer balance. This reduced some of common core, fewer turns are required to get thought was a DC shunt choke is adding
the strain on the magnetics in the transformer minimum reactance when compared to two excessive leakage reactance to the output
and core heating, at the expense of more separate transformer cores. The only trade off circuit and needed to go. Heavier coax
complications, but introduced additional is that an output balun is required. could be used and the shield would handle
leakage reactance in the output circuit. I found that an output balun is a good idea more DC current. The question was finding
Along the way I downloadeda Power in all configurations to isolate the secondary an approach of creeping up on a workable
Point presentation from the Internet, which ground connection from the transformer. design that wouldnt blow up the finals.
was written by people working at CERN.1 When the output transformer is at the low First, I consulted a very poor quality
They were building basically the same frequency end of the design range, uneven copy of the bible on broad band amplifier
amplifier I was working on, but theirs core heating was observed in all transformer transformer design, ECOM-2989 Broadband
operated between 0.5MHz and 6MHz. configurations. The heating issue was Transformer Design for Transistor Power
They were winding both transformer phases improved with the addition of the balun. Amplifiers, by Octavius Pitzalis and Thomas
and the DC shunt choke on a common core. The 1200W module came with interesting P. Course.2 As stated in Motorola application
I duplicated that transformer with a type 43 output transformers set up to run at 80MHz, note AN749 and confirmed by Pitzalis
core of the same size. A quick test yielded as shown in Figure 3. This amplifier has andCourse, the minimum coax length for a
acceptable results, but above 20meters the four SD2932 amplifiers combined to make broadband transformer is about 4.5inches on
efficiency wasnt very good, and the IMD 1200W. They are similar to the Motorola a type 61 core at 160meters. As an interesting
was around 24dBc IP3. A Harris amplifier MRF151G, but a newer vintage. My thought observation, this is about the same length of
board from the junk box used this same was to design a transformer for the MRF150 coax used in a 2meter amplifier without
transformer design with a 1:1 output turns stage amplifier, and later modify the four ferrite. The output transformer wound on
ratio. SD2932 amplifiers. The SD2932 amplifier a common core is not a new idea, just not
common in the typical amateur transmitter.
A transformer having 40 times the
reactance as the one in the SD2932 amplifier
at 80MHz would be a safe place to start. The
first attempt was a pair of #22 single shielded
Teflon wire cables each 36inches long. This
cable has an impedance of just below 25W,
and would make a good transmission line.
A #24 single shielded Teflon wire has an
impedance closer to 25W but the conductors
are small, resulting in a lot of temperature
rise at 300W. A #20 single shielded cable
is also a good choice, but it has even lower
impedance. I used a double stack of six
(12 total) 0.87inch type 61 toroids and
threaded two windings into the core stacks.
The transformer had two 7turn windings
on two core stacks. Figure 7 illustrates
the initial transformer design and the final
configuration.
I installed a balun on the output,
consisting of 12 turns of RG316 on a single
1.25inch type 61 toroid. When a Guanella
Transmission Line Transformer is wound
on a common core, a balun is required to
isolate it from an unbalanced load.3, 4 This
was a small price to pay for eliminating the
DC shunt choke and getting a tight coupling
Figure 7 This photo shows the initial balanced transformer design on the left and the final between drain phases. Testing showed
configuration on the right.

6 QEX September/October 2015


acceptable results, and there was no problem temperature rise was barely above room same. The only difference noted was that
with DC on the transformer. The cores stayed ambient temperature. there was slightly more core heating. It was
stone cold and the IMD results were fairly This transformer uses the core material warm after running at full power.
good with IP3 on 15, 10 and 6meters at as the original Erbtec circuit, and did not The final configuration was to try a type
25dBc. The IMD on 160 and 80meters was require a DC shunt choke. An output balun 61 balun of the same size and compare
quite good, with IP3 = 34dBc.5 The results with 12turns of RG316 coaxial cable on a the temperature rise. The type Fair-Rite
degraded with frequency, so it was clear the 1.25inch type 61 toroid was used to isolate 2861010002 balun also worked the same
transformer was too big. This configuration the unbalanced load. The second core as the other two configurations but there
was decreased in size until the IMD peak material tested was a Fair-Rite 2843009902, was less core heating than the type 43. The
performance was shifted up to the center of two hole balun. Again only one turn through primary inductance was measured at 4.7mH,
the HF band. The IMD on 10 and 6meters both holes was required for each phase using slightly higher than the type 61 sleeves. This
still needed some help so I put my attention 5inches of #22 single shielded Teflon wire transformer can also be wound on a toroid
on the driver stage. The Driver output fed DC for each phase. A single turn through both with similar results. Two windings of five
through the uncoupled transformer but there holes measured 8mH, so two turns would be turns each on a 1.25inch type 61 toroid was
was also a shunt choke across the drains with around 32mH. The inductance of the primary acceptable, but required a couple of more
the center tap bypassed to ground acting as a was much higher but the test results were the inches of cable on each phase. The toroid was
180 magic T. Again the transformer was a
two core transmission line transformer using
a pair of type 61 baluns. The shunt choke
and the drain transformers were removed.
They were replaced with a pair of type 43
baluns and the transformer was rewound
in a different configuration. Each winding
was one turn of #24 twisted pair threaded
through both cores and soldered into the
circuit. Now both drains were coupled to
each other in the transformer, eliminating the
need for the shunt winding. This last design
change produced at least 30dBc IMD on
160 through 6meters. The DC power on the
transformer eliminated the need for the extra
reactance of the DC shunt choke.
The final transformer configuration in
the Erbtec amplifier boiled down to three
possible combinations. Each used two pieces
of #22 single shielded Teflon wire, each
5inches long. This pair was passed through
the core material with only one turn on each
phase, providing good coupling between
drains. Figure 6D shows a schematic of the
output transformer. It is a 1:4 impedance
transmission line transformer with DC
passing through the shields to power each
FET. The transformer is balanced and the
drains are tightly coupled to each other.
The first core configuration was a pair
of the sleeves used in the Erbtec amplifier
only requiring one turn of the shield for each
phase. The core material is type 61, 0.68inch
1.25inches 0.325inch ID. Two turns, one
per phase on two sleeves measured 4.5mH,
which is sufficient inductance for 160meters
at 12.5W drain to drain impedance. This
single turn per phase using type 61 material
satisfies Equation 2.6 in Jerry Sevicks
Transmission Line Transformers, Fourth
Edition (see Note 4). The 5inch cable
length is well below the maximum length for
6meters. Tests show the IMD was very well
behaved over the frequency range. Also, the
second harmonic energy on all bands was
very good, in the 35dBc to 40dBc range.
At full power 300W the transformer
Figure 8 Here is the final configuration of the Erbtec amplifier with a 1:1 output transformer.

QEX September/October 2015 7


a bit harder to mount with short leads. resistors AC coupled between the drain and are well below 300W, so the Figure 6F
The 2843009902 balun core was installed gate of each output FET. The dissipation transformer configuration was tested in the
back in the amplifier for additional testing as is quite high so they were replaced with Erbtec amplifier. The connections of the
shown in Figure 8. The type 61 material was 100 W resistors. The new third winding center conductors were rearranged to form a
slightly better, but my junk box contained was configured as feedback to the gate load 1:1 transformer to limit the output power to
enough type 43 baluns to modify the 1200W resistors with a pair of 160W series resistors. around 100W. We would get a better match
module. This was just repeated to verify 43 The amplifier IMD performance did not by using 50W cable, but the 25W cable
material as a usable core material. A third change, but the overall gain dropped slightly. produced acceptable results with good IMD
one turn winding of #22 Teflon wire was The addition of this feedback was not tested because of the short cable lengths. When the
added as a monitor winding and interfaced to with the gate to drain feedback removed. predistortion software was enabled, the IP3
an oscilloscope. A schematic of the monitor FET amplifiers will sometimes oscillate sidebands fell into the 55dBc range, and
winding added to the transformer is shown at low levels without some light feedback higher order sidebands went into the noise.
in Figure 6E. The Amplifier was powered directly between the drain and gate. This At 100W the Hermes receiver monitor signal
up to measure the voltage across the third test was just to confirm another possible was around 25dBm on the receiver display,
winding. This voltage was measured at configuration. The feedback components with a noise floor set at 120dBm. At
around 80Vpk-pk, 30VRMS. The flux density were removed, since they had no effect on 25dBm into the receiver, the predistortion
on 160meters is 163gauss = 3000 / (4.44 IMD performance with the 160W series software is actually working well below
1.8MHz 1 Turn 2.3cm2). Type 43 resistors. Lower resistance values were not the point of optimum performance, but the
material has been successfully used in DC tested. The tight coupling between drains signal was still very clean. Again, the IP3
shunt chokes, so the DC offset caused by one in the transformer appeared to be sufficient was around 30dBc (Mil Method) on all
FET conducting and the other FET turned off without additional feedback. There is usually bands before the predistortion software was
did not appear to be a problem. a slight IMD improvement when feedback is enabled. The 1:1 transformer puts a light
The IMD performance does not suffer, added around the DC shunt choke in typical load on the FETs, so there is not much gain
and efficiency is acceptable, so there is no transformer configurations. change near the saturation point compared to
reason to increase the core size or number This new small transformer duplicated the the heavier load of running a 1:2 ratio. This
of turns. It is surprising that type 43 material configuration of the 80MHz MRI amplifier transformer configuration also provides DC
can be driven so hard without excessive core scaled down to HF and will easily fit in place isolation so there is no need for coupling
heating. of the original small core if it is mounted on capacitors on the output to block DC.
Next, the third winding was configured its end. Figure 9 is a picture of the 1200W This 2843009902 balun core was
to source feedback to the gates. The Erbtec amplifier strip final configuration. previously tested in the outputs of the
amplifier comes with 25W feedback The 1200W amplifier drive requirements 1200W amplifier. The windings were not

Figure 9 Tis photo shows the 1200W amplifier, with the new balanced transformers on type 43 baluns.

8 QEX September/October 2015


balanced. Each phase was wound with 1 and the second harmonics were down 35dB. power the regulation is poor.
turns, so there were two turns in one hole The bias is set low around 300mA per Simulation showed the best IMD
and one turn in the other. Both phases wound FET. The bias current was set higher, to performance is when the FETs are biased
in the balun core formed three turns in each 500mA per FET, resulting in an IP3 of around 650mA each, but this would have
of the two holes. This put the drains at one 30dBc on all but the 40m and 10m bands. increased the stress on the power supply.
end of the balun and the DC power and At full power above 40meters the efficiency When the amplifier was tested over the air
output at the other. The core ran quite hot fell off slightly, putting stress on the 30A on multiple bands with the predistortion
when DC power was passed through the power supply running the two tone test. software enabled, the two tone IMD dropped
shields because of the uneven turns count. The output baluns are three turns of to around 40dBc measured by local
The extra turn reduced the flux density but RG316 in type 43 sleeves 0.68 1.25inch hams. The IMD was around 50dBc
the DC offset was much higher because of size. The output balun cores ran warm under voice conditions. There is 26dB of
the additional turn per phase, and caused compared to the type 61 balun, but the attenuation between the Hermes transceiver
winding imbalance. The core temperature cable lengths were shorter. RG316 runs a and the driver amplifier. This may allow
was reduced to an acceptable level when bit warm above 200W, having a small #26 the elimination of one of the four stages of
a DC shunt choke was installed, removing center conductor. The next larger size coax amplification in the future, which should
DC power form the windings. The IMD is RG303, with a larger center conductor but improve the IMD slightly. Typically, IMD is
and efficiency were not acceptable over the a lot harder to work with at almost 0.2inch measured by the PEP method in commercial
whole HF band. outside diameter. equipment, meaning the IMD performance
The new transformer configuration was The last output transformer after the numbers in Table 1 would be improved by
installed in the four stages of the 1200W combiner is oversized and may be causing 6dB.
amplifier board for testing. The cable length some efficiency issues on the higher bands, The Driver performance is included with
is 5inches per phase. The balun core was having 24inch cable lengths. The DC input each output FET biased at 500mA, and
wound with one turn through both holes current was slightly higher during the two the output transformer configured with a
per phase to maintain a good balance and tone test on the higher bands so the baluns 1:1 ratio. The reason for increased current
tight coupling between drains. This new and output transformer still need some more on 6meters is suspected to be due to the
transformer replaced the DC shunt choke work. The extra heat just made the heat sink cable impedance in the output transformer.
having seven turns of bifilar #20 wire on a temperature a bit warmer. When configured as a 1:2 transformer, the
1inch type 43 toroid and two transmission The amplifier has been used on 160 efficiency was comparable to the other
line transformers each wound with nine turns through 6meters with good reports. Table 1 bands. At this low power the extra dissipation
of #22 single shielded wire on each of the shows the IMD test results, with the signal is not an issue.
1.25inch type 61 cores. These original coax levels measured on the receiver display A 1:4 impedance step up output
windings measured 16inches long each. with the coupling factor of the feedback transformer is commonly used in a 300W
The SD2932 Amplifier was then tested hardware. The power supply capability 48V amplifier. When higher ratios are
using the Erbtec amplifier strip as a low did not allow two tone tests at 1kW PEP required a second transformer can be
power driver with the three stages running on the higher bands because of a slight cascaded after the drain transformer to
in class A. The amplifier produced good degrading of efficiency. The amplifier and achieve the final ratio. This method is used
power throughout the 160 through 6meter power supply functions at full power under in the Erbtec driver stages, with two 2:1
frequency range, and again the balun core voice conditions. The limited power supply transmission line transformers cascaded
temperature was just warm to the touch after capacity is presently the only protection to get a 16:1 step down. Other amateurs
running at 1kW PEP with a two tone source. for the amplifier. The power supply is rated have successfully used this method to
The cores do not show as much temperature for 30ARMS, so expecting it to function at build higher step up transformation ratios.
rise during a typical voice transmission of a 50% overload is really pushing things. It Roderick Blocksome, KDAS, published
couple minutes at over 1KW PEP. The third is a constant voltage transformer used as a an interesting article on transformer design
order IMD was around 28dBc (Mil method) telephone system battery charger, so at full that illustrates cascaded transformers (see

Table 1
Amplifier Test Results
Band PEP Output W PEP Output Coupler Factor 2 Tone Level Distortion Level IP3 Distortion DC Current
160m 1258 61 dBm 69 dB 14 dBm 44 dBm 30 dBc 23 ARMS
80m 1258 61 69 14 44 30 23
40m 1258 61 69 14 42 28 24
20m 977 59 69 16 46 30 24
15m 977 59 68 15 45 30 25
10m 977 59 68 15 43 28 24
6m 977 59 68 15 47 32 24
Driver Amplifier Strip 1:1 Turns Ratio Transformer, 500 ma Bias Each Output FET
160m 100 50 69 25 66 41 2.0 ARMS
80m 100 50 69 25 62 37 1.8
40m 100 50 69 25 62 37 2.0
20m 100 50 69 25 62 37 2.2
15m 100 50 68 24 63 39 2.5
10m 100 50 68 24 66 42 2.4
6m 100 50 68 24 63 38 3.7

QEX September/October 2015 9


Note 5). Jerry Sevick, W2FMI, also used so it is not a final stage efficiency issue. The operating in the same phase as the primary
cascaded transformers to achieve large HPSDR Hermes transceiver operates up to winding. This transformer configuration
transformation ratios (see Note 4). There 6meters, so 2meters was outside the scope uses the shields to perform the function of
is no reason the configuration could not be of my requirements. The 1200W amplifier the DC shunt choke as a coupled pair 1:1
modified to eliminate the DC Shunt choke, module should operate down to 600meters transmission line transformer, while the
and feed DC through the primary, as long with the type 43 cores in the transformers, connection of the center conductors provides
as the transformer is wound in a balanced but it was not tested because the input the 1:2 turns ratio step up transmission
configuration. transformer would need to be modified. line transformer that carries the RF power.
In the case of high power, larger cores The simulations were run using LTspice. It
such as sleeves with larger inside diameters was a challenge to simulate a transmission
Additional Configurations Possible
would allow larger cables to support higher line transformer with DC current running
When considering the 1:1 primary turns
current and lower operating impedances. through it. The transmission line simulation
ratio transformer, it may be possible to use
Larger diameter cores with longer magnetic treats DC like a series resistance equal to the
two twisted pair shielded, twisted triple
path lengths would also support more impedance. Im not sure if the simulations
shielded or twisted quad shielded cables
DC offset when running higher operating of the final design are accurate, but testing
as the two conductors, with the shields
currents with larger FETs. Stacks of toroids proved this configuration to be superior.
acting as the coupled primary and the center
could replace the ferrite sleeves as long as the This project is a work in progress with a
conductors configured as a 1:2, 1:3 or 1:4
cable coupling to the core is maintained. The goal of building a bullet proof, low IMD solid
step up secondary. This would increase
cable could also consist of multiple cables state final amplifier. The 1200W amplifier
the length of the secondary and may affect
in parallel to get to the desired impedance in the military and commercial world would
high frequency performance. Also this
and low resistance for the power required. be rated at 400W. One of my long term
could be built with multiple single shielded
Type 61 material would be a better choice projects is to mount four of these modified
conductors, with the shields in parallel and
at high power because it will handle greater MRI boards on a large heat exchanger into
center conductors in series. Only the single
DC offsets than type 43, and has lower core a combiner. The bias current would be
conductor shielded configuration was tested.
losses. increased and drain voltage will be reduced
This method would be usable in a 12V DC
The final cable length in the modified to around 40V for added protection. The
final requiring four secondary turns. The only
output transformer is 5inches per phase, third conductor feedback method will also
issue would be that the primary is two turns,
which is the same length used in 2meter be explored with lower series resistance. My
so the secondary would need eight turns.
applications. It should be possible to build goal is to point out my transformer design
This long secondary may be a problem, but
an amplifier that operates from 160 through observations to anyone who wants to build a
maybe smaller cores could be used at this
2meters with a single gain stage if the broadband amplifier with two or four modern
low impedance to offset the additional cable
layout is modified to couple both phases of 1200W FETs.
length with two primary turns.
the transformer. Transformer cables with
sufficient ferrite loading would increase the Frank Carcia, WA1GFZ, has been licensed
reactance high enough to support 160meters Conclusion since 1966. He is an avid home brewer for 50
and have a loss low enough to operate on A DC shunt feed choke is not required years, mainly interested in receiver design.
2meters. Imagine a pair of 1200W FETs if the output transformer is a balanced Some of his other Interests include gardening,
with a 1:2 drain transformer followed by transmission line transformer design. This woodworking and metal working. Frank has
a 1:2 or 1:3 transmission line transformer means both primary phase windings must been employed in the electronics industry for
producing the legal limit from 160 through pass through all sleeves or toroids of an 40 years in test, field service and design. He
is presently employed as an EMC engineer
2meters. This wide band operation is output transformer with an equal number of
at United Technologies Aerospace Systems
commonly available in the commercial turns. This provides tight coupling between (UTAS).
world, where broadband amplifiers cover drains, resulting in improved broadband IMD
even wider frequency ranges. IMD could performance and even harmonic attenuation.
be improved if the two drain transformer Another benefit of winding a transformer Notes
cables in a 2meter amplifier were coupled on a common core is the reduced length
to each other rather than floating in two of cables, since less turns are required to
1
M. Paoluzzi, High Power, Wideband, Solid-
State Amplifiers for Leir and J-Parc RF
isolated loops of coax cable. This floating achieve minimum reactance low frequency Systems, 28 March 2008.
loop configuration is typical in many VHF performance, as pointed out by Jerry Sevick, 2
Octavius Pitzalis, Thomas P. Course, ECOM-
amplifiers. A layout change would allow this W2FMI (see Note 4). These reduced cable 2989 Broadband Transformer Design for
drain coupling method. Type 43 losses might lengths improve high frequency losses due to Transistor Power Amplifiers, July 1968.
3
Philips Application notes ECO6709,
be too high for 2meters, so type 61 or type reduced phase shift between the two drains. ECO7213, AN98032, Power Amplifier
67 would be a better choice. This transformer configuration can also Design, March 23, 1998.
The three stage Erbtec amplifier provide a source of feedback by adding a 4
Jerry Servick, W2FMI, Transmission Line
performance drops off above 80MHz, so the third winding. The offsets between drain Transformers, Fourth Edition, SciTech
Publishing, Dec 2001.
driver stages would need to be modified to phases are just like those present in the 5
Roderick K. Blocksome, KDAS, Practical
cover 2meters. The driver stage transformers DC shunt choke. These offsets would be Wideband RF Power Transformers,
are wound with twisted pair transmission aggravated by slight differences between Combiners, and Splitters, Proceedings of
line and may not be suitable for 2meter output devices. The feedback winding is RF Expo East, 1986.
operation. The drive power drops off quickly, operating as a flux transformer because it is

10 QEX September/October 2015


QEX September/October 2015 11

S-ar putea să vă placă și