Documente Academic
Documente Profesional
Documente Cultură
PAGE
A. INTRODUCTION........................................................................................................................... A - 1
PERFORMANCE SPECIFICATION
A. INTRODUCTION
Reliability
The reliability of the system shall require for consideration of all supply sources including power
supply, water supply, telecommunication network which shall not have total interruption or no totally
failure.
Redundant incoming power sources shall be provided where applicable and economical available.
Secondary source of water supply or adequate storage is another sample to reliability issues.
Design consideration shall be given on continuous hotel operation during periodic service
maintenance required of the equipment. Design shall have a standby set in the group to operate in
place of the unused set or to run in tandem in severe condition for example drainage sump pumps or
flooding pumps.
Equipment specification and selection shall also be important for reliability aspect. Design shall be in
compliance with recognized standards and/or local regulatory requirements. Reputable and good
quality equipment shall be selected including reliable after- installation services and spare parts.
Comfort
Guest comfort aspect is a prime consideration for hotel to achieve good impression from guests and
the building system can play a significant supplementary role.
Indoor air quality comes directly almost the first guest perception upon their walking in the hotel. The
comfort air distribution in terms of proper design temperature level and humidity control including
system acoustically treatment shall be deemed necessary.
Guest room facilities are to be highly focused on the comfort for hotel guests. Design of the MEP
works shall follow the guidelines stated in the performance specification. Besides of the room air
quality aspect, comfort issues shall also include of good and welcoming light illumination, clean
potable water and good pressure no fluctuation shower and IT facility for guests use.
Design shall also consider on acoustic comfort in the guestrooms and all public areas up to high level
standards.
PERFORMANCE SPECIFICATION
A-1
Life Safety
Life safety is the primary design aspect of the system which designer shall be complied with. Design
of the life safety shall strictly followed international standard requirements and any stringent codes by
local regulatory authorities.
Consideration shall be given to life safety of guests and all staffs in the operation both at the normal
and emergency conditions. A normal condition is such as using earth-leak circuit breaker protection
for some circuits which can concern electric shock. The life safety under emergency condition is the
situation of fire hazard and during power failure.
Adequate emergency power supply by the standby generators shall be provided. Fire monitoring and
alarm system and fire protection system must be complied with the prevailing fire and life safety codes
i.e. NFPA or BS standard.
The system design must be directed to cost efficient design using life cycle cost analysis to maximize
the investment.
High efficiency equipment should be selected to reduce hotel operating cost particularly the air
conditioning system equipment which renders approximately fifty percent of energy use in the hotel.
Energy saving for lighting shall be considered of using high efficacy lamps that have higher
illumination while consume low power.
Equally necessity for the system operation is the building monitoring and automatic control system
that will shave the energy usage and on top of that will monitor the preventive maintenance of the
system which will upkeep the equipment and cut energy loss in return.
Environment friendly issues shall be focused on the system design. All materials use shall not impact
on the environment such as ozone depreciation substances containing CFC, HCFC and hazardous
materials such as asbestos or alike.
Water conservation aspect shall be considered on the recycle of waste disposal by treatment and
reuse for flush water or plant irrigation or cooling tower makeup where appropriate. Water saving
sanitary wares for example low consumption water closet, self closing lavatory valve for back of house
toilets can be considered.
Maintainability
Design consideration shall also be given to the service and maintenance aspect in order to maintain
the healthy working condition of the system.
All main equipment installation must have enough space for servicing. Access shall be provided for all
equipment concealed in the ceiling which will need to have periodic service.
PERFORMANCE SPECIFICATION
A-2
Performance Specification Divisions
The first division of the PERFORMANCE SPECIFICATION shall describe the minimum requirements
of the air conditioning, electrical, plumbing and drainage and fire and life safety systems of the
building. The second division shall describe the minimum requirements of individual area of the hotel.
The third division shall describe the guideline of material specifications mainly used in the projects.
And the fourth division shall be system criteria and diagrams.
PERFORMANCE SPECIFICATION
A-3
B. SYSTEM PERFORMANCE SPECIFICATION
System Selection/ Selection of the system for the project shall base on life
Requirement cycle cost analysis comparison of capital investment/
operating and maintenance cost.
PERFORMANCE SPECIFICATION
B-1
1. HVAC System Performance Specifications
Cooling Tower Select cross flow induced draft type/ multi-cell for each
chiller. Fan motor installed out of stream
Chilled water Pump Provide primary and secondary pump system. Primary
pump motor shall be constant speed type and secondary
pump motor shall be VSD
Water Distribution System Provide proper pipe sizes to attain adequate flow and
velocity in order to avoid noise problem
PERFORMANCE SPECIFICATION
B-2
1. HVAC System Performance Specifications
Air Distribution System Air duct distribution shall be sized correctly to velocity/ static
loss
Provide return air with the air duct to the unit. Return though
ceiling plenum is not hygienic and should be avoid
Supply air and return air outlets should be placed not too
close to cause short circuit of the air flow. When there is a
site constraint then air velocity of supply air and return air
should be checked
Provide fire damper for the air ducts except kitchen exhaust
when passing through the 2-hr rated fire wall. The fire
damper should have access for inspection
Area Temperature Shall be maintained at not over 28 degC in chiller plant room
Noise Level Equipment , air distribution and outlets selection shall not
exceed the noise criteria NC values
Water Distribution Velocity Pipe Dia. < 50 mm (2) Max. Velocity 1.2 m/s (4 fps)
Pipe Dia.> 50 mm(2) Max Head Loss 300 Pa (3 ft/100ft)
and Max. Velocity 2.5 m/s (8.3 fps)
Air Balance Normally outside air intake of the building shall be at least
10% higher than the exhaust
PERFORMANCE SPECIFICATION
B-3
1. HVAC System Performance Specifications
Automatic Control Automatic control valve shall be single seated electric spring
returned type with 30 second travel from fully open to fully
closed and vice versa.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow proper access for loading and unloading of the chiller
Considerations as normally the chiller will need to be replaced within 25
years. .
Energy saving For tropical climate regions, the HVAC system energy
consumption will be approximately 50% of the total energy
cost of the hotel. The energy efficiency measure of heat
recovery of guestroom exhaust and fresh air is
recommended.
Air Quality Provide pre-cooled fresh air system supply directly at the
supply air grille or connect to the supply air duct / air filter
shall be aluminum or synthetic type
Building Management BMS system shall be provided for the control and monitoring
System(BMS) of such as chillers, pumps. AHUs, cooling towers, ventilation
fans, designated electrical system, potable water system,
waste treatment system, fire monitoring alarm devices
PERFORMANCE SPECIFICATION
B-4
1. HVAC System Performance Specifications
Noise Level Treatment Equipment, ducting and piping design shall follow latest
ASHREA design guide handbook of acoustic design
PERFORMANCE SPECIFICATION
B-5
2. Electrical System Performance Specifications
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
System Requirement Provide reliable source of power supply for the hotel.
Secondary source of power from another incoming feeder
shall be provided where available and suit with the economic.
Wherever the power supply from the Authority network is not
reliable, the 100% standby generator should be installed.
LV cable/ Bus duct Copper bus duct is preferable for less energy loss. Enclosure
of Type IP 42 is general used and IP 65 for outdoor or damp
locations
PERFORMANCE SPECIFICATION
B-6
2. Electrical System Performance Specifications
7. IT / computer equipment
14.Drainage pumps
Standby generator Shall be diesel type standby rating duty but in area where
power failure is often shall be prime duty rating type
PERFORMANCE SPECIFICATION
B-7
2. Electrical System Performance Specifications
Earthing and Grounding Earthing systems shall comply with NEC or BS standard
General Lighting General lighting in public and BOH shall be provided with
enough level of illumination to the standard
Power Distribution Power distribution from the main electrical room shall be
cables run in conduits & wireways or bus ducts depend on
the sizing of the loads. The number of feeders required shall
be reviewed from the areas classified for individual use
where each functional unit shall have its local sub-distribution
boards and consumer panelboards.
PERFORMANCE SPECIFICATION
B-8
2. Electrical System Performance Specifications
Energy saving LV Switchgear and lighting shall have capacitor bank for
change power factor to 0.9 lagging
Tel/Data cabling Provide data rack for each area or distance not over 90 m.
PERFORMANCE SPECIFICATION
B-9
3. Plumbing and Drainage System Performance Specifications
System requirement System pressure shall be 1.5-4 bars. Minimum pressure for
rain shower is 2 bars. The system pressure on the zone that
higher than the specified range shall be modulated by
pressure reducing valve (PRV)
For fire safety hazard, PVC pipe shall not be allowed to use
above in the ceiling or expose except in pipe riser and
encased in walls.
Potable Pump Station Provide underground storage tank which can be used for 2
days at peak consumption. Roof tank shall also be provided
at 30 min storage at minimum. Concrete tank or fibreglass
reinforced tank are preferable. Underground tank shall be
two compartments in able to close one for cleaning.
PERFORMANCE SPECIFICATION
B - 10
3. Plumbing and Drainage System Performance Specifications
Consider using heat pump system for the hot water system
for its high efficiency
Domestic Pipe Distribution Provide shutoff valves at the accessible location for all risers
and outlets to control and balance the system flow.
Soil/waste system Soil and waste pipe should be separated to avoid cross
smell and choke. Cast iron pipe is recommended for soil and
waste pipe. Vent pipe can be PVC
Storm Drainage Provide a complete storm drainage piping inside the building
and discharge to site drainage. Pipe shall run in gravity fall
and if it is below the gravity level shall be collected and
discharged by a pump. The pump shall be duplex for stand
by and supplied with emergency power from generator.
PERFORMANCE SPECIFICATION
B - 11
3. Plumbing and Drainage System Performance Specifications
Waste Water treatment Waste water shall be treated prior to discharge to public
drainage system except where the public central waste
treatment system is available. The treatment shall conform
to the local standard regulation. If the local standard is not
available, the treatment system should follow the given
standard as a minimum.
Water Conservation For water saving measure policy on the project where water
resource is critical, the building waste treatment gray water
shall be treated and reused as flush water for the toilets
using separate pipe from domestic piping system, cooling
tower or plant irrigation.
PERFORMANCE SPECIFICATION
B - 12
3. Plumbing and Drainage System Performance Specifications
PERFORMANCE SPECIFICATION
B - 13
4. Fire & Life Safety Performance Specifications
System requirements Avoid and limit the use of combustible materials that will
generate a potential large fire load (kg/sqm.). Fire accident
causing by human behavior such as smoking should be
controlled.
All fire exit stairwell doors shall be opened into the stairwell
direction. The doors must be unlocked and able to open
PERFORMANCE SPECIFICATION
B - 14
4. Fire & Life Safety Performance Specifications
from inside the stair at each floor. If the door is locked for
security reason, it should be electrically opened at fire
condition.
PERFORMANCE SPECIFICATION
B - 15
4. Fire & Life Safety Performance Specifications
Fire Alarm System Fire alarm system shall be provided for the entire areas of
the building in compliance to NFPA 71 & 72A
The fire alarm control panel for fire monitoring & alarm
system shall be complete with central processing unit
(CPU),l control modules, control switches, enunciators and
others for a complete system operation
PERFORMANCE SPECIFICATION
B - 16
4. Fire & Life Safety Performance Specifications
Fire Protection System Fire pumps shall be designed and installed in accordance
with the latest NFPA 20 "Standard for the Installation of
Centrifugal Fire Pumps". Each unit shall be tested and
approved by UL and/or FM
Provide fully wet pipe system protection for the hotel except
the IT and computer room/ electrical room where dry pipe or
FM 200 system shall be considered.
PERFORMANCE SPECIFICATION
B - 17
4. Fire & Life Safety Performance Specifications
General Considerations minimum of 1 in 100 rooms fully equipment for blind, deaf,
and wheelchair bound guests
Disability
Arrangements System requirements Fire smoke detector with sounder base and strobe light or
flashing light/ Emergency evacuation speaker at the
entrance ceiling for guests with seeing disability
PERFORMANCE SPECIFICATION
B - 18
C. INDIVIDUAL AREA PERFORMANCE SPECIFICATION
Noise Level Treatment The room FCU shall be selected with the noise criteria of
below 37/42/49 dBA when lo/med/hi speed measuring at
bed head
Air Velocity Below 500 fpm at supply air grille. Supply grille shall be
linear bar type with fix horizontal bar facing slightly upward
with gasket seal
Air Balance Maintain positive pressure in guest bed room. Normal pre-
cooled fresh air supply to the room (preferably to the supply
air grille) is 90 CMH per room and toilet exhaust is 50 85
CMH
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow proper access panel for the FCU as well as fire
Considerations dampers for servicing.
PERFORMANCE SPECIFICATION
C-1
Area 1: Guest Rooms Performance Specifications
Air Quality Provide pre-cooled fresh air system supply directly at the
supply air grille or connect to the supply air duct / air filter
shall be aluminum or synthetic type
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Specific Provisions Dual voltage 110/220V shaver socket above the lavatory in
bathroom/ mirror demister/ night light at bedside and toilet/
bathroom mirror lamp/ do-not-disturb and make-up room
switches
PERFORMANCE SPECIFICATION
C-2
Area 1: Guest Rooms Performance Specifications
Safety ELCB on all circuits, No 240 Volts in Zone 1 (as per IEC
Regulations)
Energy saving Use energy saving lamps/ employ key card system. Cold
cathode tube which generates high heat should not be used
and should be replaced with LED lamp.
Room Control Unit Room control unit shall be programmable processor base
with lighting control/ air-condition setting and energy saving
modes. The unit enclosure shall be IP 557 when install in
ceiling or inside shaft
Maintenance The room control unit should be accessible for servicing. All
Considerations lamps replacement shall have enough space to handle
System Pressure System pressure shall be 1.5-4 bars. Minimum pressure for
rain shower is 2 bars. The system pressure on the zone that
higher than the specified range shall be modulated by
pressure reducing valve (PRV)
pressure balance Maintain pressure balancing of hot water and cold water at
any outlet by Thermostatic Mixing Valve
Drainage Floor drain shall have P-trap to prevent foul smell. Minimum
drain pipe shall be 2.0 inch or sizing for flow velocity of 0.9
Plumbing
m/sec to prevent noise. Slope of pipe is 1% minimum.
/Drainage
Connect basin waste drain to floor drain to keep trap primed
Cold water/Hot water Copper pipe is recommended for both cold and hot water
system pipes. Hot water temperature is normally supplied at 60
degC and distributed at 55 degC shall be insulated to avoid
energy loss. Insulation shall be 15 mm thick fibreglass at
2 o
0.040/w/m / K.
PERFORMANCE SPECIFICATION
C-3
Area 1: Guest Rooms Performance Specifications
Normal waiting time for HW when open the tap shall not be
over 5 seconds
Maximum dead end hot water supply pipe w/o return keep
not more than 6 meter.
Soil/waste system Soil and waste pipe should be separated to avoid cross
smell and choke. Cast iron pipe is recommended.
Vent Pipe shall be PVC to prevent corrosion problem.
Bathroom wall shall verify to keep fully integrity to keep
minimum noise and smell problem.
Flush water For water saving measure policy on the project where water
resource is critical, the building waste treatment gray water
shall be treated and reused as flush water for the toilets.
The flush water pipe will be separated from the domestic
cold and hot water pipe to avoid contamination.
The water closet cistern shall be water saving design with
the cistern capacity of maximum 6 litres.(Recommend at 4.5
litre/flush)
Tel/Data cabling 4-pair Cat-6 UTP for telephone and 2-pair Cat-6 UTP for
data
PERFORMANCE SPECIFICATION
C-4
Area 1: Guest Rooms Performance Specifications
Fire protection Provide quick response sprinkler head for all guest room
floor space.
Life safety ELCB on all outlet circuits, No 240 Volts in Zone 1 (as per
IEC Regulations)
Solid core wood for entrance door with 1/2 hr fire rating
Noise Level Treatment Below 37/42/49 dBA for the room FCU when lo/med/hi
speed measuring at bed head
Sound Transmission Class Between adjacent room : not less than or equal to 54 STC
(STC) Rating
Between room and corridor : not less than or equal to 50
STC
PERFORMANCE SPECIFICATION
C-5
Area 1: Guest Rooms Performance Specifications
General Considerations minimum of 1 in 100 rooms fully equipment for blind, deaf,
and wheelchair bound guests
Spy Glass and Safety latch Provide two spy glasses at 1.0m and 1.5m above finished
floor. Safety latch shall be mounted 1.2m above finished
floor
Height of switches All light switches shall be mounted at not more than 1.2 m
above finished floor
Fire Detection Fire smoke detector with sounder base and strobe light or
flashing light/ Emergency evacuation speaker at the
entrance ceiling for guests with seeing disability
Floor covering
Telephone Specifications Provide phone set with a light to show incoming calls and
volume control
PERFORMANCE SPECIFICATION
C-6
Area 2: Guest Room Corridors Performance Specifications
Air Balance Normal air condition system design for guest corridor shall
be supplied from a centralized AHU or pre-cooled air unit
(PAU) and distributed air duct along the corridor. Design air
flow rate shall be 1 air change/ hour
The BMS points for the AHU shall be at least consist of on-
off control
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow enough space as required inside the AHU room for
Considerations periodic checking and cleaning of the filter and coil.
Energy saving Employ air-to-air heat recovery system using toilet exhaust
from guestrooms exchange with the outside air for pre-
cooling air to the AHU
Fire safety All air ducts passing through 2-hr fire wall shall be equipped
with 1.5-hr fire rated dampers. Fire damper is not required
for 1 hr fire rate wall and barrier.
PERFORMANCE SPECIFICATION
C-7
Area 2: Guest Room Corridors Performance Specifications
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Energy saving Use energy saving lamps such as PLC fluorescent and LED.
Cold cathode tube which generates high heat should not be
used
Maintenance Provide one power socket in the AHU room for general use.
Considerations
PERFORMANCE SPECIFICATION
C-8
Area 2: Guest Room Corridors Performance Specifications
Sound Transmission Class Between room and corridor : not less than or equal to 50
Acoustic
(STC) Rating STC
PERFORMANCE SPECIFICATION
C-9
Area 3: Ball Room/ Function Room Performance Specifications
VAV?
Noise Level Treatment The room shall achieve the noise criteria of NC 30. Duct
crossing between the ballrooms should be avoided and if
not possible. Duct silencer may be used where the site
constraint is dictated.
Air Balance Maintain slightly negative pressure in ball room and function
room than the public areas.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
Automatic Control Interface all AHU's to the BMS system for on-off control and
monitoring. Digital thermostat shall be used in able to adjust
the room temperature from the BMS to suit with various
function needs.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
PERFORMANCE SPECIFICATION
C - 10
Area 3: Ball Room/ Function Room Performance Specifications
Maintenance Allow enough space as required inside the AHU room for
Considerations periodic checking and cleaning of the filter and coil.
Air Quality Provide pre-cooled fresh air system supply directly to the
AHU. The fresh air flow rate shall follow ASHRE standard
requirement.
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Power Socket Provision for minimum of 3 sets of 3ph 30A power outlets for
the event of exhibition or any special functions in each
individual room. Provide adequate general outlets for
Electrical cleaning
PERFORMANCE SPECIFICATION
C - 11
Area 3: Ball Room/ Function Room Performance Specifications
Energy saving Lighting designer shall specify the type of lighting fixtures
but try to use energy saving lamps as much as possible.
Cold cathode tube which generates high heat should not be
used and should be replaced with LED lamp.
Room Power Distribution Provide separate power DB for each function room with at
Board least 20% spare capacity
Telephone/Data socket Provide RJ 11 for telephone sockets and RJ-45 for data
sockets at regular interval for each invidual room
Tel/Data cabling Cat-6 UTP for telephone and Cat-6 UTP for data
PERFORMANCE SPECIFICATION
C - 12
Area 3: Ball Room/ Function Room Performance Specifications
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted. Upright
sprinkler shall be provided inside the ceiling void of 800 mm
or more
Sound Transmission Class Between adjacent room : not less than or equal to 35 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 13
Area 4: Kitchen & Food Preparation Performance Specifications
Outside fresh air intake with air filter shall be provided at the
side of hood as a plenum assembly with the hood. Pre-
cooled fresh air will be required for areas which high
HVAC ambient temperature and humidity.
Each hood shall have separate PAU and EAF for efficient
control. In case of one system used with multiple hoods (2
hoods or more), variable speed drive controller (VSD)
should be furnished
Automatic Control Interface with BMS system for remote control and
monitoring of AHU/FCU and fans
Specific Requirements Provide dish washer exhaust separate from kitchen hood
exhaust
PERFORMANCE SPECIFICATION
C - 14
Area 4: Kitchen & Food Preparation Performance Specifications
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Considerations Allow proper access panel for the FCU and space around
the AHU for servicing.
Air Quality Provide pre-cooled fresh air system supply for kitchen air
makeup and for AHU/FCU. Outdoor air intake can be
considered where the outdoor environment is not dusty and
humid. Air filter shall be aluminum or synthetic type
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/ 2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Safety Provide ELCB protection for all outlet circuits and fixed
appliance circuits
PERFORMANCE SPECIFICATION
C - 15
Area 4: Kitchen & Food Preparation Performance Specifications
Maintenance Considerations Panel board and control board shall be in room if not shall
be weatherproof type.
Cold water/Hot water system Provide soften hot and cold water for dish washer.
Gas System LPG gas design should be complied with the local code
regulations and NFPA standard.
Gas metering system shall be provided for each kitchen.
LPG gas pipe shall exposed installation as much possible.
PERFORMANCE SPECIFICATION
C - 16
Area 4: Kitchen & Food Preparation Performance Specifications
Telephone/Data socket Provide telephone and data sockets at the working area and
chef office.
Life safety ELCB on all outlet circuits and fixed kitchen appliance
circuits.
Sound Transmission Class Between adjacent room : not less than or equal to 50 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 17
Area 5: Foyer & Lobby Reception Area Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 35.
Air Distribution/ Velocity Lobby area shall have various activities during the day
which relate to the AC load. Provide AHU unit for reception
and lobby area with variable speed driven (VSD) controller
for AHU to automatically adjust the air flow in response to
actual load requirement.
Provide return duct back to the AHU and ceiling return will
not be allowed.
Air Balance Normally the reception and lobby area shall connect to the
main entrance of the hotel. It leads to the possibility of
outdoor air infiltration into the lobby that increase heat load
(during summer) and humidity. Ideal solution is having a
vestibule with a double door to lessen the wind effect.
Provide exhaust system for the area to regulate air flow and
maintain the air circulation.
Automatic Control Interface all AHU's to the BMS system for on-off control and
monitoring.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow enough space as required inside the AHU room for
Considerations periodic checking and cleaning of the filter and coil.
PERFORMANCE SPECIFICATION
C - 18
Area 5: Foyer & Lobby Reception Area Performance Specifications
Air Quality Provide pre-cooled fresh air system supply directly to the
AHU. The fresh air flow rate shall follow ASHREA standard
requirements. Outdoor air intake is not allowed due to the
heat, humidity and dusty condition.
Condensate drain For new projects, condensate drain of the entire air-
condition system should be collected and reused for flush
water or plant irrigation.
Fan Coil Unit (FCU) FCU shall be employed in front office area for individual on-
off control. FCU shall be ceiling mounted concealed type
with ducting system. Chilled water shall be controlled with 2-
way motorized valve shall be used.
Returned air plenum box with filter shall be provided with the
unit.
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
PERFORMANCE SPECIFICATION
C - 19
Area 5: Foyer & Lobby Reception Area Performance Specifications
Energy saving Select the use of energy saving lamps and LED as much as
possible.
Water pressure for flush valve water closet for public toilet
shall be designed with suitable pipe size.
Fire, Life Safety Provide emergency evacuation paging speaker above the
ceiling of the entrance which linked to the system for typical
room and with strobe light for disable room. The speaker
should have a fireproof back box.
PERFORMANCE SPECIFICATION
C - 20
Area 5: Foyer & Lobby Reception Area Performance Specifications
Fire protection wet pipe system / quick response sprinkler head/ fire
dampers at fresh air and toilet exhaust ducts
Sound Transmission Class Between adjacent room : not less than or equal to 40 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 21
Area 6: Restaurant & Bar Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 35. .
Air Distribution/ Velocity Supply/ return air duct shall be rigid galvanized metal sheet
construction. Long flexible duct is not allowed.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
Automatic Control Interface all AHU's to the BMS system for on-off control and
monitoring. Digital thermostat shall be used in able to adjust
the room temperature from the BMS to suit with various
needs.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow enough space as required inside the AHU room for
Considerations periodic checking and cleaning of the filter and coil.
Air Quality Provide pre-cooled fresh air system supply directly to the
AHU. The fresh air flow rate shall follow ASHREA standard
requirement.
PERFORMANCE SPECIFICATION
C - 22
Area 6: Restaurant & Bar Performance Specifications
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
PERFORMANCE SPECIFICATION
C - 23
Area 6: Restaurant & Bar Performance Specifications
Energy saving Lighting designer shall specify the type of lighting fixtures
but try to use energy saving lamps as much as possible.
Cold cathode tube which generates high heat should not be
used and select LED lamp.
Room Control Unit Room control unit shall be programmable processor base
with lighting control/ air-condition setting and energy saving
modes. The unit enclosure shall be IP 557 when install in
ceiling or inside shaft
Maintenance The room control unit should be accessible for servicing. All
Considerations lamps replacement shall have enough space to handle
Cold water/Hot water Provide hot and cold water for toilet and display kitchen if
system any. Copper pipe is recommended for both cold and hot
water pipes.
Drainage Floor drain shall have P-trap to prevent foul smell. Minimum
drain pipe shall be 2.0 inch or sizing for flow velocity of 1.20
m/sec to prevent noise. Slope of pipe is 1% minimum.
Soil/waste system Soil and waste pipe should be separated to avoid cross
smell and choke. Cast iron pipe is recommended
Flush water For water saving measure policy on the project where water
resource is critical, the building waste treatment gray water
shall be treated and reused as flush water for the toilets.
Telephone/Data socket Provide RJ 11 for telephone sockets and RJ-45 for data
sockets for each invidual room and POS at cashier station
PERFORMANCE SPECIFICATION
C - 24
Area 6: Restaurant & Bar Performance Specifications
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted.
Sound Transmission Class Between adjacent room : not less than or equal to 35 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 25
Area 7: Meeting Room Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 30. Duct
crossing between the rooms should be avoided and if not
possible, duct silencer may be used where the site
constraint is dictated.
Air Distribution/ Velocity Supply/ return air duct shall be rigid galvanized metal sheet
construction. Long flexible duct is not allowed.
Air Balance Maintain slightly negative pressure in meeting room than the
public areas.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
Automatic Control Interface all AHU's to the BMS system for on-off control and
monitoring. Digital thermostat shall be used in able to adjust
the room temperature from the BMS to suit with various
function needs.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Air Quality Provide pre-cooled fresh air system supply directly to the
AHU/FCU. The fresh air flow rate shall follow ASHREA
standard requirement.
PERFORMANCE SPECIFICATION
C - 26
Area 7: Meeting Room Performance Specifications
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Power Socket Provision for minimum 4 power outlets for room activity
Electrical functions in each individual room.
PERFORMANCE SPECIFICATION
C - 27
Area 7: Meeting Room Performance Specifications
Energy saving Lighting designer shall specify the type of lighting fixtures
but try to use energy saving lamps as much as possible.
Cold cathode tube which generates high heat should not be
used and select LED lamp.
Room Power Distribution Provide separate power DB for each meeting room with at
Board least 20% spare capacity
Fire, Life Safety Cable used for emergency evacuation paging speaker shall
be fire-rated cable
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted. Upright
sprinkler shall be provided inside the ceiling void of 800 mm
or more
PERFORMANCE SPECIFICATION
C - 28
Area 7: Meeting Room Performance Specifications
Sound Transmission Class Between adjacent room : not less than or equal to 35 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 29
Area 8: Shop Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 35.
Air Distribution/ Velocity Supply/ return air duct shall be rigid galvanized metal sheet
construction. Long flexible duct is not allowed.
Air Balance Maintain slightly negative pressure in shop than the public
areas.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
HVAC
Automatic Control Not required
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Air Quality Provide pre-cooled fresh air system supply directly to the
FCU. The fresh air flow rate shall follow ASHRE standard
requirement.
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
PERFORMANCE SPECIFICATION
C - 30
Area 8: Shop Performance Specifications
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Electrical Power Socket Provision for 2 power outlets for each shop
Power Distribution Board Provide separate power DB for each shop with 10% spare
capacity
PERFORMANCE SPECIFICATION
C - 31
Area 8: Shop Performance Specifications
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted. Upright
sprinkler shall be provided inside the ceiling void of 800 mm
or more
Sound Transmission Class Between adjacent room : not less than or equal to 40 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 32
Area 9: Office Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 35.
Air Distribution/ Velocity Supply/ return air duct shall be rigid galvanized metal sheet
construction. Long flexible duct is not allowed.
Air Balance Maintain slightly negative pressure in office than the public
HVAC areas.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Air Quality Provide pre-cooled fresh air system supply directly to the
FCU. The fresh air flow rate shall follow ASHREA standard
requirement.
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
PERFORMANCE SPECIFICATION
C - 33
Area 9: Office Performance Specifications
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Energy saving Lighting designer shall specify the type of lighting fixtures
but try to use energy saving lamps as much as possible.
Cold cathode tube which generates high heat should not be
used and select LED lamp.
Power Distribution Board Provide separate power DB for office with 20% spare
capacity
Maintenance
Considerations
PERFORMANCE SPECIFICATION
C - 34
Area 9: Office Performance Specifications
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted. Upright
sprinkler shall be provided inside the ceiling void of 800 mm
or more
Sound Transmission Class Between adjacent room : not less than or equal to 40 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 35
Area 10: Back of House Area Performance Specifications
Noise Level Treatment The room shall achieve the noise criteria of NC 45.
Air Distribution/ Velocity Supply/ return air duct shall be rigid galvanized metal sheet
construction. Long flexible duct is not allowed.
Air Balance Maintain slightly negative pressure than the public areas.
Provide exhaust system for the room to regulate air flow and
maintain the air circulation.
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Air Quality Provide fresh air system supply directly to the AHU/FCU.
The fresh air flow rate shall follow ASHREA standard
requirement.
PERFORMANCE SPECIFICATION
C - 36
Area 10: Back of House Area Performance Specifications
AHU/FCU The AHU/FCU shall have enough capacity to cover all heat
loads including the solar heat. The unit selected should
meet with the noise criteria specified. FCU shall be ceiling
mounted concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Specific Provisions
Electrical
Safety Provide battery backup emergency light. Illumination level
shall be minimum 10 lux
Energy saving Provide sub-meter for each operation unit for energy
management
Power Distribution Board Provide separate power DB for each operation unit with 10%
spare capacity
PERFORMANCE SPECIFICATION
C - 37
Area 10: Back of House Area Performance Specifications
Soil/waste system Soil and waste pipe should be separated to avoid cross
smell and choke. Cast iron pipe is recommended
Flush water For water saving measure policy on the project where water
resource is critical, the building waste treatment gray water
shall be treated and reused as flush water for the toilets.
PERFORMANCE SPECIFICATION
C - 38
Area 10: Back of House Area Performance Specifications
Fire protection Wet pipe system / quick response sprinkler head/ cover
plate of concealed sprinkler must not be painted. Upright
sprinkler shall be provided inside the ceiling void of 800 mm
or more
Sound Transmission Class Between adjacent room : not less than or equal to 40 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 39
Area 11: Laundry Performance Specifications
Air Balance/ Air Distribution Maintain negative pressure in laundry during operation
period in relation to the surrounding areas.
Specific Requirements Laundry exhaust will contain with lint which should be
filtered before discharge
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow proper access panel for the FCU and space around
Considerations the AHU for servicing.
Energy saving Interface to BMS system for remote control and monitoring
Air Quality Provide pre-cooled fresh air system supply for AHU/FCU.
Outdoor air intake can be considered where the outdoor
environment is not dusty and humid. Air filter shall be
aluminum or synthetic type
PERFORMANCE SPECIFICATION
C - 40
Area 11: Laundry Performance Specifications
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 1 1/ 2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Maintenance
Considerations
PERFORMANCE SPECIFICATION
C - 41
Area 11: Laundry Performance Specifications
Fire protection Provide Sprinkler head under AC duct which have width
greater than 1.20 m to ensure that the fire hazard is
coverage by sprinkler head.
Sound Transmission Class Between adjacent room : not less than or equal to 50 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 42
Area 12: Guest Lift Lobby Performance Specifications
Air Balance Normal air condition system design for guest lift lobby shall
HVAC
be from the guest corridor AC. Design air flow rate shall be 1
air change/ hour
Environmental n/a
Considerations
Maintenance n/a
Considerations
Fire safety All air ducts passing through 2-hr fire wall shall be equipped
with 1.5-hr fire rated dampers. Fire damper is not required
for 1 hr fire rate wall and barrier.
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
PERFORMANCE SPECIFICATION
C - 43
Area 12: Guest Lift Lobby Performance Specifications
Specific Provisions Provide general socket for cleaning service along the
corridor at every 15 m
Provide clear exit signage at the lift lobby. Guest lift shall
normally not permitted to be used during fire condition
Energy saving Use energy saving lamps such as PLC fluorescent and LED.
Cold cathode tube which generates high heat should not be
used
Maintenance n/a
Considerations
Drainage n/a
Specific Requirements Provide one house phone point at the lobby console to be
coordinated with interior design
Life safety The guest lift lobby life safety shall integrate with the guest
room corridor system.
PERFORMANCE SPECIFICATION
C - 44
Area 12: Guest Lift Lobby Performance Specifications
Sound Transmission Class Between room and corridor : not less than or equal to 45
Acoustic
(STC) Rating STC
PERFORMANCE SPECIFICATION
C - 45
Area 13 : Fitness Center Performance Specifications
Standby/Emergency n/a
Provision
Air Velocity/ Air Distribution Provide air-conditioned supply from AHU/FCU but with
separate unit for dry and wet area. Return air shall be
ducted and ceiling return air is prohibited. Air filter shall be
aluminum or synthetic type
Environmental Use non CFC/ HCFC refrigerant and halogen free materials
Considerations
Maintenance Allow proper access panel for the AHU/FCU as well as fire
Considerations dampers for servicing.
Air Quality Provide pre-cooled fresh air system supply to the units.
PERFORMANCE SPECIFICATION
C - 46
Area 13 : Fitness Center Performance Specifications
Fan Coil Unit (FCU) The FCU shall have enough capacity to cover all heat loads
including the solar heat. The unit selected should meet with
the noise criteria specified. FCU shall be ceiling mounted
concealed type.
Returned air plenum box with filter shall be provided with the
unit. Filter at the return air grille should be avoided. The
FCU returned air chamber should be completely sealed
particularly on the toilet side to prevent moisture
Fire safety All air ducts passing through 2-hr fire wall shall equipped
with 2-hr fire rated dampers
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Specific Provisions Provide individual power distribution board with 15% spare
capacity
Electrical
TV sockets and volume control in fitness area as be
required
Energy saving Use energy saving lamps/ Cold cathode tube which
generates high heat should not be used and should be
replaced with LED lamp.
PERFORMANCE SPECIFICATION
C - 47
Area 13 : Fitness Center Performance Specifications
System Pressure System pressure shall be 1.5-4 bars. Minimum pressure for
rain shower is 2 bars.
pressure balance Maintain pressure balancing of hot water and cold water at
any outlet
Drainage Floor drain shall have P-trap to prevent foul smell. Minimum
drain pipe shall be 2.0 inch or sizing for flow velocity of 1.20
m/sec to prevent noise. Slope of pipe is 1% minimum.
Cold water/Hot water Copper pipe is recommended for both cold and hot water
system pipes. Hot water temperature is normally supplied at 60
degC and distributed at 55 degC shall be insulated to avoid
energy loss. Insulation shall be 15 mm thick fibreglass at
2 o
0.040/w/m / K.
Normal waiting time for HW when open the tap shall not be
over 5 seconds
Soil/waste system Soil and waste pipe should be separated to avoid cross
smell and choke. Cast iron pipe is recommended
Flush water For water saving measure policy on the project where water
resource is critical, the building waste treatment gray water
shall be treated and reused as flush water for the toilets.
Telephone/Data socket RJ 11 for telephone sockets and RJ-45 for data socket at
Data reception counter
Communication
Tel/Data cabling Cat-6 UTP for telephone and data
PERFORMANCE SPECIFICATION
C - 48
Area 13 : Fitness Center Performance Specifications
Sound Transmission Class Between adjacent room : not less than or equal to 50 STC
(STC) Rating
PERFORMANCE SPECIFICATION
C - 49
Area 14: External Area Performance Specifications
General Considerations Safety/ Energy Saving and reliability with maximum amount
of emergency power
Standby/Emergency Some landscape lightings for security visibility i.e. walk way
Provision
Lightings around swimming pool area/ porte cochere/
external parking lots
Electrical Power Socket Provide at specific locations for some outdoor activities as
required by users
Energy saving Provide sub-meter for each operation unit for energy
management
Power Distribution Board Provide separate power DB for each operation unit with 10%
spare capacity
Cold water/Hot water Provide water supply for plant irrigation. Where applicable,
system irrigation water should be recycled gray water
Plumbing
Provide water sub-meter for record and management
/Drainage
Provide tap outlet at car park area for floor and car cleaning
PERFORMANCE SPECIFICATION
C - 50
Area 14: External Area Performance Specifications
PERFORMANCE SPECIFICATION
C - 51
Area 15: Swimming Pool Performance Specifications
System Selection/ Swimming pool Pump shall be plastic Self priming with
Requirement build-in Basket strainer. Water feature pump shall be end
suction with bronze or epoxy coat impeller for corrosive
condition.
PERFORMANCE SPECIFICATION
C - 52
Area 15: Swimming Pool Performance Specifications
PERFORMANCE SPECIFICATION
C - 53
D. MATERIAL SPECIFICATION GUIDELINE
PERFORMANCE SPECIFICATION
D-1
HVAC SYSTEM
PERFORMANCE SPECIFICATION
D-2
CHAPTER 1 TECHNICAL SPECIFICATION AND REQUIREMENTS
Unless otherwise specified elsewhere in the Contract, the entire system shall be manufactured,
installed, tested and balanced conforming to the latest issue of the following standards:
PERFORMANCE SPECIFICATION
D-3
CHAPTER 2 CENTRIFUGAL WATER CHILLER
1. General
Water chillers shall be of factory assembled package type, each consisting of a centrifugal
compressor, motor, water cooler, condenser, economizer, lubricating system, purge unit (for
R-123), electrical and microprocessor control system, etc. All equipment shall specifically be
designed for refrigerant R-123 or R-134 A. Chiller performance shall be rated in accordance with ARI
standard 550-92
2. Compressor
Compressor shall be of the hermetic type, centrifugal, single stage or multi-stage, direct drive or gear
drive.
3. Motor
Compressors motor shall be of the single speed, non-reversible, squirrel cage induction type. Motor
shall have a minimum of 95% efficiency and 85% power factor.
4. Lubricating System
Each compressor shall have a completely forced feed lubricating system with pump, cooler, reservoir,
filter, etc. Crankcase heater shall be provided to heat up lubricating oil during starting stopping and
normal operating conditions.
Compressors and gearboxes shall be provided with thermometers to indicate either bearing
temperatures or lubricating oil temperatures.
6. Oil Heater
In case lubricating oil and refrigerant in the system can be mixed up, thermostatically controlled
electric oil heaters with adequate capacity shall be installed in order to prevent oil bubbles when
refrigerant pressure changes.
City water shall not be used for lubricating oil coolers, purging devices, etc. If required, either
condensing water or chilled water shall be allowed to use in a coolant circuit.
Each compressor shall be provided with an automatic micro-processor control for varying the
compressors capacity in the range of maximum to minimum values. The capacity reduction
PERFORMANCE SPECIFICATION
D-4
equipment shall consist of a hot gas bypass and the butterfly or the radial type suction damper or shall
be equipped with one stage or multi stages inlet guide vane. The capacity reduction equipment shall
be arranged for automatic operation, and shall be able to reduce the capacity in range of 30% to
100%.
The evacuator unit of non-condensable gases or purging devices used for evacuation shall consist of
a small air or water-cooled, motor-driven dry compressor condensing unit, oil separators, etc
according to standard of manufacturer. The unit shall be of the self-condensing thermal type,
completed with piping, gauges, air indicating instrument and controls. Evacuators shall be automatic
in operation and enclosed in cabinets. The contractor shall install purging discharge pipe of R-123
directly to ambient outside the room where good ventilation. Purging R-123 inside the room shall not
permit.
The cooler and condenser shall be designed, constructed and tested in accordance with ASME and
ANSI-B 9.1 Code requirements and recommendations of ARI standard 550.
Water cooler and condenser shall be 2-pass construction of the shell and tube type.
Water boxes shall be of marine type and made of cast-iron or welded steel arranged so, as to permit
inspection of tubes from either side without disturbing the refrigerant chamber or the chilled
water/condenser water piping connections.
Shell of water cooler shall be insulated with at least 25-mm. thick closed cell insulation. The insulation
shall have thermal conductivity of less than 0.038 W/mk (0.27 Btu/Hr/sq.ft/F/inch).
Current demand limiting controller shall limit the current draw of compressors motor not exceeding
105% of maximum running amps.
Each water chiller shall be mounted on steel spring isolators which are, in turn, placed on a concrete
base.
PERFORMANCE SPECIFICATION
D-5
15. Safety and Control Devices
The controller of the unit shall be of the microprocessor type which will be able to directly
interface with chiller manager system. The controller shall include, but is not limited to, the
following main functions:
Microprocessor control panel shall automatically shut down the unit when emergency
conditions happen. As minimum, the following lists to be shown shall be given as conditions
to shut down the system on the control board:
PERFORMANCE SPECIFICATION
D-6
17. Accessories
The following accessories shall be provided, but are not limited to, for each chiller:
PERFORMANCE SPECIFICATION
D-7
CHAPTER 3 RECIPROCATING or SCREW or SCROLL WATER-COOLED WATER CHILLER
1. General
Water chiller shall be of the unit or "package" type, with water-cooled condenser. All equipment shall
be designed for R-134a or R407C for reciprocating or Scroll or Screw compressor. Each chiller shall
consist of multiple compressors, dual refrigerant circuits, water cooled condensers, water-coolers,
control panels and necessarily manufactured standard accessories.
2. Compressor
Each compressor shall be a reciprocating (accessible and serviceable) or screw or scroll compressor.
Motor shall be hermetic or semi-hermetic, direct driven compressor, and equipped with, but is not
limited to, the following.
- A crankcase heater.
- A capacity unloader.
- A self-reversible positive displacement type oil pump with an oil filter, a strainer, a sight glass,
an oil drain, a magnetic plug, a charging valve, and an oil pressure switch.
- Suction and discharge shut-off valves.
- A suction gas-cooled induction compressor motors for hermetic compressor and air-cooled
for open type compressor.
- A heat sensor in motor winding as inherent motor protection.
3. Cooler
Water cooler shall be of the shell and tube type, dual refrigerant circuits, direct expansion coolers.
4. Condenser
Condenser shall be of the multi-pass shell and tube type with seamless, integral fins copper tubes,
mechanically bonded to steel or non-ferrous metal tube sheets.
Each chiller shall have two separated condensers with common pipe connection manifolds. Safety
relief valve or rupture disk shall be provided according to the safety standard.
5. Control Panel
Control panel shall consist of an electrical control panel and a refrigerant control panel with gauge
board, which shall be installed on each water chiller.
The electrical control panel section shall at least include the following.
PERFORMANCE SPECIFICATION
D-8
- A control fuse or circuit breaker, control switches or/and push buttons with necessary
indicator lamps for safety and operational control circuits, i.e. anti-short cycling start,
automatic sequence start-stop, automatic recycling pump down on the lagging compressor,
etc.
- A manual sequence switch.
- An hour meter.
The refrigerant control panel section shall at least include the following.
The following gauge board panel section shall at least include for each compressor:
Other related safety devices to be connected to the control circuit shall at least include:
6. Capacity Control
7. Refrigerant Circuit
PERFORMANCE SPECIFICATION
D-9
- A charging valve.
All suction lines shall be insulated with 25-mm (1-inch) thick closed cell insulation.
8. Vibration Isolator
Each water chiller shall be mounted on spring isolators which are, in turn, placed on a concrete base.
9. Shell Insulation
Shell of water cooler shall be insulated with at least 25-mm (1-inch) thick closed cell insulation.
PERFORMANCE SPECIFICATION
D - 10
CHAPTER 4 CROSS FLOW COOLING TOWER (SPLASH BAR FILLING)
The cooling tower shall be of induced-draft, cross flow and draw-through type. The tower shall be
equipped with a PVC splash bar as the basic heat transfer.
Casing shall be constructed of fiberglass reinforced polyester (FRP) with galvanized steel framework.
The casing shall be designed to resist corrosion and withstand severe vibration and heavy wind
forces. Louvers shall be of fiberglass reinforced polyester.
Filling shall be constructed of treated timber splash bar. Filling shall be supported by fiberglass
reinforced polyester (FRP) in order to achieve a uniform water distribution.
4. Drift Eliminator
Tower shall be provided with drift eliminators or equivalents for limiting drift loss. Drift eliminators
shall be constructed of polyvinyl chloride (PVC). Drift loss shall be in the range of 0.002-0.2% of
rated water flow.
The metering orifice shall distribute water uniformly over the entire filling area. The hot water from the
system shall enter hot water basin, which shall be constructed of hot dipped galvanized steel or
fiberglass reinforced polyester (FRP). The hot water shall be distributed to filling area by gravity feed
through metering orifice. In case one cooling tower consists of 2 hot water basins, the tower shall
have 2 sets of cast iron body type flow control valves with locking bar. These valves shall be installed
to balance the flow of water to each cell.
Water distribution system shall be designed to meet a water flow of 150 percent of rated capacity
without over-flowing or harmful splashing.
6.1 Fan shall be of the axial flow type with airfoil section blades and made of light aluminum alloy.
Fan shall be quiet in operation.
6.2 The steel shaft shall be used for torque transmission. Fan speed reducer shall be of gear-
drive type. Gear reducer shall have a long service life, and heavy duty.
6.3 The motor shall be out of hot air stream. Fan shall be totally enclosed fan cooled, insulation
class F, IP55 and service factor of 1.15.
PERFORMANCE SPECIFICATION
D - 11
7. Cold Water Basin
Basin shall be of fiberglass reinforced polyester (FRP). The internal surface shall be smooth. Cold
water basin for each cooling tower shall be separated to ease a cleanup service.
8. Miscellaneous
8.1 The contractor shall provide outlet & inlet connections, over flow, drain, pilot operated float
controlled valve (for make-up water), inlet air screen, suction strainer etc
8.2 Service door shall be the same construction as its casing. When the door is closed, it shall
have no air leakage.
8.3 Provide service catwalk inside the cooling tower in case more than 2 cooling towers are
installed.
8.4 Provide ladder, handrail and guard in order to access to the deck of cooling tower. All
materials shall be of non-corrosive materials.
8.5 Hot air duct shall not be less than 1.27 mm galvanized steel sheet or FRP
8.6 Bolts & nuts used for outdoor installation should be of stainless steel type.
PERFORMANCE SPECIFICATION
D - 12
CHAPTER 5 PUMP
1. Type of Pumps
Pump shall be of the non-overloading, centrifugal, volute type, single stage, horizontal split or
vertical split, and double suction type with suction and discharge connections in the lower half
of the casing, designed to disassemble the rotating components without disturbing pipe
connections and operating at not over the speed indicated on the pump schedule.
Pump shall be of the non-overloading, centrifugal, volute type, single stage horizontal
mounted and end suction type. The pump shall be designed so that disassembly of the pump
impeller shall not interfere with the piping system (back-pull-out pump).
Pump shall be of in-line, closed-coupled centrifugal type, single stage vertical mounted type,
and equipped with suction and discharge flange connections.
2. Details of Components
2.1 Casings
Casing material shall be cast-iron, precision-manufactured for the best performance and
durable functions. The casing shall be tested by hydrostatic test at 1.5 times of casing design
maximum working pressure. Suction and discharge flange connection shall have the same
working pressure as pump casing. Casing shall be provided with tapped and plugged fittings
for vent and drain purpose.
All pumps having discharge connections larger than 50 mm (2 inches) and operating at more
2
than 2-kg/cm (30 psig) total dynamic head shall be provided with casing wearing rings.
2.3 Impellers
PERFORMANCE SPECIFICATION
D - 13
2.4 Shafts
Shafts for pump with stuffing boxes shall be of stainless steel, (chrome-iron or nickel-iron)
extending through the stuffing boxes.
Shaft sleeves shall be keyed to the shaft and extended through the stuffing box. O rings or
gaskets shall be provided at sleeve ends to protect the shaft from water corrosion.
2.5 Bearings
Bearings shall be heavy-duty ball bearings with a minimum average life of L10 -20,000 hours.
The bearings shall be self-sealed, and housed in malleable-iron housing aligned to a bearing
bracket by means of large precision registers.
2.6 Seal
Balance type mechanical seals shall be used when the casing working pressure exceeds 20
2
kg/cm (300 psig).
2.7 Couplings
All pumps, other than close coupled pumps, shall be provided with urethane flexible couplings
or steel pins and bushing with a service factor of at least 1.5 for an individual application.
Each flexible coupled pump shall be provided with a cast-iron or fabricated steel base plate to
hold both the pump and the motor in correct alignment.
High points of pump casings shall be provided with automatic air vent and valve. Low points
of casings shall be provided with valve drains
2.10 Anti-Vibration
Each pump shall be mounted on inertia base and spring isolators which are placed on a
concrete foundation. The maximum static deflection of spring isolators shall be 25 mm (1
inch).
2.11 Insulation
Chilled water pumps shall be insulated with at least 25-mm (1-inch) thick closed cell
insulation.
PERFORMANCE SPECIFICATION
D - 14
3. Motor
3.1 Motor shall be of totally enclosed fan cooled squirrel cage induction motor.
3.2 Unless otherwise specified, the speed of motor shall not be more than 1500 RPM.
3.3 Motor winding insulation shall be of class F
3.4 Service factor of motor shall not be less than 1.15
3.5 Bearing of motor shall be of anti-friction type ball bearing or roller bearing. The seal of motor
shall be of dust and moisture protection type.
3.6 Motor terminal box shall be of waterproof. Conduit for terminal box shall be of waterproof
flexible conduit.
4. Installation
PERFORMANCE SPECIFICATION
D - 15
CHAPTER 6 STANDARD AIR HANDLING UNIT SINGLE SKIN TYPE
1.1 The standard single skin air-handling unit shall be design for the supply air system which the
operated total air pressure dose not exceed 500 Pa. (2.0 '' WG.) The frame shall be sturdily
constructed of 3-mm thick galvanized angle steels. The frame contacting the cool air shall be
insulated and any surfaces of frame that touch moisture or water shall be enameled with an
anticorrosive material.
1.2 The casing, which is made of either, galvanized steel sheet or steel sheet processed by
means of the baked-on enamel shall be not less than 1.2 mm thick. The casing contacting
the cool air shall be insulated and any surfaces of casing touching moisture or water shall be
enameled with an anticorrosive material.
1.3 The frame and casing construction, which is designed to be double-skinned panels, shall be
allowed to use. The installation and assembly of air handling unit construction shall be of a
flange method.
1.4 The air-handling unit shall be provided with an access door to ease maintenance and service.
Hinge type access door shall be installed if the door dimensions are larger than 600 mm. x
600 mm. (24 inches x 24 inches). The locations to be provided with an access door shall be
as follows:
- Fan
- Air Filter
- Cooling Coil
2.1 All surfaces of casing and frame, which are in contact with the cool air, shall be insulated
inside in order to prevent condensation insulation material shall be either closed-cell-foamed
elastomer or polyurethane foam (fire retardant type) and insulation thickness shall not be less
than 25 mm. All seams and joints on insulation shall be completely sealed.
2.2 The condensate drain pan, which is fully provided under the entire cooling coil, shall be
fabricated from a minimum 1.5 mm. thick stainless steel sheet. The upper surface of pan
contacting the water shall be enameled with anticorrosive material and the lower surface of
the pan shall be fully insulated with either closed-cell foamed elastomer or polyurethane
foam (fire retardant type).
2.3 The condensate drain shall be equipped with a drain trap near the drain pan and sloped down
according to the water flow direction.
3. Cooling Coil
3.1 The cooling coil, 4 to 6 rows, shall be a thick seamless copper tube with outside diameter of
not less than 15.8 mm. (5/8 inch). If the numbers of rows are more than 6 rows, the cooling
coil shall be spliced in two parts and the distance between each part shall not less than 500
mm. (20 inches)., the fin shall be of the aluminum plate type. The number of fins shall be
360-560 fin per meter (9 to 14 fins per inch).
PERFORMANCE SPECIFICATION
D - 16
3.2 Coil face velocity shall not exceed 2.5 m/sec (500 fpm).
3.3 Water pressure drop of cooling coil shall not exceed 4.5 meters of water (15 feet of water)
4. Fan
4.1 The fan shall be constructed of either galvanized steel sheet or steel sheet. The fan, In
general, shall be of a forward-curved blade. In case the total static pressure of fan is exceed
50 mm. of water, the fan shall be either backward-curved blade or airfoil blade.
4.2 The fan of air handling unit shall be of draw-thru type. If the air-handling unit has more than
one fan, these fans shall be mounted on the same shaft.
-5
4.3 The sound pressure level of fan shall not be exceeding 65 dBA (RE 2 x 10 Pa, AMCA 301-
76) at distance 1 m. (3.28 feet). If the sound pressure level measure is higher than the
specified level, the contractor shall provide additional sound absorber to alleviate the sound
pressure level.
4.4 Outlet air velocity from discharge side of fan shall not exceed 9 m/s (1,800 fpm)
5. Motor
5.1 The motor shall be totally enclosed fan-cooled squirrel cage induction motor, IP54 and class
B for winding insulation. The revolutions per minute of motor shall be 1,450 rpm.
5.3 The service factor for backward curved blade or airfoil blade centrifugal fan shall be 1.15 and
the service factor for forward curved blade centrifugal fan shall be 1.2
5.4 The fan shall be driven by V-belt fitted with variable pitch pulleys.
6. Air Filter
6.1 Pre-filter shall be of synthetic fiber panel (P-2). The thickness of the air filter shall not be less
than 50 mm. (2 inches) and the efficiency shall not be less than 85% arrestance measured by
ASHRAE method.
6.2 In case medium filter is needed to use, the classification of medium filter shall be specified
6.3 One set of inclined manometer and differential pressure switch shall be provided for each
filter bank.
7. Vibration Isolator
7.1 Shall be provided with quantities and sizes of the spring isolators according to the
manufacturer's recommendation. The static deflection of spring isolator shall not less than 25
mm. (1.0 inch)
PERFORMANCE SPECIFICATION
D - 17
CHAPTER 7 CHILLED WATER SMALL FAN COIL UNIT
1.1 The frame shall be sturdily constructed of galvanized angle steel of not less than 1.6 mm.
(0.064 inch). The frame contacting the cool air shall be insulated and any surfaces of frame
that touch moisture or water shall be enameled with an anticorrosive material.
1.2 The casing shall be made of galvanized steel sheet or steel sheet processed by means of the
baked-on enamel shall not be less than 1.2 mm. (0.048 inch). The casing contacting the cool
air shall be insulated.
1.3 The casing shall have access door(s) for piping and control.
2.1 All surfaces of casing and frame, which are in contact, with the cool air, shall be insulated
inside in order to prevent condensation. Insulation material shall be either closed cell
insulation or polyurethane foam (fire retardant type) and insulation thickness shall not be less
than 19 mm. (3/4 inch).
2.2 The condensate drain pan shall be fabricated of from a minimum 1.2 mm. (0.048 inch) thick
galvanized steel sheet. The upper surface of pan contacting the water shall be enameled with
anti-corrosive material and lower surface of pan shall be fully insulated with fire retardant
insulation.
3. Cooling Coil
3.1 The cooling coil, 3 to 4 rows, shall be of the seamless copper tube with outside diameter of
not less than 12 mm. (1/2 inch the fin shall be aluminum plate type. The numbers of fins shall
be 9 to 14 fins per inch.
3.2 Coil face velocity shall not exceed 2.25 m/s (450 fpm) at maximum speed.
4.1 Fan shall be double width, double inlet forward curve centrifugal type. Single or multiple fan
shall be on the same rigid shaft mounted in self-aligning bearing.
4.2 The capacity sound pressure level of fan measured at 1.0 m. (3.281 ft) from the fan shall not
exceed 55 dBA at high-speed capacity or as specified.
4.3 Motor shall be equipped with permanent split capacitor and three-(3) tap-off winding for high-
medium-low speed control. Winding insulation shall be class B, IP 54. Motor shall be
furnished with motor over-current protection device.
5. Control System
PERFORMANCE SPECIFICATION
D - 18
a) Control temperature set points
b) Indicate temperature set point via digit number
6. Air Filter
6.1 Synthetic fiber panel filter (PF-1) shall be provided for ceiling concealed unit. Air filter shall
have a minimum thickness of 9 mm. (3/8 inch) and shall have the efficiency of not less than
65% arrestance measured by ASHRAE method.
PERFORMANCE SPECIFICATION
D - 19
CHAPTER 8 SPLIT-TYPE AIR-CONDITIONING UNIT (AIR-COOLED OR WATER-COOLED)
1. Condensing Unit
Condensing unit shall be vertical or horizontal hot air discharge type as specified and shall
consist of rotary scroll or reciprocating compressor with sealed hermetic or semi hermetic
type. All compressors shall be compatible with R-407C or R-410a in single or dual circuits as
recommended by the manufacturer. Qualifications shall conform to the following lists: -
1.1.1 Casing of condensing unit shall be made of galvanized steel or black steel with well
rustproof and external painting to be suitable for outdoor condition.
1.1.2 Condensing fan shall be propeller or centrifugal type driven by weatherproof motor.
1.1.3 Condensing coil shall be copper tube with aluminum plate fins mechanically bonded
to tubes. The number of fins shall not be less than 480 fins per meter (12 fins per
inch)
1.1.4 Standard accessories for condensing unit shall include the following:
Water-cooled condensing unit will be consist of sealed hermetic type scroll or reciprocating
compressor, plate or tube in tube heat exchanger, condenser water piping and accessories,
refrigerant piping and accessories. The refrigerant circuit shall be of single circuit and designed
for refrigerant-22. The unit requirement and specification shall be as below.-
1.2.1 The casing shall be of galvanized steel sheet or painted enamel steel sheet.
1.2.2 The heat exchanger between refrigerant system and cooling water system shall be of
plate heat exchanger type which made of AISI 316 stainless steel or tube-in-tube
counter flow type which will be of copper tube in steel pipe.
1.2.3 The unit accessories shall be as below.-
PERFORMANCE SPECIFICATION
D - 20
d. Hi/Low Pressure Switch
e. Suction/Liquid/Hot Gas Line Shut-Off Valve
f. Refrigerant Filter Drier
g. Sight Glass
h. Refrigerant Charging Port
2.1 Fan shall be centrifugal blower, single or double discharge installed on the same shaft. Fans
motor capacity of more than 0.75 kW (1 hp) of shall be direct-on-line starter.
2.2 Fan motor shall be direct-drive or belt drive with adjustable pulley(s). Fan shall be statically
and dynamically balanced from the factory.
2.3 Casing of fan coil unit shall be of galvanized steel or black steel with well rust-proof and
external painting. Closed cell insulation or fire retardant polyurethane shall be lined inside
casing with effective thickness to prevent condensation. Drain pan shall be complete with the
same insulation, as casing from factory.
2.4 Cooling coil shall be of direct expansion coil and made of copper tube with aluminum plate-
type fins mechanically bonded to tubes. Each cooling coil matched with condensing unit shall
have capacity as specified.
2.5 Standard accessories for fan coil unit shall include the following :-
a. Thermostatic expansion valve and solenoid valve (for the unit of more than 10.5 kW
or 36 MBH of capacity)
b. Capillary tube (for the unit of less than 10.5 kW or 36 MBH of capacity)
c. Drain and drain pan connection
d. Air filter
e. Refrigerant pipe connection
PERFORMANCE SPECIFICATION
D - 21
CHAPTER 9 VENTILATING FANS
1. Centrifugal Fan
2. Propeller Fan
2.1 Wheels shall be steel, aluminum or heat resistant plastic with heavy hubs. Fan guard shall be
properly provided for fan's suction side.
2.2 Gravity shutter shall be of multi blade type and shall be mounted at the fans outlet.
4. Ceiling Fan
4.1 The fan shall consist of centrifugal fan, discharge gravity damper, tightly sealed motor with
automatic oil-circulation system, and baked on enamel casing.
5. Roof Ventilator
5.1 The fan shall be of vertical propeller, axial flow or centrifugal type as specified on the
drawings, and shall be mounted on structure frame. The fan casing shall be made of
corrosion proof steel, aluminum or fiberglass reinforced plastic.
5.2 The fan shall be of direct drive or belt drive squirrel cage induction motor. The maximum
speed of motor shall not exceed 1,500 RPM.
PERFORMANCE SPECIFICATION
D - 22
CHAPTER 10 AIR-TO-AIR HEAT EXCHANGER & HEAT RECOVERY WHEEL
1. Component description
1.1 Air-to-air heat exchanger as specified on the equipment schedule shall consist of:
a. Casing shall be constructed of rigid galvanized steel frame equipped with service
panel for servicing the pre-filter, heat exchanger element and accessories.
b. Heat exchanger shall separate both exhaust air and outside air by the static
transmission plates. The plates shall be stationary components and both airflow
patterns shall be a counter flow to achieve the maximum heat transfer efficiency. The
overall thermal efficiency of air-to-air heat exchanger shall not be less than 55
percent.
c. The pre-filter efficiency shall not be less than 80% arrestance test in accordance with
ASHRAE standard 52-76 or latest version.
d. The heat exchanger shall be equipped with 2 direct-drive centrifugal fans. Each fan
shall be provided for supplying the outside air to the unit and extracting the cooled air
to outside respectively.
e. Step control switch shall be of heavy duty and flush mounted type. The box shall be
made of metal sheet. The control switch shall be able to control hi-low speed level
and on-off function as minimum requirement.
The heat exchanger wheel shall be a rotary regenerative type. Both outside air and exhaust
air shall not be mixed up during operation. Both airflow patterns shall be of a counter flow
type. The specifications shall include, but are not limited to, the following.
a. The casing shall consist of galvanized steel sheet frame or heavy gauge steel frame
with corrosion preventing primer.
b. The rotary wheel shall be as follows:
Wheel : Aluminum or stainless steel coated with absorbent
media.
Sensible efficiency : Not less than 60%
Latent efficiency : Not less than 55%
Face velocity : Not more than 4 m/s
Air pressure drop : Not more than 250 Pa. (1 in.wg)
c. The wheel driving motor shall be a geared motors with belt-pulley system.
PERFORMANCE SPECIFICATION
D - 23
CHAPTER 11 AIR FILTER
PERFORMANCE SPECIFICATION
D - 24
1.4 Type PF-4
PERFORMANCE SPECIFICATION
D - 25
1.8 Type MF-4
PERFORMANCE SPECIFICATION
D - 26
Rated Capacity : 1) Not less than 1,060 L/s (2200 CFM). Initial
pressure drop of 250 Pa. (1 in.wg). Depth of
media not less than 145 mm (5 7/8 INCHES)
2) Not less than 2,118 L/s (4400 CFM). Initial
pressure drop of 250 Pa. (1 in.wg). media depth
of not less than 290 mm (11 1/2 INCHES)
Testing : Scan tested
Efficiency : Not less than 99.99% DOP efficiency measure of by
ASHRAE (52-76 or the latest version), based on
particle size of 0.3 micron
2. Accessories
Inclined manometer shall be used as local monitor to show air pressure drop status across
the air filter. The contractor shall provide and install the inclined manometer (linear scale
type) in scale range of 0-600 Pa. (0-2.4 in.wg) for large air handling units
The contractor shall provide and install differential pressure switch in scale range of 0-600 Pa.
(0-2.4 in.wg) to show air pressure drop status across air filter.
PERFORMANCE SPECIFICATION
D - 27
CHAPTER 12 PIPE AND FITTING MATERIAL
1.1 Chilled water pipes which are 650 mm. (26 inches) in diameter or larger shall be made of
spiral welded black steel pipe. The wall thickness of pipe shall not be less than 5.5 mm.
and shall conform to AWWA C201-60T standard.
1.2 Pipe fittings which are 650 mm. (26 inches) in diameter or larger such as TEE, WYE, elbow
and reducer shall be fabricated with the same material as the connected pipes and weld-o-let
method shall be applied. Wash-primer shall be applied on the whole surface of pipe.
1.3 Chilled water pipes, which are 600 mm. (24 inches) in diameter or smaller shall be made of
ERW seamed black steel pipe conforming to API-5L or ASTM-A-53 grade B. The wall
thickness of pipe shall not be less than schedule 40.
1.4 Pipe fittings, which are 600 mm. (24 inches), in diameter or smaller shall be of standard
weight fittings with thread or welded end.
Pipes fittings which are 65 mm. (2 1/2 inches) to 600 mm. (24 inches) diameter shall be either
welded joints or flanged connections.
Pipes fittings which are 50 mm. (2 inches) in diameter or smaller shall be a threaded end
connection.
Gaskets shall be made of natural rubber or asbestos. Union shall be of bronze or brass to
iron seat ground joint.
Pressure rating of pipefitting shall not be less than 1.5 times of working pressure.
2.1 Condenser water pipes which are 650 mm. (26 inches) in diameter or larger shall be made of
spiral welded black steel pipe. The wall thickness of pipe shall not be less than 5.5 mm.
and shall conform to AWWA C201-60T standard.
2.2 Pipe fittings which are 650 mm. (26 inches) in diameter or larger such as TEE, WYE, elbow
and reducer shall be fabricated with the same material as the connected pipes and weld-o-let
method. Wash-primer shall be applied on the whole surface of pipe.
2.3 Condenser water pipes, which are 600 mm. (24 inches) in diameter or smaller shall be made
of ERW seamed black steel pipe conforming to API-5L or ASTM-A-53 grade B. The wall
thickness of pipe shall not be less than schedule 40.
2.4 Pipe fittings, which are 600 mm. (24 inch), in diameter or smaller shall be of standard weight
fittings with thread or welded end.
Pipes and fittings which are 65 mm. (2 1/2 inches) to 600 mm. (24 inches) in diameter shall
be either both welded joints or flanged connections.
Pipes and fittings, which are 50 mm. (2 inches) in diameter or smaller shall be a threaded end
connection.
Gaskets shall be made of natural rubber or asbestos. Union shall be of bronze or brass to
iron seat ground joint.
Pressure rating of pipefitting shall not be less than 1.5 times of working pressure.
PERFORMANCE SPECIFICATION
D - 28
All condenser water pipe around cooling tower plant shall be of galvanized steel pipe and
shall conform to BS 1387. The pipe fitting shall be of galvanized malleable cast-Iron ASTM A
120-73 standard
3.1 Make-up water pipe, drain pipe from cooling tower, make-up water pipe to expansion tank
and fittings shall be of galvanized steel, and medium weight, and shall conform to BS 1387.
3.2 Galvanized steel fittings shall be of galvanized malleable cast-iron, and shall conform to
ASTM A 120-73.
4.1 Drainpipes from air-conditioning units shall be of PVC, class 8.5 conforming to TISI 17-2532.
4.3 Drainpipes shall be insulated with minimum 12 mm. (1/2 inch) thick closed cell fire retardant
insulation.
5.1 Chemical pipe and fittings for chemical feed and ozone system shall be of rigid PB pipe;
which conform to TISI 910-2532.
PERFORMANCE SPECIFICATION
D - 29
CHAPTER 13 CHILLED WATER PIPE INSULATION (CLOSED-CELL FOAMED ELASTOMER)
All chilled water pipes and drainpipes shall be insulated with closed-cell insulation. The characteristic
of insulation complied with the ASTM standard shall be as follows.
a. Self-extinguishing.
b. Low smoke density while burning.
c. Excellence in ozone resistance.
2
d. The thermal conductivity value shall not exceed 0.038 W/mk (0.27 BTU. inch/ft hr.F)
e. The water absorption valve is less than 5 percent by weight.
3 3
f. The density of material shall be more than 60 Kg/m (3.75 lb/ft )
g. The thickness of insulation for any chilled water pipe sizes run in general area shall be
according to the following list.
150 mm. (6 ) and smaller Not less than 38 mm. (1 1/2 inchas)
200 mm. (8 ) and larger Not less than 50 mm. (2 inches)
h. The thickness of insulation for any chilled water pipe sizes run in very high humidity or
outdoor area shall be according to the following list.
i. The thickness of closed-cell insulation for drainpipes shall not be less than 12 mm. (1/2 inch).
PERFORMANCE SPECIFICATION
D - 30
CHAPTER 14 PIPING INSTALLATION
1. Sleeves
Vertical pipes passing through floors shall be provided with sleeves of black steel pipes. Sleeves
shall be of a proper length to pass through the entire floor construction and shall terminate 40 mm
(1 inches) above the finished floor level.
Horizontal pipes passing through walls and partitions shall be provided with full thickness sleeves
made of standard weight black steel pipes.
Sleeves shall be large enough to leave not less than 12.7 mm ( inch) clearance around the pipe and
covering insulation, if there is any. Sleeves shall be set in place when the walls and partitions are
built.
Sleeves in concrete work shall be flanged at the bottom or provided with temporary centering caps
and securely nailed or screwed to formwork before the concrete is poured.
Chromium-plated escutcheons shall be provided where exposed pipes pass through walls or floors.
When sleeves are installed through a firewall, the clearance between sleeves and pipes shall be filled
with fire-resistant material. The fire rating of the fire-resistant material shall be at least equivalent to
that of the firewall.
When pipes pass through waterproof walls, water-retaining rings with approved type of sealant shall
be applied.
2. Supports
Hangers or supports shall be provided at intervals as specified herein, both in horizontal and vertical
runs. In addition, it is required that a hanger be provided at not more than 300 mm (12 inches) from
each change of direction on the side of the longest run and also at point adjacent to all valves,
strainers, etc. All hangers and supports for horizontal piping shall be adjustable in height over a
minimum distance of 50-mm (2 inches).
PERFORMANCE SPECIFICATION
D - 31
Steel Hangers and Supports
PERFORMANCE SPECIFICATION
D - 32
CHAPTER 15 VALVES
1. Gate Valve
Gate valve sizes in the range of 15 mm. (1/2 inch) to 50 mm. (2 inches) shall be made of bronze
body, and consist of screwed bonnet, rising stem, solid wedge disc and screwed ends.
2. Globe Valve
Globe valve sizes in the range of 15 mm. (1/2 inch) to 50 mm. (2 inches) shall be made of bronze
body, and consist of screwed bonnet, replaceable plug type disc and screwed ends.
3. Check Valve
3.1 Check valve sizes in the range of 15 mm. (1/2 inch) to 50 mm. (2 inches) shall be selected
from 2 options as follows:
Option 1: For single disc type, the body made of bronze shall be of Y-pattern, consisting of
Teflon seat, stainless steel spring and screwed ends.
Option 2: The body made of bronze shall be of swing type.
3.2 Check valve sizes of 65 mm. (2 1/2 inches) and larger shall be made of cast iron or semi-
steel body. Valve shall consist of bronze seat and bushing, stainless steel spring. Check
valve shall be of silent type, globe style, single disc and flanged ends.
4.1 Balancing valve sizes in the range of 15 mm. (1/2 inch) to 50 mm. (2 inches) shall be of
bronze body and screwed ends.
4.2 Balancing valve sizes of 65 mm. (2 1/2 inches) and larger shall be of cast iron or ductile iron
body, and flanged ends.
4.3 Balancing valve shall be selected from 2 options as follows:
Option 1 : Balancing valve with flow measuring ports and revolution indicator.
Option 2 : Globe valve installed with external flow measuring port.
5. Butterfly Valve
5.1 Butterfly valve sizes of 65 mm. (2 1/2 inches) and larger shall be made of cast iron or ductile
iron body, consisting of stainless steel or aluminum bronze disc.
5.2 Lever-operated valves shall be used for sizes in range of 65 mm. (2 1/2 inches) to 100 mm. (4
inches).
5.3 Hand wheel gear-operated valves shall be used for size up to 150 mm. (6 inches).
5.4 Position indicator shall be provided to check valve disc position.
PERFORMANCE SPECIFICATION
D - 33
6. Pressure Relief Valve
6.1 Pressure relief valve shall be of hydraulically operated type, pilot control, diaphragm type and
globe pattern body.
6.2 Pilot control shall be of direct-acting, adjustable spring loaded, diaphragm-type valve.
6.3 Pressure relief valve shall be made of cast iron or cast iron and flange connection.
7.1 Valve shall be designed to control the flow of water by means of cartridge and spring. The
accuracy of controlling the flow of each valve shall be in the range of + 5 percent of water
pressure drop.
7.2 Cartridge and spring shall be made of stainless steel.
7.3 Valve sizes in the range of 15 mm. (1/2 inch) to 65 mm. (2 1/2 inches) shall be made of alloy
metal or steel body and screwed ends.
7.4 Valve sizes of 80 mm. (3 inches) and larger shall be made of steel body and flanged ends.
7.5 Valves body shall have temperature and pressure measuring port with drain valve.
PERFORMANCE SPECIFICATION
D - 34
CHAPTER 16 AIR DISTRIBUTION AND ACCESSORIES
1. General
1.1 Unless otherwise specified, all ducts shall be of galvanized steel sheet in accordance with
Thai Industrial Standard (TIS) 50-2538. The galvanized steel sheet gauge application shall be
tabulated as follows.
2. Duct Types
a) Flexible round ducts shall be the factory-fabricated ducts consisting of 2 layer of fire-
resistance aluminum foil sheets of not less than 17 microns thick each and
aluminized polyester film with adhesive. The total thickness shall not be less than 68
microns.
a) Ducts shall be constructed of minimum 2.0 mm. (0.08 inch) thick black steel sheet by
means of longitudinal seam welding method.
Each duct section shall be fabricated with flanged connection and air leakage on all
duct connection shall not be per milted.
PERFORMANCE SPECIFICATION
D - 35
3. Duct Insulation
Alternative 1
PERFORMANCE SPECIFICATION
D - 36
o o
- Maximum thermal conductivity valve : 0.080 W/m k at 200 C mean
2 o
temperature (0.55 Btu.in/ft .h. F at
o
390 F mean temperature).
- Attached with fiberglass insulation by fire resistant adhesive, major composition
of single-faced aluminum foil laminate shall consist of, but is not limited to: 2
aluminum foil, kraft paper, polyethylene and reinforcing fiberglass scrim. Double-
faced aluminum foil laminate shall meet the ACI Sisalation 436, the flame stop
524 or equivalent.
Alternative 2
4.1 Duct supports and hangers selection shall be based on applications, installation location,
duct weight, etc. Expansion bolts shall be used with reinforced concrete for supports and
hangers. Power actuated pins shall not be permitted.
4.2 Duct supports and hangers shall be adjustable types.
4.3 Duct hangers and supports installed in humid area or corrosive area, such as batteries room,
boiler room, chiller room, dishwashing room, kitchen and laundry room, etc. the hangers and
supports shall be painted with two coats of epoxy red lead primer and one coat of epoxy black
finishing paint.
4.4 Duct supports and hangers for normal application shall be painted with two coats of red lead
primer and one coat of alkyd gray finishing paint. Screws, nuts and spring washers shall be of
Hot Dipped Galvanized Steel or Stainless Steel.
5. Access Door
5.1 Where fire dampers, VAV boxes, motorized dampers, smoke dampers, splitter dampers, and
volume dampers size up to 0.1 m2 (150 in2) are installed, the contractor shall provide access
doors.
PERFORMANCE SPECIFICATION
D - 37
6. Dampers
Splitter dampers shall be fabricated with the galvanized steel sheet. Splitter damper thickness
shall have the same gauge number as each installed duct.
Single blade or multiple blade volume damper shall be applicable for ductwork, made of
minimum 1.6 mm. galvanized steel (gauge no. 16) and hemmed in form of interlocking edges.
Frames and blades shall be constructed of zinc-coated steel with fire rated at minimum 1
hours, certificate by UL approval fusible links for fire damper shall be designed for operating
o o o o
at 28 C (50 F) above room temperature, but not less than 71 C (160 F).
In case shutter type fire dampers are installed, the shutters should be out of air stream before
being operated.
Smoke dampers for smoke exhaust system shall be the same fabrication as volume dampers
and shall be approved by the UL institute with UL555S Leakage Class I certification.
PERFORMANCE SPECIFICATION
D - 38
CHAPTER 17 STANDARD FIELD TESTS
1. General
1.1 Witness tests shall be performed to the Engineer, the Supervisor or the owner's
representative. The Contractor shall timely schedule and provide his skillful Engineer /
Supervisor for the field test. The cost of all tests, including the supply of instruments shall be
paid by the Contractor.
1.2 Work which fails to meet the test requirements or the contract documents shall be considered
defective and shall be promptly corrected or removed from the site.
1.3 Instruments shall be tested for accuracy by the approved laboratory or the manufacturer.
Instruments and measuring devices required for tests shall be provide by the Contractor. If
gauges, thermometers, and the like used for tests are permanently installed, they shall be
tested and calibrated before installation.
1.4 The Contractor shall submit the start-up and test report form to the Engineer/Supervisor for
approval before starting-up and testing.
After installations are completed, all equipment shall be test run. Any necessary adjustments shall be
made to assure that all equipment shall operate with the required performance. Report forms
following items, but is not limited to shall include design and actual conditions for each item
mentioned.
Evaporator pressure
Evaporator temperature
Entering / Leaving water pressure
Water pressure drop
Entering / Leaving water temperature
Water temperature drop
Water flow rate
(g) Condenser
Condenser pressure
Condenser temperature
Entering / Leaving water pressure
PERFORMANCE SPECIFICATION
D - 39
Water pressure drop
Entering / Leaving water temperature
Water temperature drop
Water flow rate
(h) Compressor
(i) Refrigeration
PERFORMANCE SPECIFICATION
D - 40
Motor sheave Diam./ Bore
Fan sheave Diam./ Bore
Sheave & Distance
No. of Belts / Brand name / Size
2.3 Pump
PERFORMANCE SPECIFICATION
D - 41
(f) Motor manufacturer / Frame
(g) Motor KW / RPM
(h) Volts / Phase / Hertz
(i) Full load amps / Service factor
(j) Seal type
(k) Pump - off pressure
(l) Discharge Pressure
(m) Suction Pressure
(n) Final dynamic pressure
(o) Final water flow rate
(p) Voltage
(q) Amperage
Primary Side
Secondary Side
PERFORMANCE SPECIFICATION
D - 42
(h) Static pressure In / Out
(i) Total static pressure
(j) Motor manufacturer / Frame
(k) Motor KW / RPM
(l) Volts / Phase / Hertz
(m) Full load amps / Service factor
(n) No. of Belts / Manufacturer / Size
PERFORMANCE SPECIFICATION
D - 43
(f) Motor
Motor Data
- Manufacturer / Frame
- KW. / RPM
- Volts / Phases / Hertz
- Full load amps
PERFORMANCE SPECIFICATION
D - 44
Air filter pressure drop
- Pre filter
- Secondary filter
- Final filter
PERFORMANCE SPECIFICATION
D - 45
Return air condition DB / WB
Entering air condition DB / WB
Leaving air condition DB / WB
Fan RPM
Voltage
Amperage
(f) Motor
Manufacturer / Frame
KW. / RPM
Volts / Phase / Hertz
Full load amp. / Service factor
PERFORMANCE SPECIFICATION
D - 46
Inlet pressure
Outlet pressure
Air pressure drop across terminal unit
Supplied air flow rate at design temperature
By-pass air flow rate
3.1 Check the operating sequences of related fans as specified in the specification.
3.2 Check door operation and its latches or hinges floor by floor, starting from the highest floor to
the lowest floor.
3.3 Check the fan operation by smoking directly to the detector or each floor.
3.4 During procedure on item 3.3, all doors shall be completely closed. Then following checks
shall be done:
3.5 Test relief damper operation by closing up all doors while the fan runs to reach the set point
pressure switch (50 Pa)
a) The relief damper shall be in opening position, measuring air velocity via relief
damper to check air volume and the adjust relief damper as required.
b) Check the operating range of pressure switch. The damper shall close up when air
pressure decreases.
3.6 Test duct-type smoke detector operation. The power supply to the fan shall be off when
smoking directly to the fans suction.
3.7 Control and electrical wiring shall be connected from emergency power supply.
4.1 Check the operating sequences of related fans as specified in the specification.
4.2 Check relief damper position on every lift lobby. All damper shall be in fully dosed position.
4.3 Check the fan operation by smoking directly to the detector on each floor.
4.4 During procedure on item 4-3, all doors shall be completely closed. Then following checks
shall be done:
PERFORMANCE SPECIFICATION
D - 47
a) Force of door opening. Adjust if the door needs pushing overmuch.
b) Check air velocity passing three the door. The recommended air velocity shall be in
the range of 0.375 to 0.75 m/s. Balance air velocity as equally as possible by
adjusting the volume dampers within lift lobby case.
4.5 Adjust the relief damper operation by means of setting pressure switch valve or counter
weight of damper to obtain pressure differential valve of not lese than 40 Pa.
4.6 Test duct-type smoke detector operation. The power supply to the fan shall be off when
smoking directly to the fans suction.
4.7 Control and wiring shall be connected from emergency power supply.
5.1 Check the operating sequence of related fans as specified in the specification.
5.2 Check air intake. Damper position shall be normally-closed. When smoke fans are activated,
Damper position shall be fully open.
5.3 Check air leakage volume via make-up dampers.
5.4 Control and power wiring shall be connected from emergency power supply.
6.1 All water piping shall be tested with water pressure as specified. All testing shall be under the
contractors responsibility.
6.2 Partial piping system testing shall be performed after the Supervisors approval, if necessary.
6.3 Tested pipes shall be filled up with water and pressurized according to specified pressure. All
test shall be witnessed by the Supervisor.
6.4 Schedule 40 or standard weight pipes shall be tested at water pressure of not less than 1.5
times of maximum working pressure or 1034 kPa (150 Psi), whichever is greater, and
maintained with testing pressure of not less than 24 hours.
6.5 All drain pipes shall be tested and maintained with water pressure of not less than 3-meter
water column (10 ft) and 1 hour, respectively.
6.6 In case more than 5 percent of testing pressure decreases during testing period, pipe
leakages shall be verified and repaired before being retested.
6.7 Leaks in screwed fittings shall be corrected by replacing with a new one. Leaks in welded
joints shall be cut not and rewelded.
6.8 If operating pressure of equipment installed on the pipes is less than specified testing
pressure, the equipment shall be disassembled before starting test procedure.
7.1 To prevent entry of dust, dirt, water or other obstructing material, open ends of pipes shall be
closed with covers or plugs. All pipes stored on site shall be kept above ground.
7.2 Inside surfaces of pipes and fittings shall be thoroughly cleaned before being installed.
7.3 When pipe installation is complete, pipe system shall be filled up and flushed with water at
least 2 times before being refilled up and recirculated with pumps until drained water without
debris or scrap metal.
PERFORMANCE SPECIFICATION
D - 48
8. Balancing for Pipe System
8.1 During commissioning period, water flow rate through equipment as shown on the equipment
schedule shall be balanced.
Maximum allowable flow deviation from specified values on the equipment schedule shall be
+ 10 percent.
8.2 Water flow balancing through pumps shall be done by comparing differential pressure
measured across pipe inlet and outlet with the manufacturers pump curve.
8.3 When completion of balancing valve setting, final position on all hand wheels shall be
indicated.
8.4 Orifices or flow meters as indicated on the drawings shall be installed according to the
manufacturers recommendation.
9.1 During ductwork installation, scrap of material, rubbish or plastic inside air ducts shall not be
residual.
9.2 Before ceiling installation, all inside air ducts shall be cleaned with the portable fan or installed
air handling units in order to remove dust or small particles from air ducts.
9.3 In case air handling units are used to clean air duct system. Air filters shall be installed in right
position. And the contractor shall provide new air filters for the air handling units after finishing
air duct cleaning.
10.1 During commissioning period, airflow rate for grilles as indicated on the drawings shall be
adjusted to achieve air distribution. Maximum allowable airflow deviation from specified
figures on the drawings shall be + 10 percent.
10.2 Traverse method with pitot tube shall be used to measure air flow at main air ducts and
branch takeoff. All measuring holes for pitot tube shall be sealed completely after finished
calibration.
10.3 Airflow rate generated by the fans of air handling units shall be done by means of fans
revolution adjustment. Wherever branch-takeoffs are installed on straight ducts, required air
flow shall be balanced by volume damper or splitter damper adjustment. After completion of
air balancing, final position on damper rods shall be indicated.
PERFORMANCE SPECIFICATION
D - 49
ELECTRICAL SYSTEM
PERFORMANCE SPECIFICATION
D - 50
CHAPTER 1 24 KV SF6 CIRCUIT BREAKER (METAL-ENCLOSED SWITCHGEAR)
1. Reference Standard
The equipment shall be manufactured and tested in conformity with the latest revision of the standard
listed below:-
2.1 Metal-enclosed switchgear shall be designed so that normal service, inspection and
maintenance operations shall be carried out safely.
2.2 An earthing conductor shall be provided extending the whole length of the metal-enclosed
switchgear.
The earthing conductor of lightning arrester, if applied, shall be connected to the grounded
shield cable and separated from the earthing conductor of the switchgear.
2.3 Metal-enclosed switchgear shall be provided with durable and clearly legible nameplates
2.4 The minimum degree of protection shall be as follows:-
Circuit breaker, shall be of SF6 gas trip-free type. The SF6 gas density monitoring system
shall be provided for alarm and lockout breaker.
3.2 Fuse
PERFORMANCE SPECIFICATION
D - 51
3.3 Earthing Switch
The earthing switch shall be general purpose, group-operated, single throw, and fault making
capability.
3.4 Busbar
PERFORMANCE SPECIFICATION
D - 52
CHAPTER 2 24 kV SF6 (FUSE) LOAD BREAK SWITCH (METAL-ENCLOSED SWITCHGEAR)
Switches shall be quick-make, quick-break with the speed of opening or closing entirely
independent of the operator. The (fused) load break switches shall be three-pole, two-
position, with a stored energy spring mechanism to provide quick switch operation
independent of the handle speed
PERFORMANCE SPECIFICATION
D - 53
CHAPTER 3 12/24 kV CAST RESIN TRANSFORMER
1. Reference Standards
The cast resin transformer shall be manufactured and tested in conformity with the latest revision of
the standard listed below:-
2. General Requirements
The transformer shall be able to withstand maximum short circuit current limiting by only its
impedance for at least 2 seconds, both electrically and mechanically.
3. Core
The core shall be made of high quality, non-aging, grain-oriented, low loss and high permeability
silicon steel
4. Winding
Transformer winding shall be of either copper or aluminum in the insulation class B or class F or class
H. External insulation for winding shall be composed of epoxy resin and quartz powder.
The transformer shall be installed in steel enclosure which ventilated by ventilated fan. Ventilated fan
shall be automatically operated by thermostat.
PERFORMANCE SPECIFICATION
D - 54
CHAPTER 4 MAIN DISTRIBUTION BOARD
1. Enclosure Construction
The main distribution board framework shall be fabricated on a die formed steel base assembly
consisting of formed steel and commercial channel welded or bolted together to rigidly support the
entire unit for floor mounting. The framework is to be formed in 3 mm thick (min.) code gauge steel,
rigidly welded and bolted together to support all cover plates, bussing, and component devices during
installation.
The enclosure shall be constructed as to prevent the entry of all flies and rodents and have minimum
degree of protection IP31 (ACCD to IEC).
The approximate dimension of each section of the distribution board shall be as follow:-
2. Bussing
The bussing shall be bare copper and of sufficient cross sectional area to continuously conduct rated
full load current with a maximum average temperature rise of 25C, above an ambient temperature of
40C. The current carrying capacity of bus bar shall be of the bare bus bar rating, conformed to DIN
43671
The phase and neutral main horizontal bus shall consist of a single continuous solid 98% copper.
Parallel bus bar conductors for each phase will be permitted only for current exceeding 1,000
amperes.
The circuit breakers shall be equipped with, but not be limited to the following:-
(a) Triple pole type with overcurrent, overload, earth-fault protection and instantaneous trip unit.
(b) Shunt trip coil, closing coil, motor operating mechanism.
(c) Local breaker control.
(d) Trip supply healthy, breaker open, breaker close, breaker trip, phase indication lamps.
(e) Auxiliary contacts for interlocks, local status indications, controls and 50% spares.
(f) Setting levels of all adjustable tripping devices shall be clearly indicated and marked up on
equipment. A record sheet indicating the final settings shall be submitted.
(g) If indicated on the drawing, key lock shall be provided.
PERFORMANCE SPECIFICATION
D - 55
4. Feeder Circuit Breakers
Circuit breakers shall be equipped with individually insulated, braced and protected connectors. The
front faces of all circuit breakers shall be flush with each other
All circuit breakers shall be selected to perform in coordination pattern along the protective lines.
PERFORMANCE SPECIFICATION
D - 56
CHAPTER 5 ELECTRICAL DISTRIBUTION SYSTEM
The panelboards shall be of the dead-front safety type equipped with molded-case circuit breakers.
They shall be of the NEMA standard or approved equivalent.
Molded-case circuit breaker shall be quick-make, quick-break, thermal- magnetic, trip-indicating, and
have a common trip on all multipole breakers with internal tie mechanism.
The distribution board and panelboard busbar assembly shall be enclosed in a steel cabinet. The box
shall be fabricated from galvanized steel or equivalent rust-resistant steel
All cables, wires, terminals, etc. shall be colour coded as follows: white or grey for neutral, black for
phase R, red for phase S, blue for phase T and green for ground. Large wires, cables and busbars
shall be colour-coded with suitable heat shrinkage sleeves.
3. Safety Switch
All safety switches shall be of the NEMA Heavy Duty Type or approved equivalent. The switches
shall be either Fused Safety Switches (FSS) or Non-Fused Safety Switches (NFSS) as required.
4. Cables/Conductors
The cables shall be of the single-core, with XLPE insulation of copper wire screen and
extruded outer conductive layer The permissible operating temperature and short-circuit
temperature are 90C and 250C, respectively.
All cables shall conform to the Thai Industrial Standard, No. 11-2531. All conductors of the
insulated cables shall be copper wire.
Unless otherwise noted, the type of low tension cables to be installed shall be as follows:
(a) Type NYY for direct burial or exposed wiring, or cable trench.
(b) Type THW for running in conduit.
PERFORMANCE SPECIFICATION
D - 57
5. Raceway
5.1 Conduit
Rigid steel conduit and Intermediate Metal Conduit (IMC) rigid conduit shall be in accordance
with ANSI C80.1. IMC shall be in accordance with ANSI C80.6.
Nonmetallic conduit and fittings shall be rigid plastic in accordance with NEMA TC-2 and
NEMA TC-3.
PVC conduit for electrical wiring shall be rigid PVC conduit and comply with the Thai Industrial
Standard No. 216-2520. PVC conduit shall be used in the corrosive area both under ground
and above ground installation.
PVC conduit installation shall conform to the Electricity Authority regulation.
5.2 Main Feeder Wire Way and Branch Circuit Wire Way
All main feeder wireway and branch circuit wireway shall be of hot-dip galvanized steel or
made of aluzinc sheet or electro galvanized steel sheet with epoxy paint.
The main feeder wireway shall be securely supported at intervals not exceeding 1.5 m. unless
specially approved for supports at maximum interval, but in no case shall distances between
supports exceed 2.40 m.
6. Socket Outlets
In general, all socket outlets shall be flush mounted type, rated 15 amperes at 250 volts single phase
2-pole, 3-wire, with third-pole grounded and as shown on the drawings.
The cover plate of the socket outlet shall be aluminum or stainless steel.
All socket outlet boxes which are to be embedded in concrete shall be of cadmium plated steel box
and shall be of cast metal box for surface mounting. In general, the socket outlet mounting height
shall be at 300 mm above finished floor level or as otherwise noted.
PERFORMANCE SPECIFICATION
D - 58
7. Wall Switches
Wall switches shall be flush, quiet type, large tumbler switches, rated 10 amperes and 250 volts single
phase.
Switches indicated on the plans shall be installed directly adjacent to the entrance door, at the strike
side of the door and, in general, the mounting height shall be 1.2 m above finished floor.
PERFORMANCE SPECIFICATION
D - 59
CHAPTER 6 LIGHTING FIXTURES AND LAMPS
The emergency lights and fire exit lights shall be of the surface mounted type. Each unit shall be
equipped with the following:
(a) Seal-lead battery, 12V DC for 2 x 55 w. halogen lamps minimum back-up time of 2 hour.
(b) Solid state charger.
(c) Low and high voltage cut-off.
(d) Overload and short circuit protection.
(e) Status indicating lamp for "Power On", "Fully Charged" & "Short Circuit".
(f) Corrosive-proof housing.
(g) The housing of luminaire shall be steel and diffuser shall be glass diffuser.
The low voltage cut-off shall be set at 1.6 volts per cell.
PERFORMANCE SPECIFICATION
D - 60
CHAPTER 7 GENERATING SET
1. Standards
The diesel engine, alternator, tank and control board shall be manufactured and tested in accordance
with the latest standards, such as SAE, BS, DIN, IEC, JEC, or NEMA
2. Principal Requirements
The engine shall be of the heavy duty, four-cycle compression ignition type. The engine shall
be turbo-charged with air-cooled charge and vee-form. The engine shall be certified by the
engine manufacturer for its capability in driving a generator yielding a KW rating at 1,500 rpm.
A residential type silencer of suitable size as recommended for low noise operation shall be
supplied by the engine manufacturer. Flexible exhaust connections shall be provided.
Exhaust pipe shall be black steel pipe, medium class and shall be insulated with 40 mm
thickness of calcium silicate with 0.6 mm thickness of stainless steel or aluminum jacket.
(d) Filter
Replaceable element type filters shall be provided on the engine for fuel oil, lubricating oil and
air cleaner.
(e) Governor
The governor shall be of the Electric Isochronous type. Frequency regulation shall be within
+ 0.25 % of rated frequency during steady state condition. Frequency variation shall be within
+ 3 %, 6 seconds recovery time when load is stepped from 0 % to 60 % load.
The 24-volt DC electric starting system shall include a starting motor, a charger with ammeter,
2 x 12 volts lead acid battery of the heavy duty type with a rack for the battery attached to the
engine frame.
PERFORMANCE SPECIFICATION
D - 61
(g) Engine Fuel System
The engine fuel system and fuel tank shall conform to the following standards.
Engine protection devices shall have sensing elements located on the engine to initiate the
following preliminary alarms and engine shutdowns:-
(k) Anti-vibration
The engine panel mounted on the engine shall consist of, but not limited to, the following
components:-
(m) Alternator
The alternator shall be of the single- bearing, brushless, screen protected type The
construction of the alternator shall conform to NEMA MG 1-22.
The generator control panel shall be mounted on the top of the alternator conduct box or as
otherwise agreed.
The generator control panel shall consist of, but not limited to, the following components:-
PERFORMANCE SPECIFICATION
D - 62
- One (1) triple pole circuit breaker with pad lock shunt trip, three-phase overcurrent
release, auxiliary contact rating as indicated on the drawings.
- Ammeters (3 ammeters).
- Voltmeter.
- Volt selector switch.
- DC ammeter
- Indicating frequency meter.
- Indicating watt meter, 3-phase, 4-wire unbalanced load.
- Watt-hour meter, 3-phase, 4-wire unbalanced load.
- Set of current transformers.
- Set of indicating lamps, LED type.
- Set of instrument fuses.
- Set of protective relays as indicated on the drawings.
The automatic transfer switch shall be located in MDB in the main electrical room shall be composed
of at least the following.
(a) Motor operated circuit breaker for both main incoming and generator side
(b) Mechanical and electrical interlock shall be provided for the above circuit breakers.
(c) Control unit shall be of the solid state type.
(g) Transition time from the instant of failure of the nominal power source to diesel-generation
set.
Delays the transfer from emergency to permit stabilization of the normal power source before
retransfer is made;
(j) In normal condition, the engine shall be warm started-up every week for 15-30 minutes
adjustable. (Weekly exercise) the generator set shall be run for no load.
PERFORMANCE SPECIFICATION
D - 63
4. Certificate of Performance
Test certificate of the performance of the generating set from the original manufacturer shall be
submitted.
PERFORMANCE SPECIFICATION
D - 64
PLUMBING AND DRAINAGE SYSTEM
PERFORMANCE SPECIFICATION
D - 65
INTRODUCTION
Otherwise specified elsewhere in the Contract, the entire system shall be manufactured, installed,
tested and balanced conforming to the latest issue of the following standards:
PERFORMANCE SPECIFICATION
D - 66
CHAPTER 1 PUMP (END SUCTION CENTRIFUGAL TYPE)
1.1 General
1.2 Motors
Each pump shall be totally enclosed fan-cooled class F insulation motor and protection class
IP 54.
The rated KW shall be at least 1.15 times the maximum power required.
1.3 Casings
Casing material shall be cast-iron, precision-manufactured for best performance and long-
term duty.
1.4 Impellers
1.5 Shafts
Shafts for pumps with stuffing boxes shall be of stainless steel, (chrome-iron or nickel-iron)
extending through the stuffing boxes. Where stuffing boxes are used, shafts shall be
provided with water slingers.
1.6 Anti-Vibration
Each pump shall be mounted on inertia base and spring isolators which are placed on a
concrete foundation.
The maximum static deflection of spring isolators shall be 25.4 mm (1 inch). They shall be
selected and installed in accordance with the manufacturer's recommendations such that no
disturbing vibration and noise is being transmitted to the nearby structure.
PERFORMANCE SPECIFICATION
D - 67
CHAPTER 2 PUMP (SPLIT CASE CENTRIFUGAL TYPE)
1.1 General
Pump shall be of the non-overloading, centrifugal, volute type. It shall be of the horizontal
split, or vertical split, double suction type with suction and discharge connections in the lower
half of the casing, allowing removal of the rotating element without disturbing pipe
connections.
1.2 Motors
Each pump shall be totally enclosed fan-cooled class F insulation motor and protection class
IP 54.
The rated KW shall be at least 1.15 times the maximum power required.
1.3 Casings
Casing material shall be cast-iron, precision-manufactured for best performance and long-
term duty.
1.4 Impellers
1.5 Shafts
Shafts for pumps with stuffing boxes shall be of stainless steel, (chrome-iron or nickel-iron)
extending through the stuffing boxes. Where stuffing boxes are used, shafts shall be
provided with water slingers.
1.6 Anti-Vibration
Each pump shall be mounted on inertia base and spring isolators which are placed on a
concrete foundation.
The maximum static deflection of spring isolators shall be 25.4 mm (1 inch). They shall be
selected and installed in accordance with the manufacturer's recommendations such that no
disturbing vibration and noise is being transmitted to the nearby structure.
PERFORMANCE SPECIFICATION
D - 68
CHAPTER 3 HOT WATER CIRCULATING PUMP
1. Pump Requirement
The pump shall be in-line close-coupled centrifugal type, single stage, vertical split case stainless
steel and bronze impeller design for suitable 1,206 kPa (175 psig) working pressure and 82C
(180F) working temperature, with flange suction and discharge connections.
Pumps shall have a mechanical seal with a carbon seal ring rotating against a ceramic seat and a
removable bearing assembly.
PERFORMANCE SPECIFICATION
D - 69
CHAPTER 4 AUTOMATIC OPERATED WATER SOFTENER
1. Equipment Requirement
Each water softener shall comprise a closed cylindrical steel tank, containing a bed of strong cationic
exchange resin for catching calcium and magnesium. When one softener is in service, the other is
either in the stage of regeneration or standby. The cycle-end of each unit is fixed on a pulse counter
which receives one pulse for each cubic meter of water flow through the water meter mounted on the
upstream of each unit. When the pre-determined volume of treated water decreases, down to zero,
an acoustic alarm will (actuate) the end of the cycle then the unit shall start regenerating. Each unit
shall be provided with a selector switch with two positions, one for the softener in service phase and
the other for the softener in regeneration phase. The regeneration shall be started by a pushbutton
and will proceed automatically by a series of timers to open and close each pneumatic operated type
butterfly valve to control the valves different phases. At the end of the regeneration, the indicating
lamp mounted on the control panel will switch on, indicating that the softener regeneration is over, and
then the unit becomes in standby position and ready for service.
The unit shall be of automatic duplex softener, galvanized steel tank of capacity. The unit shall be
equipped with microprocessor control, pressure gauges, isolating valve, bypass valve, brine tank and
other necessary control devices.
PERFORMANCE SPECIFICATION
D - 70
CHAPTER 5 UNITS FIXTURE ACCESSORIES
1. Self-Closing Faucet
The faucet shall be automatically slow self-closing type for wash basins and lavatory in public places.
The water shall be discharged when the lever is pressed, and stops automatically after a set time
which can be adjusted between 5 and 10 seconds. The spout shall have aerator which prevents the
water from splashing.
The faucet shall be operated in the pressure range of 70-550 kPa (10-80 psi).
The tube shall be of synthetic rubber covered with stainless steel braiding. It can be used in the
pressure range of 70-550 kPa (10-80 psi) without any leakage of water throughout the line and both
connection ends.
Automatic flush valve with sensor shall be used with urinal in the public toilet. The unit shall be
equipped with photoelectric sensor which will detect when a person stands in front of the urinal. In
case the detection period is more than 3-5 seconds, when the user leaves the urinals, the sensor shall
send the flushing signal from the control box to activate the flushing mechanism to flush the urinal.
The valve shall be polished chrome, external adjustable, diaphragm type with vacuum breaker, 25
mm (1 inch) screw driver angle stop and oscillating handle. The valve shall have working pressure in
the range of 140-550 kPa (20-80 psi) without any water leakage.
The valve shall be polished chrome, external adjustable diaphragm type with vacuum breaker, 20
mm. ( inch) screw driver angle stop and oscillating handle, the valve shall have working pressure in
the range of 140-550 kPa (20-80 psi) without any water leakage.
Automatic faucet with sensor shall be used in lavatories for public toilets. The unit shall be equipped
with non-tough faucet which is provided with a photo-electric sensor to eliminate handle operation for
public use. When the user puts the hand under the spout, the sensor shall send the signal to the
control box to activate the supply water and remove the hand to stop water.
PERFORMANCE SPECIFICATION
D - 71
CHAPTER 6 ULTRA-VIOLET PURIFIER
1. Equipment Requirement
The unit shall complete with ultraviolet monitor, solenoid valve, alarm and flow control valve.
PERFORMANCE SPECIFICATION
D - 72
CHAPTER 7 CARTRIDGE FILTER
1. Equipment Requirement
The inlet and outlet connections shall be threaded with a size of not smaller than 25 mm (1 inch) in
diameter nominal pipe size.
The filter element shall be for removal dirt and rust at the retention rating 10 micron.
PERFORMANCE SPECIFICATION
D - 73
CHAPTER 8 DRINKING WATER TREATMENT UNIT
Drinking water treatment unit shall be used to improve cold water quality up to drinking water quality standard
from WHO. The unit shall be package type and comprise of the following:-
The unit shall be guaranteed of the treated water quality from the supplier with at least 1 year maintenance
period.
PERFORMANCE SPECIFICATION
D - 74
CHAPTER 9 SWIMMING POOL EQUIPMENT (HIGH RATE SAND FILTER)
1. Filter Plant
The filter plant shall be capable of filtering all water in the pool within the turnover period of 6 hours.
The filters shall be of the high rate sand type with a filtration rate of 50 m/hr. 20 gallons per minute per
square foot. Circulation shall be maintained by means of mechanical seal end suction centrifugal
pumps with in-line perforated stainless steel strainer basket. The filtering plant shall comprise sand
filters pumps, piping, valves, pressure gauges and complete with other accessories supplied from the
manufacturer.
The unit shall be the design for wall mounting analog readout completed with all necessary
components as well as complete ready to used installation control panels and sensor for chlorine
residual and PH in swimming pool.
PERFORMANCE SPECIFICATION
D - 75
CHAPTER 10 VALVES
1. Gate Valves
Valves of sizes up to 50 mm (2 inches) in diameter shall be bronze where appropriate, with threaded
ends, solid wedges and nonrising stems. Valves of sizes 65 mm (2 inches) in diameter and larger
shall be cast-iron where appropriate, with flanged ends, solid wedges and rising stems.
2. Globe Valves
Valves of sizes up to 50 mm (2 inches) in diameter shall be bronze where appropriate with threaded
ends and union bonnets. Valves of 65 mm (2 inches) in diameter and larger shall be cast-iron,
bronze-trimmed where appropriate, with flanged ends.
3. Swing-Check Valves
Valves shall be of the swing type suitable for the horizontal or vertical operation with a two-piece
hinge and accessible disc cover.
(a) Valves of sizes up to 50 mm (2 inches) in diameter shall be bronze where appropriate, with
threaded ends and full area Y pattern bodies.
(b) Valves of sizes 65 mm (2 inches) in diameter and larger shall be cast-iron, swing pattern
and bronze-trimmed where appropriate, with flanged ends.
4. Silent-Check Valves
Silent-check valves shall be installed at the location where noise and water hammer would cause a
problem, normally installed at the discharge of the pump. The valve shall be of a spring closed type.
(a) Valve of sizes up to 50 mm (2 inches) in diameter shall be bronze with threaded ends.
(b) Valve of sizes 65 mm (2 inches) in diameter and larger shall be cast-iron where
appropriated, with flanged connection.
Wafer-type check valve shall be of the dual discs, or dual plates, wafer style with torsion spring
induced closure.
Valve of size 50 mm (2 inches) in diameter and larger shall be cast-iron with flanged connection.
PERFORMANCE SPECIFICATION
D - 76
6. Modulating Check Valves
Modulating check valves shall be installed at the discharge side of all water supply pumps (both cold
water and hot water pumps), and shall contain auxiliary controls which permit adjustment of the
opening and closing speed. The valves shall be of the modulating diaphragm type.
(a) Valves of sizes up to 50 mm (2 inches) in diameter shall be bronze with threaded ends.
(b) Valves of sizes 65 mm (2 inches) in diameter and larger shall be cast-iron with flanged
ends.
7. Balancing Valves
Balancing valves shall be plug pattern of the square head type. Those smaller than 65 mm (2
inches) in diameter shall be all bronze, brass, with threaded ends and those 65 mm (2 inches) in
diameter and larger shall have iron bronze or brass plugs with cast-iron body where appropriate and
flanged ends.
8. Butterfly Valves
A butterfly valve can be used instead of a gate valve if its size is over 100 mm (4 inches) in diameter it
shall have flange bolt centering holes for easy installation and be drilled to suit precisely the piping
flange. The body shall be cast-iron with aluminum-bronze disc where appropriate of sufficient rigidity
and strength to resist distortion. The stem shall be through-shaft design to provide high strength and
positive disc control.
9. Ball Valves
Valves shall be ball pattern of the square head type with stainless steel ball conforming to AISI 304.
Valves of sizes up to 50 mm (2 inches) in diameter shall be bronze with threaded ends conforming to
ASTM B62 and for valves of sizes larger than 50 mm (2 inches) in diameter.
Float valves shall be hydraulically operated, diaphragm-actuated globe or angle pattern valve.
Operation of the main valve shall be controlled by a two-level remote float control. The body shall be
cast-iron with flanged ends and shall have a pressure rating of 1,206 kPa (175 psi) class 125. A
stilling well must be provided around the float to protect against water surface turbulence.
Pressure regulating valve shall be automatically reduces a higher inlet pressure to a steady lower
downstream pressure regardless of changing flow rate and/or varying inlet pressure. This valve is an
PERFORMANCE SPECIFICATION
D - 77
accurate pilot-operated regulator, capable of holding downstream pressure to a pre-determined
delivery pressure. The body of main valve shall be cast-iron with screwed or flanged ends.
Solenoid valves shall be of normally closed types, remaining in closed position when the coil is de-
energized, and shall be of stainless steel construction.
Foot valve shall be installed at the end pipe of pump suction, where the pump installed above the
water level, which foot valve can protect the water back flow to the tank and keep the water full in the
suction line of the pump. The disc of the foot valve shall be closed completely to the seat by the
spring closed type.
The casing, guide, and the seat shall be cast-iron. The spring shall be stainless steel and the seal
shall be nitrile.
The foot valve shall be co-operated with plate strainer, which plate strainer made of galvanized steel.
PERFORMANCE SPECIFICATION
D - 78
CHAPTER 11 PIPES AND FITTINGS MATERIAL
Cold water pipe of size up to 100 mm (4 inches) in diameter and smaller shall be galvanized steel
pipes, medium weight, conforming to TISI 277-2532 or BS 1387.
Fittings for galvanized steel pipes of size 100 mm (4 inches) in diameter and smaller shall be
galvanized malleable cast-iron, conforming to ASTM A 120-73 or TISI 249-2520 with screw joints.
Cold water and soft water pipes of greater than 100 mm (4 inches) in diameter shall be ERW
galvanized steel pipes, conforming to ASTM A-53, grade A, schedule 40.
Fitting for galvanized steel pipe of size greater than 100 mm (4 inches) in diameter shall be of wrought
carbon and alloy steel with hot-dip galvanized, conforming to ASTM A 234 and galvanized steel flange
joints or welded joint.
Exposed cold water pipe running on roof floor of the building shall be insulated with closed cell foam
plastic insulation of 25 mm (1 inch) thickness and covered with aluminum jacket of 0.6 mm thick.
All hot water pipes of nominal size 76 mm (3 inches) in diameter and smaller shall be of the hard
drawn copper tube type L, conforming to ASTM B-88 or BS 2871.
Copper tube fitting of nominal size 76 mm (3 inches) in diameter and smaller shall be wrought copper
welded fitting (solder type) or solder to thread and shall be rated at 10 kg/cm (150 psig).
All hot water pipes of nominal size greater than 76 mm (3 inches) in diameter shall be seamless
galvanized steel pipes, conforming to ASTM A-53, grade A, schedule 40.
Fitting for hot water pipe of nominal size greater than 76 mm (3 inches) in diameter shall be of
wrought carbon and alloy steel with hot-dip galvanized, conforming to ASTM A234 and galvanized
flange joint or welded joint.
The insulation shall be preformed fibreglass density of 56 kg/m (3.5 lbs/ft) with fire resistant type
aluminum foil covering and the following thickness:-
Up to 40 mm (1 inches) 25 mm (1 inch)
50 mm (2 inches) and over 40 mm (1 inches)
PERFORMANCE SPECIFICATION
D - 79
Insulation for hot water pipe embedded inside the wall shall be closed cell foamed plastic of 10 mm
(3/8 inches) thick.
Exposed hot water pipe running on roof of building shall be insulated with closed cell foamed plastic
insulation of 40 mm (1 inches) thick.
Aluminum sheet of 0.6 mm thickness shall be cover on all exposed hot water pipes.
Soil, waste and drain water pipes of size 40 mm (1 inches) in diameter and smaller shall be
galvanized steel pipes, medium-weight, conforming to TISI 277-2532 or BS 1387.
Fittings for galvanized steel pipes shall be galvanized malleable cast-iron conforming to ASTM A 120-
73 or TISI 249-2520 with screw joints.
Pipes size 50 mm (2 inches) in diameter and larger unless otherwise specified on the drawing shall be
hub and spigot extra heavy, grade cast-iron, conforming to ASTM A 74-75 with coal tarred or asphaltic
or bitumen internally and externally.
Fitting for cast-iron pipes shall be cast-iron wastewater and drain pipe fitting, conforming to ASTM A
74-75.
Main soil and wastewater pipes and fittings shall be extra heavy grade cast-iron pipe with flanged joint
and conforming to ISO R 13, class B.
Soil, waste and drain water pipes of size 40 mm (1 inches) in diameter and smaller shall be
galvanized steel pipes, medium weight, conforming to TISI 277-2532 or BS 1387.
Fitting for galvanized steel pipes of size 40 mm (1 inches) in diameter and smaller shall be
galvanized malleable cast-iron, conforming to ASTM A 120-73 or TISI 249-2520 with screw joints.
Soil, waste and drain water pipes of size 50 mm (2 inches) in diameter and larger shall be hubless
cast-iron pipes, heavy grade, conforming to TISI 533-2527.
Fitting for soil, waste and drain water pipes of size 50 mm (2 inches) in diameter and larger shall be
hubless cast-iron, heavy grade, conforming to TISI 533-2527. Rubber sleeve shall be neoprene or
other approved synthetic rubber, natural rubber is not acceptable.
Shafts, washers, nuts, screws and collar or coupling shall be made of stainless steel grade 304.
PERFORMANCE SPECIFICATION
D - 80
5. Soil, Waste, Drain and Vent Pipe (PVC)
Soil, waste, drain and vent pipes shall be polyvinyl chloride pipe (PVC), conforming to TISI 17-2532
class 13.5.
Fittings for use with PVC shall be injection molded suitable for PVC pipe of the type and material
corresponding to the application and to the material of the pipe.
The threaded end of PVC fittings shall be jointed with PTFE (teflon) tape only.
Fittings for polyvinyl chloride pipes shall be rigid, unplasticized polyvinyl chloride (PVC) as designated
in ASTM D 2241, ASTM D 1785, schedule 40 with solvent cement joint.
6. Vent Pipes
Vent pipes shall be polyvinyl chloride pipe (PVC), conforming to TISI 17-2532 class 13.5
Fittings for use with PVC shall be injection molded suitable for PVC pipe of the type and material
corresponding to the application and to the material of the pipe.
The threaded end of PVC fittings shall be jointed with PTFE (teflon) tape only.
Fittings for polyvinyl chloride pipes shall be rigid, unplasticized polyvinyl chloride (PVC) as designated
in ASTM D 2241, ASTM D 1785, schedule 40 with solvent cement joint.
Drain pipe from AHU room of air-conditioning system shall be polyvinyl chloride pipe (PVC),
conforming to TISI 17-2532 class 13.5. Horizontal drain pipe shall be insulated with closed cell foam
insulation of inch thickness and wrapped with PVC tape for exposed pipe only, vertical drain pipe
can be uninsulated.
Fitting for use with PVC shall be injection molded suitable for PVC pipe of the type and material
corresponding to the application and to the material of the pipe.
The threaded end of PVC fittings shall be jointed with PTFE (teflon) tape only.
Fittings for polyvinyl chloride pipes shall be rigid, unplasticized polyvinyl chloride (PVC) as designated
in ASTM D 2241, ASTM D 1785, schedule 40 with solvent cement joint.
PERFORMANCE SPECIFICATION
D - 81
8. Flush Water Pipes
Flush water pipes shall be galvanized steel pipes, medium weight, conforming to TISI 277-2532.
Fittings for galvanized steel pipes shall be galvanized malleable cast-iron, conforming to ASTM A 120-
73 or TISI 249-2520.
9. Irrigation Pipes
Irrigation pipes shall be high density polyethylene pipe (HDPE), conforming to DIN 8074, 8075, class
PN 6.
Fittings for pipes size 40 mm (1 inches) in diameter and smaller shall be compression joints fitting.
Fittings for pipes size larger than 40 mm (1 inches) shall be fabricated fitting with butt-welding joints.
Rain water pipes inside building of size 100 mm (4 inches) in diameter and smaller shall be
galvanized steel pipes, medium weight, conforming to TISI 277-2532 or BS 1387.
Fittings for galvanized steel pipes of size 100 mm (4 inches) in diameter and smaller shall be
galvanized malleable cast-iron, conforming to ASTM A 120-73 or TISI 249-2520 with screw joints.
Rain water pipes of greater than 100 mm (4 inches) in diameter shall be ERW galvanized steel pipes,
conforming to ASTM A 53, grade A, schedule 40.
Fitting for galvanized steel pipe of size greater than 100 mm (4 inches) in diameter shall be of wrought
carbon and alloy steel with hot-dip galvanized conforming to ASTM A 234 and galvanized steel flange
joint or welded joint.
All swimming pool pipes shall be polyvinyl chloride pipe (PVC), conforming to TISI 17-2532 class 13.5
Fittings for polyvinyl chloride pipes shall be rigid, unplasticized polyvinyl chloride (PVC) as designated
in ASTM D 2241, ASTM D 1785, schedule 40 with solvent cement joint.
Drinking water pipe shall be stainless steel AISI 304 and ASTM A 269, schedule 20 all fittings shall
also be stainless steel.
PERFORMANCE SPECIFICATION
D - 82
13. Gas Pipes
Gas pipe shall be black steel pipe, schedule 80, seamless conforming to ASTM A-53, grade A,
welded joints shall be of fusion-welded conforming to ASTM-234.
Sewerage pipes installed outside building and connected between sewer manhole shall be high
density polyethylene pipe (HDPE), conforming to DIN 8074, 8075, class PN 4.
Drainage pipes installed outside building and connected between drainage manhole of size smaller
than 300 mm (12 inches) in diameter shall be asbestos cement pipe, conforming to TISI 622-2529,
class SDP 2.
Drainage pipes of size 300 mm (12 inches) in diameter and greater shall be reinforced concrete pipes,
conforming to TISI 128-2523, class 2.
PERFORMANCE SPECIFICATION
D - 83
CHAPTER 12 PIPING INSTALLATION
1. Location of Device
All valves, cleanouts, equipment, accessories, and devices shall be so located that they are
accessible for repair and replacement.
All pipes shall be securely supported. Horizontal piping shall be supported by adjustable clevis type
hangers with solid rods securely attached to the building structure. Where several pipes run in a
parallel fashion, trapeze hangers may be used in lieu of separate hangers.
Maximum Interval
Nominal Pipe Size Hanger Rod (m)
(mm) Min. Size
(mm) Steel Pipe PVC Pipe Copper Pipe
Horiz. Vert. Horiz. Vert. Horiz. Vert.
15 9 2.0 2.4 0.9 1.2 1.5 1.8
20 9 2.4 3.0 1.0 1.2 1.8 2.4
25 9 2.4 3.0 1.0 1.2 1.8 2.4
32 9 2.4 3.0 1.2 1.8 2.0 3.0
40 9 3.0 3.6 1.3 1.8 2.4 3.0
50 9 3.0 3.6 1.5 1.8 2.4 3.6
65 12 3.0 4.5 1.8 2.4 3.0 3.6
80 12 3.6 4.5 2.0 2.4 3.0 3.6
100 15 4.0 4.5 2.4 2.4 3.6 3.6
125 15 4.8 4.5 2.4 3.0
150 22 4.8 4.5 2.4 3.0
200 22 6.0 4.8 3.0 3.6
250 22 6.0 4.8
300 22 6.0 4.8
Cast-Iron Pipe
Horizontal maximum shall be 3.00 m (10 ft), with at least one hanger for each pipe section. Hangers
should be located adjacent to joints, changes in direction and branch connection.
Vertical support shall be provided at the base and at each story height.
PERFORMANCE SPECIFICATION
D - 84
3. Underground Pipes
All steel pipes to be buried underground shall be externally coated in the mill of the fabricator.
Material shall conform to AWWA C 214 - Tape coating system for the exterior of steel water pipelines,
Section 4 and AWWA C 209 - Cold applied tape coating for the exterior of special sections,
connections and fittings for steel water pipelines, section 2. Application, testing and inspection shall
be in accordance with AWWA C 214 and AWWA C 209.
Underground pipe supports attached to the building structure shall be made of stainless steel.
PERFORMANCE SPECIFICATION
D - 85
FIRE AND LIFE SAFETY SYSTEM
PERFORMANCE SPECIFICATION
D - 86
INTRODUCTION
The entire system shall be manufactured, installed, tested and balanced conforming to the latest issue
of the following standards:
PERFORMANCE SPECIFICATION
D - 87
CHAPTER 1 FIRE PUMP (DIESEL ENGINE DRIVE)
1. General
Pumps shall be designed and installed in accordance with the latest NFPA 20 "Standard for the
Installation of Centrifugal Fire Pumps". Each unit shall be tested and approved by UL and/or FM.
2. Type
Pumps shall be of the non-overloading, centrifugal, volute type. They shall be of the horizontally split,
double suction type with suction and discharge connections in the lower half of the casing, allowing
removal of the rotating element without disturbing pipe connections and operating at not over 3,000
rpm.
3. Casing
Casing of horizontally split pumps shall be capable of withstanding a hydrostatic test pressure of 20
kg/cm (300 psig) or 150% of rated operating pressure (rated head), whichever is greater.
Casing material shall be cast-iron, precision- manufactured for best performance and long-term duty.
4. Wearing Ring
Wearing rings shall be suitable for an individual application. Rings shall be replaceable, and positively
keyed to prevent rotation.
5. Impeller
Impellers shall be one-piece, cast-bronze SAE 40 and dynamically balanced. Impellers of pumps
shall be fully enclosed and hydraulically balanced.
6. Shaft
Shafts for pumps with stuffing boxes shall be of stainless steel, chrome-iron or nickel-iron extending
through the stuffing boxes.
7. Bearing
Bearings shall be heavy-duty ball bearings with a minimum average life of 100,000 hours. The
bearing shall be self-sealed, and housed in malleable-iron housings aligned to a bearing bracket by
means of large precision registers.
8. Relief Valve
Each pump except engine-driven pump shall be provided with a 20 mm ( inch) in diameter
circulation relief valve for pump overheat protection
PERFORMANCE SPECIFICATION
D - 88
9. Pressure Switch
Switches shall be used for pump control and shall be able to withstand 28 kg/cm (400 psig) working
pressure without any damage.
10. Anti-Vibration
Each pump shall be mounted on approved vibration isolators which are, In turn, placed on a concrete
base.
The engine brake horse power shall be rated at least 1.10 times the maximum power required. The
engine shall be of a reputable manufacturer from which spare parts can be obtained easily.
12. Governor
The engine shall be provided with an adjustable governor capable of regulating engine speed within a
range of 10 percent between shut-off and maximum load conditions of the pump.
The device shall be arranged such that the engine is shut-down at a speed approximately 20 percent
above the rated engine speed, and that it can be manually reset.
The position of the overspeed shut-down device shall be indicated at the controller and will continue
to show an overspeed trouble signal until the device is manually reset to normal operating position.
14. Tachometer
A tachometer shall be provided to indicate revolutions per minute of the engine. An hour meter shall
be provided to record total time of engine operation.
The engine shall be provided with oil pressure gauges indicating lubricating oil pressure.
The engine shall be provided with a temperature gauge to indicate cooling water temperature.
The engine shall be provided with two maintenance free storage battery units, each having sufficient
capacity, at 5C (41F) to maintain cranking speed recommended by the engine manufacturer through
a 6-minute cycle (15-second cranking and 15-second rest, in 12 consecutive cycles).
PERFORMANCE SPECIFICATION
D - 89
Two means for recharging shall be provided. One shall be the generator furnished with the engine.
The other shall be an automatically controlled charger taking power from the building power supply.
The exhaust pipe shall be galvanized steel sized in accordance with the manufacturer's
recommendations. The exhaust pipe shall be insulated with 40 mm (1 inches) thick calcium silicate
and 0.6 mm (0.024 inch) thick aluminum jacket.
Stainless steel flexible connection shall be made between the engine exhaust outlet and the exhaust
pipe.
The tank shall be fabricated from at least 3 mm thick steel sheet, rigid frame shall be steel angle and
the tank's support legs shall be fabricated from suitable steel pipe Fuel tank shall have a capacity of at
least equal to 1 gallon per horsepower (5.07 l/kw) plus 5 percent volume for expansion and 5 percent
volume for sump.
Fuel tank should be located preferably inside the pump room or pump house, if permitted by local
regulations.
21. Controller
The controller shall be UL listed or FM approved, completely assembled and wired from the factory.
PERFORMANCE SPECIFICATION
D - 90
CHAPTER 2 FIRE PUMP (ELECTRIC MOTOR DRIVE)
1. General
Pumps shall be designed and installed in accordance with the latest NFPA 20 "Standard for the
Installation of Centrifugal Fire Pumps". Each unit shall be UL listed and/or FM approved.
2. Type
Pumps shall be of the non-overloading, centrifugal, volute type. They shall be of the horizontally split,
double suction type with suction and discharge connections in the lower half of the casing, allowing
removal of the rotating element without disturbing pipe connections and operating at not over 3,000
rpm.
Pumps shall be selected for a total efficiency of not less than 65 per cent.
3. Motor
Each pump shall be driven not over 3,000 rpm, totally enclosed fan-cooled Class F insulation motor.
The rated HP shall be at least 1.15 times the maximum power required.
4. Casing
Casing of horizontally split pumps shall be capable of withstanding a hydrostatic test pressure of 20
kg/cm (300 psig) or 150% of rated operating pressure (rated head), whichever is greater.
Casing material shall be cast-iron, precision- manufactured for best performance and long-term duty.
5. Wearing Ring
Wearing rings shall be suitable for an individual application. Rings shall be replaceable, and positively
keyed to prevent rotation.
6. Impeller
Impellers shall be one-piece, cast-bronze SAE 40 and dynamically balanced. Impellers of pumps
shall be fully enclosed and hydraulically balanced.
7. Shaft
Shafts for pumps with stuffing boxes shall be of stainless steel, chrome-iron or nickel-iron extending
through the stuffing boxes.
PERFORMANCE SPECIFICATION
D - 91
8. Bearing
Bearings shall be heavy-duty ball bearings with a minimum average life of 100,000 hours. The
bearing shall be self-sealed, and housed in malleable-iron housings aligned to a bearing bracket by
means of large precision registers.
9. Relief Valve
Each pump except engine-driven pump shall be provided with a 20 mm ( inch) in diameter
circulation relief valve for pump overheat protection
Switches shall be used for pump control and shall be able to withstand 28 kg/cm (400 psig) working
pressure without any damage.
11. Anti-Vibration
Each pump shall be mounted on approved vibration isolators which are, In turn, placed on a concrete
base.
12. Controller
The controller shall be UL listed or FM approved, completely assembled and wired from the factory.
PERFORMANCE SPECIFICATION
D - 92
CHAPTER 3 JOCKEY PUMPS (PRESSURE MAINTENANCE PUMP)
1. Type
Pumps shall be regenerative turbine pumps with suction arrangement suitable for suction of water from
the water reservoir.
2. Motor
Each pump shall be driven not over 3,000 rpm totally enclosed fan-cooled Class F insulation motor.
The rated HP shall be at least 1.15 times the maximum power required.
3. Casing
Casing of jockey pump shall be designed for a working pressure of 20 kg/cm (300 psig) or 1.5 times
the actual discharge pressure, whichever is greater.
Casing material shall be cast-iron, precision- manufactured for best performance and long-term duty.
4. Wearing Ring
Wearing rings shall be suitable for an individual application. Rings shall be replaceable, and positively
keyed to prevent rotation.
5. Impeller
Impellers shall be one-piece, cast-bronze SAE 40 and dynamically balanced. Impellers of pumps
shall be fully enclosed and hydraulically balanced
6. Shaft
Shafts for pumps with stuffing boxes shall be of stainless steel, chrome-iron or nickel-iron extending
through the stuffing boxes.
7. Bearing
Bearings shall be heavy-duty ball bearings with a minimum average life of 100,000 hours. The
bearing shall be self-sealed, and housed in malleable-iron housings aligned to a bearing bracket by
means of large precision registers.
Each pump shall be provided with a 20 mm ( inch) in diameter circulation valve for pump overheat
protection.
PERFORMANCE SPECIFICATION
D - 93
9. Pressure Switch
Switches shall be used for pump control and shall be able to withstand 28 kg/cm (400 psig) working
pressure without any damage.
10. Anti-Vibration
Each pump shall be mounted on approved vibration isolators which are, in turn, placed on a concrete
base.
11. Controller
The controller shall be UL listed or FM approved, completely assembled and wired from the factory.
PERFORMANCE SPECIFICATION
D - 94
CHAPTER 4 FIRE PROTECTION EQUIPMENT
1. General
The fire protection equipment as described in this section shall be either listed by Underwriters'
Laboratories (UL) or approved by Factory Mutual (FM) except instantaneous fire hose couplings, fire
hosereels and nozzles which shall conform to BS standard.
Fire hose cabinets shall be fabricated from steel sheet of at least 1.2 mm. The cabinets shall be
suitable for accommodating the fire fighting equipment as specified on the drawing and shall be
complete with internal hinges, door locks and letter signs. The door can be open to 180
3. Fire Hose
Fire hoses shall be single jacket lined which consist of a synthetic rubber liner, woven jacket and
treated to abrasion resistant, mildew proof.
Fire hoses for fire hydrant or outdoor used shall be entrusion covered of synthetic red rubber for
highly ozone resistant.
The fire hoses shall be hydrostatically tested to 34.5 bar (500 psi). The hoses shall have DN 40 and
DN 65 in sizes with 30 m (100 ft) in length, completed with light weight fire fittings.
CO2 portable fire extinguishers shall be constructed according to the Department of Transportation
(DOT) specifications for pressure vessels containing carbon dioxide and designed for 124 bar or
higher pressure. Each unit shall have CO2 capacity of 4.5 kg and at least UL rating 10 B:C.
The extinguishers shall be ABC multi-purpose dry chemical fire extinguishers with 4.5 kg capacity.
The body shall be constructed of low carbon steel, coated with primer and finished with stove baked
enamel red paint.
The units shall be in accordance with TIS 332-2531 or have at least UL rating 4A : 60BC.
The fire hydrant outlet shall be cast brass body with two-way male instantaneous outlet connections,
including caps and chains. The unit shall be either free standing or wall mounted approximately 0.70
m high.
PERFORMANCE SPECIFICATION
D - 95
7. Upright Sprinkler Head
(a) Applicable for storage areas, machine room warehouse, and as specified.
(b) Frangible bulb type.
(c) Upright style.
(d) 13 mm ( inch) in diameter nominal orifice.
(e) Chrome finish.
(f) Temperature rating as specified on drawings.
Ceiling sprinkler heads shall be of the recessed type with an outstanding architectural appearance.
They shall have the following features:-
(a) Applicable for guest room area in the where ceiling sprinkler cannot be used.
(b) Flangible bulb type.
(c) 14 mm (17/32 inch) in diameter nominal orifice.
(d) Chrome finished.
(e) Temperature rating as specified on drawings.
(f) Water distribution at pressure 2.1 kg/cm (30 psi) not less than 6 m (20 ft) length and 4.5 m
(15 ft) width.
PERFORMANCE SPECIFICATION
D - 96
CHAPTER 5 FIRE PROTECTION PIPES
All fire protection pipes and fittings installed above ground level or installed inside the building shall be
black steel pipes, seamless schedule 40, conforming to ASTM A53, grade B.
All fire protection pipes and fitting to be buried underground shall be black steel pipes, seamless
schedule 40, conforming to ASTM A53, grade B and stall be externally coated in the mill of the
fabricator
3. Drain Pipes
Drain pipes shall be galvanized steel pipe class medium conforming to TIS 277-2532 or BS 1387.
PERFORMANCE SPECIFICATION
D - 97
CHAPTER 6 PIPING INSTALLATION
All pipes shall be securely supported. Horizontal piping shall be supported by adjustable clevis type
hangers with solid rods securely attached to the building structure. Where several pipes run in a
parallel fashion, trapeze hangers may be used in lieu of separate hangers. The maximum distances
between hangers and supports for horizontally mounted and vertically mounted pipes shall be as
indicated below.
Maximum Interval
Nominal Pipe Size Hanger Rod (m)
(mm) Min. Size
(mm) Steel Pipe PVC Pipe Copper Pipe
Horiz. Vert. Horiz. Vert. Horiz. Vert.
15 9 2.0 2.4 0.9 1.2 1.5 1.8
20 9 2.4 3.0 1.0 1.2 1.8 2.4
25 9 2.4 3.0 1.0 1.2 1.8 2.4
32 9 2.4 3.0 1.2 1.8 2.0 3.0
40 9 3.0 3.6 1.3 1.8 2.4 3.0
50 9 3.0 3.6 1.5 1.8 2.4 3.6
65 12 3.0 4.5 1.8 2.4 3.0 3.6
80 12 3.6 4.5 2.0 2.4 3.0 3.6
100 15 4.0 4.5 2.4 2.4 3.6 3.6
125 15 4.8 4.5 2.4 3.0
150 22 4.8 4.5 2.4 3.0
200 22 6.0 4.8 3.0 3.6
250 22 6.0 4.8
300 22 6.0 4.8
PERFORMANCE SPECIFICATION
D - 98
CHAPTER 7 FIRE MONITORING AND ALARM SYSTEMS
1. System Requirements
The fire monitoring and alarm system shall include all central control console, remote terminal units
(remote control units), local and remote annunciators, manual stations, smoke detectors, heat
detectors, alarm bells or horns, and all other equipment necessary for a complete installation and
operation of the system.
The system shall use supervised multiplex data communications circuits, closed loop initiation circuits,
individual zone supervision, and individual audio and/or visual signal circuit supervision.
The system wiring shall use digital, full duplex multiplex communication techniques over all
communication network and multi-addressable peripherals network.
All interior wiring shall be in strict accordance with NFPA, codes 70, 72 and MEA regulations. All fire
monitors and alarm equipment shall be UL listed and Factory Mutual approved or equal.
The Central Control Console (CCC) for fire monitoring and alarm system shall be complete with all
control modules, control switches, annunciators and others for a complete system operation and as
specified herein.
The Central Processing Unit (CPU) shall communicate with the monitor, and shall control all other
modules in the panel. Removal, disconnection or failure of any control panel modules shall be
detected and reported by the Central Processing Unit.
The Central Processing Unit (CPU) shall contain and execute all control-by-event programs for
specific action to be taken if a fire situation is detected in the system.
Such control-by-event programs shall be held in non-volatile programmable memory, and shall not be
lost even if the primary and secondary power failures of the system occur.
The Central Processing Unit (CPU) shall also provide a real-time clock to execute custom time control
programs except in fire situations.
The loop interface module shall be provided to monitor and control each loop of the addressable
peripheral devices. This module shall communicate and provide power to all devices on its loop over
a single pair of wires.
The display interface modules shall be provided for all controls and indicators.
PERFORMANCE SPECIFICATION
D - 99
The printer shall provide hard-copy printout of all changes in status of the system and shall time-
stamp such printouts with the current time- of-day and date. The printer shall be wide carriage with
80-characters per line and shall use standard pin-feed paper. The printer shall be enclosed in a
separate cabinet suitable for placement on a desk top or table. The printer shall communicate with
the control panel using a fully supervised interface device complying with Electric Industries
Association standard RS 232.
The enunciator panel shall provide visual display of alarm/normal status for the specified zones of the
system.
The power supply for the panel and all fire monitor and alarm peripherals shall be integral to the
control panel. The power supply shall provide all control panel and peripheral power needs. The
audio-visual power may be increased as needed by adding additional modular expansion power
supplies. All power supplies shall be designed to meet UL and NFPA requirements for power-limit
operation on all external signaling lines, including initiating circuits and indicating circuits.
Fuses, circuit breakers, or other overcurrent protection shall be provided on all power outputs.
Input power shall be 220 VAC, 50 Hz. The power supply shall provide internal batteries and charger.
The battery shall be of nickel-cadmium or maintenance free type with a capacity of not less than 4
hours for full system operation.
4.1 When fire condition is detected by one of the system initiating devices, the following functions
shall immediately occur:-
4.2 When a trouble condition is detected by one of the system initiating devices, the following
functions shall immediately occur:-
PERFORMANCE SPECIFICATION
D - 100
shall have priority over trouble messages and if such an alarm must also be
displayed, the trouble message will not be displayed on the LCD.
(d) The appropriate message shall be sent to CRT(s) (if required) and printer(s).
(e) The system trouble indicator on remote annunciators shall be illuminated.
4.3 Activation of the acknowledge switch of the control panel shall silence the panel sounding
device and change the "System Alarm" or "Trouble LED" from flashing to a steady "ON"
condition. In case additional new alarm or trouble conditions exist in the system, activation of
this switch shall advance the display to the next alarm or trouble condition that exists, and
shall not silence the local audible device or change the flashing LED to steady "ON" until all
new conditions have been so acknowledged. New alarm conditions shall always be displayed
before new trouble conditions. Activation of the acknowledge switch shall also cause a
corresponding message to be displayed on CRT system and printers. Occurrence of a new
alarm or trouble condition shall cause the panel to "Resound" and the sequences described in
4.1 and 4.2 shall repeat.
Activation of the "Signal Silence Switch" shall cause all appropriate indicating appliances and
relays to return to the normal condition after an alarm condition.
The selection of indicating circuits and relays silenced by this switch shall be fully
programmable and changeable in the field.
Activation of the "System Switch" shall cause all electronically-latched initiating devices or
zones, as well as all associated output devices and circuits, to return to the normal state. If
alarm conditions still exist in the system after the "System Reset Switch" activation, the
system shall then resound the alarm conditions as indicated in paragraph 4.1.
Activation of the "Test Switch" of the system shall initiate an automatic test of all intelligent
detectors in the system. Such test shall activate the electronics in each intelligent device,
simulating an alarm condition. A report summarizing the results of this test shall be displayed
automatically on the front panel, as well as on any CRT or printers of the system.
Activation of the "Lamp Test Switch" shall turn "ON" all LED indicators, LCD display and local
sounder and then return to the previous condition.
5. Field Programming
The system shall be fully programmable, configurable, and expandable in the field without the need of
special tools or PROM programmers and shall not require replacement of IC memory. All
programming may be accomplished through the standard control panel keyboard or CRT. All
programs shall be stored in non-volatile memory.
The programming function shall be entered with a special password that may be selected when the
system is installed. The password may be changed in the field to a new value at any time by entering
the old password and requesting a password change. In the event that the programmer may enter a
PERFORMANCE SPECIFICATION
D - 101
password and then lose or forget it, the system shall be designed such that the password may be
determined by special procedures available from the manufacturer of the system.
A separate password shall be used for changes in system status (e.g. turning a control point ON or
OFF). Including the door key, the system therefore provides 3 levels or security.
The monitor module shall be used in connecting a supervised zone of the conventional initiating
devices (any normally open (n.o.) dry contact device, including 4-wire smoke detectors) to the
communication loop. The monitor module shall be mounted in a square electrical box. The zone
wiring to be used shall be either class A or class B.
The monitor module shall provide address-setting means using rotary decimal switches and shall also
store an internal identifying code which the control panel shall use to identify the type of device. An
LED shall be provided which shall flash under normal conditions, indicating that the monitor module is
operational and in regular communication with the control panel.
The control module shall be used in connecting a supervised zone of conventional indicating devices
(any 24V polarized audio/visual indicating appliance) to the communication loop. The control module
shall be mounted in a standard square electrical box. The zone wiring to be used shall be either class
A or class B. The control module may also be wired as dry contact relay. Power for the relay
actuation shall be provided by the detector loop to reduce wiring connection requirements.
Audio/visual power shall be provided by a separate loop from the main control panel or from the
supervised remote power suppliers.
The control module shall provide address-setting means, and shall also store an internal identifying
code which the control panel shall use to identify the type of device. An LED shall be provided which
shall flash under normal conditions, indicating that the control module is operational and in regular
communication with the control panel.
The ionization detectors shall be connected with two wires to one of the control panel loops. The
detectors shall use the dual-chamber ionization principle to measure the products of combustion and
shall, on command from the control panel, send data to the panel representing the analog level of the
products of combustion. The detectors shall be ceiling-mounted and shall include a twist-lock base.
The detectors shall provide address-setting means on the detector head. The detectors shall also
store an internal identifying code which the control panel shall use to identify the type of detector.
The thermal or heat detectors shall be connected with two wires to one of the control panel loops.
The detectors shall use an electronic sensor to measure temperature levels in its chamber and shall,
on command from the control panel, send data to the panel representing the analog temperature
level. The detectors shall be ceiling-mounted and shall include a twist-lock base.
The detectors shall provide address-setting means on the detector head. The detectors shall also
store an internal identifying code which the control panel shall be used to identify the type of detector.
PERFORMANCE SPECIFICATION
D - 102
7. Conventional Peripheral Devices
The smoke detector shall be of the dual chamber ionization type. One chamber shall be isolated from
the products of combustion and, shall monitor internal sensitivity, and the other chamber shall
measure the level of the combustion products. Both chambers shall be ionized by a single americium
241 radioactive source of not more than 1.0 microcurie. The detector head shall have a stainless
steel screen to prevent foreign objects from entering the dual chamber. Each detector shall have a
flashing status indicating LED for visual supervision. The detector shall be operable in a temperature
range of -18C to 38C (0F to 100F) with a maximum air flow of 320 meters (1,050 feet) per minute.
The thermal fire detector or heat detector shall be of dual thermal element using two distinct and
independent methods of heat detection. The detectors shall operate on the combination of "Rate-of-
Rise" and "Fixed Temperature" principles. The rate-of-rise method shall detect fires when the rate of
heat rises, exceeding 9C (15F) per minute. The fixed temperature method shall detect fires that
build temperature to a high level at a slow rate, by responding to a temperature setting at 57C
(135F) or 93C (200F) as specified on the drawings.
The manual pull station shall be single action, non-coded, pull lever type for pre-signal/general alarm
requirement. The station shall be constructed of metal and be of red colour. All glass rods shall be
affixed to the station, and upon actuation, the station shall remain open for easy identification. The
unit shall be suitable for semi-flush mounting on a standard metal box.
The audible alarm device shall consist of alarm bells of the vibrating type with 0.15 m (6 inches) hot-
pressed steel gongs. The shell-finish shall be satin chromium. The bells shall be complete with
stainless steel hexagonal plungers and shall be designed for series operation on a supervised circuit.
The sprinkler waterflow alarm switches shall be provided for wet sprinkler pipe systems and
connected to the fire alarm system such that the activation of the sprinkler system shall sound an
alarm at the center console.
Sprinkler supervisory devices shall be connected to the fire alarm system such that the movement of
a valve from the normal (open) position shall sound a supervisory trouble signal, at the center
console.
All doors for fire stairs shall have magnetic door switches, which shall be connected to the alarm
system. The remote annunciator for these switches shall be provided at the security room.
PERFORMANCE SPECIFICATION
D - 103
E. SYSTEM CRITERIA / DIAGRAMS
PERFORMANCE SPECIFICATION
E-1
PERFORMANCE SPECIFICATION
E-2
PERFORMANCE SPECIFICATION
E-3
PERFORMANCE SPECIFICATION
E-4
PERFORMANCE SPECIFICATION
E-5
TYPE OF LOAD
TOTAL
LOAD
ESSENTIAL NORMAL
LOAD LOAD
UP
S UNINTERRUPTED EMERGENCY
LOAD LOAD
PERFORMANCE SPECIFICATION
E-6
FIRE ALARM SYSTEM
PERFORMANCE SPECIFICATION
E-7
MATV. SYSTEM
PERFORMANCE SPECIFICATION
E-8
PERFORMANCE SPECIFICATION
E-9
BUILDING AUTOMATION SYSTEM
POWER
CCTV STATUS
PERFORMANCE SPECIFICATION
E - 10
PERFORMANCE SPECIFICATION
E - 11
PERFORMANCE SPECIFICATION
E - 12
PERFORMANCE SPECIFICATION
E - 13
PERFORMANCE SPECIFICATION
E - 14
PERFORMANCE SPECIFICATION
E - 15
WHO drinking water standards 1993
PERFORMANCE SPECIFICATION
E - 16
WHO drinking water standards 1993
PERFORMANCE SPECIFICATION
E - 17
Average Illuminance Levels and Lighting Loads
Ballroom 400 40
Exhibition 500 50
Assembly 400 40
Lobby 200 20
Lounge 200 15
Bar 200 20
PERFORMANCE SPECIFICATION
E - 18
Area Minimum Lighting Intensity (LUX) Maximum Watts / SQ m
Stairwells 100 15
Offices 400 15
Valet 500 20
Storage 150 10
Exteriors 65 -
Garage 75 10
PERFORMANCE SPECIFICATION
E - 19
Area Minimum Lighting Intensity (LUX) Maximum Watts / SQ m
Note : Lighting load for decorative areas can be varied to lighting designer design
PERFORMANCE SPECIFICATION
E - 20