Documente Academic
Documente Profesional
Documente Cultură
SEISMIC RESPONSE
Submitted by
Dr. S S GADVE
1 INTRODUCTION 3
2 BACKGROUND 3
3 PROTOTYPE BUILDING 4
4 EFFECT OF TMD 4
5 CONCLUSION 5
6 REFERENCES 6
LIST OF FIGURES
LIST OF TABLES
2
1. INTRODUCTION
Tuned mass dampers (TMD) have been widely used for vibration control in mechanical
engineering systems. The elements in such devices are: mass, spring and dashpot. TMD is
attached to a structure in order to reduce the dynamic response of the structure. The frequency of
the damper is tuned to a particular structural frequency so that when that frequency is excited,
the damper will resonate out of phase with the structural motion. The mass is usually attached to
the building via a spring-dashpot system and energy is dissipated by the dashpot as a relative
motion develops between the mass and the structure.
2. BACKGROUND
The optimum TMD parameters have been given by Den Hartog, Weisner and Wirsching for
different excitation forces. Den Hartog gave the solution for single degree of freedom system
subjected to sinusoidally varying force, Weisner for wind excitation and Wirsching for ground
excitation.
3
3. PROTOTYPE BUILDING
A prototype building with large lateral surface area was chosen. The 25 storey building was
modelled as lumped-mass model with 8 nodes. Gravity loads are resisted by a steel frame, and
all lateral loads are assumed to be resisted by the two reinforced concrete elevator core. The
fundamental period of the building in the N-S direction was calculated to be 3.75 sec. The
damping coefficient was chosen to be 5%.
4. EFFECT OF TMD
The TMD was designed using a mass ratio of 0.65% with effective mass ratio of 0.026. The
optimum TMD parameters for the building as per Den Hartog, Weisner and Wirsching are given
in the table below.
4
Table 1. - Optimum TMD Constants
The prototype building was subjected to the first 30 sec of the N-S component of El Centro 1940
with and without a TMD. Figure 4 compares the linear elastic tip displacement response with
and without an optimum Den Hartog TMD. This figure shows the TMD to have no much effect
on the building's maximum response.
5. CONCLUSION
Results show that TMD is not much effective in reducing the maximum response of tall
buildings under seismic excitation.
5
6. REFERENCES