Designation: E564 06

Standard Practice for


Static Load Test for Shear Resistance of Framed Walls for
Buildings1
This standard is issued under the fixed designation E564; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon () indicates an editorial change since the last revision or reapproval.

1. Scope 2. Referenced Documents


1.1 This practice describes methods for evaluating the shear 2.1 ASTM Standards:2
capacity of a typical section of a framed wall, supported on a E4 Practices for Force Verification of Testing Machines
rigid foundation and having load applied in the plane of the E575 Practice for Reporting Data from Structural Tests of
wall along the edge opposite the rigid support and in a direction Building Constructions, Elements, Connections, and As-
parallel to it. The objective is to provide a determination of the semblies
shear stiffness and strength of any structural light-frame wall E631 Terminology of Building Constructions
configuration to be used as a shear-wall on a rigid support.
1.2 LimitationsThis practice is not intended to be used as 3. Terminology
a basis for classifying sheathing shear capacity or as an 3.1 For definitions of terms used in this standard, see
evaluation of combined flexure and shear resulting from the Terminology E631
wall being loaded on a flexible foundation. 3.2 Definitions of Terms Specific to This Standard: Defini-
1.2.1 The effect of sheathing variations is assessed by tions:
holding all other variables constant. Permitted variations in 3.2.1 rackingwhen applied to shear walls, refers to the
framing configuration and boundary conditions, however, re- tendency for a wall frame to distort from rectangular to
quire accurate documentation of the test setup to validate rhomboid under the action of an in-plane force applied parallel
across-study comparisons of sheathing contribution to wall to the wall length.
shear capacity. 3.2.2 shear wallstructural subassembly that acts as a
cantilever/diaphragm to transfer horizontal building loads to
NOTE 1A wall tested on a flexible foundation is evaluated by
comparing shear stiffness and strength results to those of an identical wall the foundation in the form of horizontal shear and an overturn-
tested on a rigid foundation, following this practice. However, no methods ing moment.
are given for the measurement of wall bending displacements or assess- 3.2.3 upliftthe vertical displacement measured at the
ment of stress distribution resulting from foundation flexure. Any extrapo- loaded end stud with respect to the test apparatus.
lation of wall racking behavior from the foundation conditions specified 3.3 Symbols:
by this practice to flexible conditions shall be done with the support of a 3.3.1 aheight of cantilevered shear wall, in metres (feet).
comparative test on a representative foundation.
3.3.2 blength of cantilevered shear wall, in metres (feet).
1.3 This standard does not purport to address all of the 3.3.3 Cinitial length of the diagonal =a2 1 b 2, in me-
safety concerns, if any, associated with its use. It is the tres (feet).
responsibility of the user of this standard to establish appro- 3.3.4 ddiagonal elongation, in millimetres (inches).
priate safety and health practices and determine the applica- 3.3.5 Dtotal horizontal displacement of the top of the wall
bility of regulatory limitations prior to use. measured with respect to the test apparatus, in millimetres
(inches). This value includes effects due to panel rotation,
translation, and shear.
1
This practice is under the jurisdiction of ASTM Committee E06 on Perfor-
mance of Buildings and is the direct responsibility of Subcommittee E06.11 on
2
Horizontal and Vertical Structures/Structural Performance of Completed Structures. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Jan. 15, 2006. Published January 2006. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1976. Last previous edition approved in 2000 as E564 001. DOI: Standards volume information, refer to the standards Document Summary page on
10.1520/E0564-06. the ASTM website.

Copyright. (C) ASTM International. 100 Barr Harbour Dr. P.O. Box C-700 West Conshohocken, Pennsylvania 19428-2959, United States

Copyright by ASTM Int'l (all rights reserved); Wed Aug 29 09:01:27 EDT 2012
1
Downloaded/printed by
Universidad Nacional de Colombia pursuant to License Agreement. No further reproductions authorized.
E564 06
3.3.6 G8global shear stiffness of the assembly, includes or roof members that will be used in the actual building
rotation and translational displacements as well as diaphragm construction. When required to minimize distortion, reinforce-
shear displacement. ment, such as a strong-back attached along the length of the top
3.3.7 G8intinternal shear stiffness of the assembly, in- plate or a steel bearing plate attached to the end of the top plate
cludes only the shear displacement of the wall in calculation. shall be installed. The wall test assembly shall be laterally
3.3.8 Pconcentrated load applied at the top edge of the supported along its top with rollers or equivalent means so as
wall at the selected reference displacement, in newtons (pound- to restrict assembly displacement outside the plane of loading.
force). Lateral support rigidity shall not exceed that provided in the
3.3.9 Puhighest load level held long enough to record actual building construction.
gage measurements, in newtons (pound-force). 6.5 Wall SizeTest wall size will vary with the study
3.3.10 Suultimate shear strength of the assembly, in new- objectives. Tests conducted to assess the structural perfor-
tons per metre (pounds per foot). mance of actual building construction shall have dimensions
commensurate with those of the shear walls being simulated.
4. Significance and Use 6.6 Curing and ConditioningFor framed wall construc-
4.1 This practice is used to determine static load capacity tions containing elements whose structural performance is a
and deflection of framed wall sections. This practice is used to function of age, curing conditions, moisture content, or tem-
establish a load deflection curve. It is used to evaluate various perature, the wall test assembly shall be conditioned prior to
framed systems representative of those intended for use in the test in accordance with the appropriate voluntary consensus
actual building constructions. standards, manufacturer specifications, or industry curing prac-
tices for the various products used, or as needed to meet the
5. Summary of Practice intent of the test. Care shall be taken to ensure that curing and
conditioning are representative of that expected in the actual
5.1 The shear strength and stiffness of a wall assembly and
building construction and that all elements of the wall test
its connections are determined by forcing a racking deforma-
assembly at the time of the test are approximately at the
tion. This is accomplished by anchoring the bottom edge of the
equilibrium conditions expected in service.
wall assembly and applying a force to the top edge oriented
6.7 Environmental EffectWhen required to evaluate wall
perpendicular to the wall height dimension and parallel to the
assembly performance for simulated environmental conditions,
wall length dimension. Wall distortion is restricted to the plane
preconditioned specimens shall be tested in an environmental
of the unstressed wall. The forces required to rack the wall and
chamber.
the corresponding displacements at each load interval are
measured. 7. Procedure
7.1 Number of TestsTest a minimum of two wall assem-
6. Wall Test Assembly blies to determine the shear capacity of a given construction.
6.1 GeneralA wall assembly consists of frame elements For unsymmetrical shear walls, run the second test with the
including any diagonal bracing members or other reinforce- specimen orientation reversed with respect to the direction of
ments, sheathing elements, and connections. The wall assem- the load application used in the first test. If the strength or shear
bly tested in accordance with this practice shall represent the stiffness of the second test is not within 15 % of the results of
minimum acceptable stiffness using the targeted frame and the first test, test a third wall assembly with the wall oriented
sheathing materials. in the same manner as the weaker of the two test values. The
6.2 ConnectionsThe performance of the wall test assem- strength and stiffness values reported shall be the average of
bly is influenced by the type and spacing of framing connec- the two weakest specimen values if three or more tests are
tions, sheathing-to-frame connections and the wall assembly performed.
anchorage connection to the test fixture, floor, or foundation. 7.2 Loading Procedure:
6.2.1 All connections used in the test shall be representative 7.2.1 GeneralRacking loads shall be applied parallel to
of those used in the actual building construction. and at the top of the wall, in the central plane of the frame,
6.2.2 Connector size and location on the frame shall corre- using a hydraulic jack or similar loading device capable of
spond to specifications. maintaining a constant displacement rate for continuous load to
6.3 Frame RequirementsThe frame is an integral part of failure or holding a static load in the case of incremental
the wall test assembly. The test wall shall consist of the same loading. Loads shall be applied at a constant rate of displace-
number, size, and grade of framing members as are intended to ment to reach the target limit (that is, limiting displacement of
be used in service. ultimate load) in no less than 5 min.
6.4 Test SetupProvisions shall be made to resist rigid- 7.2.2 Gravity loads, when required, shall be applied along
body rotation in the plane of the wall where this reflects the use the top of the wall in a manner consistent with floor or roof
of the assembly in actual building constructions. This shall be frame loading.
done by application of relevant gravity or other loadings 7.2.3 Static Load TestMaintain the duration of load ap-
simultaneously with the racking loads. The bottom of the plication at each increment at least 1 min before load and
assembly shall be attached to the test base with anchorage deflection readings are recorded. Apply preload of approxi-
connections simulating those that will be used in service. Load mately 10 % of estimated ultimate load and hold for 5 min to
distribution along the top edge of the wall shall simulate floor seat all connections. Remove the load, wait 5 min, and read all

Copyright by ASTM Int'l (all rights reserved); Wed Aug 29 09:01:27 EDT 2012
2
Downloaded/printed by
Universidad Nacional de Colombia pursuant to License Agreement. No further reproductions authorized.
E564 06
gages as the initial readings. At load levels approximately one 7.3.2 Displacement MeasurementsShear displacement
third and two thirds of the estimated ultimate load, remove the measurement of a wall frame shall be accurate to 0.25 mm
load and record the recovery of the wall after 5 min. Reload to (0.01 in.). Two approaches to estimating the shear stiffness are
the next higher load level above the backoff load. Continue provided in this practice: direct measurement and that esti-
loading and unloading in this manner until ultimate load is mated by measuring the diagonal elongation of the frame.
reached. 7.3.3 Direct MeasurementFour (numbered in Fig. 2) dis-
7.3 Data AcquisitionThe objectives of a study determine placement measurements are used to evaluate shear deforma-
the data required from this test. These generally include tion by the direct measurement. The measurement is compli-
quantification of the shear strength and stiffness of the wall cated by the fact that the assembly tends to rotate and translate
diaphragm. Shear strength is denoted as the maximum load per as a rigid body, as the frame is deformed from a rectangle to a
unit length of the wall. Shear stiffness requires measurement of skewed parallelogram. In addition, the individual elements of
the racking load and corresponding shear displacement. Shear the shear diaphragm rotate with respect to the frame as the
strain is determined as the angular displacement (D/a, see Fig. shear load is applied.
1). 7.3.3.1 Slip at the BaseFor this reading, the displacement
7.3.1 Racking load shall be monitored using either the line is measured at the centroid of the bottom plate with respect to
pressure to a calibrated loading ram or a load cell mounted in the test machine in a direction parallel to the length of the wall.
series with the loading device. When load measurement is 7.3.3.2 Uplift of the Stud at the Loaded EndThe distance
accomplished by monitoring hydraulic line pressure, the load which the bottom of the stud at the loaded end of the wall is
versus pressure calibration shall have been developed at the lifted off the base of the test machine indicates the degree of
same, or greater, hydraulic flow rate as occurs in the test to rigid body rotation. This displacement divided by the horizon-
reduce chances of overestimating load due to drag effects. The tal distance along the base from the vertical-displacement-
loading measurement shall be accurate to 61% of the maxi- measurement reference point to the opposite end of the bottom
mum measured load. The load measuring instrumentation shall plate is the tangent of the angle of rotation of the wall. As the
be calibrated in accordance with Practices E4. end stud is rotating as well as being lifted, the uplift reading
shall be taken as close as possible to the centerline of the stud.
7.3.3.3 Top Plate Horizontal Displacement This measure-
ment, taken at the centroid of the top plate, gives total
horizontal displacement at Point 3, as shown in Fig. 2, due to
a combination of rigid body rotation, horizontal translation of
the entire wall, and shear deformation. Subtracting the dis-
placement at Point 1 from the measured horizontal displace-
ment of Point 3 and dividing by the stud length plus one plate
thickness approximates the angle of rotation of the end stud.

NOTE 1Horizontal shear displacement calculated on the basis of the


diagonal elongation simplifies the test by eliminating the need to measure
rigid body rotation and horizontal translation of the wall.
~C 1 d!2 5 ~b 1 D! 2 1 ~a2 2 D2!

substituting:
a2 1 b2 5 c2

gives:
2 c d 1 d2 2 2 b D 5 0 NOTE 1The horizontal load is measured using a load cell in series
with the loading ram. Wall shear displacement is determined using either
and: four gages to separate shear from uplift, rotation, and horizontal slip of the
wall or by measuring diagonal elongation to measure wall racking
~ 2 c d 1 d2 ! deformation directly. To restrain rigid-body rotation, apply boundary
D5 2b conditions to simulate those that control wall performance in service.
FIG. 1 Horizontal Measurement FIG. 2 Test Wall Configuration

Copyright by ASTM Int'l (all rights reserved); Wed Aug 29 09:01:27 EDT 2012
3
Downloaded/printed by
Universidad Nacional de Colombia pursuant to License Agreement. No further reproductions authorized.
E564 06
7.3.3.4 Vertical Displacement at the Toe of the Wall With P a
G int 5 D 3 b (2)
Reference to the BaseSubtracting this value from displace- int
ment Number 2 and dividing by the distance between the 8.4 Internal Shear Displacement Using Horizontal and
reference points of the two displacements gives another Vertical Displacement Measurements, DintThis displacement
method for estimating the walls rigid body displacement. shall be determined as a function of Measured Displacements
(1) The diagonal elongation approach to estimating shear 1 through 4 shown in Fig. 2 using Eq 3:
deformation requires only one measurement as labeled in Fig. a
2 and the calculation shown in Fig. 1. Dint 5 D 3 2 D1 2 ~D 2 2 D4! 3 b (3)
(2) Record the load-deformation curve either continuously
or incrementally. Instead of the availability of continuous assuming displacements to be positive when up and to the
deformation measuring devices, choose load increments such right, or as a function of the diagonal elongation indicated in
that at least fie sets of readings (equal increments of displace- Fig. 1:
ment or load) are taken for each load cycle to establish the ~ 2 C d 1 d2 !
load-deflection curve. Dint 5 2b (4)
(3) For shear walls with openings, measurements of the 8.5 Internal Shear Displacement Using Diagonal Displace-
change in lengths of the opening diagonals will also provide ment MeasurementsFig. 2 shows a diagonal measurement
measurement of shear deformation helpful in verifying the taken to facilitate the analysis of panel racking deformation.
accuracy of the racking measurements for the full length wall. This measurement is intended to be used to evaluate a wall
8. Calculation shear stiffness without the necessity of accounting for small
rotation and translation. Although the shear stiffness exhibited
8.1 Data collected from this test permit evaluation of by a wall is influenced by its boundary conditions, the shear
racking stiffness, strength at defined limit-state displacements, load and shear displacement will characterize the net affect.
and ultimate load capacity. If fewer than 10 tests of a single 8.6 Ultimate Shear StrengthDetermine the ultimate shear
wall configuration are conducted, base the evaluation of these strength, Su, in load per unit length of wall tested as follows:
wall performance characteristics on the mean values.
8.2 When shear stiffness is evaluated as a global value (G8) Pu
Su 5 b (5)
it includes rotation or translation of the wall, or both. This
evaluation is of value if the test boundary conditions are
9. Report
identical to those used in construction and the objective is to
provide an overall evaluation of wall performance within the 9.1 The report shall conform to the provisions of Practice
final assembly. The global shear stiffness G8 is computed as: E575.
P a 9.2 Load Deflection CurvesPlot the load deflection curves
G8 5 D 3 b (1) for all assemblies tested and note the gravity or other vertical
loads acting on the wall during the test.
This expression implies linearity. However, wall racking 9.3 In addition to the provisions of Practice E575 the report
tests, especially those where nailed connections control stiff- shall include the rate of loading and the duration of load at each
ness and strength, are almost totally nonlinear. Therefore, load level.
values for D or P shall be selected at a reference load or
deflection that is within acceptable performance levels. One
10. Precision and Bias
reference load is 0.33 3 Pu. Other reference load levels or net
wall deflections may be used. If the initially selected reference 10.1 A statement cannot be made on the precision or bias
load level produced deformations beyond acceptable levels, due to the many individual elements which could comprise the
select a reduced reference load level to yield the accepted wall and the small number of replicate specimens that are
deflection limit. tested. A generally accepted method for determining precision
8.3 Internal Shear Stiffness (G8int)This is the actual shear and bias is not currently available.
stiffness of the wall assembly due only to the wall shear
displacement. It is calculated using the same expression used 11. Keywords
for G8 except that D has been adjusted to remove effects of 11.1 framed walls; racking loads; rigid support; shear dis-
rotation and translation. placement; shear stiffness; shear strength

Copyright by ASTM Int'l (all rights reserved); Wed Aug 29 09:01:27 EDT 2012
4
Downloaded/printed by
Universidad Nacional de Colombia pursuant to License Agreement. No further reproductions authorized.
E564 06

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).