Power over Ethernet Lighting

Evolution or Revolution?
Power over Ethernet Lighting

Lighting made a huge leap forward early in the 20th century when scientists learned how to generate usable light by passing electrical
current through a thin strand of metal contained in a sealed glass chamber (aka, the light bulb). During the past century, lighting
technology has been rendered reasonably safe through the implementation of measures that regulate how the products are built,
how they are installed, and how people interact with them. The system of regulations, products standards and installation codes seeks
a balance between desirable lighting technology characteristics (maximum light quantity, quality and flexibility), safety considerations
(including fires and the risk of injuries), and undesirable characteristics (excessive operating costs, resource consumption, and toxic
waste at the end of useful life). The development of highly efficient LEDs in the 21st century is showing itself to be a very positive
game-changer, and the regulatory system is doing its best to keep pace with this technology and facilitate its deployment.

At the same time, wired communications technology, and presents a pathway delivery precision because the energy
technology has also come a long way, for demonstrating compliance with the levels involved are more refined and
from the telegraph to telephone to fax current regulations and codes. manageable.
machine, and then more recently to
Compared to power distribution systems,
the digital world. The electrical power Power vs. Communication electrical control and communication
demands of communication systems
In its simplest form, the basic concept circuits generate far less heat and can
have always been much lower than that
behind a control system is its ability to be effective at far lower voltages. The
of systems required to do mechanical
manage a large amount of power with National Electrical Code (officially titled
work, such as moving, heating,
a small amount of effort. One set of ANSI/NFPA 70, but usually referred to as
cooling and lighting. As a result, wired
tools and techniques is used to gather the NEC) recognizes these characteristics
communications systems generally
the energy, and a different set of tools and relieves these circuits from many
require fewer safeguards to prevent
and techniques are used to release it. of the fire and electric shock injury
injuries and property damage.
The releasing tools the control system safeguards typically applied to power
Power over Ethernet (PoE) lighting allow for more accurate timing and systems. NEC Article 725 applies to these
exemplifies the convergence of highly
efficient (low power demand) lighting
and sophisticated digital control and
communication equipment. These
technologies (low voltage lighting and
Ethernet communications) are already
fully deployed and accepted at both
the product standard and installation
code level. Many applicable regulations
have prescriptive rules that establish
expectations and set the stage for
acceptance or rejection of products, based
on how well or how clearly they conform
to these expectations.

This white paper explores some of


the compliance issues raised by the
anticipated deployment of PoE lighting

page 2
Power over Ethernet Lighting

limited power circuits, and is explained in computer communications, utilizing a technology is commonly referred to as
Section 725.1 of the Code as follows: similar look-and-feel to that found in 4P POE or 4-pair PoE. Other powering
legacy telephone wires and connectors. In schemes, such as Power over HDBaseT
The circuits described herein are
2003, IEEE 802.3af was published, limiting (PoH) are also under development and
characterized by usage and electrical
the transmission of power over these are expected to be available in the near
power limitations that differentiate them
cables to 15.4 watts, a level nonetheless future.
from electric light and power circuits;
sufficient to operate small equipment
therefore, alternative requirements to These higher power levels open up PoE
under most circumstances without the
those of Chapters 1 through 4 are given to even more classes of equipment,
need for a separate power unit. This
with regard to minimum wire sizes, potentially eliminating the need for
development directly facilitated the
ampacity adjustment and correction many of the individual AC-to-DC
evolution of standalone communications
factors, overcurrent protection, insulation power converters that supply digital
equipment with limited functionality, i.e.,
requirements, and wiring methods and equipment throughout the commercial
telephones, to full-fledged networked
materials. environment. Because every such power
communications devices, each operating
converter generates a measurable
Until recently, facility lighting has with individual IP (internet protocol)
amount of waste heat, the potential
required power levels beyond the capacity addresses.
energy savings associated with reducing
permitted under NEC Article 725. A typical
To meet the power demands of other new the number of individual conversion
facility lighting system has multiple
network-capable devices, such as wireless devices is significant. Further, while the
luminaires operating directly from a
access points and security cameras, capabilities of power sourcing equipment
shared 15- or 20 amp, 120- or 277 volt AC
an upgraded version of the standard, are expanding, the power demands of
branch circuit, as well as separate control
IEEE 802.3at, was published in 2009, potential candidates for this technology
inputs for sensing daylight, occupancy, or
increasing the transmitted power limit to are decreasing due to improvements
time of day in order to more effectively
30 W (or an estimated 25.5 W after cable in energy efficiency. A specific example
manage energy consumption.
losses). Designated as PoE+ or PoE Plus, can be found in highly efficient LED
However, improvements in LED luminaire the source of this power (power sourcing luminaires that are capable of operating
efficiency now make it feasible for these equipment, or PSE) is typically referred at low voltage input levels. The
luminaires to operate within Article to as an Ethernet switch. This switch widespread deployment of LED luminaires
725 power limits. This allows them to is responsible for directing electronic makes them ideal candidates for PoE
be managed by sophisticated digital communications traffic based on the IP applications.
power sources with their own control addresses embedded in the signal, as well
circuit intelligence, thereby reducing as the protocols (sometimes referred to PoE Efficiency, Safety and
the need for separately routed control as a handshake) between the switch and Addressability
inputs. The potential to use lighter the devices to which it is connected (the
weight communication cables without Today, the energy savings attributable
powered device, or PD).
a protective conduit, as permitted under to the use of LED lighting are well
The next generation standard, IEEE established. Although the relatively high
Article 725, can also provide significant
802.3bt, which is expected to be price of LED lighting compared with that
cost and labor savings.
published in 2016, will boost the power of legacy lighting technologies remains
transmission limit up to 95 W, primarily a challenge, this consideration is being
PoE Lighting Development
by doubling from two to four the number offset by other factors, such as a longer
Ethernet cables and connectors were of paired conductors used for power expected operating life, reduced energy
originally designed and deployed for transmission within the cable. This consumption, better color rendition,

page 3
Power over Ethernet Lighting

dimmability, and less hazardous material DC power distribution eliminates the Low Voltage LightingUL 2108
to deal with at their end of life. These conversion losses associated with
ANSI/UL 2108, Standard for Safety of Low
factors are widely considered by both converting alternating current (AC) power
Voltage Lighting Systems, addresses the
facility managers and consumers when it distribution to DC power at the branch or
minimum construction and performance
comes to purchasing new or replacement individual device level.
requirements for luminaires whose input
lighting.
In addition to their potential for increased voltage is within the Class 2 voltage limits
Further, the digital, discrete and modular energy efficiency, LEDs also significantly of NEC Tables 11(A) and 11(B) (30 Vac
nature of LED lighting technology reduce the risk of fire or injury. Individual and 60 Vdc, respectively, for damp and
can provide greatly expanded control LEDs function with a forward voltage that dry locations). The Standard also requires
options that can further reduce overall is typically near three volts. The threshold that power output for low voltage
system energy consumption. Efficiency point at which a risk of electric shock lighting power units remains within those
improvements within LED technology injury becomes a concern for a DC circuit, voltage limits under all anticipated use
take three forms. First, LEDs limit either in a dry or damp location, is 60 conditions.
the amount of waste heat from the volts. As such, lighting arrays that connect
UL 2108 was revised in July 2015 to
conversion of electrical current to light up to 20 LEDs in series are possible
explicitly require that PoE luminaires
within the diode itself. As new materials without triggering concerns about injury
be subjected to the same investigative
and thermal management designs from electric shock. The light output of
approach as that used with Class 2
continue to evolve, LEDs hold even more such an array, measured in lumens, can
luminaires. For the purpose of the
potential to reduce energy conversion greatly exceed that of the typical 34 W
Standard, PoE is defined as:
losses. high efficiency fluorescent tube lamp.
This capability allows PoE luminaires to A wiring system conforming to the
Second, LEDs offers unique advantages
directly compete with fluorescent lighting Standard for Ethernet, IEEE 802.3 that uses
in its directionality and its direct
within commercial environments. And, category 5 (CAT 5) or similar cables and
current (DC) operation. Legacy lighting
because the operating voltage is so much connectors to concurrently carry power
technologies such as incandescent,
lower, fewer safeguards are needed to and data, with voltage and power within
fluorescent and high-intensity discharge
protect against electric shock during lamp the class 2 limits of the National Electrical
(HID) emit light in all directions and rely
replacement. Code, NFPA 70. Also covers POE+.
on a luminaires optics to direct light
toward a specific location. However, every Finally, addressability is an important The generic reference in UL 2108 to IEEE
effort to redirect or reflect light involves and distinguishable feature of PoE. An 802.3 is intended to include both IEEE
some losses due to energy absorption individual PoE switch may have a number 802.3af and IEEE 802.3at, as well as future
or interference. Although light emitted of output ports, each of which is capable generations of the standard. UL 2108
from an LED is omnidirectional, the LEDs of two-way communication between now also includes a reference to CAT 5 as
small light emitting surface permits the the PSE and its connected equipment. an example of permitted output cable
optical elements to be designed with far These ports can individually control every connection types for Class 2 power units.
greater precision, thereby more efficiently LED feature available through a digital The Standard does not currently address
directing the luminaires light output. interface. As a digital device itself, the other LAN cable-based communication
PSE can be programmed or remotely protocols, such as HDBaseT, that operate
Third, because LEDs operate from direct
managed, thus permitting a much within similar power limits but are not
current, LED luminaires can be made
wider range of light level adjustments, tied to the IEEE 802.3 standards. The
plug-and-play ready for DC power
scalable from an individual luminaire to text of UL 2108 may be expanded in the
distribution systems that are now being
facility-wide lighting. future to specifically address these other
deployed in some commercial facilities.

page 4
Power over Ethernet Lighting

approaches where the safety concerns are


similar.

The 2015 edition of UL 2108 also expands


the output marking requirements to allow
any power unit whose output is limited
to the NEC Class 2 levels to be marked
"Suitable for Class 2 Wiring. A Class 2
marking had previously been reserved for
only those outputs explicitly evaluated to
UL 1310, the Standard for Class 2 Power
Units, or UL 5085-3, the Standard for Class
2 and Class 3 Low Voltage Transformers.
This modest revision in UL 2108 formally
recognizes the other limited power circuit
designations that align with the Class
2 wiring requirements of NEC Article
725, and explicitly acknowledges the
significance of the electrical voltage, eligible source. This subsection also A proposed revision for the 2017 edition of
current, and power available from includes an Informational Note which the NEC is intended to expand the scope
the output rather than the particular refers to UL 60950-1:2011 as a source of 725.121(A)(4) to include audio/video
standard used to identify that output. for determining the applicable listing and communication equipment. These
requirements for such equipment, devices also fall within the scope of UL
As a result of these revisions, UL 2108 is
stating typically such circuits are used 62368-1, Standard for Safety of Audio/
now fully positioned as a certification
to interconnect information technology Video, Information, and Communication
standard for PoE power units and
equipment for the purpose of exchanging Technology Equipment, which is slated to
PoE-powered luminaires installed in
information (data). replace UL 60950-1, Standard for Safety
accordance with NEC Article 411. While a
of Information Technology Equipment, in
PSE may still function as a switch, it can Informational Notes within the NEC are
the near future. The proposed NEC revision
now also be certified and approved as a added for explanatory purposes and do
goes even further to include industrial
lighting power unit. not establish mandatory requirements.
equipment, with an Informational
However, both subsection 725.141(A)
Note that cites both UL 62368-1 and
The National Electrical Code (4) and the Informational Note pose
UL 61010-2-201, Standard for Safety
potential challenges for the deployment
Article 725.121 of the 2014 NEC Requirements for Electrical Equipment for
of PoE lighting. Thats because equipment
addresses power sources for Class 2 and Measurement, Control and Laboratory Use.
installers and code authorities (formally
Class 3 circuits, and is quite specific as
referred to within the NEC as Authorities As of this writing (October 2015), the NEC
to the types of power sources that are
Having Jurisdiction, or AHJs) do not Code Making Panel responsible for Article
eligible to supply Class 2 wiring methods
generally consider a lighting power source 725 has recommended adoption of this
and materials (as subsequently identified
as information technology equipment, proposed revision, and is soliciting public
under NEC Article 725.130). Subsection
or that conductors supplying a luminaire comment prior to taking a final vote. This
725.121(A)(4) identifies a limited power
are transmitting data for the purpose of action signals the Panels recognition
circuit of listed information technology
exchanging information. that the features and performance of
(computer) equipment as one such

page 5
Power over Ethernet Lighting

power sources evaluated to the criteria different environments, such as dry or wet 1838, Standard for Safety of Low Voltage
in these standards applicable to limited locations. They also distinguish between Landscape Lighting Systems, and UL
power circuits are also valid for a variety circuits that contain an overcurrent 2108. NEC Section 411.3(B) requires
of device types, not just information and protection device, e.g., a fuse, versus Class 2 lighting systems to conform with
communication technology equipment. those whose current output is inherently Tables 11(A) or 11(B), and UL 2108 Table
limited. While there are some nuanced 3.1 mandates the same voltage limits.
Another subsection within Article
distinctions, these Tables generally align Therefore, PoE lighting technologies
725.121 appears to provide even broader
with electrical circuit parameters for operating between 44 and 57 Vdc clearly
application allowances for low power
Class 2 and limited power sources (LPS) fit within the scope of NEC Article 411.
circuits. Subsection 725.121(A)(3) refers
found in various product standards. The
to other listed equipment marked to
identify the Class 2 or Class 3 power
accessible circuit connectors in modern NEC Article 725Class 2
source, with the exception of limited
electronic devices, such as USB, HDMI, Wiring Methods
Ethernet, firewire, etc., all operate within
power circuits of listed equipment where NEC Section 725.121(A) provides several
these same parameters
these circuits have energy levels rated options for determining whether a
at or below the limits established in power source is eligible to supply a circuit
Chapter 9, Table 11(A) and Table 11(B).
NEC Article 411
using Class 2 wiring methods. The basic
The Informational Note that follow this The current title of Article 411 is Lighting premise is that Class 2 circuits present
exception provides examples of other Systems Operating at 30 Volts or Less and a sufficiently low risk of fire and electric
listed equipment. Although lighting Lighting Equipment Connected to Class shock, so they can be safely routed
equipment power sources are not listed 2 Power Sources. The Class 2 aspect of through a building without most of the
among the examples, citing examples is the title was added during the 2014 NEC safeguards typically required of higher
intended for guidance only and does not revision cycle, a proposed 2017 revision power circuits. As presented in a number
constitute an exclusive list. Theoretically, recommends the title be simplified to of different product standards, there are
this text provides installers and AHJs Low Voltage Lighting. several approaches that can be employed
with the discretion to accept any listed to establish that a power source conforms
Article 411 was originally developed
equipment whose output is rated and with the requirements of NEC 725.121(A).
to address landscape lighting systems
marked as conforming with the limits
supplied by an isolating power source Compliance with UL 1310 or UL 5085-3
found Tables 11(A) or 11(B).
with a maximum 30 V output. Since its results in marking the product output as
NEC Tables 11(A) and 11(B) identify the original introduction, the scope of Article Class 2. Use of a Class 2 transformer or
electrical circuit parameters, including 411 has grown to cover a wider variety power supply provides clear conformance
voltage, current and power, that qualify a of low voltage lighting equipment and with Subsections 725.121(A)(1) and (A)(2),
circuit for the more limited suite of wiring systems. Article 411 limits these systems respectively.
method protection measures described to 25 amperes of low voltage current
Power units more commonly used
in Article 725. Circuits that exceed the (appropriate for legacy landscape lighting
for consumer electronics, computing,
identified limits must otherwise conform strings of incandescent lamps), and
multimedia, and communications
to the more restrictive wiring methods requires the output to be isolated from
equipment are typically evaluated to the
found in NEC Chapter 3. The Tables and the branch circuit and ungrounded.
requirements of UL 60950-1 or those of
their associated Informational Notes
These constraints are mirrored in the its planned successor UL 62368-1. These
include adjustment factors for different
two associated UL product standards Standards incorporate an LPS evaluation
electrical waveforms, such as interrupted
that directly reference Article 411, UL program whose output parameter
DC or combination AC+DC, and for

page 6
Power over Ethernet Lighting

requirements are aligned with the Class 2 Class 2 wiring methods in accordance designation label applied to the source,
parameters of NEC Tables 11(A) and 11(B). with previously noted exception to NEC that ultimately matters.
The use of the term LPS rather than Class 2 725.121(A)(3).
The cables that run from the PSE to the
is intended to align the terminology used
UL 2054, Standard for the Safety of PD are Category Cables such as Cat 5,
in the Standards with that of equivalent
Household and Commercial Batteries, Cat 5e (which offers better crosstalk
international standards, and does not
has a limited power source test program prevention), and Cat 6 or 6a (even quieter
represent any substantive difference in
whose output parameter requirements and with a higher top-end capacity).
the level of power or safety involved. This
align with those of both UL 60950-1 and Each of these Category Cables have
alignment is also explicitly acknowledged
UL 62368-1. The Standard authorizes multiple twisted pairs of small conductors
by NEC 725.121(A)(4), which permits the
compliant battery packs to be marked contained within an insulated jacket.
LPS output of equipment certified under
LPS, which qualifies them to serve as a They are commonly referred to as
UL 60950-1 to supply Class 2 wiring and
source for Class 2 wiring under the same Ethernet cables and are usually certified
which parallels the allowance granted to
exception to NEC 725.121(A)(3). as CM (communications) cables, often
Class 2 transformers and power supplies.
with additional suffix designations,
A proposal currently under consideration The limited available voltage and current
such as CMR or CMP, to designate
for the 2017 NEC revision will expand the carried by Class 2 circuits make them
suitability for use within building risers or
Informational Note associated with Article suitable for routing through a building
plenums. They were originally designed
725.121(A)(4) to include equipment without the more robust enclosures and
and are still predominantly used for
certified in accordance with UL 62368-1. grounding/bonding requirements required
applications covered by NEC Article 800,
by NEC Chapter 3. Subsection 725.121(A)
There are still other options. UL 8750, Communication Circuits. They may
identifies several types of common
Standard for the Safety of LED Equipment, also be certified as type CL, CLR, CLP, etc.
power sources in order to simplify the
is used to investigate and certify LED However, the CM designation is more
specification and approval process. But
drivers. It is one of several UL standards versatile and thus more commonly applied
the expanding list of exceptions and the
that includes an evaluation program since the CM types are shown in NEC
reference to Tables 11(A) and (B) reflect
to assess whether internal circuitry is Figure 725.154(A) as eligible substitutes
the Codes tacit acknowledgement that
limited to the voltage and current levels for the CL2 cables used for Class 2 circuits
it is the electrical characteristics of the
permissible in Class 2 or LPS circuits. The within Article 725.
power source, rather than the product
UL 8750 low voltage, limited energy (LVLE)
evaluation program is used within the
context of the Standard to allow some
latitude from otherwise required fire
and electric shock safeguards, similar
to the way in which the NEC exempts
Class 2 circuits from otherwise required
wiring protection methods. When an
LVLE-compliant circuit is isolated from
the branch circuit connection by a
transformer and its output is limited to
100 VA, the circuits output fully aligns
with NEC Tables 11(A) or 11(B). This
qualifies the LVLE circuit as compliant with

page 7
Power over Ethernet Lighting

For most building power distribution be prescriptive and literal. While and maintaining effective safety.
cables, the major concerns are current- code authorities retain a great deal
PoE switches certified in accordance with
generated heat and the insulations of discretion, clear and unequivocal
UL 60950-1 have been routinely installed
ability to avoid breakdown that can lead determinations are easier when
and approved within IT equipment rooms
to electric shock or ground faults. In the installations are explicitly permitted in
under NEC Article 645, Information
case of Cat 5 low voltage, low power the text of the Code. However, this is not
Technology Equipment. Section 645.3(D)
communication cables, the concerns always possible since technology often
explicitly permits the output of such
are more related to maintaining the moves faster than the Code can adapt, and
equipment to use Class 2 wiring methods
integrity of the data. But the NEC and because the wide diversity of products and
in accordance with Subsection 725.121(A)
the product standards used to certify their applications places practical limits on
(4). Whether transmitted electrical energy
these cables require appropriate flame what can be captured in a Code document
is used to transfer files from one computer
propagation and smoke generation testing before it becomes too unwieldy to use.
to another or to illuminate a space isnt
to determine that they do not provide
Ultimately, the NEC provides AHJs with relevant from a safety perspective. So
an unintended fire path as they travel
sufficient discretion in such cases, as an AHJ that is comfortable approving
through a building, or create an excessive
stated in Section 90.4, which reads (in a PSE for data transmission activity
amount of smoke if ignited.
part): under Section 645.3(D) has good cause
For a single cable, there is no real concern to be comfortable approving the same
The authority having jurisdiction
that the cable itself will be ignited from equipment when that data is used, some
for enforcement of the Code has the
within. But, in cases in which many cables 30 100 meters away in the building, to
responsibility for making interpretations of
are bundled together, cumulative heat create light.
the rules, for deciding on the approval of
generation and the reduced ability of the
equipment and materials, and for granting Regarding PoE luminaires, the situation
confined cables to dissipate this heat can
the special permission contemplated in a is greatly simplified as a result of recent
become a concern for degradation of the
number of the rules. By special permission, revisions to UL 2108 that provide clear
cable insulations flame retardant and
the authority having jurisdiction may and unambiguous listing opportunities
smoke limiting properties. The ability of
waive specific requirements in this Code for PoE luminaires, thereby fulfilling the
bundled PoE cables to avoid long term
or permit alternative methods where it is NEC 411.4 requirement that low voltage
insulation degradation is currently being
assured that equivalent objectives can be luminaires be listed. Other requirements
studied, and is also a current topic for the
achieved by establishing and maintaining discussed in this white paper relating
NEC Code Making Panel 16 responsible for
effective safety. to isolation, grounding, and concealed
Article 800. The questions currently being
conductors still apply whether the power
explored include whether and to what PoE lighting technology has not yet
source is a PSE or traditional Class 2
extent bundled cables should be de-rated garnered the attention of many of the
transformer. Therefore, for a listed PoE
regarding the amount of current they are NECs Code Making Panels. Indeed, no
luminaire, meeting the equivalent
permitted to carry. The specifics of any public inputs on this topic were submitted
objectives threshold of Article 90.4 of
changes are likely be worked out over the for the 2017 revision cycle. But PoE
the NEC should be a straightforward
next several NEC Code revision cycles. lighting is not the first new technology to
proposition.
seek AHJ approval under the discretionary
Code Authority Acceptance allowances provided for in the Code. For
most AHJs, the final phrase of Section
Evolution or Revolution?
All of the issues discussed above
90.4 holds the key to approval, that is, to PoE lighting is simply an evolutionary
are important when it comes to PoE
provide assurances that equivalent concept in the context of the Internet of
lighting. Code enforcement can often
objectives can be achieved by establishing Things (IoT), and is a natural expansion

page 8
Power over Ethernet Lighting

of the smart home environment in Just as a smart phone is no longer just


which everything, from appliances to a phone but a fully integrated mobile For more information about
heating systems and security, can be information and communications device, ULs standards applicable to
remotely monitored and controlled. The future luminaires will integrate all of
PoE lighting technology, go to
energy efficiency improvements in LED this functionality into a single package.
lighting now make it practical to add Effectively managing the communications
www. ulstandards.ul.com. For
lighting controls to the list of smart home interface will take time and will likely details on ULs certification
capabilities, and lighting technologies require various standardization efforts of PoE lighting equipment,
will produce further increases in energy within and between the involved industry
contact Michael Shulman at
efficiency as the number of user control sectors. But these challenges are surely
and programming options proliferate. within the capabilities of the innovative Michael.Shulman@ul.com.
In the context of lighting equipment,
companies driving this revolution. for other inquiries related to
however, PoE has even larger, potentially UL has already taken the first step, ULs lighting solutions please
game-changing potential. Luminaires certifying basic PoE lighting equipment contact lightinginfo@ul.com
have already been recognized as locations and establishing requirements within
and visit www.ul.com/
within a building infrastructure where the applicable lighting product standard.
electrical power, mechanical enclosures, If history serves as a guide, the next few lighting today.
and line-of-sight are all readily available. years will see increased competition
As a result, several different facility in both basic equipment and in the
systems, such as security, energy peripherals and application software that
management, and mobile communication, will expand the reach and functionality of
can potentially use luminaires as nodes PoE lighting technology. These innovations
where other equipment can be co-located. will serve as the basis for further revisions
And, because of the vast communication of the NEC and applicable product
capacity of a PoE network, all of these standards in order to clarify requirements
additional systems can not only be and minimize confusion, with innovation
co-located within a luminaire but can driving regulation and regulation
also leverage a single, integrated wired channeling further innovation.
or wireless communication system. In
such a scenario, the potential savings
in hardware, software, and interference
avoidance may be considerable.

2015 UL LLC. All rights reserved. This white paper not be copied or distributed