Documente Academic
Documente Profesional
Documente Cultură
Greg Shirek
Milsoft
Loads are voltage dependent. The power consumed by a load is simply P=VI, so as the supply
voltage changes, the current may changes and the power and energy consumed may change, all
depending upon which load type is being addressed. The three generally accepted load types are:
The equations used for analyzing each of these along with numerical examples are as follows.
*
S S
IL = = / = IL / (1)
V V
From equation (1), it can be seen that as V changes, the load current IL must change inversely to
hold S constant.
*
S
IL = S = IL*V
V
Consider an example of 1000W load rated 120V, if the voltage were lowered 10% to 108 volts, the
current would have to increase by 0.9(-1) or 1.11 p.u. as below.
1000
IL= =8.33 amps (rated current)
120
1000
IL = =9.26 amps
108
S
IL = S = IL * V 1000W = 9.26 A * 108 V
V
So this shows that constant PQ type load rules are that the load current must change inversely
to the change in delivered voltage to hold the power (PQ) constant.
For a wye connected load, the complex power S is specified at a rated line-to-neutral voltage V .
This data is then used to calculate the impedance of the load Z .
Then Z is used in the following equation to find load current IL at rated voltage.
V V
IL = = / = IL / (3)
Z Z
From equation (2) it can be seen that a Z type load varies quadratically with voltage. As an
example, if the rated voltage for a 1000 Watt load was 120 volts, the calculated Z would be:
2 2
V 120
Z= = = 14.4
S 1000
V 120
IL = = = 8.33
Z 14.4
If the voltage delivered to this load were reduced by 10% to 108 volts from the 120 volt rated, the
new load current would be:
V 108
IL = = = 7.5
Z 14.4
And the new effective calculated power would be P=VI=108* 7.5 = 810 Watts
So this shows that constant impedance type load rules are that the load current changes
linearly with the change in delivered voltage and the demand varies as a squared function of
the voltage change.
*
S S
IL = = / = IL / (4)
V V
IL = IL / (5)
IL is held constant while the angle of the voltage changes resulting in a changed angle on the
current while the power factor of the load is held and remains a constant.
From equation (4), it can be seen that the power S varies linearly with the change in voltage since
ILa remains constant. That is, for a change in voltage of X percent, the current will change X
percent.
As an example, 1000W load at 120 volt rated would give load current of:
1000
IL = =8.33 amps
120
So this shows that constant current type load rules are that the power delivered to the load
varies linearly with the change in voltage delivered to the load.
Also of interest are the 13.9 Amps of load current. Basically 13.89 amps multiplied by the 120 volts
equals 100 kW.
Now lower the voltage by 10 percent to 108 volts and rerun load allocation.
The amount of allocated load to the consumer shown in the calculated load tab remains at 100 kW
and is not dependent upon the voltage delivered, thus proving constant PQ load mix is voltage
independent. The current had to increase by 11 percent (108/120)-1 * 13.890 amps to get the
15.433 amps to equal the constant PQ load total of 100 kW.
Since no losses are introduced into this circuit, allocating 100 kW of LCP load should show 100 kW
allocated to the consumer as shown below. The consumer demand is calculated at the base voltage
of 120 volts, which is also delivered to the consumer.
Notice that the amount of allocated load is now different since the voltage delivered to the
consumer is lower than 120 volts which was the voltage used to calculate Z. This Z value is then
used subsequently in the power flow equations as shown in equation 2 during the allocation
process. The calculated load tab shows that 123.4 kW has been allocated. So why can the allocated
To explain numerically, whatever increase above the LCP kW added to the consumers calculated
load will have to be subtracted from the total allocated load and will be shown in the adjustments
category of the load allocation report. Note the adjustments value of -123.4 kW in the allocation
report. This was calculated as follows:
1. The Z of the load was calculated at 120V base (7200 V L-G) as described in equation 2.
2 2
V 7.20
Z= = / = 0.5184 / ohms
S* 100
V 7.2
IL = = = 13.89amps
Z 0.5184
2. The voltage delivered to the load is 108 V (6.48 kV L-G), so the current decreases
V 6.48
IL = = = 12.5 amps
Z 0.5184
P=VI=6.48 * 12.5 = 81 kW
What occurs in WindMil is a somewhat inverse relationship. That is, WindMil assigns a
calculated load that is larger than what the truly effective load is at the consumer, effectively
meaning it would be recorded with a power meter. WindMil then subtracts this additional kW
value assigned to the consumer to the adjustments category in the allocation report.
Since WindMil allocates load based on a set LCP value (which is converted to amps at the
defined source voltage, 108 volts), in this case:
LCP kW
IL = = 15.43amps
( BusVolt / 120 )* 7.2V (7)
WindMil then assigns a calculated load at the consumer based on this amp value and the voltage
ratio factor:
= 1 = 1.234 1 100 = 23.4 (9)
This adjustment value is the reduced kW demand needed by the consumer when the voltage is
lowered.
3.3 Constant I
The allocation process for constant current is comparable to the above constant Z method, however
the allocated kW value is a linear voltage adjustment rather than the exponential adjustment for the
Z load mix. The WindMil results for the 10 percent voltage decrease are seen below.
The following chart lists some common loads and their load mix type.
A good way to illustrate the voltage change versus demand change can be seen in the following
graph.
1.05
1.00 Constant PQ
0.95 Constant I
0.90
Constant Z
0.85
0.80
0.9 0.92 0.94 0.96 0.98 1.0 1.02 1.04 1.06 1.08 1.1
Voltage (P.U.)
Many references exist with these load mix percentages based on load class, winter vs. summer
peak, etc. Below is a list of some rules of thumb:
Web searches or other industry publications should be used as guidance for setting up your load
mix percentages in WindMil.
This chart shows that new technologies such as plasma and LCD TVs as well as CFL light bulbs will
need to be incorporated into the total diversity of loads served in a typical household therefore
affecting the blended load mix of the entire household load. This should be noted as new system
models are created with new loads allocated in WindMil.
Overall, a blended ZIP model needs to be developed in the WindMil model and it is up to the user to
perform the research necessary to establish the load mix equipment definitions. Many references
with reasonable ZIP values per load type that have been used throughout the past thirty years are
still for the most part valid, however as the above results from PNNL indicate, new technologies
may justify some slight adjustments. The weighting factor needs to consider what percentage of the
loads contribute to the system peak kW values. For example, in the winter is electric heat a large
percentage of the load and in the summer are air conditioning units the largest load on a residential
Still to this day, however, the assumption of constant kVA representing motor loads may be
somewhat correct as long as the motor is running at rated torque or above as shown in the graphs
on the red or green lines. However, residential motor loads for HVAC, air conditioning or heating,
will most likely be running at less than rated load, especially if the manufacturer correctly and
In addition to reducing the amount of line losses, capacitors help to increase line voltage delivered
to the end-use consumer. Obviously this can cause an adverse effect during periods of full CVR
implementation since capacitors raise line voltage. The voltage drop through the line is a function
of the voltage drop through the line resistance as well as the drop through the line reactance, V =
IRcos+ IXsin. So reducing the line current will reduce the voltage drop, or conversely stated will
increase the voltage utilized at the loads.
Care should be taken when deciding how many capacitors should be turned on or off during times
of running CVR on the system.
Load allocation assigns a calculated load to each consumer based upon the consumers billing
information supplied as well as the consumers load mix. Therefore to see the affects of voltage
reduction on the system loading, WindMils subsequent voltage drop analyses after load allocation
will need to be set up to accommodate the voltage reduction via equipment that is capable of
transforming the voltage, most likely a regulator or a source output voltage, or could even be a
transformers input and output values to represent off-nominal taps to increase or decrease
delivered voltage.
1. Run load allocation for existing metered peak demand at source. This will be called the
BASE SYSTEM load.
a. Make sure loads are modeled with a proper load mix
b. Make sure source, transformers rated in/out, and/or regulator voltages used in the
model have output voltage set correctly to coincide with value at time of peak, or the
kW demand or current assigned to the LCP
c. Run load allocation.
i. Note the kW and kVAR values in the ADJUSTMENT category. These are due
to the constant Z or constant I loads. Note if 100 percent constant PQ (kVA)
mix is used, there will be not adjustment values.
ii. Note the load and losses in the load allocation report
iii. Review the load allocation summary report to verify allocated kW and kVAR
results appear reasonably accurate. Pay attention to system loss values as
well.
2. Analyze benefits using Voltage Drop Analysis
a. Change the various elements with voltage settings such as source bus voltage or
nominal voltages, regulator output voltages, or transformer input/output voltages if
representing off-nominal taps or LTCs.
b. Run a Voltage Drop Analysis
c. Note the new values in the ADJUSTMENT category. If voltage reduction was
represented, the ADJUSTMENT value should have decreased (a larger negative
value). This represents the reduction in the total delivered kW and kVAR the loads
would demand from the system for the modified voltage settings.
d. Note the losses category in the Voltage Drop report. Due to the lowering of demand
delivered to the consumers, the line losses may decrease as well.
e. Lastly, note the total kW in the summary report. This is the key value to focus on as
this will be the total demand reduction due to your CVR implementation which will
be a summation of reduced end-use consumer demands, and the reduction in line
losses.
Reviewing the above table, the Adjustments category indicates 91 kW and 35 kVAR. What is
interesting is that the adjustment values are positive. This indicates that the average voltages at the
customers are above 120 volts in which the base Z values were calculated; the constant impedance
portion of the load mix for the two customer classes is not being significantly affected because the
utilization voltages at the customers is more less above the 120 volt base.
The following table shows the adjustments as well as the total kW losses that were found by
running voltage drops after the initial base allocation at each ten percent increment load level.
140 122.5
120
122
100
80 121.5 End of Line
kW Voltage (120V
60 121 Base)
40
120.5
20
0 120
5,000 6,000 7,000 8,000 9,000 10,000
Notice the adjustments value is relatively consistent for each load level, hovering right around 100
kW. It would seem the adjustments value would become less (a larger negative value) as the load is
decreased. However, this is not the case because the substation regulators are still establishing a
123 volt output, and with reduced load on the system, the voltage delivered to the customers will
increase thus negatively affecting any demand reduction required by customers due to the constant
impedance load mix. The voltage is way too high at these light load levels; it meets criteria, but by
way too much. At the 5,000 kW level, the lowest voltage at the focal point is excessively high and
there is less than 1.0 volt drop from substation to end of line as can be seen in the voltage profile.
This signifies that there should be much lower voltage set at the substation due to only a one volt
profile range.
Also make note that the kW losses range from 34 kW at minimum load to 128 kW at maximum load.
The losses are calculated exponentially as a function of the current, I2R, so the values appear to be
reasonable.
Rather than determining the substation voltage regulator LDCs settings manually, WindMils SET
REGULATION analysis is used. This feature has a setting to calculate the regulator settings to either
hold a high or low set voltage, as well as a most desired voltage. For our purposes, the setting to
hold lowest voltage to greater than minimum, or 118 volts, will be used. Also the most desirable
voltage is 118 volts.
At this point, a voltage drop analysis with these LDC settings at each load level increment results in
the following.
The kW Adjustments category has now been greatly affected which is expected with a decrease in
voltage. The initial load allocation with the existing system at the peak load level of 10,000 kW
resulted in an adjustment value of 92 kW as was shown in Table 1. With the substation regulator
LDC settings, the value has now decreased to -56 kW. This is a net improvement of 148 kW, or
about 1.4 percent. Overall this indicates power purchases during the annual peak at the substation
level have decreased 1.4 percent.
A key metric shown is the CVR factor which is a measure of how effective voltage reduction is from
an energy and demand standpoint. It is simply the ratio between the percent demand (or energy)
reduction and the percent voltage reduction.
%
= (10)
%
Notice throughout the min to max load range, the CVR Factor does not change that significantly, and
averages about 1.2.
7.5 Losses
With constant impedance loads, the line losses decrease proportional to the square of the voltage
decrease. With constant kVA or PQ type loads, the line losses will increase proportionally to the
square of the voltage decrease since the current must increase to maintain the constant kVA. Since
the sample system contained a mixture of constant Z and constant kVA load types, the system losses
were very unaffected by the small voltage change percentages due to the LDC.
The reason there is really no difference in losses between the base system with no LDC and the
system with LDC is that the total demands required by the consumers have only been reduced by a
small percentage, 1 to 2 percent, so the line current does not change much either; since line losses
are for the most part I2R, there is not much change. This indicates there is very little, if any at all,
line loss savings with such a small voltage change with the example system CVR plan.
During peak conditions, voltage criteria are still met with these LDC settings, with the lowest
voltage being 119.3 volts in the far north part of the system, while the LDC settings caused the
voltage regulator to boost to 121.5 volts during peak load conditions.
For the annual peak of 10,000 kW the voltage at the regulators and end of line at the far north part
of the system are 121.5 and 119.3 volts.
Lastly, the minimum voltage at the end of the north feeder still meets the 118 volt minimum criteria
during the minimum load period at 5,000 kW with the LDC set. Also notice the voltage profile
shows only a 1.7 volt range.
For typical planning study economic analysis, developing a loss savings approach is needed, and
usually the kW loss savings are calculated at peak for such items as load balancing a feeder, line
upgrades, new substations, etc. With that approach those peak kW demand savings are converted
to an annual loss savings by using a loss factor as shown below.
This works reasonably well for figuring savings for typical system upgrades or other loss saving
measures since the equation is based upon the fact that as the load decreases in the study area, the
line current decreases as well, but by a squared factor.
However, for the CVR economics, the above equation does not pertain because as shown previously,
the demand savings at the lower load levels are still large and does not decrease as a squared
function like typical I2R line losses do. We are dealing with a savings in required kW and kWh
purchases at the delivery point rather than line losses.
The following diagrams show the kW adjustments with and without LDC. The net is the potential
savings in power purchases at those load levels if CVR is used via the LDC.
200
150
100
kW 50
-50
-100
5,000 6,000 7,000 8,000 9,000 10,000
Load Level (kW)
Of interest, is that the net savings stay within a rather small band, from 128 kW to 174 kW. Again,
the reason for this is that the LDC boosts varying amounts based on the current or load through the
regulator. Furthermore, it is not a linear function due to the mixture of constant kVA and constant Z
type loads.
Fortunately, this makes the economic analysis much simpler. An engineering judgment can be
made to use a linear relationship between each interval to find the kW savings according to the
peak demands per month.
The monthly peak demands are as follows along with the kW savings based on the linear
approximations per interval.
Since the utility incurs a monthly peak demand charge, it is beneficial to implement the LDC
settings on the substation regulators during what could be the anticipated peak period each month.
As shown earlier, the kW demand reduction can be calculated for given monthly peak from
historical data according to the difference in kW with and without LDC.
Very simply, the peak demand cost savings are calculated by:
= (12)
Using this equation, the system demand reduction benefit per month is listed below and totals
$13,811 in savings.
Since the wholesale power charges to the utility are less than the retail energy charges for the end-
use consumers, reducing the voltage will reduce the number of kWh sales during CVR
implementation. For this example, the kWh revenue for the utility per kWh is simply the difference
between the wholesale and retail rates, $0.10 - $0.06, or $0.04.
Therefore, the longer CVR is employed on the system the more potential kWh sales are lost. To
calculate those values, simply use the following formula:
= (13)
Consider the utility uses CVR two times per month for six hours each time, or twelve total hours per
month. For January, that would amount to:
= . $. $. = $
Using this same procedure per all twelve months results in the following:
The lost sales metric is a very minor part of the overall economics, but is a simple calculation and
may want to be included depending upon the amount of detail needed.
9.0 Summary
As demonstrated, one must be aware of how various customer classes and the load mix type
assigned to them affect the load allocation and voltage drop analyses in WindMil. For conservation
voltage reduction studies, this is crucial. Simply using WindMils default load mix type which is set
Keep in mind the effect on kW demand requirements as voltage changes for the three load mix
options.
The example system studied simply made us of more aware of the capabilities of step voltage
regulators. Too often, utilities may set the output voltage at a higher level thus ensuring the ANSI
voltage ranges are maintained at each customer on the substation, but, as demonstrated, this has
adverse benefits for potential kW demand savings during lightly loaded periods.
Regulating line voltage via regulators with LDC in conjunction with capacitors, either fixed or
switched, proves to be one of the most, if not the most, promising actions for Volt/VAR projects
from a cost benefit standpoint. The payback is very short with the LDC implementation since the
only cost is the labor and time for the engineering or operations personnel to develop the correct
value and program them into the controls. There are basically no material costs in this option.
Also as shown, the line loss savings by reducing the voltage and thus load requirements has a very
insignificant benefit compared to the delivered demand reduction.
10.0 References
Schneider, Fuller, Tuffner, Singh, Evaluation of Conservation Voltage Reduction on a National
Level, Prepared by Pacific Northwest National Laboratory for the U.S. Department of Energy, July
2010.
Tom Wilson, Measurement and Verification of Distribution Voltage Optimization Results for the
IEEE Power & Energy Society, presented at the 2010 PES General Meeting, July 2010.
American Public Power Association, Distribution System Performance Improvement Guide, March
1997.
Rob Ardis, Peak Shaving via Voltage Reduction, Presented at the CRN Summit, June 2010.