Documente Academic
Documente Profesional
Documente Cultură
INTRODUCTION
Loadability of a transmission line is defined as the optimum power transfer capability of a
transmission line under a specified set of operating criteria. The loadability of short
transmission lines is limited by the thermal rating of the conductors, medium line voltages
regulation and long lines by stability consideration which is lower than the thermal rating.
Compensation can be used to increase loadability of long lines toward their thermal limit.
OBJECTIVES
1. To understand the use of series compensation for increasing transmission line
loadability.
2. To compare effect of compensation at receiving end, sending end and at both ends.
THEORY
There are some physical properties associated to the transmission system that limit power
transfer in spite of the capability of the generator or therequirement of the load.Transmission
systems are designed to operate according to specific voltagelevels.
Depending on the characteristic of the transferred power, the voltage at thetransmission line
ends, for instance, can be either below or above certain limits,modifying the system capacity to
transfer power. Actions are frequently taken to recover the assigned voltagelevels, allowing the
system to attend to the power demand at adequate operating condition.
The physical parameters of transmission lines, which depend upon the linelength and voltage
level, strongly restrain power transfer. As stated before,the loadability of short transmission
lines is limited by the thermal rating of the conductors. This is the magnitude of the current,
continuingover time and increasingly heating the conductor that limits the loading.As the
conductor heats up, the resistance of theconductor increases with temperature, it stretches,
and the line sags (can be irreversible).
Series and shuntcompensations have been traditionally used to modify the natural parameters
oftransmission lines. Compensation generally describes the intentional insertion of reactive
power devices (inductive or capacitive) into a power network to achieve a desired effect.
Series capacitors are sometimes used in long lines to increase the loadability. Capacitor banks
are installed in series with each phase conductor at selected points along the line. They reduce
the net series impedance of the line in series with the capacitor bank thereby reducing line
voltage drops and increasing the steady state stability limit.
The characteristic of power transfer (P-V characteristic) relates the voltage at the receiving-end
bus bar to the active power reaching it, for a given sending-end voltage, power factor and
impedance of transference. It is affected by changes either in the sending-end voltage
magnitude or in the impedance of transference between sending and receiving ends, or even in
the transfer power factor.
The graph below depicts a P-V characteristic where curves 1, 2 and 3 depict reactance X1, X2
and X3 respectively where X1> X2> X3.The line VSM shows the point with maximum power
transfer.
CASE STUDY
The power system shown below was studied.
765.0 kV 677.1 kV
slack
Bypassed 1100 MW
1100.0 MW Bypassed
Line Angle Difference: -11.9 Deg 825 Mvar
393.3 Mvar
The generator connected at bus 1 represents a large power system with an equivalent rating of
3750 MVA and the nominal voltage of both the generator and the load buses is 765 kV.
PROCEDURE
1. The PowerWorld Simulator was started and case example 5_10 with series capacitive
compensation on both ends of the line in service was opened.
2. The load was set such that PL = 0 MW and QL = 0 MVAr.
3. After running the simulation, the corresponding values of sending end reactive power,
QS, load bus voltage, VL and load angle, (measured with VL as the reference) were
tabulated.
4. The power factor was maintained as a constant (0.8 lagging) and PL was increased in
steps of 200 MW until the system became unstable while corresponding values of Q S, VL
and were tabulated.
5. Steps 2 to 4 were repeated with series compensation at the receiving-end in service and
that of the sending-end out of service.
6. Steps 2 to 4 were repeated with series compensation at the receiving-end out of service
and that of the sending-end in service.
7. Steps 2 to 4 were repeated with series compensation at both ends out of service.
RESULTS
The load power factor is kept constant at 0.8 lagging.
800
700
600
200
100
0
0 500 1000 1500 2000 2500
PL (kW)
Graph of QS vs PL
3500
3000
2500
2000
-1000
-1500
PL (MW)
CALCULATIONS
Determination of the maximum amount of power that can be transferred to the load
0.8 p.u. is the minimum value allowed for the load voltage. This means that the corresponding
power on the VL vs. PL plot will be the maximum amount of power that can be transferred to
the load since after this point the system would be unstable. Transforming this to actual values,
we have:
Vactual = Vpu Vbase
Taking the Vbase as 765 kV;
Vactual = 0.8 765 kV
= 612 kV
Thus reading from the graph, the values can be approximated as:
a) Compensation at both ends: Pmax 1820 kW
b) Compensation at receiving end: Pmax1610 kW
c) Compensation at sending end: Pmax1520 kW
d) No compensation: Pmax1390 kW
DISCUSSION
For the VLvs. PL curve, it is observed that an increase in the line loadability leads to a decrease in
the receiving end voltage until the point where maximum amount of power transfer is
attained.Beyond this point the system is unstable thus a blackout occurs.
This corresponding real power at this point is highest for the system compensated at both ends
(2200 MW), followed by those compensated at either the receiving of sending end (1800 MW)
and lastly is the system that has no compensation (1600 MW).
The effect of transmission line reactance on the curve is to increase the maximum real power
that can be transferred at a given receiving end voltage as is clearly depicted by the curves of
the graph.The line that is compensated on both ends allows for the maximum transfer of power
as compared to the rest.
For the QSvs. PL curve, it is observed that as you increase the line loading the reactive power
increases in an exponential mannerfrom negative values to positive ones.QS is negative for
PL<PO(where PO is the surge impedance loading)and the system absorbs reactive power. This is
when we have light loading.
When PL>PO, QS is positive and reactive power is supplied to the line. This is known as heavy
loading. The effect of series compensation on the QSvs. PLcurve is to increase the maximum
power that can be transmitted for a specific value of QS. It is also noted that when there is
compensation at both ends, the highest value of PLis attained.
CONCLUSION
Series compensation by using capacitors reduces the net series impedance of the line in series
with the capacitor bank thus increasing the line loadability (power transfer can be increased).
From the graph ofQS vs. PL, we observe that when series compensation is introduced, we have
an increase in the maximum power that can be transmitted for a specific value of QS.
The lines compensated at either the receiving end or the sending end have almost similar
power transfer (P-V characteristic). However, the line compensated at both ends leads to the
most reduction in series impedance, and as a result, to the largest increase in line loadability.
REFERENCES
1. Power Systems Analysis and Design, J. Glover, P. Sarma, T. Overbye, pgs. 261 270.
2. Electrical Power Systems, Alexandra von Meier, pgs. 182 183.
3. Lecture Notes on Power Systems I, K. K. Kaberere.
COLLEGE OF ENGINEERING AND TECHNOLOGY
SCHOOL OF ELECTRICAL, ELECTRONICS AND INFORMATION
ENGINEERING
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
COURSE: ELECTRICAL AND ELECTRONICS ENGINEERING
EEE 2413: POWER SYSTEMS I
GROUP MEMBERS