New improved CALIt

Halon and CO*


Liquid Level Detector

l New improved version.


l User-friendly - no messy gels required.
l For both CO2 and Halon containers.
l Dual indication of liquid level without disconnecting
container.
l Accurate! Determines level within 1!8th inch.
l Versatile, safe, easy to handle.
l Portable! Built-in battery and test meter.
l For welded and spun steel cylinders and spheres.
l Simplifies maintenance, saves time.
New CALi
Simplest way yet
to accurately check
liquid levels

With the new improved second the probe light indicates the location of Specifications
generation CALI- Liquid Level the liquid level. To record the level on CALI- Liquid Level Detector
Detector, you give your personnel the the container, apply a CALI Level Nom. dimensions, including carrying
easiest and most precise way to make Indication Sticker. case: 12 wide, 10 high, 4 deep.
sure your Halon or CO* supply cylinders Easy-to-follow instructions for
Weight, including carrying case:
or spheres are loaded for business at operating and troubleshooting are
5 lb. 2 oz.
all times - you make it easier to check included with each CALI- unit.
tanks on a regular basis. Battery charger voltage:
Uses and Limitations Input, 120 VAC - 60 HZ - 8W
The new CALI- Detector,
The CALI- is designed to detect Output, 12 VDC - 150 MA
patented by Chemetron, makes it
the liquid level in Halon and CO* Operating time with batteries fully
possible for a trained operator to
containers. When compressed, Halon charged: 3.5 hrs.
quickly determine liquid levels with
and CO2 gases convert to a liquid state.
precision - within 1/8th of an inch - Time required to bring discharged
In a container, Halon and CO2 exist in
and finish the job without disconnecting battery to fully charged state: 12 hrs.
both the liquid state (in lower portion of
or moving the container. Operating temperature: 4OOF - 11OOF
container) and a gaseous state (in
Description upper portion).
The new CALI- Detector is a Temperature will affect the amount of
compact portable battery-operated liquid and gas in a container. As
device that uses ultrasonic technology ambient air temperature increases, Ordering Information
to locate levels. The battery is enclosed more of the liquid is converted to gas. To purchase a CALI- Liquid
in the unit housing and may be re- As higher temperatures cause an Level Detector, contact Chemetron Fire
charged thousands of times using an increase in gas volume, the liquid level Systems and order the CALI- Kit,
AC adapter supplied with the unit. becomes less discernible. And general- Stock Number 7-024-0171.
When battery power is too low for an ly, the lower the temperature, the easier The basic CALI- Kit includes
accurate reading, special circuitry it is to find a liquid level. the following:
renders the unit inoperative, and The optimum temperatures for using CALI- Detector Electrical Unit
indicates the need to recharge. the CALI-2000 are: Carrying Case
Two container probes are available to Halon Containers Blue probe for use on welded Halon
assure maximum accuracy and versatili- Welded Cylinders and Spheres 85OF or less
cylinders and spheres.
ty: a red probe for heavy-wall 600 psi Heavy-wall Cylinders 8OoF or less
CALI- Detector Level Indication
and CO2 cylinders; a blue probe for 360 Carbon Dioxide Cylinders 7OoF or less
Stickers (60 qty.)
psi cylinders and spherical containers. Note: The CALI- should not be Battery Recharger
A convenient carrying case with used to find the liquid level on CO2 The Red probe, S/N 7-024-0164
shoulder strap keeps hands free. cylinders when the cylinders are stored for use on 600 psi Halon and carbon
Operation at temperatures above 75OF. dioxide cylinders, is available as an
Insert the appropriate probe into the It is generally much easier to added option; it must be ordered
CALI- Detector. Switch power on determine the liquid level on smooth separately.
by turning the Select switch to either walled, clean, welded containers. It is
CO2 or Halon. Place the probe against more difficult to find the level on dirty,
the top area of the container, and turn rusted containers, or on containers with
the Gain switch until the meter a poor, irregular, chipped surface.
indicates that the gain is properly Those surfaces distort the ultrasonic
adjusted. Move the probe up and down beam of energy generated by the CALI.
the container wall until the meter and/or

CHE,,,ETROn Distributed by

Fire System:
4801 Southwick Drive, Third Floor
Matteson, IL 60443
7081748-I 503
Fax 7081748-2847

0 1987 The seller makes no warranties, express or implied


including, but not limited to, the implied warranties of
Chemetron Fire Systems, Inc.
merchantability and fitness for a particular purpose,
Printed in U.S.A.
except as expressly stated in sellers sales contract or
No. 7-000-0089 sales acknowledgement form.
4/87/lOM