RRU&BBU Optical Fiber Cable Distribution

Guide
Internal Use Only
RRU&BBU Optical Fiber Cable Distribution Guide
Content
Quick Install Guide and Quick Card for Optical
Fiber Cables
Unpacking Warning
Distributing Optical Fiber Cables
Threading Optical Fiber Cables Through Holes in
the Wall
Tubing Optical Fiber Cables
Bundling and Fixing Optical Fiber Cables
Connecting Optical Fiber Cables at the RRU Side
Distributing Optical Fiber Cables at the BBU Side
Handling Common Problems
Internal Use Only
Read this Quick Install Guide before installing the optical fiber cables.

Each packing box contains a


installation guide for optical
fiber cables. The left figure
is just an example.
Internal Use Only
Read the Quick Card before connecting optical fiber cables.

Installing
steps

Removing
steps

Each optical fiber cable is equipped with a Quick Card. Do read it before connecting
the optical fiber cables. The above two pictures are just examples. The real materials
may be different from those in the pictures.
Unpacking Warning
Sealing cap

PE film

Protective tube

Protective bag

Before distributing and bundling optical fiber cables,


do not remove the sealing caps, dustproof caps, PE
films, protective tubes or protective bags!
Dustproof Warning

Sealing cap Dustproof cap

Dustproof cap Dustproof cap

The optical fibers are delicate and they shall not be contaminated by dust. To avoid dust dropping into the
connectors, do not remove the dustproof caps and the sealing caps at both ends of the optical fiber cables too
early. Remove them right before connecting the equipment when the optical fiber cable is 1 m from the equipment.
The dustproof caps should be well kept in the boxes composed of the removed sealing caps for the cables and the
sealing caps for the equipment optical ports. If the optical fiber cables are disconnected in the middle of the cable
route, cover the cable connectors with the caps. If the optical fiber cables are disconnected from the equipment
temporarily, screw down the sealing caps (the sealing capacity can reach IP65 at this time).
Engineering Distributing Optical Fiber Cables 1

Do not pull the optical


fiber cable from the
inner side of the coil
because the cable may
get tangled.

If the cable is
tangled, carefully
Carefully release the untangle it and
optical fiber cable coil make sure the
after coil. bending radius is
at least 200 mm.
Engineering Distributing Optical Fiber Cables 2

Two technicians should


cooperate: one pulls the cable
and the other releases the Bind the optical cable end
cable coil after coil. connecting RRU to a rope and
then lift the optical cable through
a pulley fixed in the tower. This
Distribute the cable in a tower
method is quite convenient.

Compared with distributing the cable in a tower, lifting the cable through a pulley is
more convenient.
Engineering Threading Optical Fiber Cables Through
Holes in the Wall

Two technicians should cooperate at the two sides of the wall to thread the optical
fiber cables through holes in the wall or feeder outlets smoothly: one pulls the cable
and the other releases the cable coil after coil so that the cable will not get tangled.
Engineering Tubing Optical Fiber Cables

Lay the optical fiber cable neatly and let it go through tubes in sequence. During this
process, avoid cable tangling and do not tramp over the cable on uneven ground.
Engineering Bundling and Fixing Optical Fiber Cables

Do not bundle the


optical cable too
tightly. Otherwise,
optical loss will be
increased.

If the optical cables


are laid outdoors,
they shall be
bundled together
with the power
cables with anti-
ultraviolet ties or
clips. The intervals
between adjacent
ties/clips should be
consistently 500
mm.
Step 1 Connecting Optical Fiber Cables at the RRU Side

Note: Optical modules of


Step 1: Remove the different kinds of
dustproof cap, hold the equipment may have
LC connector with the Press here to
unplug the LC different directions. Please
thumb and the carefully distinguish the
forefinger, and insert the connector.
direction before inserting
connector in the correct the connector.
direction (if it is inserted
successfully, you can
hear a crisp sound). Hold the two flank
sides when inserting
the LC connector.
Step 2 Connecting Optical Fiber Cables at the RRU Side

Check the two sub-


cables to make sure
they are not tangled.
They can have a
slight curvature.

Step 2: Gently insert the


inner sleeve into the
optical port.
Step 3 Connecting Optical Fiber Cables at the RRU Side

After the outer sleeve is


Step 3: Screw the
tightly screwed, if the yellow
outer sleeve upward
ring is exposed, then it is
to make it tightly
considered that the inner
cover the flange of
sub-cables are not crooked.
the optical port.
Otherwise, redo Step 2.
Step 1 Connecting Optical Fiber Cables at the BBU Side

Remove the dustproof caps


from the connectors right
before connecting the
optical fibers.

Remove the corrugated hose


after the optical fiber cable
gets close to the BBU during
the distribution. After the dustproof caps are
removed, take care to keep the
front of the cable connector
clean and avoid contaminating it
with sweat, grease and dust.
During the maintenance, mount
the dustproof caps if the optical
fibers are disconnected.
Step 2 Connecting Optical Fiber Cables at the BBU Side

The optical fibers at the BBU side To unplug the LC connector, you
should be protected with a winding should hold the two flank sides of
tube. And this section can be laid in the connector and press down the
the cable trough. The bending blue part to unlock the connector.
radius must be at least 80 mm.

Only the branches of the optical fiber cable can be placed in the BBU cable trough . The surplus
optical cable shall not be coiled in it. Please coil the surplus optical cable outside the equipment.
Step 3 Connecting Optical Fiber Cables at the BBU Side

Keep the optical fiber


cables from sharp Correct operation: The
edges and make sure optical cable should be
placed along the outer
the bending radius is at side of the E1 cable so
least 40 times of the that its bending radius
cable external diameter. can be increased.
Misoperation

Using the soft-connection


fibers in the hard-connection
way may break the optical
fibers.

Operate step by step


according to the Quick
Install Guide.
Misoperation

For this optical port, the


correct direction of the dual-
LC connector is as shown in
the lower-left picture and the
wrong one is as shown in the
lower-right picture.

The direction of
the LC connector
is correct.

The direction of
the LC connector
is reversed.

The direction of
the LC connector
is reversed.
Misoperation
Holding
the blue
shell is
correct.

Holding both
the blue shell
and the white
tail tube is
correct.

The wrong method


of holding the
optical fiber may
break the fiber.

The wrong method of


holding the optical
fiber may break the
fiber.
Misoperation

Although twisted
The small bending fibers may not get
radius may break broken, they will
the optical fiber. absolutely cause
more optical loss.
Handling Common Problems
If the LC springs are on
the top of the duplex
clip, you need to press
them back, as shown in
the lower picture.

Here is the slot.


When you
reposition the
LC connector,
you can hear a
crisp sound.

Faulty contact and reposition:


The dual-LC connector may
have faulty contact (as shown in
the upper-left picture). In this
case, push the LC connector to
the original slot (as shown in the
upper-right picture).