1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 250 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' KIT&DIN&STO (0F) '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.3 F / 76.3 F HEATING OA DB / WB 59.0 F / 49.4 F
OCCUPIED T-STAT 73.4 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 205 ft 16955 - 205 ft - -
Wall Transmission 556 ft 1512 - 556 ft 691 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 205 ft 3297 - 205 ft 1629 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 22 ft 161 - 22 ft 80 -
Floor Transmission 538 ft 0 - 538 ft 0 -
Partitions 750 ft 2557 - 750 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 3364 W 8034 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 10 2801 2699 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1750 860 - 0 0
Safety Factor 10% / 10% 5413 356 20% 480 0
>> Total Zone Loads - 59540 3915 - 2880 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' KIT&DIN&STO (0F) '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WSW EXPOSURE
WALL 324 0.113 - 841 - 403
WINDOW 1 11 0.724 0.786 174 487 86
DOOR 22 0.336 - 161 - 80
SSE EXPOSURE
WALL 233 0.113 - 671 - 289
WINDOW 1 194 0.724 0.786 3123 16469 1543
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 93.2 74.2 58 3000.4 43978.3 43766.8 0.0 0.0 0.0
0100 92.1 74.1 58 3000.4 43599.8 43591.9 0.0 0.0 0.0
0200 91.0 74.1 59 3000.4 43219.9 43124.3 0.0 0.0 0.0
0300 90.1 74.6 60 3000.4 42874.7 42058.6 0.0 0.0 0.0
0400 89.4 74.1 59 3000.4 42566.3 42512.8 0.0 0.0 0.0
0500 89.2 74.5 60 3000.4 42331.2 41693.9 0.0 0.0 0.0
0600 89.6 74.0 59 3000.4 42455.7 42537.3 0.0 0.0 0.0
0700 90.7 74.4 59 3000.4 43310.1 42830.1 0.0 0.0 0.0
0800 92.7 74.3 58 3000.4 44368.8 43964.8 0.0 0.0 0.0
0900 95.6 74.7 58 3000.4 45436.5 44478.4 0.0 0.0 0.0
1000 98.9 74.1 56 3000.4 46315.6 46277.0 0.0 0.0 0.0
1100 102.6 74.9 57 3000.4 46997.7 45867.9 0.0 0.0 0.0
1200 106.1 74.7 56 3000.4 47573.8 46866.5 0.0 0.0 0.0
1300 108.8 74.0 55 3000.4 48204.4 48369.1 0.0 0.0 0.0
1400 110.5 74.5 55 3000.4 48653.9 48045.3 0.0 0.0 0.0
1500 111.2 75.2 55 3000.4 48891.6 47484.7 0.0 0.0 0.0
1600 110.5 74.5 55 3000.4 48787.6 48351.7 0.0 0.0 0.0
1700 109.0 74.9 55 3000.4 48348.5 47367.1 0.0 0.0 0.0
1800 106.6 74.5 56 3000.4 47403.9 47005.0 0.0 0.0 0.0
1900 103.7 74.6 56 3000.4 46579.8 46104.7 0.0 0.0 0.0
2000 100.9 74.1 56 3000.4 45954.6 46129.5 0.0 0.0 0.0
2100 98.4 74.5 57 3000.4 45395.0 45004.9 0.0 0.0 0.0
2200 96.2 75.0 58 3000.4 44862.1 43786.4 0.0 0.0 0.0
2300 94.5 74.4 58 3000.4 44389.6 44159.2 0.0 0.0 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft
0.012
2 0.010
35 67
8
4 0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )