Hygienic Technical Data - HPS

The hygiene concept deliberately does away with biocide Type 250 500
and chemical disinfectants. Only demineralized water* Power rating [kW] 0.94 1.6
without additives gets into the air you breathe.
Water capacity (75 bar) [l/h] 46 250 90 500
The systems contain no porous or water storing Current connection [A] 4.0 6.7
components. Standing water is effectively eliminated
Voltage connection [V/ph/Hz] 230/1/50
and when stopped, the system is automatically emptied
Control signal * [V] 0 10
and checked at regular cycles in compliance with
VDI 6022. Dimensions Vortex modules [mm] 150 x 150

Number of nozzles 6 39 18 104


In the HPS and LPS models only inert materials come into
Absorbtion distance (optimum) [m] 0.9
contact with the humidification water and thanks to their
material properties ensure hygienically safe and flawless Overall installation length, min. [m] 1.5

humidification - a basic prerequisite in air conditioning. Flow rate [m/s] 0.9 2.8

Pressure drop in duct [Pa] 80 at 2.0 m/s air velocity

Technical Data - LPS


Conserving resources Certified
Type 45 72 110
HygroMatiks adiabatic humidification systems provide The HPS and LPS comply with German standards
Power rating [l/h] 0.15 0.16 0.18
high humidification performance and low energy VDI 6022, 3803 and DIN 1946, the equivalent Aus-
consumption. Thanks to their high efficiency and exact trian and Swiss standards and European Standard Water capacity (16 bar) [l/h] 4-56 10-90 20-130

controllability, the systems provide a particularly efficient DIN EN 13779. Current connection [A] 1.9 2.1 2.7
use of the demineralized water* employed. Voltage connection [V/ph/Hz] 230/1/50
A recognized, independent testing laboratory
Humidification with demineralized water* prevents has examined and confirmed conformity with Control signal * [V/mA] 0 10 / 4 20

scaling and guarantees low maintenance requirements. the Directives and the recognized state of the Dimensions Vortex modules [mm] 150 x 150
art technology (VDE Test Report No. 802300- Number of nozzles 15 22 32
HygroMatik systems means fast amortization and long

Humidifying and Cooling


3980-0001/85569 for HPS, and VDE Test Report
service life by using high quality components. Absorption distance (optimum) [m] 0.9
No. 8023003980002/141937 for LPS). The HPS
Overall installation length, min. [m] 1.5
and LPS are CE-certified and hold the hygiene con-
Flow rate [m/s] 0.9 2.8
formity certificate for air conditioning and hospitals.
Pressure drop in duct [Pa] 80 at 2.0 m/s air velocity
Adiabatic High and Low Pressure Systems
Made only with inert materials
Control system optimized for hygiene * Other control signals on request
Subject to technical amendments without notice
VDI 6022-compliant stand-by flushing Simple modular assembly as

per VDI 6022 requirements


Installation and commissioning
by qualified staff
All components are easy to clean

Adjustment of flushing and idling


parameters during commissioning
Design
Maintenance according to schedule
- annually or every 2500 h
Fast and long-term availability of spare parts
Safe and
Extensive service partner network hygienic
Technical Hotline operation

Service
Installatio
12/2013

n A member of the group


* Residual conductivity 5-20 S/cm
C
Adiabatic high pressure nozzle system HPS A1 A2
low pressure nozzle system LPS
The adiabatic HPS and LPS, high and low pressure nozzle systems by HygroMatik,
humidify the air in air conditioning and ventilation systems with demineralized water 1
1
and offer very high humidification with particularly low energy consumption and
high control accuracy.
High and low pressure atomization makes for an optimum spray pattern with 3
minimum energy consumption. The evaporation of the fine mist cools the air adi- A B
abatically. When cooling exhaust air in the summer, this can save up to 1/3 of the
cooling capacity in the design of your cooling coil.
2

Dry D 3
4
High-precision, stainless steel nozzles produce a very fine mist which is rapidly
absorbed into the air in the humidification chamber. 4

With their varying spray angles and the production of optimal droplet sizes, they
E
ensure almost completely dry walls in the humidification chamber. 2

Furthermore, the Vortex wall assembled from specially developed Vortex modules 1. Operation 1. Operation
A. Vortex module wall C. 2-stage droplet separator
2. Water supply 2. Water supply
mixes air and water mist effectively and over a very short absorption distance. A1. Vortex module D. Humidification chamber or duct
3. Water distribution 3. Water distribution
A2. Nozzle with service door and water pan
The rapid and efficient absorption takes place with virtually no loss of water - yet 4. Pump station 4. Pump station
B. Dimmable inspection window E. Drain (with U-bend)
another saving. Due to its optimal efficiency, the system provides extremely short (required as per Geman VDI 6022)
absorption distances.

Equipment features at a glance

Humidification capacity from 46-520 l Humidification capacity from 4-130 l

HPS Up to 15% higher efficiency at a humidification capacity of 46-130 l LPS Up to 80% efficiency
Up to 95% efficiency The water lubricated pump runs cleanly and safely without oil and provides
maintenance-free operation for up to 5 years (25,000 operation hours)
Graphic display shows all messages and operating data
Small and compact
Easy menu navigation for setting relevant operating parameters
Low noise
Leakage protection by means of level regulation in the water pan
Pump temperature monitoring
Water sampling tap

Perfectly adjustable and safe


Thanks to their modular construction, the HPS and LPS systems are suitable for Features common to both models
any air duct. The high-quality control system offers the most precise control of
proportional humidification. Continuous monitoring of all system components and The systems are easy to install. The straightforward set-up provides easy and timesaving installation
functions ensures maximum operating safety. It goes without saying that operating and commissioning for the technician
and fault signals are integrated into your central building control system.
The systems are also ideal for retrofitting in air conditioning ducts and scrubber chambers
Low power consumption combined with extremely low maintenance requirements