TECHNICAL GUIDE
ii ENERGY RECOVERY WHEEL
TABLE OF CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Typical Wiring Schematic. . . . . . . . . . . . . . . . . . . . . 25
The Ventilation Mandate. . . . . . . . . . . . . . . . . . . . . . . 1 Mounting Arrangements. . . . . . . . . . . . . . . . . . . . . . 26
Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Wheel Drive Options. . . . . . . . . . . . . . . . . . . . . . . . . 26
Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ordering Key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Performance Data for TEC Wheels. . . . . . . . . . . . . . 28
Recovering Total Energy. . . . . . . . . . . . . . . . . . . . . . . 6 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Recovering Sensible Only. . . . . . . . . . . . . . . . . . . . . . 7 Sample Specification. . . . . . . . . . . . . . . . . . . . . . . . . 29
Unit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 How to Reach SEMCO. . . . . . . . . . . . . . . . . . . . . . . . 30
Unit Selection Example. . . . . . . . . . . . . . . . . . . . . . . 11 Wheel Configuration Checklist . . . . . . . . . . . . . . . . . 31
Purge Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fan Location Options. . . . . . . . . . . . . . . . . . . . . . . . . 16
Drive Motor Location. . . . . . . . . . . . . . . . . . . . . . . . . 16
Filtration Requirements. . . . . . . . . . . . . . . . . . . . . . . 17
Odors and Contaminants. . . . . . . . . . . . . . . . . . . . . . 18
Wheel Speed Control. . . . . . . . . . . . . . . . . . . . . . . . . 19
Preheating to Avoid Frost Formation. . . . . . . . . 20
Controlling Wheel Speed To Avoid Frost . . . . . . 20
Avoiding Overheating (Economizer Cycle) . . . . . 21
Automatic Summer-Winter Change Over. . . . . . 21
Condensation on Sensible Only Wheels. . . . . . . 21
Sensible Wheel Performance. . . . . . . . . . . . . . . . . . 22
Sensible Wheel Applications. . . . . . . . . . . . . . . . . . .23
Condensation & Frosting. . . . . . . . . . . . . . . . . . . . . . 23
Cleaning The Wheel Media. . . . . . . . . . . . . . . . . . . . 24
Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . 24
The information in this owners manual is furnished for informational use only, is subject to
change without notice, and should not be construed as a commitment by SEMCO LLC. SEMCO
LLC assumes no responsibility for any errors that may appear in this manual.
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 1
INTRODUCTION
This design manual presents the SEMCO True 3 total Please contact your local SEMCO sales representative
energy (TE3) and sensible only (TS) recovery wheels. for additional design support or to answer any technical
It explains features and benefits provided by this questions, which go beyond the scope of this brochure.
technology, provides a detailed selection procedure and You will find a listing of SEMCO sales representatives
reviews specific guidelines to assure an effective system on our website, www.semcohvac.com. You can reach
design. This material should be reviewed carefully before SEMCO on our toll free line at 888-473-6264.
beginning the design process.
Boston
St. Louis
TECHNICAL GUIDE
2 ENERGY RECOVERY WHEEL
TYPICAL APPLICATIONS
Energy recovery equipment can be applied to a wide variety of applications:
Schools, universities, dormitories;
Offices, condominiums, apartments;
Smoking lounges, casinos;
Hospitals, nursing homes, day care centers;
Hotels, motels, department stores;
Clean rooms, circuit board, chip manufacturing;
Breweries;
Swimming pools, sports arenas;
Convention centers, airports, prisons;
Bus and train maintenance facilities;
Welding, foundry, casting areas;
Printing operations;
All humidity controlled spaces; and
Product drying operations.
BENEFITS
The SEMCO True 3 technology affords a number of benefits:
Independently certified wheel performance.
Equal latent and sensible heat transfer.
Highest effectiveness for given size equipment.
Virtually no cross-contamination (independently certified to be less than 0.04 percent).
Field adjustable purge section.
Wheel independently certified to pass NFPA 90A requirements for flame spread and smoke generation based upon
ASTM E84 fire test method.
Reliable operation.
Low maintenance.
Low operating costs.
Long life expectancy.
Can be applied where stationary heat exchangers cannot.
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 3
DESIGN FEATURES
800 77.0 70.5 A unique flute design, coupled with numerous other design innovations,
provides for the highest possible heat transfer characteristics while
1000 74.5 66.0
simultaneously reducing pressure loss parameters. These combined
Pressure Loss (in in. w.g.) features optimize the sensible (temperature) recovery portion of the
Velocity performance.
True 3 Competition
(fpm)
Providing latent (moisture) recovery efficiencies that match the improved
400 0.37 0.45
sensible values is made possible by True 3s 3 molecular sieve desiccant
600 0.56 0.66 coating. The rate of adsorption by this transfer surface is more than twice
800 0.79 0.89 that of other desiccants. This allows for effective moisture transfer from the
1000 1.05 1.15 high velocity airstreams inherent in energy recovery applications.
TECHNICAL GUIDE
4 ENERGY RECOVERY WHEEL
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 5
TECHNICAL GUIDE
6 ENERGY RECOVERY WHEEL
100
Supply Air (SA)
Outdoor Air (OA) CSA
80
40
HSA
HRA
20
HOA HEA
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 7
CSA COA
100
Supply Air (SA)
40
HEA HRA
20
HOA HSA
TECHNICAL GUIDE
8 ENERGY RECOVERY WHEEL
UNIT SELECTION
1. Wheel Selection.
Wheel selection is based on face velocity. The energy recovery wheel has been optimized for a face velocity of
about 800. This achieves the best balance between energy recovery effectiveness, pressure loss and first cost.
Using the True 3 Performance Chart (See Figure 4), find the desired airflow volume on the left hand margin of the
performance chart. Selection is always based on the smaller of the supply or return airflow when using unequal
airflows. Read across until intersecting the appropriate True 3 TE3 model number, then read down to obtain the
face velocity. Reading down the chart further will give the associated pressure loss for this face velocity. This
procedure must be repeated at the larger airflow volume to determine the pressure loss for the opposite air stream
in unequal flow applications.
FIGURE 4. Performance charts for TE3
TOTAL ENERGY RECOVERY WHEEL SIZE Series Total Energy Recovery Wheels.
70
60 TE3-70
50
40 TE3-56
AIRFLOW (SCFM X THOUSAND)
30
TE3-46
20 TE3-43
TE3-35
15
TE3-28
TE3-24 TE3-18
TE3-13
10
8 TE3-9
6
4 TE3-5
2 TE3-3
0
1100
400 500 600 700 800 900
1000
FACE VELOCITY (FPM)
95 FLOW
EFFECTIVENESS (%)
RATIO
Vmin/Vmax
90
85 .5
.6
.7
80 .8
.9
75 1.0
0 1100
400 500 600 700 800 9001000
FACE VELOCITY (FPM)
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 9
2. Unit Effectiveness
To calculate the supply and exhaust air conditions leaving the module, the ASHRAE defined unit effectiveness
must be determined as shown in Figure 5.
Since the supply and exhaust air quantities often differ, the unit effectiveness and the airflow ratio must be used
in order to find the efficiency (the amount of temperature or moisture transferred) for both the supply and return
air streams.
TECHNICAL GUIDE
10 ENERGY RECOVERY WHEEL
3. Unit Performance
Once the unit effectiveness is known, the equations provided by Figure 5 are used to calculate the dry bulb
temperature (Tdb), moisture content (w) and enthalpy (h) conditions leaving the exchanger.
NOTE: Wet bulb temperatures cannot be substituted for grains or pounds of moisture per pound of dry air.
In most cases, the supply air leaving condition (as shown above) will be required for both the heating and cooling
modes. In many cases, the exhaust air conditions must be calculated as well. This is required for applications in
colder climates, where ambient temperatures fall below 15F and where condensation and frost may form. (See
page 19, Avoiding Frost and Condensation.)
4. Purge Volume
A purge section is utilized to avoid carry-over of exhaust air into the supply air stream. A small portion of outdoor
air, in addition to that required for space conditioning, is required for purge operation. Figure 8 on page 15 will
provide the quantity of purge air required by your application. This air volume must be added to the capacity of the
appropriate system fan(s) as shown by Figure 9 (indicated as Vp).
This reduction in required chiller and/or boiler capacity should be carefully evaluated when making final unit
selections since even a modest cut in the mechanical plant will offset the cost of the SEMCO total energy recovery
wheel.
Utilizing the equations provided below, the potential chiller and boiler reduction can be estimated as follows:
Chiller Capacity = {supply air volume} ( EnthalpyIN - EnthalpyOUT ) 4.5 in tons of cooling
12,000
Boiler Capacity = {supply air volume} ( EnthalpyIN - EnthalpyOUT ) 4.5 in boiler horse power
33,000
The actual reduction made in the mechanical plant capacity, as compared to the potential reduction as determined
above, will change from project to project. Factors such as weather data, hours of operation and multiple modules
on the project and the need for redundant capacity must be carefully considered.
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 11
TECHNICAL GUIDE
12 ENERGY RECOVERY WHEEL
TE3-24 TE3-18
X(w)2 = 133 gr/lb. - [.80 (10,800/12,000) (133 - 64)] TE3-13
10
X(w)2 = humidity ratio = 83.3 gr/lb 8 TE3-9
6
4 TE3-5
2 TE3-3
X(h)2 = 43.5 Btu/lb - [.80 (10,800/12,000) (43.5 - 28.0)] 0
1100
400 500 600 700 800 900
1000
FACE VELOCITY (FPM)
X(h)2 = enthalpy = 32.3 Btu/lb
95
X(Tdb)2 = dry bulb temperature= 51.0 F FLOW
EFFECTIVENESS (%)
RATIO
Vmin/Vmax
90
85 .5
.6
X(w)2 = 4 gr/lb - [.80 (10,800/12,000) (4 - 43) gr/lb] .7
80 .8
.9
X(w)2 = humidity ratio = 32.1 gr/lb 75 1.0
0 1100
400 500 600 700 800 9001000
FACE VELOCITY (FPM)
X(h)2 = 1.1 Btu/lb - [.80 (10,800/12,000) (1.1 - 23.5)]
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 13
TECHNICAL GUIDE
14 ENERGY RECOVERY WHEEL
PURGE SECTION
Operation
As energy recovery wheel rotates from the exhaust air its rotation into the supply air stream. Figure 7 provides
stream into the supply air stream, a small amount of the a graphic representation of the purge section operation.
exhaust air is traversing the flutes of the wheel media as
The purge section is adjustable. This allows for
it passes by the seal separating the two air streams. If
optimizing the required purge volume during system
this volume of exhaust air were allowed to mix with the
startup, regardless of the pressure difference between
clean supply air stream, cross-contamination would
the outdoor and return air streams (provided that the
occur.
return air pressure is lower than that of the outdoor air).
Cross-contamination is virtually eliminated by a purge
section, which is an integral part of the casing design.
The purge section utilizes the pressure difference which
exists between the outdoor and return air streams to
purge the transfer media with clean outdoor air prior to
Return Air
Exhaust Air
Purge Air
Supply Air
Outdoor Air
Rotation Direction
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 15
Selection
The required purge volume is determined by using the intersection provides the air volume required for purge
chart provided in Figure 8. and seal leakage.
First, the wheel size and the estimated pressure After determining the difference between the return and
difference between the outdoor and return air stream outdoor pressures, use Table 4 to determine the correct
is determined. Traverse upward until intersecting purge index.
the appropriate wheel size. Reading to the left at the
FIGURE 8. Chart to determine required purge volume, based on purge pressure and wheel size.
5000
4500 TE-70
4000
TE-56
Purge Volume (cfm)
3500
TE-46
TE-43
3000
TE-35
2500 TE-28
TE-24
2000
TE-18
1500 TE-13
TE-9
1000 TE-5
TE-3
500
0
1 2 3 4 5 6 7 8
Purge Pressure (POA - PRA ) in.wg.
TECHNICAL GUIDE
16 ENERGY RECOVERY WHEEL
PURGE = VP PURGE = VP
ARRANGEMENT 3 ARRANGEMENT 4
PURGE = VP PURGE = VP
OUTDOOR AIR = VS + VP
OUTDOOR AIR = VS + VP SUPPLY AIR = VS
SUPPLY AIR = VS
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 17
FILTRATION REQUIREMENTS
The True 3 media is designed to induce laminar flow under all conditions. This results in a flow profile, which causes
airborne particles smaller than approximately 800 microns, to pass freely through the rotor media (See Figure 10).
TECHNICAL GUIDE
18 ENERGY RECOVERY WHEEL
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 19
60
Effectiveness (%)
50
40
70
30
20 60
10 50
25
0
-10 0 10 20 30 40 50 60 70 80 90
Outdoor Temperature (F)
For applications in extremely cold outdoor air conditions, the risk of frost formation should always be analyzed. True 3
provides a significant advantage over sensible only recovery (temperature only) devices. It dehumidifies the exhaust air
stream as it is cooled. This prohibits the exhaust air stream from reaching saturation under all but extreme conditions.
If the saturation condition is avoided, frost will not form on the exchange surface.
Frosting can also be avoided during the extreme conditions by monitoring the exhaust air temperature and reducing the
recovery effectiveness by the amount required to avoid saturation. Additionally, frosting can be avoided by preheating
the outdoor air, heating the return air or bypassing the exchanger. Preheating or speed control are the most common
methods.
TECHNICAL GUIDE
20 ENERGY RECOVERY WHEEL
20
0 10 20 30 40 50 60 70 80
-10 5 22 35 72
Dry Bulb Temperature (F)
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 21
TECHNICAL GUIDE
22 ENERGY RECOVERY WHEEL
SENSIBLE ONLY ENERGY RECOVERY WHEEL SIZE FIGURE 13. Performance charts for TS series sensible only
recovery wheels.
70
60 TS-70
50
40 TS-56
AIRFLOW (SCFM X THOUSAND)
30
TS-46
20 TS-43
TS-35
15
TS-28
TS-24 TS-18
TS-13
10
8 TS-9
6
4 TS-5
2 TS-3
0
1100
400 500 600 700 800 900
1000
FACE VELOCITY (FPM)
FLOW
95 RATIO
Vmin/Vmax
EFFECTIVENESS (%)
90
.5
85 .6
.7
.8
80 .9
1.0
75
0 1100
400 500 600 700 800 9001000
FACE VELOCITY (FPM)
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 23
TECHNICAL GUIDE
24 ENERGY RECOVERY WHEEL
INSTALLATION GUIDELINES
Provisions should be made to allow access to all four Carefully review the purge, fan location and filter
sides of the module to facilitate seal adjustment and recommendations covered by this brochure prior to
routine inspection. completing any design. Select the appropriate control
option for the application. Please consult SEMCO for any
Locate the A/C inverter control panel in a dry, conditioned
additional design assistance required.
space, which is clearly visible to the operations
personnel. A rotation detector should be included as a Consult SEMCO for design recommendations with
part of the control package for all critical applications. applications involving hazardous contaminants, exhaust
air temperatures in excess of 180F and/or high humidity
The purge section must always face the conditioned
conditions (drying ovens, swimming pools, etc.).
airside of the system. Rotation is such that a spot on
the media in the return air section would rotate towards
the purge section without first passing into the supply
section.
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 25
L1 N
120V
COM
ROTATION
GND IN4 GND IN3 DETECTOR
RESET
H CR1
H ALARM
ERW
N N
ZONE 583
WHITE
GREEN
BLACK
RED
AC
A1
SIGNAL AND START/STOP
CONTACT TO BE FIELD WIRED
Lstat Rnet
FROM TERMINAL BLOCK TO VFD
BT485 Rx Format
2
Short
pins Ground
Lstat
Net + Tx
IN-5 Hot
1
Comm
Net - Batt
X
SC
24 Vac
S1
Pwr
Run IN-7
Shield
- + Pot. +3V
Only Gnd
78 78 Err
CR IN-8
456
901
456
901
IN-1
Tens
23 2032 Thermistor/dry
23
contact
0-5Vdc
78 78 IN-2
Sense Thermistor/dry
456
901
456
901
Ones
contact
+12V
23 0-5Vdc
W
On
23 R
U
S
E
Rnet-
T
4
Rnet+
3
BLACK Gnd Gnd
4
2
3
1
O
2
N
WHITE Rnet +
Local
1
GREEN Rnet -
EIA-485 Comm
Selector
BACnet
Over DIP Switch Gnd
RED BAUD
ARC156
+12V
RATES
SW1 SW2 PROTOCOLS SW3 SW4
AO-3
9600 Off Off BACnet Off Off
19.2 K Off On MS/TP On Off
IN-1 38.4 K On Off N2 Off On Gnd
Inputs 1 & 2 76.8 K On On Modbus
REQUIRED BRANCH
CIRCUIT PROTECTION
BY OTHERS
VFD S/S
ALARM CONTACT
GND
24V COM
AC
SC
S1
A1
H
H
H
N
N
N
SC
S1
A1
H
H
H
N
N
N
TECHNICAL GUIDE
26 ENERGY RECOVERY WHEEL
Mounting Arrangements
The True 3 units can be mounted in six different positions (see Figure 14). The number of support points required for
horizontal mounting may vary depending on the size of the unit. Consult SEMCO for support details.
When installing an True 3 unit, the purge section must always face the conditioned airside of the system. Rotation
is such that a spot on the media in the return air section would rotate towards the purge section without first passing
into the supply section.
SA SA
RA
RA
RA SA
RA RA
SA
OA
EA
SA
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 27
ORDERING KEY
T__-__-_-_-_-_-_
TYPE OF UNIT
TE3: Total Energy Wheel
TS: Sensible Only Energy Wheel
MOTOR TYPE
0: 208/230V/1Ph/60Hz, Variable Speed, With Inverter
1: 208/230V/3Ph/60Hz, Variable Speed, With Inverter
2: 460V/3Ph/60Hz,Variable Speed, With Inverter
3: 208-230V/3Ph/60Hz, Variable Speed, Without Inverter
4: 460V/3Ph/60Hz, Variable Speed, Without Inverter
7: 208-230V/3Ph/60Hz, Constant Speed
8: 460V/3Ph/60Hz, Constant Speed
Note: Not all motors are available in all sizes
TEMPERATURE CONTROLLER
0: No controller
1: 24V/1Ph with 4 Point Sensors
2: 120V/1Ph with 4 Point Sensors
3: 24V/1Ph with Averaging SA & EA Sensors
4: 120V/1Ph with Averaging SA & EA Sensors
ROTATION DETECTOR
0: No rotation detector
1: 24V/1Ph
2: 120V/1Ph
TECHNICAL GUIDE
28 ENERGY RECOVERY WHEEL
UNIT DIMENSIONS
SIZE 13-70 SIZES 3, 5, 9
Mounting
MountingArrangements
Arrangements
A, A,
BB Mounting
MountingArrangements
Arrangements
C, C,
D, D,
E, E,
andand
FF
AA AA
Y
DD EE
V E E CC DD CC
BB BB
X
Dimensions (inches) Flow
Wheel Net Wt. Nominal
area /
Size A B C D E (lbs.) cfm
side, ft2
3 39.8 48.8 20.0 19.2 18.2 380 2.8 2,000
Z Z W
5 51.8 58.2 20.0 25.2 24.2 520 5.3 4,000
V 9 63.8 70.2 20.0 31.2 30.2 700 8.6 7,000
TECHNICAL GUIDE
ENERGY RECOVERY WHEEL 29
SAMPLE SPECIFICATION
A. Total Energy Recovery Wheel Unit - The rotor Purge Sector - The unit shall be provided with a
media shall be made of aluminum, which is coated factory set, field adjustable purge sector designed
to prohibit corrosion. All media surfaces shall be to limit cross contamination to less than .04 percent
coated with a non-migrating solid adsorbent layer of that of the exhaust air stream concentration when
prior to being formed into the honeycomb media operated under appropriate conditions.
structure to ensure that all surfaces are coated
Rotor Seals - The rotor shall be supplied with
and that adequate latent capacity is provided. The
labyrinth seals only, which at no time shall make
media shall have a flame spread of less than 25
contact with any rotating surface of the exchanger
and a smoke developed of less than 50 when rated
rotor face. These multi-pass seals shall utilize four
in accordance with ASTM E84. In addition to the
labyrinth stages for optimum performance.
desiccant coating that is applied to the surfaces
of the aluminum substrate, the two faces of the Rotor Support System - The rotor media shall be
total energy recovery wheel shall be covered and provided in segmented fashion to allow for field
sealed with a two part polymer heavy duty coating erection or replacement of one section at a time
specifically chosen for chemical resistance. without requiring side access. The media shall be
rigidly held in place by a structural spoke system
The desiccant shall be inorganic and specifically
made of extruded aluminum.
developed for the selective adsorption of water
vapor. The desiccant shall utilize a 3A molecular Rotor Housing - The rotor housing shall be a
sieve certified by the manufacturer to have an structural framework, which limits the deflection
internal pore diameter distribution which limits of the rotor due to air pressure loss to less than
adsorption to materials not larger than the critical 1/32. The housing is made of galvanized steel to
diameter of a water molecule (2.8 angstroms). prevent corrosion. The rotor is supported by two
pillow block bearings which can be maintained or
Submit certification by a qualified independent
replaced without the removal of the rotor from its
organization documenting equal sensible and latent
casing or the media from its spoke system.
recovery efficiencies conducted in accordance
with ASHRAE 84-78P and the results presented in Rotor Housing - The rotor housing shall be structural
accordance with ARI 1060 standards. framework, which limits the deflection of the rotor
due to air pressure loss to less than 1/32. The
An independent wheel test from a credible test
housing is made of galvanized steel to prevent
laboratory shall document that the desiccant
corrosion. The rotor is supported by two pillow
material utilized does not transfer pollutants typically
block bearings which can be maintained or replaced
encountered in the indoor air environment. The
without the removal of the rotor from its casing or
cross-contamination and performance certification
the media from its spoke system.
reports shall be provided upon written request for
engineering review. Optional Temperature Control Panel - Variable
speed control shall be accomplished by the use of
Media Cleaning - The media shall be cleanable with
an A/C inverter. The inverter shall include all digital
low-pressure steam (less than 5 PSI), hot water
programming with a manual speed adjustment on
or light detergent, without degrading the latent
the front of the inverter. The drive system shall allow
recovery. Dry particles up to 800 microns shall pass
for a turndown ratio of 100:1 (20 rpm to 1/5 rpm).
freely through the media.
The control system shall include four linearized
TECHNICAL GUIDE
30 ENERGY RECOVERY WHEEL
TECHNICAL GUIDE
Wheel ENERGY RECOVERY WHEEL 31
Configuration
Checklist Desiccant Wheel Products
RA SA
T__-__-_-_-_-_-_ Arrangement B
TYPE OF UNIT SA RA
Arrangement C
PURGE INDEX SETTING
0, 1, 2, 3, 4, 5, 6, 7
A, B, C, D, E, F
RA
MOTOR TYPE
0: 208/230V/1Ph/60Hz, Variable Speed, With Inverter
1: 208/230V/3Ph/60Hz, Variable Speed, With Inverter
2: 460V/3Ph/60Hz,Variable Speed, With Inverter
Arrangement D
3: 208-230V/3Ph/60Hz, Variable Speed, Without Inverter
4: 460V/3Ph/60Hz, Variable Speed, Without Inverter
7: 208-230V/3Ph/60Hz, Constant Speed
8: 460V/3Ph/60Hz, Constant Speed
Note: Not all motors are available in all sizes RA
SA
TEMPERATURE CONTROLLER
0: No controller
1: 24V/1Ph with 4 Point Sensors
2: 120V/1Ph with 4 Point Sensors Arrangement E
3: 24V/1Ph with Averaging SA & EA Sensors
4: 120V/1Ph with Averaging SA & EA Sensors
ROTATION DETECTOR SA
0: No rotation detector
1: 24V/1Ph RA
2: 120V/1Ph
Arrangement F
TECHNICAL GUIDE
32 ENERGY RECOVERY WHEEL
TECHNICAL GUIDE
Energy Recovery Wheel Technical Guide www.semcohvac.com
WE BRING
AIR TO LIFE
WWW.SEMCOHVAC.COM | Energy Recovery Wheel | 20160216
To learn more about SEMCO offerings and to contact your nearest representative please visit
www.semcohvac.com
SEMCO embraces a policy of continuous development and improvement, the right is reserved to supply products which may differ from those illustrated and described in this
publication. Certified dimensions will be supplied upon request on receipt of order.
SEMCO LLC 2015 All Rights Reserved. SEMCO and the SEMCO logo are registered Trademarks of SEMCO LLC.