Medium Voltage Distribution

Merlin Gerin Instrument Transformers


Catalogue
Current transformer - Voltage transformer
2000
Instrument
Tr a n s f o r m e r s

Instrument
Tr a n s f o r m e r s

We do more with electricity.


Instrument transformers
Contents

page

Main characteristics 2
A certified quality system 3
Current transformers 4
Current transformers types 4
Specifications 6
Standardized current transformers 8
Order form 34
Voltage transformers 35
Voltage transformers types 35
Specifications 36
Standardized voltage transformers 38
Order form 53

Schneider Instrument Transformers


Electric Merlin Gerin 1
Instrument Main characteristics
Transformers

The range of Merlin Gerin, brand of Schneider


Electric, instrument transformers has been designed Compliance with standards
for 0.72 kV to 36 kV voltage and rated currents from
5 A to 24000 A. All Merlin Gerin instrument transformers comply with IEC standards, sections
In order to comply with higher and higher short circuit 2099 2134, and with the recommendations of IEC 60044-1/IEC 60044-2.
levels in the systems, the current transformers have Transformers compliant with other countries regulations can also be supplied
been designed to withstand 60 kA x1 second short (AS 1675 AS 1243, IEEE C57.13, BS7626 BS7625, NFC 42502 NFC 42501,
circuit currents. VDE 0414 ).
All Merlin Gerin, brand of Schneider Electric,
instrument transformers are up to the new and Specifications
stricter provisions of the IEC standards
(partial discharge testing is performed after the The working parts (windings and magnetic cores) are entirely enclosed in an epoxy
induced voltage withstand test). resin in block casting, whose twofold function is to:
c guarantee electric insulation of the device both inside and outside
c Current transformers can be in accordance with: c ensure the highest strength.
v the precision classes "TPS-TPX-TPY-TPZ" defined
by the standards IEC 44-6 and referring to Product quality over time is guaranteed not only by thirty years of experience in the
transformer behaviour during short circuit transient manufacture of resin insulated instrument transformers but also by:
phases.
v standard IEC 79-7 EN 50.019 concerning the use c The use of silica-loaded epoxy resin resulting in:
of increased safety and protection electrical v high dielectric strength including at high temperatures
appliances in environments with potentially explosive (18 kV/mm at 180 C for 20000 hours)
atmosphere. v insulation class B according to IEC 60 044-1 provisions.

c Their standard shape, top electric performance, c Extremely good ageing behaviour both to heat mass ageing according to IEC 216
reduced weight and overall dimensions make these (over 20 years at 120 C) and to surface ageing obtained in salty mist
devices suitable for use in:
v metalclad units c In case of fire, no toxic substances are released in accordance with standards
v metal enclosed units IEC 20-37, IEC 20-22 and ASTM D 3286.
v large motor terminal strips
v environments with potentially explosive c Extremely effective behaviour in tropical climates.
atmosphere (Eex).
c High strength even at the highest working temperatures
(Martens point exceeding 105 C).

F2 Forces applied
not simultaneously
up to 100C
F1 F1 = 500 daN
F2 = 300 daN

c Accurate production process resulting in


v no blisters or blowholes in the resin thanks to vacuum casting
v low constant partial discharge value also thanks to the high quality of the other
insulating materials used (SF6 injection in voltage transformer windings)
v high strength and very good electric conductivity in primary and secondary
terminals even at the temperatures reached during a short circuit, thanks to
mechanical seaming
v process parameters remaining unchanged over time thanks to computer control
used to manage and monitor the whole production line.

Instrument Transformers Schneider


2 Merlin Gerin Electric
Instrument A Certified Quality System
Transformers

Quality is obtained by planning and implementing Magrini Galileo, brand of Schneider Electric can prove its Guaranteed Quality via:
every phase, from the initial design all through c documentations explaining the company quality policy
production and testing to product delivery and c the planning of each individual product development phase
after-sales service. c continuous assessment of special indicators showing any possible quality faults
This means operating in full application of the Quality throughout the production process
Guarantee. By this procedure it is possible to supply a c a set of technical/quality papers providing evidence of what has been done all
product with all the design characteristics on the one through the production and testing process in order to guarantee the required
hand, and to show the Customer all that is planned quality level.
and implemented in order to come up with a good
product on the other hand. Production process applies standard Guarantee and Quality Control methods.
Quality Control Plans ensure that established procedures are applied to product
checking from construction material reception all the way to product delivery.
The earliest phases of product design and industrialization are also set up and
verified according to Guaranteed Quality principles.

CSQ has certified Magrini Galileo Cie, subsidiary


of Schneider Electric
The CSQ (independent organization for the certification of company management
system) issued a declaration of compliance of Magrini Galileo with the
UNI - EN 29001 standards (ISO 9001), which requires a company to operate a
comprehensive Quality System covering all aspects from product definition to after
sales customer service.

CSQ is an independent
organisation for the
certification of company
management system,
member of the CISQ
(Italian Certifiers of
Company Quality Systems),
its active within the scope
of IMQ with the support of
CESI, these being
internationally
acknowledged boards in the
electrical engineering
industry.

Schneider Instrument Transformers


Electric Merlin Gerin 3
Current Current transformers types
Transformers

Post type
type reference short-circuit max possible refer notes
voltage thermal current primary number to
(kV) in multiple of rated of CT page
Ipn x 1 s current cores (n)
(max 60 kA x 1s) (A) (no.)
ARM1 7.2 - 12 100400 SR 800 1-2 8
ARM1 ARM2 ARQ1 17.5 - 24 DR 800-400 compact
ARM2 7.2 - 12 100630 SR 800 1-2-3 9 size
ARQ2 17.5 - 24 DR 800-400

ARM3 7.2 - 12 1001000 SR 800 1-2 10


ARQ3 17.5 - 24 DR 800-400
ARM4 7.2 - 12 1001200 SR 800 1-2-3 11
ARQ4 17.5 - 24 DR 800-400

ARM3 ARM4 ARM8 7.2 - 12 1001200 SR 800 1-2-3 22 for extra


17.5 - 24 - 36 DR 800-400 short
circuit
current or
extra high
output

ARPJ3 7.2 - 12 max 60 kA x 1s SR 1250 1-2-3 12 for high


17.5 -24 DR 1200-600 current and
ARJM3 7.2 - 12 max 60 kA x 1s SR 1600 1-2-3 13 compact
17.5 - 24 DR 1500-750 size
ARM8 ARJA1 7.2 - 12 max 60 kA x 1s SR 2500 1-2-3 14 for extra
17.5 - 24 DR 2000-1000 high current

AD12 7.2 - 12 107630 SR 800 1-2-3 15 according to


DR 800-400 DIN 42600
AD13 7.2 - 12 max 60 kA x 1 s SR 1250 1-2-3 16 according to
DR 1200-600 DIN 42600
AD21 7.2 - 12 1001000 SR 800 1-2- 17 according to
17.5 - 24 DR 800-400 DIN 42600
AD22 7.2 - 12 1001000 SR 800 1-2-3 18 according to
17.5 - 24 DR 800-400 DIN 42600
ARJA1 AD12
AD23 7.2 - 12 max 60 kA x 1s SR 1250 1-2-3 19 according to
17.5 - 24 DR 1200-600 DIN 42600

ARM6 36 1071000 SR 800 1-2 20


DR 800-400
ARM7 36 1071200 SR 800 1-2-3 21
DR 800-400
ARM9 36 max 60 kA x 1s SR 2500 1-2-3 23 for extra
DR 2000-1000 high current

ARM6 ARM7
Note
(1) SR = single ratio - DR = double ratio,
(2) All the apparatus have a 120% extended range, which means that the transformers can
be overloaded 20%beyond their rated current without exceeding the class.

ARM9

Instrument Transformers Schneider


4 Merlin Gerin Electric
Current
Transformers

Support type
type reference short-time max possible reter notes
voltage thermal current primary number to
(kV) (A) rated current of CT page
cores (n)
ARO1a 7.2-12 max 60 kA x Ipn SR 5000 1-2-3 24 without
primary for
ARO1b 17.5 DR 5000-2500 mounting
ARO2 24-36 max 60 kA x 1s SR 4000 1-2-3 25 directly on
ARO1 ARO2 busbar
DR 4000-2000

Toroidal type (cable mounting)


ARF1 0.72 max 60 kA x 1s SR 2500 1-2 26 epoxy resin
insulated
ARF2 0.72 max 60 kA x 1s SR 2500 1-2-3 27 epoxy resin
insulated
ARF3 0.72 max 60 kA x 1s SR 2500 1 28 epoxy resin
insulated
ARF1 ARF2 ARF4 0.72 max 60 kA x 1s SR 2500 1-2 29 epoxy resin
insulated
ARF5 0.72 max 60 kA x 1s SR 2500 1-2 30 epoxy resin
insulated
ARF6 0.72 max 60 kA x 1s SR 2500 1-2 31 epoxy resin
insulated
AOP-C 0.72 max 60 kA x 1s SR 2500 1-2 32

ARL4 0.72 max 60 kA x 1s SR 2500 1-2 33 for more


alined
cables
ARF3 ARL4
Note
(1) SR = single ratio - DR = double ratio,
(2) All the apparatus have a 120% extended range, which means that the transformers
can be overloaded 20%beyond their rated current without exceeding the class.

Schneider Instrument Transformers


Electric Merlin Gerin 5
Current Specifications
Transformers

Selection criteria Terminal markings


Single ratio
1 Define the Primary Current (Ipn)
Use the standard values prescribed by the IEC
standards:
10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75 A,
and their decimal multiples.
2 Define the Short Circuit Current
for 1 second Ith
The short circuit current generally refers to 1 second.
Should this current be known for different time values 1 secondary 2 secondaries 3 secondaries
"t", calculate the value for 1 second by applying the
following formula:
Ith (for 1 sec.) = Ith x t Double ratio with switching on the primary
(i.e. 25 kA for 3 sec. = 25 x e = 43.3 kA for 1 sec.)
3 Calculate the "K" coefficient
This value will be the access key to the various
tables.
Ith for 1 sec.
K=
Ipn

(i.e. Ipn = 100 A, Ith = 12.5 kA 1 sec.


 K = 12500/100 = 125.) 1 secondary 2 secondaries 3 secondaries

4 Position on the table


Enter the "K" column and position on the line Double ratio with tap on the secondary
corresponding to the K value immediately above
the calculated value.
(i.e. calculated K = 125 K line = 150.)
5 Check feasibility
A current transformer is feasible with the
specifications indicated in the columns marked with
boxes c.
1 secondary 2 secondaries 3 secondaries
Remarks:
For protection secondaries the following formula is
guaranteed:
A CT open secondary can be dangerous!
FI x VA = constant K
i.e. 10 VA / 5 P10 = 10 x 10 = 100 In case of a CT with several secondaries, short-circuit the ones that are not
5 VA / 5 P20 = 5 x 20 = 100 in use.

Warning:
This equation is only guaranteed during CT selection phase.

Current transformers with primary terminals


(available on request)
Horizontal terminals Vertical terminals

266 160
Dimensions (mm)
8
8

Type A B C
ARM1 250 290 310
14

ARM2 250 290 310


ARM3 300 340 360
A

ARM4 300 340 360


C
B

ARM6 370 410 430


ARM7 370 410 430
ARM8 370 410 430
14
P2
50

50
P1

P2

220
P1

Instrument Transformers Schneider


6 Merlin Gerin Electric
Current
Transformers

Rated performance Table for choosing primary current only for


calculation table measuring CTs
Power absorbed by measuring instruments and protection Standard range of primary current with ratio and phase
relays (alternating current 50 to 60 Hz) primary rated current errors practically constant
Type of instrument or relay VA
(with burden up to Ze = 2 )
Ammeter Isn
Eletromagnetic 3 VA
A A
Electronic 1 VA
5 26
Transducer
Self powered 3 VA 10 4 12
Power supply 1 VA 15 6 18
Meter 20 8 24
Induction 2 VA 25 10 30
Electronic 1 VA 30 12 36
Wattmeter - Varmeter 1 VA 40 16 48
Power factor meter 1 VA 50 20 60
Multifunction panel meters
60 24 72
and protections 1 VA
75 30 90
Differential protection CT characteristics
according to power 100 40 120
plant parameters 125 50 150
Copper cables links VA absorbed power 150 60 180
Section 1A 5A 200 80 240
cable (mm2) VA/m VA/m 250 100 300
2.5 0.008 0.2 300 120 360
4 0.005 0.13 400 160 480
6 0.003 0.09 500 200 600
10 0.002 0.05
600 240 720
800 320 960
Attention:
For calculation consider distance between CT and 1000 400 1200
instrument multiplied by two 1200 480 1440
1600 640 1920
2000 800 2400
2500 1000 3000
3000 1200 3600
4000 1600 4800
5000 2000 6000

VA = nominal output
Isn = secondary rated current
Ze = measuring instrument impedance (ohm)

Schneider Instrument Transformers


Electric Merlin Gerin 7
Post type with Current transformers
Wound primary ARM1/N1 - ARM1/N2
ARQ1/N1 - ARQ1/N2

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A. n of secondaries per CT 1 2
c Ipn primary rated current: see page 7. standard types ARM1/N1 ARM1/N2
c Iter short circuit thermal current (expressed as a ARQ1/N1 ARQ1/N2
multiple of Ipn): 100 400
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30
1st measuring secondary
class 0.5
Fs = 10
VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30
multiple primary measuring sec. protection sec. 2st protection secondary
of Ipn rated class 0.5 class 5P class 5P
max current (A) Fs = 10 Fl = 10 Fl = 10
60 kAx1s VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100

Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM2, ARM3, ARM4,ARM8

Dimensions (mm)
Type ARQ1/N1-N2 Type ARM1/N1-N2
Weight 13.5 kg Weight 14 kg

50 N4 fixing holes 50
M 8 x 12 86

110 43 M 12

GROUPE SCHNEIDER
287
282

279
75
274

248
243

GROUPE SCHNEIDER
240
235

P2
5

130
158
110

85
20

P1
65
115

115 97 200
N4 holes
158 225 11
M6 screw type 212 M6 screw type
secondary and earthing terminals
secondary and earthing terminals

Instrument Transformers Schneider


8 Merlin Gerin Electric
Post type with Current transformers
Wound primary ARM2/N1 - ARM2/N2 - ARM2/N3
ARQ2/N1 - ARQ2/N2 - ARQ2/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV n of secondaries per CT 1 2 3
c Isn secondary rated current: 1 or 5 A.
standard types ARM2/N1 ARM2/N2 ARM2/N3
c Ipn primary rated current: see page 7. ARQ2/N1 ARQ2/N2 ARQ2/N3
c Iter short circuit thermal current (expressed as a
1st meas. sec.
multiple of Ipn): 100 630 class 0.5
c Idin short circuit dynamic current: 2.5 Iter Fs = 10
c SR = Single Ratio VA
DR = Double Ratio with changeover on primary Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring secondary 2nd prot. sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec. 2nd protection secondary 3rd prot. sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75

Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM3, ARM4, ARM8
If such point should fall within the grey area, choose a smaller CT type:
ARM1.

Dimensions (mm)
Type ARQ2/N1-N2-N3 Type ARM2/N1-N2-N3
Weight kg 19 Weight kg 19.5
N4 fixing holes
M 8 x 12 50
50 110 86

43 M 12

NUOVA MAGRINI GALILEO


82

287
279

248
240
20
110

P2

130
158
282
274

85
5
243

GROUPE SCHNEIDER
235

90

P1
145

145 126 185 110 N4 holes


M6 screw type M6 screw type 11
158 secondary and earthing terminals 271 secondary and earthing terminals 328

Schneider Instrument Transformers


Electric Merlin Gerin 9
Post type with Current transformers
Wound primary ARM3/N1 - ARM3/N2
ARQ3/N1 - ARQ3/N2

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A. n. of secondaries per CT 1 2
c Ipn primary rated current: see page 7. standard types ARM3/N1 ARM3/N2
c Iter short circuit thermal current (expressed as a ARQ3/N1 ARQ3/N2
multiple of Ipn): 100 1000
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30
1st measuring sec.
class 0.5
Fs = 10
VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30
multiple primary measuring sec. protection sec. 2nd protection secondary
of Ipn rated class 0.5 class 5P class 5P
Max current (A) Fs = 10 Fl = 10 Fl = 10
60 kAx1s VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2.
If such point should fall within the white area, a larger CT type
should be used: ARM4 - ARM8.

Dimensions (mm) Dimensions (mm)


type ARQ3/N1-N2 type ARM3/N1-N2
Weight kg 19.5 Weight kg 20

50 N4 fixing holes 86 50 43 M 12
M 8 x 12

110
P1

NUOVA MAGRINI GALILEO


175
200
52

GROUPE SCHNEIDER
82

P2
338
330
333
325

300
292
295

110
287

23
120
90

225
5

N4 holes
11
260

198 M6 screw type 120 102 M6 screw type


secondary and earthing terminals secondary and earthing terminals
222

Instrument Transformers Schneider


10 Merlin Gerin Electric
Post type with Current transformers
Wound primary ARM4/N1 - ARM4/N2 - ARM4/N3
ARQ4/N1 - ARQ4/N2 - ARQ4/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A. n. of secondaries per CT 1 2 3
c Ipn primary rated current: see page 7. standard types ARM4/N1 ARM4/N2 ARM4/N3
c Iter short circuit thermal current (expressed as a ARQ4/N1 ARQ4/N2 ARQ4/N3
multiple of Ipn): 100 1200 1st meas. sec.
c Idin short circuit dynamic current: 2.5 Iter class 0.5
Fs = 10
c SR = Single Ratio
VA
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
Max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50
5 10-5
1200
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area..
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3.
If such point should fall within the white area, a larger CT type
should be used: ARM8.

Dimensions (mm) Dimensions (mm)


type ARQ4/N1-N2-N3 type ARM4/N1-N2-N3
Weight kg 27.5 Weight kg 28

50 N4 fixing holes 86 50 43 M 12
M 8 x 12

110
P1

GROUPE SCHNEIDER
175
200
52

GROUPE SCHNEIDER
P2
82

338
333

330
325

300
295

292
287

110

23

225
90

N4 holes
5
148

11
260

198 148 143


M6 screw type
M6 screw type secondary and earthing terminals
secondary and earthing terminals 291

Schneider Instrument Transformers


Electric Merlin Gerin 11
Post type with Current transformers
Bar primary ARJP3/N1 - ARJP3/N2 - ARJP3/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types ARJP3/N1 ARJP3/N2 ARJP3/N3
c Iter short circuit thermal current: 60 kA x 1s
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
DR = Double Ratio with changeover on secondary Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
800

1000

1200

1250

800-400

1000-500

1200-600

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARJP3/N1-N2-N3
Weight kg 22

72 M 12 x 23
P2
20

120
148

NUOVA MAGRINI GALILEO


P1
5

270

240

120
185 137 184
175 100 N4 slot
11
322 295
M6 screw type
secondary and earthing terminals

Instrument Transformers Schneider


12 Merlin Gerin Electric
Post type with Current transformers
Bar primary ARJM3/N1 - ARJM3/N2 - ARJM3/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A. n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types ARJM3/N1 ARJM3N2 ARJM3/N3
c Iter short circuit thermal current: 60 kA x 1s
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
DR = Double Ratio with changeover on secondary Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
800

1000

1200

1250

1600

800-400

1000-500

1200-600

1500-750

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARJM3/N1-N2-N3
Weight kg 25

M 12 x 23
NUOVA MAGRINI GALILEO
260
20

178
P2

120
148
P1

185 137
120
322
M6 screw type 184 N4 slot
secondary and earthing terminals 11
175 100
295

Schneider Instrument Transformers


Electric Merlin Gerin 13
Post type with Current transformers
Bar primary ARJA1/N1 - ARJA1/N2 - ARJA1/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types ARJA1/N1 ARJA1/N2 ARJA1/N3
c Iter short circuit thermal current: 60 kA x 1s
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
Fs = 10
DR = Double Ratio with changeover on secondary
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
1000

1200

1250

1500

1600

1800

2000

2500

1000-500

1500-750

2000-1000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARJP3.

Dimensions (mm)
type ARJA1/N1-N2-N3
Weight kg 30

M 12 x 23 Details of primary bars


GROUPE SCHNEIDER

Ipn Ipn Ipn


240

800 1250 A 1300 1600 A 1800 2500 A


20

P2

175
200
P1

40

45

160 148
58

70

M6 screw type
secondary and earthing terminals 120
308
60
184 60
N4 holes 70
225 11
260

Instrument Transformers Schneider


14 Merlin Gerin Electric
Post type with Current transformers
Wound primary AD12/N1 - AD12/N2 - AD12/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 kV
c Isn secondary rated current: 1 or 5 A. n of secondaries per CT 1 2 3
c Ipn primary rated current: see page 7. standard types AD12/N1 AD12/N2 AD12/N3
c Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 630 1st meas. sec.
c Idin short circuit dynamic current: 2.5 Iter class 0.5
Fs = 10
c SR = Single Ratio
VA
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot. sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec. 2nd protection secondary 3rd prot. sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75

Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.

Dimensions (mm)
TypeAD12/N1-N2-N3
Weight kg 20

M12 x 23 DETAIL PRIMARY DOUBLE RATIO CONNECTION TO CONNECTION TO


1 x Ipn 2 x Ipn
GROUPE SCHNEIDER

12.5
11

C1
P1
C1
P1

C1
P1
223

GROUPE SCHNEIDER
C2
C2

P2
C2

P2
P2
P1

P2

125
100

148

DIN 1030
M8 c c
Pg 16
18.5
254

M5 screw type secondary


and earthing terminals
120 N 4 holes 11
31

184
20

177 150
270

350

Schneider Instrument Transformers


Electric Merlin Gerin 15
Post type with Current transformers
Bar primary AD13/N1 - AD13/N2 - AD13/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types AD13/N1 AD13/N2 AD13/N3
c Iter short circuit thermal current: 60 kA x 1s
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
Fs = 10
DR = Double Ratio with changeover on secondary
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
800

1000

1200

1250

800-400

1000-500

1200-600

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type AD13/N1-N2-N3
Weight kg 20

M12 x 23
DIN 40430
M8
Pg 16 GROUPE SCHNEIDER
223
125

148
K

L
100

P1

P2
31

M5 screw type
secondary and earthing terminals
177 150
20

120 N4 holes 11

350
184

270

Instrument Transformers Schneider


16 Merlin Gerin Electric
Post type with Current transformers
Wound primary AD21/N1 - AD21/N2

c Max reference voltage for insulation:


7.2 12 17.5 24 kV
Selection table
c Isn secondary rated current: 1 or 5 A. n. of secondaries per CT 1 2
c Ipn primary rated current: see page 7. standard types AD21/N1 AD21/N2
c Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 1000
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30
1st measuring sec.
class 0.5
Fs = 10
VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30
multiple primary measuring sec. protection sec. 2nd protection secondary
of Ipn rated class 0.5 class 5P class 5P
Max current (A) Fs = 10 Fl = 10 Fl = 10
60 kAx1s VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type should be
used: AD22.

Dimensions (mm)
type AD21/N1-N2
Weight kg 23

12.5 80 M12 x 23 DETAIL PRIMARY DOUBLE RATIO CONNECTION TO CONNECTION TO


GROUPE SCHNEIDER
1 x Ipn 2 x Ipn
C1
C1

P1
P1
11

280

P2
P2

C2
C2

M8
P1

178

DIN 40430
150
100

Pg 16 18.5
319
P2

M5 screw type secondary


120 N4 holes 14 and earthing terminals
31

184
163 160
20

280
370

Schneider Instrument Transformers


Electric Merlin Gerin 17
Post type with Current transformers
Wound primary AD22/N1 - AD22/N2 - AD22/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A. n. of secondaries per CT 1 2 3
c Ipn primary rated current: see page 7. standard types AD22/N1 AD22/N2 AD22/N3
c Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 1000 1st meas. sec.
c Idin short circuit dynamic current: 2.5 Iter class 0.5
c SR = Single Ratio Fs = 10
VA
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
Max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
AD21.

Dimensions (mm)
type AD22/N1-N2-N3
Weight kg 28

12.5 M12 x 23 DETAIL PRIMARY DOUBLE RATIO CONNECTION TO CONNECTION TO


11

1 x Ipn 2 x Ipn
GROUPE SCHNEIDER
280

C1

C1
P1

P1
P1

P2

150

178
100

DIN 40430 M8
Pg 16
C2

C2
P2

P2
311

M5 screw type 18.5


120 N4 holes 14 secondary and earthing terminals
31

184
178 160
20

280
370

Instrument Transformers Schneider


18 Merlin Gerin Electric
Post type with Current transformers
Bar primary AD23/N1 - AD23/N2 - AD23/N3

c Max reference voltage for insulation: Selection table


7.2 12 17.5 24 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types AD23/N1 AD23/N2 AD23/N3
c Iter short circuit thermal current: 60 kA x 1s
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
Fs = 10
DR = Double Ratio with changeover on secondary
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
800

1000

1200

1250

1500

1600

2000

2500

DR

800-400

1000-500

1200-600

1500-750

1600-800

2000-1000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type AD23/N1-N2-N3
Weight kg 30

M12 x 23 DETAIL PRIMARY BARS


M8
DIN 40430 Ipn Ipn Ipn
Pg 16
GROUPE SCHNEIDER

800 1250 A 1300 1600 A 1800 2500 A


280
150

178
100

P2
P1

40
31

45

58

70

M5 screw type
178 160 120 secondary and earthing terminals
20

60
370 184 N4 holes 14 60
70
280

Schneider Instrument Transformers


Electric Merlin Gerin 19
Post type with Current transformers
Wound primary ARM6/N1 - ARM6/N2

c Max reference voltage for insulation: 36 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see page 7 n. of secondaries per CT 1 2
c Iter short circuit thermal current (expressed as a standard types ARM6/N1 ARM6/N2
multiple of Ipn): 100 1000
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30
1st measuring sec.
class 0.5
Fs = 10
VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30
multiple primary measuring sec. protection sec 2nd protection secondary
of Ipn rated class 0.5 class 5P class 5P
Max. current (A) Fs = 10 Fl = 10 Fl = 10
60 kAx1s VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM7 - ARM8.

Dimensions (mm)
type ARM6/N1-N2
Weight kg 22
86 50 43 M 12
P1

175
200

GROUPE SCHNEIDER
52
P2
408
400

370
362

225
N4 holes
23

11
260
5

122 102
M6 screw type
secondary and earthing terminals
224

Instrument Transformers Schneider


20 Merlin Gerin Electric
Post type with Current transformers
Wound primary ARM7/N1 - ARM7/N2 - ARM7/N3

c Max reference voltage for insulation: 36 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see page 7 n. of secondaries per CT 1 2 3
c Iter short circuit thermal current (expressed as a standard types ARM7/N1 ARM7/N2 ARM7/N3
multiple of Ipn): 100 1200
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
Fs = 10
DR = Double Ratio with changeover on primary
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
Max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50
5 10-5
1200
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM6
If such point should fall within the white area, a larger CT type
should be used: ARM8.

Dimensions (mm)
type ARM7/N1-N2-N3
Weight kg 30
86 50 43 M 12
P1

175
200

GROUPE SCHNEIDER
52
GROUPE SCHNEIDER

P2
408
400

370
362

225 N4 holes
11
23

260

157 150
M6 screw type
secondary and earthing terminals
307

Schneider Instrument Transformers


Electric Merlin Gerin 21
Post type with Current transformers
Wound primary ARM8/N1 - ARM8/N2 - ARM8/N3

c Max reference voltage for insulation: Selection table


Um 7.2 - 12 - 17.5 - 24 - 36 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see page 7 standard types ARM8/N1 ARM8/N2 ARM8/N3
c Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 1200 1st meas. sec.
c Idin short circuit dynamic current: 2.5 Iter class 0.5
Fs = 10
c SR = Single Ratio
VA
DR = Double Ratio with changeover on primary
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
"Iter" lpn alternativaly 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
of Ipn rated class 0.5 class 5P class 5P class 5P
Max. current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5 6-3
100
800 800-400
20 40-20
160
300 600-300
20 40-20
200
300 600-300
15 30-15
250
200 400-200
10 20-10
320
150 300-150
5 10-5
400
100 200-100
5 10-5
500
100 200-100
5 10-5
630
75 150-75
5 10-5
800
50 100-50
5 10-5
1000
50 100-50
5 10-5
1200
50 100-50

Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3 - ARM4 for Um 24 kV;
ARM6 - ARM7 for Um = 36 kV.

Dimensions (mm)
type ARM8/N1-N2-N3
Weight kg 45
86 50 43 M 12

GROUPE SCHNEIDER
P1

175
200
249
52
GROUPE SCHNEIDER

P2
408
400

370
362
23

225 N4 holes
5

11
260

152 150
M6 screw type
secondary and earthing terminals
302

Instrument Transformers Schneider


22 Merlin Gerin Electric
Post type with Current transformers
Bar primary ARM9/N1 - ARM9/N2 - ARM9/N3

c Max reference voltage for insulation: 36 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2 3
c Iter short circuit thermal current: 60 kA x 1s standard types ARM9/N1 ARM9/N2 ARM9/N3
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio 1st meas. sec.
DR = Double Ratio with changeover on secondary classe 0.5
Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
1000

1200

1250

1500

1600

1800

2000

2500

1000-500

1500-750

2000-1000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARM9/N1-N2-N3
Weight kg 35

M 12 x 23 DETAILS OF PRIMARY BARS

GROUPE SCHNEIDER
Ipn Ipn
800 1600 A 1800 2500 A
200
P2

175
362

P1

40

45
23

70

120
5

184
70
225 N4 holes
157 150 M6 screw type 260 11 70
secondary and earthing terminals
307

Schneider Instrument Transformers


Electric Merlin Gerin 23
Support type Current transformers
Without primary ARO1a/N1 - ARO1a/N2 - ARO1a/N3
ARO1b/N1 - ARO1b/N2 - ARO1b/N3

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 kV
c Isn secondary rated current: 1 or 5 A n. of secondaries per CT 1 2 3
c Ipn primary rated current: see selection table standard types ARO1a/N1 ARO1a/N2 ARO1a/N3
c Iter short circuit thermal current: 60 kA x 1s ARO1b/N1 ARO1b/N2 ARO1b/N3
c Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
c SR = Single Ratio class 0.5
Fs = 10
DR = Double Ratio with changeover on secondary
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
1000

1200

1500

2000

3000

4000

5000

2000-1000

3000-1500

4000-2000

5000-2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARO1a/N1-N2-N3 and ARO1b/N1-N2-N3
Weight kg 27
L


175
200

P1 P2
369
230
23

GROUPE SCHNEIDER

225
5

N4 holes
11
260

c type ARO1a/N1-N2-N3
M6 screw type secondary
L = 238 mm = 110 mm and earthing terminals
c type ARO1b/N1-N2-N3
Connection between primary
L = 248 mm = 130 mm and shielding (lenght 300 mm)

Instrument Transformers Schneider


24 Merlin Gerin Electric
Support type Current transformers
Without primary ARO2/N1 - ARO2/N2 - ARO2/N3

c Max reference voltage for insulation: 24 - 36 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2 3
c Iter short circuit thermal current: 60 kA x 1s standard types ARO2/N1 ARO2/N2 ARO2/N3
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio 1st meas. sec.
DR = Double Ratio with changeover on secondary class 0.5
Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
1000

1200

1500

2000

3000

4000

2000-1000

3000-1500

4000-2000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARO2/N1-N2-N3 248
Weight kg 32
110
175
200

P1 P2
420
280

225 N4 holes
23

GROUPE SCHNEIDER

11
5

260

M6 screw type secondary


and earthing terminals

connection between primary


and shielding (lenght 300 mm)

Schneider Instrument Transformers


Electric Merlin Gerin 25
Toroidal type Current transformers
ARF1/N1 - ARF1/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2 3
c Iter short circuit thermal current: 60 kA x 1s standard types ARF1/N1 ARF1/N2 ARF2/N3
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio 1st meas. sec.
DR = Double Ratio with changeover on secondary class 0.5
Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 7.5 10 20 30 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 15 20 30 20 30 5 10 10 15 20
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 5 10 10 15 20
50 50-100 *
100 100-200 * * *
150 150-300 * * **
200 200-4 ** ** **** *
300 300-600

400 400-800

600 600-1200

800 800-1600

1000 1000-2000

1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
3) In case of double (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF1/N1-N2
Weight kg 8

85
25

100

M6 secondary
terminals
140

170
198
GROUPE SCHNEIDER
7

P1

170
N4 slot
198 9 x 11
130
229

Instrument Transformers Schneider


26 Merlin Gerin Electric
Toroidal type Current transformers
ARF2/N1 - ARF2/N2 - ARF2/N3

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2 3
c Iter short circuit thermal current: 60 kA x 1s standard types ARF2/N1 ARF2/N2 ARF2/N3
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio 1st meas. sec
DR = Double Ratio with changeover on secondary class 0.5
Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 7.5 10 20 30 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 5 7.5 10 15 15 20 30 20 30 5 10 10 15 20
Ipn measuring sec. protection sec 2nd protection secondary 3rd prot.sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 5 10 10 15 20
50 50-100 *
100 100-200 *
150 150-300 * * **
200 200-400 ** ** ** ** *
300 300-600

400 400-800

600 600-1200

800 800-1600

1000 1000-2000

1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
If such point should fall within the grey area, choose a smaller CT type:
ARF1.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF2/N1-N2-N3
Weight kg 12

85
25

150

M6 secondary
140

170
198
7

GROUPE SCHNEIDER

terminals
P1

170 N4 slot
198 9 x 11

130
229

Schneider Instrument Transformers


Electric Merlin Gerin 27
Toroidal type Current transformers
ARF3/N1

c Max reference voltage for insulation: 0.72 kV


c Isn secondary rated current: 1 or 5 A
Selection table
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2 3
c Iter short circuit thermal current : 60 kA x 1s standard types ARF3/N1 ARF3/N2 ARF3/N3
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio 1 sec. misura
DR = Double Ratio with changeover on secondary classe 0.5
Fs = 10
VA
Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
2 sec. prot.
class 0.5 class 5P
Fs = 10 FI = 10
VA VA
alternatively 15 20 20 30 30 30 30 30 5 5 7.5 10 15
Ipn measuring sec. protection sec 3 sec. prot.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50
50 100-50

100 200-100 * **
150 300-150 * ** *
200 400-200 ** **** **
300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1200

1500

2000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF3/N1
Weight kg 7

105
30

S2
S1 S3
100

M6 secondary P1

terminals
198
GROUPE SCHNEIDER
83

113

Instrument Transformers Schneider


28 Merlin Gerin Electric
Toroidal type Current transformers
ARF4/N1 - ARF4/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2
c Iter short circuit thermal current : 60 kA x 1s standard types ARF4/N1 ARF4/N2
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on secondary

Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30


1st meas. sec.
class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 15 20 30 20 30 30 30
Ipn measuring sec. protection sec 2nd protection secondary
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 30 50
50 100-50 ***
100 200-100 * ** *** *
150 300-150 * ** * **
200 400-200 ** **** ** ** **** **
300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF4/N1-N2
Weight kg 14

105
25

100

M6 secondary
terminals
140

200
238
7

GROUPE SCHNEIDER

P1

200
238 N4 slot
9 x 11
152
271

Schneider Instrument Transformers


Electric Merlin Gerin 29
Toroidal type Current transformers
ARF5/N1 - ARF5/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
n. of secondaries per CT 1 2
c Ipn primary rated current: see selection table
c Iter short circuit thermal current : 60 kA x 1s standard types ARF5/N1 ARF5/N2
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on secondary

Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30


1st measuring sec.
class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 15 20 30 20 30 30 30
Ipn measuring sec. protection sec 2nd protection secondary
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 30 50
50 100-50 ***
100 200-100 * * ***
150 300-150 * **
200 400-200 ** **** **
300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF5/N1-N2
Weight kg 12

125
25

100

M6 secondary
terminals
140

200
238
GROUPE SCHNEIDER
7

P1

200
238 N4 slot
9 x 11
152
271

Instrument Transformers Schneider


30 Merlin Gerin Electric
Toroidal type Current transformers
ARF6/N1 - ARF6/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
n. of secondaries per CT 1 2
c Ipn primary rated current: see selection table
c Iter short circuit thermal current : 60 kA x 1s standard types ARF6/N1 ARF6/N2
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on secondary

Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30


1st measuring sec.
class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 15 20 30 20 30 30 30
Ipn measuring sec. protection sec 2nd protection secondary
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 30 50
50 100-50

100 200-100 ***


150 300-150 * * ***
200 400-200 ** ****
300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF6/N1-N2
Weight kg 10

150
25

100

M6 secondary
terminals
140

200

238
GROUPE SCHNEIDER
7

P1

200
238 N4 slot
9 x 11
152
271
Schneider Instrument Transformers
Electric Merlin Gerin 31
Toroidal type Current transformers
AOP-C/N1 - AOP-C/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2
c Iter short circuit thermal current : 60 kA x 1s standard types AOP-C/N1 AOP-C/N2
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on secondary

Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30


1st measuring sec.
class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 15 20 30
Ipn measuring sec. protection sec 2nd protection sec.
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 10 10 20 20 30 50
50 100-50 ***
100 200-100 * * ***
150 300-150 * ** ***
200 400-200 ** **** ** *** **
300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500 3000-1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type AOP-C/N1-N2
Weight kg 15

200
GROUPE SCHNEIDER
25

100

M6 secondary
terminals
373
7

P1
140

290
330

225
N4 slot
264 9 x 11

208

Instrument Transformers Schneider


32 Merlin Gerin Electric
Toroidal type Current transformers
ARL4/N1 - ARL4/N2

c Max reference voltage for insulation: 0.72 kV Selection table


c Isn secondary rated current: 1 or 5 A
c Ipn primary rated current: see selection table n. of secondaries per CT 1 2
c Iter short circuit thermal current : 60 kA x 1s standard types ARL4/N1 ARL4/N2
c Idin short circuit dynamic current: 2.5 Iter
c SR = Single Ratio
DR = Double Ratio with changeover on secondary

Iter lpn in alternativa 5 7.5 10 15 20 20 30 30 30 30 30


1st measuring sec.
class 0.5
Fs = 10
VA
alternatively 5 5 10 20 30 30 50 50
Ipn measuring sec. protection sec 2nd protection sec.
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 10 10 20 20 30 30 50
600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500 3000-1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARL4/N1-N2
Weight kg 30
25

100

220
90
GROUPE SCHNEIDER

M6 secondary
terminals

400

557

Schneider Instrument Transformers


Electric Merlin Gerin 33
Current transformers
Order form

Part 1

Type: _________________________________________________________________________________________________________

Maximum voltage level for insulation (kV): 7.2  12  17.5  24  36 

Number of secondaries: 1 2 3

Primary rated current: _______________________________________________


Double primary ratio: ________________________________________________
Secondary rated current: _____________________________________________
Rating short time current as a multiple of Ipn (max 60 kA x 1s): _______________
1st secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________

2nd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________

3rd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________

Extended range (if different from 120%) _________________________________

Standards: IEC  Others 

Part 2 - Optional accessories

Capacitive tap: 

Sealable covers on secondary terminals: 

Bus bar for ARM: horizontal  vertical 

Part 3 - Special versions

Safety factor: 5 Others 

Frequency: 60 Hz  Others 

Accuracy limit factor: 15  20  30  40 

Transformers for potentially explosive areas (EEx-e): 

Ratio change on secondary: 

Others:

Note
Apparatus with the following features are defined as standard:
 electrical features, max. reference voltage, rated current, output and class strictly as indicated in the table of option from page 8 to 33
 primary contacts and terminals, if requested, are tin plated
 pickled copper secondary terminals
 fixtures, if any, are zinc-plated steel.

Instrument Transformers Schneider


34 Merlin Gerin Electric
Voltage transformers Voltage transformers types

single (grounded) pole - phase-ground


type reference maximum output rated refer notes
voltage measuring protection max to
class 0.5 class 3P thermal page
output
kV VA VA VA n
VRFR 7.2-12 15 30 150 compact
38 size
VRFRn 17.5 30 30 200
VRF1 7.2-12 30 30 200
39
VRF1n 17.5 50 50 250
VRFR VRF1
VRF2 12-17.5 50 50 250
40
VRF2n 24 100 100 300
VRQ1 7.2-12 75 75 250 for high
41 output and
VRQ1n 17.5-24 100 100 300 compact size
VRQ2 7.2-12 30 30 200 compact
42 size
VRQ2n 17.5-24 50 50 250
VRF3 75 75 350
24-36 43
VRF3n 100 100 450
VRF2 VRQ1
VRF3Z 7.2-12 200 100 800 for high output
44 and power
VRF3Zn 17.5-24-36 250 100 1000
VDF11 7.2-12 15 30 150 according
45
VDF11n 17.5 30 30 200 to DIN 42600
VDF21 7.2-12 30 30 200 according
46
VDF21n 17.5-24 50 50 250 to DIN 42600

VRQ2 VRF3 two (insulated) poles - phase-phase


type reference prestazione massima potenza refer notes
voltage misura protezione termica to
classe 0.5 classe 3P nominale page
massima
kV VA VA VA n
VRCR 7.2-12 50 200 47 ultra
compact
size
VRC1 7.2-12 100 300 48
17.5
VDC21 VRC1
VRC2 12-17.5 100 500 49
24
VRC3 24-36 100 700 50
VDC11 7.2-12 50 200 51 according to
DIN 42600
VDC21 7.2-12 100 300 52 according to
17.5-24 DIN 42600

VRCR VRC3

Schneider Instrument Transformers


Electric Merlin Gerin 35
Voltage transformers Specifications

Notes on the phenomenon Connection diagram


known as ferroresonance A A A

A single-pole VT, connected between phase and earth,


installed on mains with insulated neutral wire or not
effectively grounded, may exhibit the phenomenon of
ferroresonance.
N N N
The voltage transformer inductance and system
capacity to ground (line or cable capacity, power factor
correction condensers etc.) will generate a potentially n n n

oscillating RLC circuit. Should an overvoltage occur in


the medium voltage system for any reason (phase-
earth fault, operated switches ), such overvoltage will
increase the VT working induction and therefore cause
the magnetization impedance value to decrease to a a a a
value similar to the system capacitive impedance.
The similarity of these two impedance values will da da da

produce resonance.

In the RLC oscillator circuit, oscillations are created


with a frequency of approximately 1/3 of the mains
frequency, which will occur as soon as ceases the dn dn dn
overvoltage that had caused the phenomenon.
These low-frequency oscillations will determine a
59
saturation of the VT magnetic core and considerably
decrease its magnetic reactance value. All this results Rs
in high circulation of magnetizing current in the primary
winding of the device, with a secondary winding only 59 = Damping resistor
mildly affected by this phenomenon. Rs = Voltage relay

The high density of current existing in the VT primary


winding will cause transformer overheating, The "antiferroresonant" devices by Magrini Galileo have been designed and built in
development of high-pressure gas and even, if the compliance with the above-mentioned specifications on work induction and are
phenomenon persists, resin envelope bursting. always equipped with a secondary winding to provide delta connection for a damping
resistor. Standard protection devices can be connected in parallel
c The steps to be taken in order to remove this to this resistor, so that the same connection can be used for two different purposes.
phenomenon or its consequences are:
v build VTs with the lowest possible rated induction
according to the size of the devices and their required Notes on the application of protections
performance, so that the knee point in the core on the primary
magnetization curve is never reached, not even in the The only purpose of using a fuse on the transformer primary winding is to protect
presence of overvoltage. This will guarantee a very the system upstream from the device. The MV fuse will not therefore prevent any
high transformer impedance value damage to the VT and the subsequent discharge to earth, but will disconnect any
v the tertiary windings, normally in a delta connection, faulty device thus allowing normal system operation. We suggest to use Schneider
should be connected in series to a resistor powerful fuses of the Tepefuse type, specially made for this purpose and available from the
enough to quickly dampen any oscillation that might CAM 4S1 A I catalogue.
occur.

Notes on the application of protections


M6 terminals on the secondary
382 In compliance with the standard IEC 2314, voltage transformers should be able to
39 304 39 withstand a 1 second short circuit at their secondary terminals without being
damaged. Should the short circuit time at secondary terminals be longer,
the transformer may be irreparably damaged. In order to protect the transformer,
100

we recommend to insert fuses or automatic circuit breakers in the secondary circuit


116
1

in the immediate vicinity of the VT. We suggest to use 10A/500V fuses for "earth
70 pole" devices and 6A/500V fuses for "insulated poles" devices.
Fairleadbush 12
Fixing slots 20 x 8
20

120

354

Instrument Transformers Schneider


36 Merlin Gerin Electric
Voltage transformers

Selection criteria Terminal markings


1 Define the Primary Voltage Up
According to the installation voltage (U) and the type of
Single (grounded) pole
transformer connection: between phase and earth:
(Up = U/e) or between phase and phase (Up = U)
VT accuracy is always guaranteed between 0.8 Un and
1.2 Un. Use this information to choose
standard voltage values.
2 Define the rated insulation level
The rated insulation level should be that immediately
above the primary voltage level.
N.B.: The industrial power frequency test according to
IEC standards should be carried out by applying the
1 secondary 2 secondaries 2 secondaries
formula: (instrument or protection) (one instrument and one residual voltage) (two instrument
5 x Up with a maximum value given by the and/or protections)
corresponding insulation value. separate operation simultaneous operation
3 Define the secondary voltage Us
The standard values are 100 and 110 divided by e,
for instrument and protection Y-connected windings,
and 100 and 110 divided by 3 for residual voltage
open delta connection.
4 Define the frequency
Values are either 50 or 60 Hz.
5 Voltage factor
It is the factor by which the primary voltage Up should
be multiplied in order to determine the maximum
insulation voltage for the Um device.
3 secondaries double primary ratio
v 1.9 for 8 hours for insulated pole voltage
(2 instrument and/or protections (with tap at secondary)
transformers (phase-earth)
plus 1 residual voltage)
v 1.2 permanent for insulated pole voltage simultaneous operation for the first a1 - n small ratio a2 - n high ratio
transformers (phase-phase) two and separate operation for the third
6 Position on the table
Enter the column corresponding to the number of Two (insulated) poles
secondaries and the type of operation (simultaneous or
separate).
7 Check feasibility
The feasible characteristics are identified by the
columns with boxes marked:

Rated performance calculation one secondary (instrument or protection) double primary ratio (with tap at secondary)
a1 - b small ratio; a2 - b high ratio
table
Power absorbed by measuring instruments and Maximum Single (grounded) pole Two (insulated) poles
protection relays reference
(alternating current 50 to 60 Hz) voltage for
Type of instrument or relay insulation

Voltmeter 7.2 kV 3: e - 3.3: e - 6: e - 6.6: ekV 3 - 3.3 - 6 - 6.6 kV

Electromagnetic 5 VA 12 kV 6: e - 6.6: e - 10: e - 11: e kV 6 - 6.6 - 10 - 11 kV


Electronic 1 VA 17.5 kV 10: e - 11: e - 15: e kV 10 - 11 - 15 kV
Transducer
24 kV 15: e - 20: e - 22: e - 24: ekV 15 - 20 - 22 - 24 kV
Self powered 5 VA
Power supply 2 VA 36 kV 25: e - 30: e - 33: e - 36: ekV 25 - 30 - 33 - 36 kV
Meter
Induction 5 VA
Digital 4 VA
Wattmeter - Varmeter 5 VA
Power factor meter 5 VA
Multifunction panel meter & prot. 1 VA
Microprocessor relay 1 VA
Frequency meter 5 VA

Schneider Instrument Transformers


Electric Merlin Gerin 37
Single (grounded) pole Voltage transformers
Phase ground VRFRn/S1 - VRFRn/S2 (high induction)
VRFR/S1 - VRFR/S2 (low induction)

c Max reference voltage for insulation: Selection table


7,2 - 12 - 17,5 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2
c Upn primary rated voltage: refer to page 37 standard types VRFRn/S1 VRFRn/S2
VRFRn/S2
c winding in class 0.2-0.5-1 are also guaranteed in VRFR/S1 VRFR/S2
VRFR/S2
class 3P with the same output as indicated in the table 1 for measuring
1 for measuring
c rated thermal output: application measuring or 1 for protection
or protection
protection or measuring
1 for residual
VRFRn = 200 VA
voltage
VRFR = 150 VA
standard secondary 100:e- 100:eor 100:eor 100:3 or
c voltage factor: 1,9 x 8 hours 100:e or 110:e
voltage (V) 110:e- 110:e 110:e- 110:3
operation
simultaneous (1) separate (2)
3rd sec. accuracy class
output
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P
output 10 15 2015 30 50 10 15 20 15 30 50 3050 75 30 30 75
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5
output 10 15 20 15 30 50 10 15 20 15 20 30 10 15 20 15 30 50 10 20 30 50
VRFRn
VRFR
(1) Output with simultaneous operation means that accuracy class of the 1st secondary
is guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed
with a simultaneous operation.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRFRn/S1-S2
VRFR/S1-S2
Weight kg 15
M 10
125
148

A
221

NUOVA MAGRINI GALILEO


30

270
5

N4 holes
M6 screw type secondary 11
and earthing terminals 300
140 117

257

Instrument Transformers Schneider


38 Merlin Gerin Electric
Single (grounded) pole Voltage transformers
Phase ground VRF1n/S1 - VRF1n/S2 - VRF1n/S3 (1)
VRF1/S1 - VRF1/S2 - VRF1/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7,2 - 12 - 17,5 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRF1n/S1 VRF1n/S2 VRF1n/S2 VRF1n/S3
c winding in class 0.2-0.5-1 are also guaranteed VRF1/S1 VRF1/S2 VRF1/S2 VRF1/S3
in class 3P with the same output as indicated in 1 for measuring
1 for measuring 2 for meas.
the table application measuring or 1 for protection
or protection or protec.
protection or measuring
1 for residual 1 for res.
c rated thermal output:
voltage voltage
VRF1n = 250 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
VRF1 = 200 VA voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
c voltage factor: 1.9 x 8 hours 100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 30 50 75 100
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 10 15 2015 25 30 30 50 75 30 50 75 10 20 30 50
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 15 30 50 40 50 75 10 15 2015 25 30 15 25 30 30 5075 10 20 30 50
VRF1n
VRF1
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is guaranted
with 1st secondary under load. In this case, classe 3P remains guaranteed with a simultaneous
operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary and
separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRF1n/S1-S2
VRF1/S1-S2-S3
Weight kg 21
M 10 170
155
180

A
240
30

155
NUOVA MAGRINI GALILEO

N4 holes
11
225
177 155
M6 screw type secondary
and earthing terminals
332

Schneider Instrument Transformers


Electric Merlin Gerin 39
Single (grounded) pole Voltage transformers
Phase ground VRF2n/S1 - VRF2n/S2 - VRF2n/S3 (1)
VRF2/S1 - VRF2/S2 - VRF2/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRF2n/S1 VRF2n/S2 VRF2n/S2 VRF2n/S3
c winding in class 0.2-0.5-1 are also guaranteed in VRF2/S1 VRF2/S2 VRF2/S2 VRF2/S3
class 3P with the same output as indicated in the table 1 for measuring 1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection or protection or protec.
protection or measuring 1 for residual 1 for res.
VRF2n = 300 VA
voltage voltage
VRF2 = 250 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 30 50 100 150
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 10 15 2030 50 75 50 75 100 50 75 100 10 20 50 75
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 25 40 50 50 75 100 10 15 2030 50 75 20 30 50 30 50 100 10 20 50 75
VRF2n
VRF2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRF2n/S1-S2
VRF2/S1-S2
Weight kg 29
M 10 186
175
200

A A
300
30

225 N4 holes
5

NUOVA MAGRINI GALILEO

11
260

177 155
M6 screw type secondary
332 and earthing terminals

Instrument Transformers Schneider


40 Merlin Gerin Electric
Single (grounded) pole Voltage transformers
Phase ground VRQ1n/S1 - VRQ1n/S2 - VRQ1n/S3 (1)
VRQ1/S1 - VRQ1/S2 - VRQ1/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7.2 -12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRQ1n/S1 VRQ1n/S2 VRQ1n/S2 VRQ1n/S3
c winding in class 0.2-0.5-1 are also guaranteed in VRQ1/S1 VRQ1/S2 VRQ1/S2 VRQ1/S3
class 3P with the same output as indicated in the table 1 for measuring 1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection or protection or protec.
protection or measuring 1 for residual 1 for res.
VRQ1n = 300 VA
voltage voltage
VRQ1 = 250 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 75 100150 200
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 15 20 3030 50 75 50 50 75 50 75 10030 50 75 100
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 30 40 50 75 10015015 20 3030 50 75 25 40 50 50 75100 30 50 75 100
VRQ1n
VRQ1
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRQ1n/S1-S2-S3
VRQ1n/S1-S2-S3
Weight kg 30
M 10 158 N4 holes M 6 x 8

A
144
82
275
25

GROUPE SCHNEIDER

180

187 170
M6 screw type secondary
357 and earthing terminals

Schneider Instrument Transformers


Electric Merlin Gerin 41
Single (grounded) pole Voltage transformers
Phase ground VRQ2n/S1 - VRQ2n/S2 - VRQ2n/S3 (1)
VRQ2/S1 - VRQ2/S2 - VRQ2/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRQ2n/S1 VRQ2n/S2
VRQ2n/S2 VRQ2n/S3
c winding in class 0.2-0.5-1 are also guaranteed in VRQ2/S1 VRQ2/S2
VRQ2/S2 VRQ2/S3
class 3P with the same output as indicated in the table 1 for measuring
1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection
or protection or protec.
protection or measuring
1 for residual 1 for res.
VRQ2n = 250 VA
voltage voltage
VRQ2 = 200 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult. and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 3010 15 20 15 30 50 50 50 75 100
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 20 15 3050 10 15 2015 30 50 50 50 75 50 5075 10 20 30 50
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 15 20 30 30 50 75 10 15 2015 30 50 15 20 30 30 50 75 10 20 30 50

VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary and
separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRQ2n/S1-S2-S3
VRQ2/S1-S2-S3
Weight kg 19
M 10 170 N4 holes
M6x8

A
265

135
82
25

NUOVA MAGRINI GALILEO

115
160 138
M6 screw type secondary
298 and earthing terminals

Instrument Transformers Schneider


42 Merlin Gerin Electric
Single (grounded) pole Voltage transformers
Phase ground VRF3n/S1 - VRF3n/S2 - VRF3n/S3 (1)
VRF3/S1 - VRF3/S2 - VRF3/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


24 - 36 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRF3n/S1 VRF3n/S2 VRF3n/S2 VRF3n/S3
c winding in class 0.2-0.5-1 are also guaranteed in VRF3/S1 VRF3/S2 VRF3/S2 VRF3/S3
class 3P with the same output as indicated in the table 1 for measuring 1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection or protection or protec.
VRF3n = 450 VA protection or measuring 1 for residual 1 for res.
voltage voltage
VRF3 = 350 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 75 100 120 150
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 15 30 5030 50 75 50 75 75 50 75 100 30 50 75 100
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 30 60 75 75 10015015 30 5030 50 75 25 30 50 50 75 100 30 50 75 100
VRF3n
VRF3

(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRF3n/S1-S2-S3
VRF3/S1-S2-S3
VRF/S1-S2-S3
Weight kg 45
M 10 230
225
255

A
390

300
30

N4 holes
11
5

GROUPE SCHNEIDER

325

192 170
M6 screw type secondary
362 and earthing terminals

Schneider Instrument Transformers


Electric Merlin Gerin 43
Single (grounded) pole Voltage transformers
Phase ground VRF3Zn/S1 - VRF3Zn/S2 - VRF3Zn/S3 (1)
VRF3Z/S1 -VRF3Z/S2 -VRF3Z/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 - 24 - 36 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VRF3Zn/S1 VRF3Zn/S2
VRF3Zn/S2 VRF3Zn/S3
c winding in class 0.2-0.5-1 are also guaranteed in VRF3Z/S1 VRF3Z/S2
VRF3Z/S2 VRF3Z/S3
class 3P with the same output as indicated in the table 1 for measuring
1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection
or protection or protec.
protection or measuring
1 for residual 1 for res.
VRF3Zn = 1000 VA
voltage voltage
VRF3Z = 800 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 100100 120150
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 50 75 100100150175 100 100120100100 120100120150175
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 100150175200300350 50 75 100100150175 100150175 200300350 100120150 175
VRF3Zn
VRF3Z
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRF3Zn/S1-S2-S3
VRF3Z/S1-S2-S3
Weight kg 65
M 10
230
225
255

A
390

300
30

N4 holes
11
5

GROUPE SCHNEIDER

325

197 175
M6 screw type secondary
372 and earthing terminals

Instrument Transformers Schneider


44 Merlin Gerin Electric
Single (grounded) pole Voltage transformers
(1)
Phase ground VDF11n/S1 - VDF11n/S2
VDF11/S1 -VDF11/S2 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2
c Upn primary rated voltage: refer to page 37 standard types VDF11n/S1 VDF11n/S2 VDF11n/S2
c winding in class 0.2-0.5-1 are also guaranteed in VDF11/S1 VDF11/S2 VDF11/S2
class 3P with the same output as indicated in the table 1 for measuring
1 for measuring
c rated thermal output: application measuring or 1 for protection
or protection
VDF11n = 200 VA protection or measuring
1 for residual
voltage
VDF11 = 150 VA
standard secondary 100:e- 100:eo 100:eo 100:3 o
c voltage factor: 1.9 x 8 hours voltage (V)
100:e o 110:e
110:e- 110:e 110:e- 110:3
operation
simultaneous (1) separate (2)
3rd sec. accuracy class
output
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P
output 10 15 2015 30 50 10 15 20 15 30 50 3050 75 30 30 75
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5
output 10 15 20 15 30 50 10 15 20 15 20 30 10 15 20 15 30 50 10 20 30 50
VDF11n
VDF11
(1) Output with simultaneous operation means that accuracy class of the 1st secondary
is guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed
with a simultaneous operation.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VDF11/S1-S2
VDF11n/S1-S2
Weight kg 15

M 10
A
100

125

148

DIN 40430
Pg 16 M8
221

GROUPE SCHNEIDER

270 N4 holes 11
M5 screw type secondary
31

350 and earthing terminals

168 150
20

Schneider Instrument Transformers


Electric Merlin Gerin 45
Single (grounded) pole Voltage transformers
Phase ground VDF21n/S1 - VDF21n/S2 - VDF21n/S3 (1)
VDF21/S1 - VDF21/S2 - VDF21/S3 (2)
(1) (2)
High induction Low induction

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2 2 3
c Upn primary rated voltage: refer to page 37 standard types VDF21n/S1 VDF21n/S2 VDF21n/S2 VDF21n/S3
c winding in class 0.2-0.5-1 are also guaranteed in VDF21/S1 VDF21/S2 VDF21/S2 VDF21/S3
class 3P with the same output as indicated in the table 1 for measuring 1 for measuring 2 for meas.
c rated thermal output: application measuring or 1 for protection or protection or protec.
protection or measuring 1 for residual 1 for res.
VDF21n = 250 VA
voltage voltage
VDF21 = 200 VA
standard secondary 100:e - 100:eor 100:eor 100:3 or 100:eor
c voltage factor: 1.9 x 8 hours voltage (V) 100:eor 110:e 110:e - 110:e 110:e- 110:3 110:e
100:3 or 110:3
operation simult.and
simultaneous (1) separate (2)
separate (3)
3rd sec. accuracy class 3P
output 10 15 20 15 30 50 10 15 2015 20 30 10 15 20 15 30 50 50 50 75 100
2nd sec. accuracy class 0,5 o 1 0,5 o 1 3P 3P 0,5 o 1
output 10 15 2015 30 50 10 15 2015 30 50 50 50 75 50 50 75 10 20 30 50
1st sec. accuracy class 0,2 0,5 0,2 0,5 0,2 0,5 0,5
output 15 20 30 30 50 75 10 15 2015 30 50 15 20 30 30 50 75 10 20 30 50

VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VDF21/S1-S2-S3
VDF21n/S1-S2-S3
Weight kg 21

M 10

DIN 40430
M8
A

Pg 16
100

150

178

280

280
n 4 holes 14
370
20
31

M 5 screw type secondary


188 160
and earthing terminals.

Instrument Transformers Schneider


46 Merlin Gerin Electric
Two (insulated) poles Voltage transformers
Phase phase VRCR/S1 - VRCR/S2

c Max reference voltage for insulation: 7.2 - 12 kV Selection table


c Usn secondary rated voltage: see selection table
c Upn primary rated voltage: refer to page 37 n of secondaries per VT 1 2
c rated thermal output: standard types VRCR/S1 VRCR/S2
VRCR/S1 = 200 VA application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VRCR/S2 = 100 100 VA
standard
c voltage factor: 1.2 ill. 100 - 100 o
secondary 100 o 110
110 - 110
voltage (V)
operation simultaneous (1)
2nd sec. accuracy class 0,5 o 1 0,5 o 1
output 15 25 20 30 50
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 15 25 25 40 50 15 25 20 30 50
feasibility
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRCR/S1-S2
Weight kg 15

100 110 A
125
148

M 10
B

270
221

NUOVA MAGRINI GALILEO

N4 holes
30

11
5

300

M6 screw type secondary


140 117 and earthing terminals

257

Schneider Instrument Transformers


Electric Merlin Gerin 47
Two (insulated) poles Voltage transformers
Phase phase VRC1/S1 - VRC1/S2

c Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2
c Upn primary rated voltage: refer to page 37 standard types VRC1/S1 VRC1/S2
c rated thermal output: application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VRC1/S1 = 300 VA
standard
VRC1/S2 = 150 150 VA 100 - 100 or
secondary 100 or 110
c voltage factor: 1.2 ill. 110 - 110
voltage (V)
operation simultaneous (1)
2nd sec. accuracy class 0,5 or 1 0,5 or 1
output 15 25 30 50 100
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 25 50 50 75 100 15 25 30 50 100
feasibility

(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRC1/S1-S2
Weight Kg 23

M 10 195

150
155
180
30

A B

155 N4 holes
240

NUOVA MAGRINI GALILEO 11


225
161 139

300
M6 screw type secondary
and earthing terminals

Instrument Transformers Schneider


48 Merlin Gerin Electric
Two (insulated) poles Voltage transformers
Phase phase VRC2/S1 - VRC2/S2

c Max reference voltage for insulation: Selection table


12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2
c Upn primary rated voltage: refer to page 37 standard types VRC2/S1 VRC2/S2
c rated thermal output: application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VRC2/S1 = 500 VA
standard
VRC2/S2 = 250 250 VA 100 - 100 or
secondary 100 or 110
c voltage factor: 1.2 ill. 110 - 110
voltage (V)
operation simultaneous (1)
nd
2 sec. accuracy class 0,5 or 1 0,5 or 1
output 15 25 30 50 100
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 25 50 50 75 100 15 25 30 50 100
feasibility
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRC2/S1-S2
Weight Kg 28

M 10 270

210
175
200
30

A B
5

300

225 N4 holes
NUOVA MAGRINI GALILEO
11
260
177 155

332 M6 screw type secondary


and earthing terminals

Schneider Instrument Transformers


Electric Merlin Gerin 49
Two (insulated) poles Voltage transformers
Phase phase VRC3/S1 - VRC3/S2

c Max reference voltage for insulation: Selection table


24 - 36 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2
c Upn primary rated voltage: refer to page 37 standard types VRC3/S1 VRC3/S2
c rated thermal output: application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VRC3/S1 = 700 VA
standard
VRC3/S2 = 350 350 VA 100 - 100 or
secondary 100 or 110
c voltage factor: 1.2 ill. 110 - 110
voltage (V)
operation simultaneous (1)
2nd sec. accuracy class 0,5 or 1 0,5 or 1
output 15 25 30 50 100
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 25 50 50 75 100 15 25 30 50 100
feasibility
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VRC3/S1-S2
Weight Kg 45

M 10 380

320
225
255

A B
390
30

300
GROUPE SCHNEIDER

N4 holes
11
192 170 325
M6 screw type secondary
362 and earthing terminals

Instrument Transformers Schneider


50 Merlin Gerin Electric
Two (insulated) poles Voltage transformers
Phase phase VDC11/S1 - VDC11/S2

c Max reference voltage for insulation: Selection table


7.2 -12 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2
c Upn primary rated voltage: refer to page 37 standard types VDC11/S1 VDC11/S2
c rated thermal output: application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VDC11/S1 = 200 VA
standard
VDC11/S2 = 100 100 VA 100 - 100 or
secondary 100 or 110
c voltage factor: 1.2 ill. 110 - 110
voltage (V)
operation simultaneous (1)
2nd sec. accuracy class 0,5 or 1 0,5 or 1
output 15 25 20 30 50
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 15 25 25 40 50 15 25 20 30 50
feasibility
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VDC11/S1-S2
Weight Kg 15

100 110
M 10

DIN 40430
A

Pg 16 M8
100

125

148

221

GROUPE SCHNEIDER
B
31

270 N4 holes 11
M5 screw type secondary
168 150 350 and earthing terminals
20

Schneider Instrument Transformers


Electric Merlin Gerin 51
Two (insulated) poles Voltage transformers
Phase phase VDC21/S1 - VDC21/S2

c Max reference voltage for insulation: Selection table


7.2 -12 - 17.5 - 24 kV
c Usn secondary rated voltage: see selection table n of secondaries per VT 1 2
c Upn primary rated voltage: refer to page 37 standard types VDC21/S1 VDC21/S2
c rated thermal output: application measuring or protection 1 for measuring or protection (1st sec.)
1 for protection (2nd sec.)
VDC21/S1 = 300 VA
standard
VDC21/S2 = 150 150 VA 100 - 100 or
secondary 100 or 110
c voltage factor: 1.2 ill. 110 - 110
voltage (V)
operation simultaneous (1)
2nd sec. accuracy class 0,5 or 1 0,5 or 1
output 15 25 30 50 100
1st sec. accuracy class 0,2 0,5 0,2 0,5
output 25 50 50 75 100 15 25 30 50 100
feasibility
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.

Dimensions (mm)
type VDC21/S1-S2
Weight Kg 21

165 130
M 10
A

DIN 40430
Pg 16 M8
100

150

178

280

GROUPE SCHNEIDER
B

280 N4 holes 14
31

M5 screw type secondary


188 160 370 and earthing terminals
20

Instrument Transformers Schneider


52 Merlin Gerin Electric
Voltage transformers
Order form

Part 1

Type: _________________________________________________________________________________________________________

Maximum voltage level for insulation (kV): 7.2  12  17.5  24  36 

Number of secondaries: 1 2 3

Primary rated voltage: ____________________________________________ kV


Secondary rated voltages: __________________________________________ V
Voltage factor: _____________________________________________________
1st secondary Output: ________________ Class: _______________________________________________________________

2nd secondary Output: ________________ Class: _______________________________________________________________

3rd secondary Output: ________________ Class: _______________________________________________________________

Operation simultaneous  separate

Standards: IEC  Others  ____________________________________________

Part 2 - Optional accessories

Cover or secondary terminals : 

Part 3 - Special versions

Frequency: 60 Hz  Others 

Non standard primary voltages:__________________________________________________________________________kV

Non standard secondary voltages:________________________________________________________________________V

Primary voltage change with secondary tap: 

Others:________________________________________________________________________________________________

Note
Apparatus with the following features are defined as standard:
 electrical features, max. reference voltage, rated voltages, output and classes strictly as indicated in the table of options from page 38
to page 52
 pickled copper primary holds and secondary terminals
 fixtures, if any, are zinc-plated steel.

Schneider Instrument Transformers


Electric Merlin Gerin 53
Schneider Electric
Industries SA Postal address As standards, specifications and design change from time to This document has been
F-38050 Grenoble cedex 9 time, always ask for confirmation of the information given in printed on ecological paper.
Tel.: +33 (0)4 76 57 60 60 this publication.
Telex : merge 320842 F
http://www.schneider-electric.com
Published by: Schneider Electric SA
Layout by: Headlines
ART. Rcs Nanterre B 954 503 439 Printed by:

04/2000

S-ar putea să vă placă și