1 Series
Float Battery Chargers
Advanced technology
microprocessor control
BATTERY CHARGER
RANGE SUMMARY
Constant potential
DC power supplies for:
Floating and charging
stationary batteries
Power for utility, UPS
and communications or
industrial type loads
RESERVE
POWER
Specifications
AC Input DC Output
Group 1 (6-25 Adc) Voltage: Voltage Ratings: Electrical Noise:
120/208/240Vac Multi-tap 60Hz 12, 24, 48, or 130Vdc nominal 32dBrnc
480Vac 60Hz Current Ratings: Ripple:
220Vac, 380/416Vac 50/60Hz GROUPI: 6, 12, 16, 20, 25Adc 12/24/48Vdc
550-600Vac 50/60Hz GROUPII: 30, 40, 50, 75, 100Adc Unfiltered on battery 1% Vrms
Group 2 (30-100 Adc) Voltage: Continuous Rating: Filtered on battery 30mVrms
120, 208, 240 or 480Vac 60Hz 110% rated current at maximum Filtered off battery 1% Vrms
220Vac, 380 or 416Vac 50/60Hz equalize voltage at 122F (50C) Battery Eliminator 30mVrms
550-600Vac 50/60Hz 130Vdc
Current Limit Adjustment Range:
Input Voltage Tolerance: 50% to 110% rated output Unfiltered on battery 2% Vrms
+10%, -12% Filtered on battery 100mVrms
Voltage Regulation:
Input Frequency Tolerance: Filtered off battery 2% Vrms
0.25% for line, load and temperature
5% Battery Eliminator 100mVrms
variations
Efficiency: *Regulation at maximum equalize voltages Surge Withstand Capability:
85-90% typical for 130Vdc at 50-100% load may not meet 0.25% Meets IEEE-472, ANSI C37.90a
Standard Features
5 year product warranty AC line failure automatic equalize Local or remote voltage sense with
Universal main control board operates timer (0-255 hr.) with indicating light redundancy to protect against remote
in any AT Series charger AC On indicating light sense failure
Alarm assembly with local LEDs and 1% Digital LED meter for Vdc, Adc, Self-diagnostics
summary relay contact for AC Failure, timer hours and alarm settings Input & output MOV surge suppressors
DC Failure, High Vdc, Low Vdc, AC input and DC output circuit Reverse polarity protection via free
Positive(+) and Negative(-) ground breakers wheeling diodes
fault
Membrane front panel CU-AL I/O compression lugs
High DC voltage shutdown
Front panel controls can be disabled Switchboard wire, UL VW-1
Forced load share during parallel for security Enclosure pre-treated using a 5-stage
operation
A redundant analog circuit for iron phosphate process with baked
Float/equalize selector switch with LVDC alarm, independent of the epoxy powder coating in ANSI 61
indicating lights microprocessor gray
Manual equalize timer (0-255 hr.) with Redundant control loops for higher
indicating lights reliability
2
Summary of Options
Filtering
Standard Battery Eliminator Ordering
Output filtering is essential An additional "battery Factory Factory Installation
whenever there is need for eliminator" feature is also Installation use Specification
YES Tables on pages
low AC ripple and low noise available, meeting the
9 & 10
on the DC bus for critical specifications of NEMA
loads. The standard DC standard PE5-1996 with no Available Field Installation use
output filtering limits ripple battery connected, measured for field Part Number
at the DC output terminals. installation Group I: EJ1072-9#
to no more than 30mV RMS YES Group II: EJ5023-9#
on 12, 24 and 48Vdc units, This feature is recommended
and 100mV RMS on 130Vdc for sites where the battery Contact manufacturer for
may occasionally be specific part number.
units, measured at the battery
terminals. This feature meets disconnected from the DC bus
the specifications of NEMA for maintenance. Additional
standard PE5-1996, and is filtering is essential to limit AC
recommended for installations ripple and noise for critical DC
using VRLA or gelled loads.
electrolyte batteries.
3
Summary of Options
Fungus Proofing
Ordering
This treatment is also referred to as "tropicalization". It coats
Factory Factory Installation
electrical components and internal wiring connections with Installation use Specification
a fungus-resistant, non-conductive film (approximately 1 YES Tables on pages
mil thickness). 9 & 10
User termination points, relay contacts and any electrical
connectors where the spray would interfere with Available Not available
for field for field installation.
functionality are not coated. The application is fully cured at installation
time of shipment. NO
Ordering
Communications Factory Installation
Factory
This option allows full remote monitoring of the AT10.1 and Installation use Part Numbering
YES when ordering:
control of the front panel features, using MODBUS or DNP3
12Vdc: EJ5037-01
Level 2 protocols. Standard serial connections are provided 24Vdc: EJ5037-02
for use with local SCADA systems. 48Vdc: EJ5037-03
130Vdc: EJ5037-04
Additional Ethernet and Fiber Optics Modem interfaces are
also available for use with the AT Communications option. Available Field Installation
for field use Part Number:
Contact EnerSys for part number.
installation 12Vdc: EJ5037-11
YES 24Vdc: EJ5037-12
48Vdc: EJ5037-13
130Vdc: EJ5037-14
4
Summary of Options
7
Group 1 6-25Adc
Group 2 30-100Adc
NOTE:
Dimensions shown are for
reference only; for installation
and mounting please refer to
user manual.
8
Group 1 6-25Adc
Circuit Breaker
AC & DC Ratings
Main Main Inductor Standard
Transformer Input: 10kAIC - 240Vac
10kAIC - 480Vac
Microprocessor Output: 10kAIC - 125Vdc*
Control Board
Medium
Input: 25kAIC - 240Vac
18kAIC - 480Vac
Rectifier Assembly I/O Assembly 18kAIC - 600Vac
Output: 10kAIC - 250Vdc
Filter Assembly High
Input: 65kAIC - 240Vac
25kAIC - 480Vac
Input Output 18kAIC - 600Vac
Circuit Breaker Circuit Breaker Output: 20kAIC - 250Vdc
*For chargers 16Adc and larger;
consult factory for other ratings.
A B C D E F G H J K L
AT10 0 1 2 0 0 6 E 2 4 0 S A U X G L X X
YOUR CODE
AT10
Main
Transformer
AT10 1 3 0 0 5 0 F 4 8 0 S F S X A X X X X
YOUR CODE
AT10
Notes
11
#
Publication No: US-AT10-RS-002 April 2013 Subject to change without prior notice. E.& O.E.