CHLORIDE

INDUSTRIAL SYSTEMS
A Chloride Power Protection Company

Safe and tailored Direct Current power solutions to meet the specific requirements of the energy,
petrochemical and transportation industries.
Especially adapted for process control systems and emergency lighting devices.
High reliability thanks to the Chlorides long experience in power protection.
Wide range of configurations.
Parallelable in ON-Line mode or Hot stand-by operation.
Compatible with all types of batteries (vented or sealed; NiCd or Lead Acid).
Electronically controlled thus optimizing battery life and performance.
Long-distance Remote monitoring LIFE 2000 (SUPRA version).

EXCEL PLUS
Input from 230VAC single phase to 440VAC 3-phase - 50 or 60 Hz
DC voltage from I2V to 400V
DC current from I6A to 4000A.
3 or 6 pulses chargers.
Digital or Analogue meters.
Easy supervision of status and alarms thanks to LED indicators.
EXCEL PACK solution: integrated battery-charger unit.

EXCEL SUPRA
3-phase input from 380VAC to 440VAC - 50 or 60 Hz.
DC voltage from 24VDC to 400VDC
DC current from 25A to 4000A.
6 or 12 pulses chargers.
Real-time supervision of more than 40 operating parameters
with the integrated microprocessor.
Real-time recording of more than 20 measures.
Power history device, helping analysis in case of malfunction
(10 seconds before and 1 second after the event)
Very low mains harmonic distortion
Measurements, status and alarms on liquid crystal display with
2 lines of 40 characters (tailored messages).
EXCEL PACK solution: integrated battery-charger unit.
RS232/485 serial link for remote monitoring via a computer
with Remote Power Manager software.
LIFE2000 service: 24h a day remote monitoring of the system.
CHLORIDE Chloride France S.A.
INDUSTRIAL SYSTEMS 30, avenue Montgolfier BP 90
A Chloride Power Protection Company 69684 CHASSIEU Cedex France
Tl. : +33 (0)4 78 40 13 56 Fax. : +33 (0)4 78 90 62 13

ELECTRICAL SPECIFICATIONS EXCEL PLUS EXCEL SUPRA


INPUT
AC input voltage : 230VAC - 1 phase to 440 VAC - 3 phases 380 VAC to 440 VAC - 3 phases
Input voltage tolerance : -10% / +15% -10% / +15%
Input frequency : 50 / 60 Hz 50 / 60 Hz
Input frequency tolerance : 5% 5%
Power factor : 0,85 (3 phases) 0,85 (3 phases)

OUTPUT
DC output voltage : 12VDC, 24VDC, 48VDC, 120VDC, 220VDC, 400VDC 24VDC, 48VDC, 120VDC, 220VDC, 400VDC
Output voltage regulation : 1% (0 to 100% of the load) 1% (0 to 100% of the load)
Current limitation : 100% of nominal rating in AUTO mode 100% of nominal rating in AUTO mode
Boost mode current limitation : 0,1 C10 (Lead Acid) / 0,2 C5 (Nickel Cadmium) 0,1 C10 (Lead Acid) / 0,2 C5 (Nickel Cadmium)

MECHANICAL SPECIFICATIONS

Presentation : Sheet steel floor mounted cubicle Sheet steel floor mounted cubicle
External protection : IP 20 as standard (other on request) IP 21 as standard (other on request)
Lock : Steel locked door Steel locked door
Standard colour : Grey RAL 7035 textured semi-gloss Grey RAL 7035 textured semi-gloss
Weight and dimensions : According to ratings / consult us According to ratings / consult us

ENVIRONMENT SPECIFICATIONS
Operating temperature : 0 to 40C 0 to 40C
Storage temperature : -20C to +70C -20C to +70C
Relative humidity : < 95% < 95%
Operating altitude : 1000 m (without derating) 1000 m (without derating)
Noise : < 60dB (natural cooling) < 60dB (natural cooling)
Cooling : Natural or fan-assisted according to ratings (ask us) Natural or fan-assisted according to ratings (ask us)

STANDARDS
Compliance (main standards) : IEC 950, 439, 146, 529, 726
American standards : Manufacturing following UL, ANSI, NEMA, IEEE standards as option
CE Marking : Directives 73 / 23 / EEC LVD and 89 / 336 / EEC - EMC

CONTROL AND DISPLAY


ON / OFF control : ON/OFF switch on front face ON/OFF switch on front face
Local measurements : On 72 x 72 analogue meter On liquid crystal display
Access to parameters, measures and alarms : / Via keyboard and / or PC with RPM software
Local information : LED indicators on front panel On liquid crystal display
Remote information : Voltage free contact Voltage-free contact and RS serial link

CHARGER OPTIONS: EXCEL EXCEL BATTERY-RELATED OPTIONS: EXCEL EXCEL


PLUS SUPRA PLUS SUPRA
Dual voltage three-phase supply : Charging regulation according to battery temperature : standard
Special supply from 110VAC to 660VAC / 50Hz or 60Hz : Monitoring and regulation of battery charging current : standard
Mains failure monitor and / or disconnection device : standard Battery low voltage cut-off device :
72x72 or 96x96 additional meter : Automatic battery test : standard
Measurements on digital display : standard
OTHER OPTIONS :
Input circuit breaker :
Reduction of supply current distorsion : Internal cubicle lighting :
Inrush current limitation : Specific external cubicle protection :
Additional DC ripple filter : Internal protection against electrical contact :
DC earth fault alarm : Special painting (AFNOR, RAL, BS standards) :
Distribution (fuses or circuit breakers) :
Anti-seismic manufacturing :
Output switch :
Ambient temperature >40C :
Front-face mimic panel :
Tropicalisation :
Alarm on additional voltage-free contact :
Special cables :
DC/DC converter (for DC voltage regulation) :
Communication interface RS232 / 485 : Remote monitoring kit LIFE 2000 :
communication software Remote Power Manager : Manufacturing according to UL / ANSI / NEMA / IEEE :

Additional options available on request. Do not hesitate to contact us for further information.
In the interest of continuous improvement of quality, performance and reliability, we reserve the right to modify or change this specification without prior notice.

S-ar putea să vă placă și