ASHRAE 62.2-2010 Ventilation Calculator


Base and Alternative Compliance Ventilation Requirement
Livable Square Footage / 100 Bedrooms + 1, or # of Occupants * 7
1,250 100 12.5 CFM 4 7.5
Kitchen Spot Kitchen Ventilation Defic
100 CFM On Demand 1 100
5 Air Changes per Hour0 20 0
Existing Fan 1 Measured CFM: 75
Operable Window 1 20
Bath 1 Spot Bath Ventilation Defic
50 CFM on Demand 1 50
20 CFM Continuous 0 0
Existing Fan 1 Measured CFM: 35
Operable Window 1 20
Bath 2 Spot Bath Ventilation Defic
50 CFM on Demand 1 50
20 CFM Continuous 0 0
Existing Fan 0 20
Operable Window 1 20

Total Spot Ventilation Deficits / 4


Whole-House Continuous Ventilation Needed

Fractional On-Time: 0.5 Cycle Time: 8 Effectiveness

If the whole-house fan runs 4.0 hours out of every 8 hour cycle:

Whole-House Intermittent Ventilation Needed

Infiltration Credit
Weatherization Factor "w" Estimated Infiltration Rate = 0.0508*w*S*CFM50,TA

TX - Austin 0.0508 0.8 1.00 1,250


Building Floors (Stories) Default Infiltration Rate = 0.02*Livable Sq
1 0.02 1,250
Infiltration Credit = 0.5*(Estimated - Defau
0.5 51 25

Whole-House Continuous Ventilation Requirement:


- OR -
Whole-House Intermittent Ventilation Needed
If the whole-house fan runs 4.0 hours out of every 8 hour cycle:
Calculator List of Links to calculated C F M numbers

equirement Livable square footage

oms + 1, or # of Occupants * 7.5 Bedrooms plus 1 or number of occupants

30 CFM Total spot ventilation deficits

Spot Kitchen Ventilation Deficits Whole-house continuous ventilation needed

Whole-house intermittent ventilation needed

5 CFM Estimated infiltration rate

Default infiltration rate

Infiltration credit

Spot Bath Ventilation Deficits Whole-house continuous ventilation requirement

Whole-house intermittent ventilation needed

0 CFM Run time and cycle statement

Spot Bath Ventilation Deficits

10 CFM

4 CFM
46 CFM
0.94

98 CFM

n Rate = 0.0508*w*S*CFM50,TARGET

51 CFM
tration Rate = 0.02*Livable Sq. f
25 CFM
redit = 0.5*(Estimated - Default)
13 CFM

33 CFM

71 CFM
State City w Source Reproduced from A Method of Determining
- Dwellings, ANSI/ASHRAE 136 - 1993
TX Abilene 1.05 TMY TX - Abilene
TX Amarillo 1.14 TMY TX - Amarillo Notes:
TX Austin 0.80 TMY TX - Austin
TX Brownsville 0.90 TMY TX - Brownsville
w[ACH] = a weather factor accounting for th
TX Corpus Chriti 0.86 TMY TX - Corpus Chriti Changes per Hour (ACH). For cities not inclu
TX El Paso 0.76 TMY TX - El Paso values of w may be estimated by using the v
TX Fort Worth 0.89 TMY TX - Fort Worth
TX Houston 0.81 TMY TX - Houston
TX Kingsville 0.72 TMY TX - Kingsville "Source" indicates the source of the weathe
TX Laredo 0.91 TMY TX - Laredo TMY = typical meteorological year
TX Lubbock 1.00 TMY TX - Lubbock WYEC = the weather year for the energy c
TX Lufkin 0.64 TMY TX - Lufkin
TX Midland Odessa 0.96 TMY TX - Midland Odessa
TX Port Arthur 0.79 TMY TX - Port Arthur
TX San Angelo 0.84 TMY TX - San Angelo
TX San Antonio 0.83 TMY TX - San Antonio
TX Sherman 0.80 TMY TX - Sherman
TX Waco 0.92 TMY TX - Waco
TX Wichita Falls 0.99 TMY TX - Wichita Falls
ed from A Method of Determining Air Change Rates in Detached
ANSI/ASHRAE 136 - 1993

a weather factor accounting for the effect of local weather, in Air


er Hour (ACH). For cities not included in the Weather Factor table,
w may be estimated by using the value of the nearest location.

ndicates the source of the weather data:


ypical meteorological year
the weather year for the energy calculations
# of Stories S Factor
1 1 Cycle Time
1.5 1.13 0-4
2 1.23 8
2.5 1.32 12
3 1.39 24

Fractional Cycle Time


On-Time 0-4 8 12 24
0.1 1.00 0.79 0.00 0.00
0.2 1.00 0.84 0.56 0.00
0.3 1.00 0.89 0.71 0.00
0.4 1.00 0.92 0.81 0.20
0.5 1.00 0.94 0.87 0.52
0.6 1.00 0.97 0.92 0.73
0.7 1.00 0.98 0.96 0.86
0.8 1.00 0.99 0.98 0.94
0.9 1.00 1.00 1.00 0.99
1.0 1.00 1.00 1.00 1.00