Sunteți pe pagina 1din 1

V1.

2 2009-11-06 BOM 31012151


1.1.5 LCD Display Panel
IRM-S04DIF Intelligent Digital Input Sensor The LCD display panel (as shown in the following figure) can display sensor
With RJ45 Ports User Manual address and measured data in real time. The four numbers from left to right in
the data area means the status of input digital 1, 2, 3 and 4 respectively.
1 Overview
Note: "-" means no equipment connected
Measured data
IRM-S04DIF intelligent digital input sensor with RJ45 ports (sensor for short), "0" means no alarm
is used to measure 4 routes digital (such as infrared, smoke, door status and Sensor address
"1" means alarm exists
water). It supports MODBUS protocol through RJ45 port in RS-485 mode to
1.1.6 Alarm Indicator
configure and collect data. It is applicable for indoor sites with need of digital
signal control such as communication rooms and IT data centers. When measured digital level is the same as configured digital level
correspondingly, the alarm indicator flashes; or the indicaor extinguishes.
1.1 Product Introduction
1.2 Technical Specification
1.1.1 Appearance and Ports
Operating voltage: 9Vdc ~ 28Vdc; Power consumption: 0.2W
The sensors appearance and ports are shown in the following figure.
2 Installation
12345678
2.1 Environment Requirement

Fixed
ON: User
RJ45 port 1 1. Operating environment should be free of conductive dust and
Group Num OFF:
LCD display DIP switch metal-corrosive & insulation-breaking gases.
panel
2. Avoid using the sensor in watery or foggy places.
Alarm indicator ALARM

3. Keep a clearance of more than 20mm around the sensors airway to ensure
Door1/DI 1

Smoke/DI 4

RJ45 port 3 RJ45 port 6


Digital Input Sensor
IRM-S04DIF
ventilation inside and outside of the sensor.
Door2/DI 2

Water/DI 3

RJ45 port 4 RJ45 port 5 4. Operating temperature: -10C ~ +50C; Storage temperature: -30C ~
+70C; Humidity: 5%RH ~ 95%RH (non-condensing).

RJ45 port 2 2.2 Unpacking Inspection


Left view Front view Right view
Unpack the sensor and visually inspect the sensors appearance. If any
Size (height width depth): 97mm 44mm 24mm Weight: about 100g damage is found, please contact the carrier immediately.
1.1.2 Communication Cascade Port Check against the consignment list to make sure the sensor and accessories
RJ45 port 1 and RJ45 port 2 are communication cascade ports of the sensor, are complete and correct.
which are used for power supply, communication and equipment connection in 2.3 Mechanical Installation
series. The pin definitions of the ports are shown in the following table. Three modes are available for the sensors mechanical installation. The
Pin Pin1 & Pin2 Pin3 & Pin6 Pin4 & Pin5 Pin7 Pin8 installation accessories and modes are shown in the following figure.
Definition +12V/24V NC GND D+ D-

1.1.3 DI Detecting Port Back installation hole


Magnet pothook
RJ45 port 3 ~ RJ45 port 6 are DI detecting ports of the sensor, which are used
to connect 4 routes digital equipment. Through these ports, the sensor can
Sensor
measure and display whether any equipment is connected and its status. The
ports also supply +12V/24V power, which is the same as the input power of the L pothook
sensor, to the connected equipment. The pin definitions of the ports are shown
in the following table. Back installation hole
Pin Pin1 & Pin2 Pin 3, Pin6, Pin7 & Pin8 Pin4 Pin5 T pothook
Definition +12V/24V DI signal input Equipment detect GND Mode one: Insert the magnet pothook into the sensors back installation hole,
and the sensor can absorb on iron surface.
1.1.4 DIP Switch
Mode two: Insert the L pothook into the sensors back installation hole, and
The DIP switch is used to set sensor address and connected equipment type
hang the pothook in the square hole of racks vertical pole gently.
to communicate with upper equipment through MODBUS protocol. The sensor
address is composed of group number and serial number within the group. Mode three: Insert the T pothook into the sensors back installation hole, insert
The DIP1 ~ DIP4 are used to set the group number; The DIP5 are used to set the bulge of the T pothook into the installation slot of the racks basic frame,
the serial number within the group; The DIP6 is used to set the type of and rotate the sensor 90 degree clockwise gently.
connected equipment. For example, the sensor address of 70 is set as shown Note
in the following figure, among which 0111 means group number 7; 0 means The sensor can not only be installed through the three kinds of accessories above,
serial number 0 within the group and 1 means that the type of connected but also can hang on fixed screws directly through the back installation hole.
equipment is user customized equipment.
0 1 1 1 0 1 2.4 Cable Connection
Note: 1. DIP switch in the ON position means 1, 1. Insert one end of the standard straight network cable into the sensors RJ45
1 2 3 4 5 6
or it means 0; port 1 or RJ45 port 2, and insert the other end into the sensor appropriative
DIP ON
2. The sensor address cannot be set as 00, port of upper equipment or sensor in series.
OFF: Fixed which is the broadcast address.
Group Num ON: User
2. Refer to 1.1.3 DI Detecting Port for port definition, and connect cables as
The settings of DIP1 ~ DIP4 are listed in the following table. shown in the following figure.
DIP1 ~ DIP1 ~ DIP1 ~ DIP1 ~ DI signal input DI signal input
Group Group Group Group Door
RJ45 port

RJ45 port
123 4567 8

123 4567 8

DIP4 DIP4 DIP4 DIP4 status, GND


0000 0 0100 4 1000 8 1100 C water, Infrared
DI signal input
0001 1 0101 5 1001 9 1101 d smoke DI signal input
0010 2 0110 6 1010 A 1110 E +12V/24V
0011 3 0111 7 1011 b 1111 F 3 Maintenance
The settings of DIP5, DIP6 are listed in the following table. 1. To clean the sensor, you should cut off the power and use a piece of soft
cloth to wipe it.
DIP5 Num DIP6 Connected equipment type
0 0 0 Fixed equipment 2. Do not disassemble the sensor, or the inside subtle parts may be damaged.
1 1 1 User customized equipment