Sunteți pe pagina 1din 3

Chapter 5 — Cold-Water Systems 143

Table 5-11 Required Air Chambers


Nominal Pipe Flow Velocity, Required Air Chamber
Pipe Diam., Length, Pressure, fps Volume, Phys. Size,
in. (mm) ft (m) psig (kPa) (m/s) in.3 (cm3) in. (cm)

½ (12.71) 25 (7.62) 30 (0.79) 10 (3.04) 8 (1.3) ¾ × 15 (1.9 × 38.1)


½ (12.71) 100 (30.5) 60 (1.57) 10 (3.04) 60 (9.8) 1 × 69½ (2.5 × 176.5)
¾ (19.1) 50 (15.25) 60 (1.57) 5 (1.52) 13 (2.1) 1 × 5 (2.5 × 12.7)
¾ (19.1) 200 (61.0) 30 (0.79) 10 (3.04) 108 (17.7) 1¼ × 72½ (3.2 × 184.2)
1 (25.4) 100 (30.5) 60 (1.57) 5 (1.52) 19 (3.1) 1¼ × 127/10 (3.2 × 32.3)
1 (25.4) 50 (15.25) 30 (0.79) 10 (3.04) 40 (6.6) 1¼ × 27 (3.2 × 68.6)
1¼ (31.8) 50 (15.25) 60 (1.57) 10 (3.04) 110 (18.0) 1¼ × 54 (3.2 × 137.2)
1½ (38.1) 200 (61.0) 30 (0.79) 5 (1.52) 90 (14.8) 2 × 27 (5.1 × 68.6)
1½ (38.1) 50 (15.25) 60 (1.57) 10 (3.04) 170 (27.9) 2 × 50½ (5.1 × 128.3)
2 (50.8) 100 (30.5) 30 (0.79) 10 (3.04) 329 (53.9) 3 × 44½ (7.6 × 113.0)
2 (50.8) 25 (7.62) 60 (1.57) 10 (3.04) 150 (24.6) 2½ × 31 (6.4 × 78.7)
2 (50.8) 200 (61.0) 60 (1.57) 5 (1.52) 300 (49.2) 3 × 40½ (7.6 × 102.9)

it retains its initial charge of air. Air-chamber In most installations where there are several
requirements are shown in Table 5-11. fixtures, usually only one fixture valve will be closed
The air charge can be depleted during the at a time. Occasionally, however, two or more fix-
flow cycle since water is drawn from all direc- ture valves may be closed at the same instant.
tions during flow. Moreover, the entrapped air is Table 5-12, “Sizing and Selection of Water-Hammer
also diminished by turbulence. During this pro-
cess the water absorbs the air, and as the unit
becomes waterlogged, it loses its ability to ab-
sorb shock.

Water hammer arresters

Symbols There are six manufactured sizes of


water hammer arrester, each having a different
capacity to control shock in piping systems of
varied sizes and scopes. The following symbols,
recommended by the Plumbing and Drainage
Institute (PDI), were devised to denote the range
in size of water hammer arrester:
A–B–C–D–E–F
“A” is the smallest-sized unit and “F” represents a b c d
the largest.
Figure 5-11 Air Chambers: (a, b) Plain Air
Sizing and placement Sizing is based on fix- Chambers, (c) Standpipe Air Chamber,
ture units for single and multiple-fixture branch (d) Rechargeable Air Chamber
lines and on pipe size.
144 ASPE Data Book — Volume 2

Arresters,” takes into consideration all design fac- To prevent the harboring of Legionella
tors, including simultaneous usage, pipe size, pneumophila, bellows containing rubber should
length, flow, pressure, and velocity. not be used.

Table 5-12 Sizing and Selection of


BACKFLOW PREVENTION
Water-Hammer Arresters
Theoretically, a well-designed and operated wa-
PDI Units A B C D E F
ter-supply system should always be under a con-
Fixture Units 1–11 12–32 33–60 61–113 114–154 155–330 stant positive pressure, and contamination via
backflow or back-siphonage should never be able
In the sizing of cold and hot-water branch to enter the distribution mains. Unfortunately,
lines, it is usual practice to obtain the total num- accidents do occur when excessive water de-
ber of fixture units on each branch line. This mands for fire protection, operation of booster
information is then applied to sizing charts to pumps, flushing of water mains, repairs, modi-
determine the required size of the branch line. fications, and maintenance to the distribution
system cause the water pressure to drop.
The properly sized water-hammer arresters
can be selected once the total number of fixture Whenever the pressure in the distribution
units for a cold or hot-water branch line is system becomes low or negative, a condition de-
known. It is only necessary to apply the fixture velops that allows contamination to enter the
units to Table 5-12 and select the appropriate distribution system through connections with
water-hammer arrester. fixtures, equipment, or tanks that contain toxic,
unsafe, or unpleasant liquids or gases. These
Note the following: physical connections by which a water supply
• When water pressure in the line exceeds 65 may be contaminated are known as “cross con-
psig, select the next larger size water-ham- nections.” There are numerous, well-documented
mer arrester. cases where cross connections have been respon-
sible for contaminating drinking water and, as a
• If the fixture-unit total includes a fraction, it result, sometimes contributing to the spread of
should be rounded up to the next larger whole fatal disease.
number. Thus, if the total is 11½ fixture units,
the unit should be sized for 12 fixture units. The contamination of a water system through
cross connections can be avoided. This section
• All sizing data in this chapter are based on describes the current recommended practice for
flow velocities of 10 fps (3 m/s) or less. the detection and elimination of unprotected
It is suggested that the engineer employ PDI cross connections.
symbols for the riser diagrams for sizing water-
hammer arresters. This practice will enable Types of Cross-Connection Control
manufacturers to furnish the correct units. Device
The location of the water-hammer arresters
from the start of the horizontal branch line to When plumbing fixtures and equipment in wa-
the last fixture supply on the branch line should ter-supply systems are subject to backflow con-
not exceed 20 ft (6.1 m) in length. When the ditions, approved air gaps, backflow preventers,
branch lines exceed the 20-ft (6.10-m) length, or vacuum breakers should be used. The follow-
an additional water-hammer arrester should be ing methods or devices can be used to protect
used and each should be sized for half the fix- against backflow or back-siphonage:
ture-unit load. It has been established that the • Approved air-gap separation.
preferred location for the water-hammer arrester
• Barometric loop.
is at the end of the branch line between the last
two fixtures served. Units for branches serving • Mechanical protection devices.
pieces of equipment with quick-closing valves • Reduced-pressure-principle backflow devices
should be placed within a few ft (m) of the equip- (RPBD).
ment isolation valve.
• Double-check valve assemblies (DCVA).
• Atmospheric vacuum breakers (AVB).
Chapter 5 — Cold-Water Systems 145

• Pressure vacuum breakers (PVB). vacuum breaker should be used only to isolate a
• Check valves with vent port (CVB). severe hazard if area isolation is provided. Where
a moderate hazard exists, a double-check valve
The theory of backflow and back-siphonage assembly, or pressure or atmospheric vacuum
and the devices for their prevention are described breaker may be used. Where a minor hazard ex-
in Volume 4, Chapter 9, of the ASPE Data Book ists, a pressure or atmospheric vacuum breaker
(forthcoming). Refer to local codes and standards or check valves with vent port (no test cocks)
before making selections. may need to be installed.
Toxicity and probability of occurrence illus-
Assessment of Hazard
trate the relationship between assessment of
The correct application of devices depends on the hazard and application of devices. Because of
correct assessment of the degree of hazard, on the subjective nature of assessing hazard, such
whether back pressure or back-siphonage will oc- illustrations cannot be used as a strict guide,
cur, and on knowledge of the operation of various providing a fixed answer for all circumstances.
types of approved backflow-prevention device. Instead, past experience and local code require-
ments must also be used as guides. Such past
In applying the recommendations outlined experience was the basis of Tables 5-13 and 5-14.
in this section, three degrees of hazard must be
considered: severe, moderate, and minor. They The requirement of protection increases as a
are defined as follows: function of both an increase in the probability
that backflow or back-siphonage will occur and
1. Severe. A cross connection or probable cross an increase in the toxicity or possible toxicity of
connection involving any substance in suffi- a potential source of contamination. Where it is
cient concentration to cause death or spread highly probable that backflow or back-siphon-
disease or illness or containing any substance age will occur, say from a standpipe in a tall
that has a high probability of causing such apartment building, the need for a backflow-pre-
an effect. vention device is low if the hazard of the poten-
2. Moderate. A cross connection or probable tial source of contamination (sinks, water closets,
cross connection involving any substance etc.) becoming toxic is very low. The converse is
that has a low probability of becoming a se- also true, however, where a known health haz-
vere hazard and would constitute a nuisance ard exists, the tendency is to be conservative
or be aesthetically objectionable if introduced when selecting a backflow-prevention device
into the domestic water supply. (RPBD used in place of DVC). The risk factor for
a health hazard is usually of greater concern than
3. Minor. An existing connection, or a high prob- the probability of backflow or back-siphonage in
ability of a connection being made, between the selection of a device.
the domestic water pipe and any pipe, equip-
ment, vat, or tank intended for carrying or
holding potable water that has a low prob- Premise Isolation
ability of becoming contaminated with any
In addition to installing backflow-prevention de-
substance.
vices at the source of potential contamination, it
The application of backflow and back-sipho- may be necessary, or required by code, to install
nage prevention devices is related to the prob- a backflow-prevention device on the water-ser-
ability of contamination as well as the recognition vice pipe to isolate an entire area or premise.
of an existing health hazard. For the assessment This additional protection for the purveyor’s wa-
of probability, consideration must be given to the ter system is warranted if the potential health
possibility of changes being made to piping, im- hazard is severe, or if a high probability exists
proper use of equipment, negligence of the cus- that piping within a premise will be changed. If
tomer, etc. inspection on private property is restricted, the
only protection for the purveyor’s water system
Where a severe hazard exists, an air-gap
is the installation of a backflow-prevention de-
separation or a reduced-pressure-principle,
vice on the water-service pipe.
backflow-prevention device should be used be-
cause these two devices offer the highest known Whenever possible, in-plant isolation is pre-
degree of protection. An atmospheric or pressure ferred over premise isolation because it protects

S-ar putea să vă placă și