Documente Academic
Documente Profesional
Documente Cultură
it retains its initial charge of air. Air-chamber In most installations where there are several
requirements are shown in Table 5-11. fixtures, usually only one fixture valve will be closed
The air charge can be depleted during the at a time. Occasionally, however, two or more fix-
flow cycle since water is drawn from all direc- ture valves may be closed at the same instant.
tions during flow. Moreover, the entrapped air is Table 5-12, “Sizing and Selection of Water-Hammer
also diminished by turbulence. During this pro-
cess the water absorbs the air, and as the unit
becomes waterlogged, it loses its ability to ab-
sorb shock.
Arresters,” takes into consideration all design fac- To prevent the harboring of Legionella
tors, including simultaneous usage, pipe size, pneumophila, bellows containing rubber should
length, flow, pressure, and velocity. not be used.
• Pressure vacuum breakers (PVB). vacuum breaker should be used only to isolate a
• Check valves with vent port (CVB). severe hazard if area isolation is provided. Where
a moderate hazard exists, a double-check valve
The theory of backflow and back-siphonage assembly, or pressure or atmospheric vacuum
and the devices for their prevention are described breaker may be used. Where a minor hazard ex-
in Volume 4, Chapter 9, of the ASPE Data Book ists, a pressure or atmospheric vacuum breaker
(forthcoming). Refer to local codes and standards or check valves with vent port (no test cocks)
before making selections. may need to be installed.
Toxicity and probability of occurrence illus-
Assessment of Hazard
trate the relationship between assessment of
The correct application of devices depends on the hazard and application of devices. Because of
correct assessment of the degree of hazard, on the subjective nature of assessing hazard, such
whether back pressure or back-siphonage will oc- illustrations cannot be used as a strict guide,
cur, and on knowledge of the operation of various providing a fixed answer for all circumstances.
types of approved backflow-prevention device. Instead, past experience and local code require-
ments must also be used as guides. Such past
In applying the recommendations outlined experience was the basis of Tables 5-13 and 5-14.
in this section, three degrees of hazard must be
considered: severe, moderate, and minor. They The requirement of protection increases as a
are defined as follows: function of both an increase in the probability
that backflow or back-siphonage will occur and
1. Severe. A cross connection or probable cross an increase in the toxicity or possible toxicity of
connection involving any substance in suffi- a potential source of contamination. Where it is
cient concentration to cause death or spread highly probable that backflow or back-siphon-
disease or illness or containing any substance age will occur, say from a standpipe in a tall
that has a high probability of causing such apartment building, the need for a backflow-pre-
an effect. vention device is low if the hazard of the poten-
2. Moderate. A cross connection or probable tial source of contamination (sinks, water closets,
cross connection involving any substance etc.) becoming toxic is very low. The converse is
that has a low probability of becoming a se- also true, however, where a known health haz-
vere hazard and would constitute a nuisance ard exists, the tendency is to be conservative
or be aesthetically objectionable if introduced when selecting a backflow-prevention device
into the domestic water supply. (RPBD used in place of DVC). The risk factor for
a health hazard is usually of greater concern than
3. Minor. An existing connection, or a high prob- the probability of backflow or back-siphonage in
ability of a connection being made, between the selection of a device.
the domestic water pipe and any pipe, equip-
ment, vat, or tank intended for carrying or
holding potable water that has a low prob- Premise Isolation
ability of becoming contaminated with any
In addition to installing backflow-prevention de-
substance.
vices at the source of potential contamination, it
The application of backflow and back-sipho- may be necessary, or required by code, to install
nage prevention devices is related to the prob- a backflow-prevention device on the water-ser-
ability of contamination as well as the recognition vice pipe to isolate an entire area or premise.
of an existing health hazard. For the assessment This additional protection for the purveyor’s wa-
of probability, consideration must be given to the ter system is warranted if the potential health
possibility of changes being made to piping, im- hazard is severe, or if a high probability exists
proper use of equipment, negligence of the cus- that piping within a premise will be changed. If
tomer, etc. inspection on private property is restricted, the
only protection for the purveyor’s water system
Where a severe hazard exists, an air-gap
is the installation of a backflow-prevention de-
separation or a reduced-pressure-principle,
vice on the water-service pipe.
backflow-prevention device should be used be-
cause these two devices offer the highest known Whenever possible, in-plant isolation is pre-
degree of protection. An atmospheric or pressure ferred over premise isolation because it protects