Sunteți pe pagina 1din 6

Energy and Exergy Based

Thermodynamic Analysis of a 62.5 MWe


Coal-Based Thermal Power Plant A Case Study
M.V.J.J. Suresh, K. S. Reddy*, Ajit Kumar Kolar

Heat Transfer and Thermal Power Laboratory


Department of Mechanical Engineering
Indian Institute of Technology Madras
Chennai 600 036, India

*ksreddy@iitm.ac.in
Tel: +91-44-22574702, Fax: +91-44-22570509, 22574652

Keywords: Coal-based thermal power plant, Energy, Exergy

Abstract
Energy and exergy analysis provides insight to find out Kingdom of Saudi Arabia by Habib et al. [2]. Rosen [3] has
efficiency improvement in various components of a power compared the performance of operating coal-fired and nuclear
generating system. The results of energy and exergy analysis steam power plant located in Canada of unit size of
carried out on a 62.5 MWe coal-based thermal power plant approximately 500 MWe using a process-simulator, Aspen
are presented in this paper. The performance of the plant was Plus. The most common unit size of power plants in India is
estimated by a component-wise modeling followed by a 100 / 110 MWe or 200 / 210 MWe. Exergy analysis of coal-
system simulation. A flow-sheet computer program, Cycle- fired power generating unit of 110 MWe at Panki Thermal
Tempo was used for this study. The detailed break-up of Power Station, Kanpur, India has been done by Asthana et al.
exergy losses for the considered plant has been presented. [4]. An exergy analysis of a coal-based thermal power plant
The maximum exergy loss was found to be in steam was reported recently by Sengupta et al. [5], using the design
generation unit followed by turbine. The variation of overall data from a 210 MWe thermal power plant under operation.
energy and exergy efficiency with parameters such as The exergy analysis is not so popular among industrial
temperature gain of cooling water across the condenser, fraternity in India and it needs much more attention and
excess air and condenser pressure are presented. The off- application so that the irreversibilities can be minimized and
design simulation resulted in an overall energy efficiency of thus the systems can be operated at much higher efficiency.
28.5% at 40% load factor compared to 31.5% at design rating. The present study is one such effort to show the application of
energy and exergy based analysis on a relatively smaller size
Introduction unit of 62.5 MWe capacity.

The rate of depletion of fossil fuel reserves has necessitated India has huge coal reserves, about 10% of the worlds total
the operation of power plants in the most efficient manner. [6] and thus the coal-based thermal power plants dominate
Energy and exergy analysis has increasingly attracted the source-wise mix with 55% installed capacity [7]. Due to
interest to achieve the above goal. Energy is always power shortage of about 7% [7], a large number of old coal-
conserved in every device or process. Unlike energy, exergy fired units are still in use, operating on much lower thermal
is not generally conserved but is destroyed. The majority of efficiencies compared to their design values. One of the
the causes of thermodynamic imperfection of thermal important factors contributing to the lower overall efficiency
processes are not accounted by energy or first law analysis. It is the high ash content of about 40 - 50% in Indian coals. It is
is the exergy or second law analysis that accounts the emphasized here that in spite of high ash content, the Indian
irreversibilities like heat transfer through a finite temperature coal is of high quality with regard to sulphur content which is
difference, chemical reactions, friction, mixing, and in general less than 0.6% [8] thus having minimal negative
unrestrained expansion [1]. environmental impact. The other factors responsible for the
lower operating performance are inadequate instrumentation,
A detailed first- and second-law analysis has been carried out mismatching of equipments and deteriorated performance of
on a 400 MWe unit of the Ghazlan thermal power plant, associated equipments over a period of time [4].

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 1
Process description of 62.5 MWe thermal power plant 1. The kinetic and potential exergies have been neglected.
2. The reference state for water / steam is saturated liquid at a
A detailed process flow-sheet of a 62.5 MWe unit of temperature of 25oC.
Ramagundam Thermal Power Station (RTPS) is shown in fig. 3. The incoming fuel temperature is 25oC.
1. This unit employs regenerative feed water heating system. 4. In order to calculate exergy, the following reference
Feed water heating is carried out in two stages of low environment model has been considered:
pressure heaters and two stages of high pressure heaters along Pressure : 1.01325 bar
with one open de-aerating heat exchanger. Temperature : 25oC
The composition of the environment (mole %) is as follows
Saturated steam from the boiler drum is fed to the superheater (Environment of Baehr) [9] :
to heat it up to 510oC at a pressure of 86.2 bar. The extraction Ar : 0.90
pressures of steams (in bars) from the turbine are as follows: CO2 : 0.03
H2O (g) : 3.12
High Pressure Heater -1 (HPH 1) :29.2 N2 : 75.65
High Pressure Heater -2 (HPH 2) :14.3 O2 : 20.30
De-aerator (DA) :6.2 5. Isentropic efficiency of turbine: 80%.
Low Pressure Heater -1 (LPH 1) :2.3 6. Isentropic efficiency of pumps / fans: 75%.
Low Pressure Heater -2 (LPH 2) :0.72 7. Generator efficiency: 97%.
The condenser pressure is taken as 10 kPa. 8. Excess air: 20%.
The composition of the coal used for the present study For the overall unit, the energy efficiency is evaluated as:
represents that of the typical Indian Coal (Singareni Mines) = net electricity produced / energy content (Lower Heating
with lower heating value of 14.5 MJ/kg. Value) of fuel
and the exergy efficiency is evaluated as:
Component Mass (%) = net electricity produced / exergy content of fuel
Carbon 38.94 where, exergy content of fuel is calculated by Cycle-Tempo
Hydrogen 2.62 [9].
Moisture 5.74
Nitrogen 0.74
Oxygen 6.69
Results and discussion
Sulphur 0.61
A detailed parametric study has been carried out as a part of
Ash 44.66
this work, in order to account the performance of the overall
system. The parameters which have been considered are gain
Table 1: Composition of coal in cooling water temperature across the condenser, excess air,
inlet air temperature, and the condenser pressure. The
System Analysis variation of overall energy and exergy efficiencies with the
gain in cooling water temperature across the condenser is
The present study has been performed using a flow-sheet shown in fig. 2. The obtained variation is about 0.2 0.25%
program, Cycle-Tempo [9], which is a well-structured for the temperature variation of 10oC. The importance of
program for the thermodynamic analysis of energy systems. proper design / maintenance of the heat exchanging devices is
The ash content of Indian coal, as already mentioned is evident from the above noted variation. The results in fig. 3
around 40 - 50% as against 5 - 10% in the coal being used in shows that both the overall energy and exergy efficiencies
the western countries. This is one of the important factors increase initially, reaches maximum at about the excess air
contributing to the lower overall efficiency of the plant. level of 20% and then starts decreasing for the further
Being a tropical country, the cooling water temperature in variation of excess air. Fig. 4 shows the variation of both the
majority of the parts in India throughout the year is around efficiencies with inlet air temperature. The study shows that
25oC. In Europe and other western countries the cooling the above parameter affects both the efficiencies in a more
water temperatures are lower in the range of 5 10oC, which dominant way when compared with the temperature gain of
enables the operation of the condenser at much lower vacuum cooling water across the condenser. The effect of one of the
pressures (5 kPa), thus resulting in higher operating most important parameter, the condenser pressure variation
efficiencies. Since, both the above factors are natures on the overall energy and exergy efficiency is presented in
limitation; though coal can be beneficiated to a small extent, fig. 5. It is seen that the overall efficiencies, both energy and
designers / plant operators focus should shift to other major exergy increases by 1.1 1.3% with the reduction in
sites of potential improvement. Thus, the goal of this paper is condenser pressure from 10 kPa to 5.5 kPa. The increase in
to identify such sites so that the overall efficiency of the the overall energy efficiency can be accounted to the decrease
system can be improved. in the mean temperature of heat rejection, whereas the
increase in overall exergy efficiency is due to the decreased
The following assumptions were made to carry out the mass flow rate of the steam. The variation of overall
simulation: efficiencies is highest with respect to this parameter. Off-

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 2
design simulation studies have also been performed for
different loads up to 40% of full load capacity and the results
are shown in figs. 6 - 9. The off-design simulation shows a 33
drop in overall energy and exergy efficiencies of 3% and
2.6% respectively at 40% load factor when compared with the 32
design rating of 62.5 MWe. Off-design operation increases

Efficiency (%)
31
the irreversibility rate in the system and the effect is more
pronounced with the reduction in load. The effect of off- 30 Overall energy efficiency
design operation on the fuel flow rate is shown in fig. 7 and Overall exergy efficiency
the variation of overall energy efficiency and irreversibility 29
rate (as a percent of input exergy) is represented in fig. 8. It is
evident from fig. 8 that operation of the plant below 50% of 28
the designed capacity results in the significant increase of
irreversibilities. The analysis shows an increase in overall 27
energy efficiency and decrease in irreversibility rate with 10 15 20 25 30 35 40 45
0
increase in load percentage. The decrease in irreversibility Temperature ( C)
rate is attributed to the decrease in irreversibilities in the
steam generation unit and turbine. Figure 4: Variation of efficiencies with inlet air temperature

33
34
32 33
Efficiency (%)

31 32
Efficiency (%)

31
30 Overall energy efficiency Overall energy efficiency
Overall exergy efficiency 30 Overall exergy efficiency
29
29
28 28

27 27
4 5 6 7 8 9 10 11 12 13 14 15 16 4 5 6 7 8 9 10 11
0
Temperature ( C) Pressure (kPa)

Figure 2: Variation of efficiencies with gain in cooling water Figure 5: Variation of efficiencies with condenser pressure
temperature across condenser

34
33
32
32
30
Efficiency (%)

31
Efficiency (%)

28
Overall energy efficiency
30
Overall exergy efficiency 26
29
24
Overall energy efficiency
28 22 Overall exergy efficiency

27 20
5 10 15 20 25 30 35 40 45 20 25 30 35 40 45 50 55 60 65
Excess air (%) Power output (MWe)
Figure 3: Variation of efficiencies with excess air Figure 6: Off-design variation of efficiencies

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 3
Air

Economiser

Superheater

H H
Stack
Air Preheater Turbine
Evaporator

Generator
H Drum

Cooling Water

Condenser
DA

Coal
F F

F F LPH1 LPH2

HPH1 HPH2

Figure 1: Schematic diagram of 62.5 MWe Ramagundam Thermal Power Station (RTPS)

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 4
1 40
62.5 MWe Design

0.9 60 MWe
35 55 MWe
0.8
Fuel flow rate ratio

30 50 MWe
0.7
45 MWe
0.6 25

Loss (%)
40 MWe
0.5
20 35 MWe
0.4
0.3 15
0.2 10
0.1
5
0
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0
Combustor Evaporator Turbine
Fraction of full load

Figure 7: Effect of off-design operation on fuel flow rate Figure 9: Percentage exergy variation

The detailed analysis carried out shows that the dominant loss
take place in steam generating unit on account of carrying out
combustion and heat transfer with a large temperature
33 78 difference. Figs. 10 and 11 show the detailed energy and
Overall energy efficiency exergy balance of the considered system at the operating load
Ireversibility
32 77 of 62.5 MWe. There is a striking difference in the
composition of the represented energy and exergy balances.
Irreversibility rate (%)

31 76 It is noted that the exergy analysis has enabled the


Efficiency (%)

identification of the causes of process inefficiencies in detail


30 75 when compared to the energy analysis.

29 74
Other losses,
Heat rejected
28 73 0.3%
through stack,
8%
27 72
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Overall
Energy
Fraction of full load efficiency,
Figure 8: Variation of overall energy efficiency and 32%
irreversibility rate with load Heat rejected
in cooling
water, 60%

The variation of percentage exergy losses in major sections of


the system with respect to the off-design operation is shown
in fig. 9. It shows that variation of irreversibilities is more in
evaporator when compared to combustor and turbine with the
decrease in load. Figure 10: Energy balance of 62.5 MWe thermal power plant

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 5
licensing a copy of Cycle-Tempo and Ir. Theo Woudstra,
Other losses,
10%
Delft University of Technology for providing the technical
Exergy loss in support.
stack, 5%
References
Exergy loss in Overall exergy
turbine, 7% efficiency, 1. Y. A. Cengel and M. A. Boles, Thermodynamics: An
28% Engineering Approach, Tata McGraw-Hill Publishing
Company Limited, New Delhi, 2004, ch. 7.
Exergy loss in 2. M. A. Habib, S. A. M. Said and J. J. Al-Bagawi,
evaporator, Thermodynamic performance analysis of the ghazlan
15% Exergy loss in
combustor,
power plant, Energy, vol. 20, no. 11, pp. 1121-1130, 1995.
35% 3. M. A. Rosen, Energy- and exergy-based comparison of
coal-fired and nuclear steam power plants, Exergy
International Journal, vol. 1, no. 3, pp. 180-192, 2001.
4. V. Asthana, P. K. Panigrahi and K. Kant, Optimization of
heat transfer in coal fired power stations using exergy
Figure 11: Exergy balance of 62.5 MWe thermal power plant analysis, Proceedings of the 18th National and 7th
ISHMT-ASME Heat and Mass Transfer Conference, pp.
1766-1773, January 4-6, 2006.
In the case of exergy balance, substantial losses under the 5. S. Sengupta, S. D. Gupta and A. Datta, Exergy analysis
head of other losses (10%) are accounted by the condenser of a 210 MW thermal power plant cycle at different
losses, losses due to mixing in the de-aerator, and losses due operating conditions, Proceedings of the 18th National
to heat transfer in feed water heaters. Energy analysis results and 7th ISHMT-ASME Heat and Mass Transfer
may lead to erroneous conclusion that maximum energy is Conference, pp.1774-1780, January 4-6, 2006.
being lost at the condenser. Thus, carrying out exergy 6. BP statistical review of world energy, June 2005.
analysis results in the quantitative analysis of the real losses www.bp.com accessed on 4th June, 2006.
taking place in the system. The overall energy, exergy 7. Ministry of Power, Government of India.
efficiencies and losses for major process sub-sections are www.powermin.nic.in accessed on 4th June, 2006.
found to be in reasonable agreement with the available 8. Central Pollution Control Board, Government of India.
literature [2-3, 5-6]. www.cpcb.nic.in accessed on 27th May, 2006.
9. Cycle-Tempo release 5.0, Delft University of Technology,
Conclusions 2006. www.cycle-tempo.nl

In the present work, an energy and exergy based


thermodynamic analysis of a 62.5 MWe coal-based thermal
power plant has been carried out. The power plant system was
simulated and a detailed parametric study was undertaken
involving parameters like the temperature gain of cooling
water across the condenser, excess air, inlet air temperature
and condenser pressure. It was noted that the influence of
variation of condenser pressure was highest on the overall
energy and exergy efficiencies. A detailed off-design study
has also been carried out to account the components having
maximum exergy destruction rates. Finally, an energy and
exergy balance of the complete system was also made. It has
been observed that the energy losses are associated mainly
with heat rejection in condenser and stack whereas exergy
losses are dominated by the losses in the steam generation
unit and turbine. The present study has enabled us to identify
sites where loss of useful energy takes place in a relatively
smaller unit of 62.5 MWe capacity.

Acknowledgements
One of the authors, Suresh MVJJ thanks Energy Technology
Section, Delft University of Technology, The Netherlands for

Presented at International Conference on Energy and Environment, August 28-30, 2006, Malaysia 6

S-ar putea să vă placă și