Continuous Maintenance
Addenda suggested by:
SSPC committee members
The public through the Change Proposal Process
Public Review
Publication
Courtesy:
Courtesy:
2012 NFPA 99
approved by
American National Standard
August 31, 2011
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
2011 American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (www. ashrae.org) Reprinted by permission from 2011 ASHRAE Standard 70-2008. This
material may not be copied or distributed in either paper or digital form without ASHRAEs permission.
Status Approved
Topic Laboratory work areas
Terminology coordinated with FGI
Laboratory Work Areas vs. Laboratories
Reduction allowed via ANSI Z9.5 risk
assessment or active sensing of
contaminants or appropriate surrogates
approach
Courtesy:
Status Approved
Topic Operating Room Air Distribution
Provides a specific definition of the primary
supply diffuser array.
Clarifies that no more than 30% of the
Primary Supply Diffuser Array may be used
for non-diffuser items.
Additional diffusers may be located outside of
the Primary Supply Diffuser Array if needed to
achieve required environmental conditions or
air change rates.
Courtesy:
Courtesy:
Status Approved
Topic Definitions of Operating and
Procedure Rooms
Continues re-definition of ORs and Procedure
Rooms included in the 2014 FGI Guidelines.
Deletes Class A, B, and C terminology and
replaces with
Operating Room, Procedure Room
New definition of Operating Room is
equivalent to Class B and C ORs previously.
New definition of Procedure Room is
equivalent to Class A ORs previously.
Definition are included from 2014 FGI Courtesy:
Status Approved
Topic Temperature in Sterile Processing
Department (SPD)
Disagreement between design (ASHRAE)
and operational (AAMI) standards.
Joint meeting with ASHRAE, AAMI, FGI,
ASHE, AORN, and APIC April 2015.
Agreed on temperature ranges for 3 spaces:
Decontamination Room 60F-73F
Clean Workroom 68F-73F
Sterile Storage Max 75F
Reference to AAMI ST-79.
Courtesy:
Courtesy:
Courtesy:
Status Approved
Electro-Convulsive Therapy (ECT) Procedure Room
Provide similar HVAC as a general exam room - 4 Total ACH / 2 OA
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Outpatient spaces
Courtesy:
Courtesy:
Courtesy:
Courtesy:
Courtesy: