Sunteți pe pagina 1din 1

Amps X 10 MT2 (Nom. kV=22.9, Plot Ref. kV=22.

9)
.5 1 5 10 50 100 500 1K 5K 10K
1K 1K
T1
FLA F-LDS F-T1
500 500
Siba Siba SE LDS
500 MVAsc
T2 HHD (DIN 442mm) HHD (DIN 442mm)
Back-up 24 kV Back-up 24 kV
FLA 100A 63A
SSEE LDS

F-LDS

H-MONTERRICO
3-1/C 3/0

R R1

CB0
F-T2 R1 - P
100 100 MONTERRICO MT
Siba Merlin Gerin
HHD (DIN 442mm) Sepam 20 F-T1 F-T2

Back-up 24 kV CT Ratio 100:5 H-T1 H-T2


50 63A OC1 50 1-3/C 50 1-3/C 50

IEC - Very Inverse (TMS) T1


1250 kVA
T2
1250 kVA
Pickup = 0.77 (0.1 - 2.4 xCT Sec)
Time Dial = 0.8 CB2 CB3

3x = 5.4 s, 5x = 2.7 s, 8x = 1.54 s TPG

Inst = 5.4 (0.1 - 24 xCT Sec)


Time Delay = 0.21 s
OC2
10 10
Inst = 12.3 (0.1 - 24 xCT Sec)
Time Delay = 0.08 s

5 5

Seconds
Seconds

1
T2 H-MONTERRICO - P 1
H-T1 - P
T1
CB3
H-T2 - P
.5 .5
Square-D MICROLOGIC 5.0
Sensor = 3200
CB2 - 3P
LT Pickup = 1 (3200 Amps) R1 - 3P
LT Band = 8 144.834kA @ 0.23kV
(Asym) 11.597kA @ 22.9kV
ST Pickup = 2 (6400 Amps) (Asym)
ST Band = 0.3 (I^x)t = OUT
Inst. Pickup = 8 (25600 Amps) CB3 - 3P F-T2 - 3P
144.834kA @ 0.23kV 11.597kA @ 22.9kV
.1 (Asym)
(Asym) .1
T2
CB2 Inrush F-T1 - 3P
.05 Square-D MICROLOGIC 5.0 11.597kA @ 22.9kV .05
Sensor = 3200 T1 (Asym)
LT Pickup = 1 (3200 Amps)
LT Band = 8 Inrush
ST Pickup = 2 (6400 Amps) F-LDS - 3P
ST Band = 0.3 (I^x)t = OUT 12.606kA @ 22.9kV
Inst. Pickup = 8 (25600 Amps) (Asym)

.01 .01
.5 1 5 10 50 100 500 1K 5K 10K

Amps X 10 MT2 (Nom. kV=22.9, Plot Ref. kV=22.9)


34.7 100 500 1K 5K 10K 50K 100K 693.9K

Amps (Plot Ref. kV=3.3) ETAP Star 12.6.0H

MONTERRICO MT-BT

Project: MONTERRICO CALL CENTER III


Location: SANTIAGO DE SURCO - LIMA
Contract: ING. LUIS LLALLICO
Engineer: ING. CSAR CHILET